The purpose of this amendment is for the follow ing:
1. Extend the solicitation response date from November 18, 2022 at 5:00PM to November 21, 2022 at 5:00PM.
2. Provide Question(s) and Answ er(s) received by interested offerors. The follow ing Question(s) and Answ er(s) shall be considered w hen submitting quotations for solicitation N42158-23-Q-0002.
3. Update FAR 52.212-1 Addendum.
4. Update Technical Capabilities Certif ication.
5. Update the Statement of Work (SOW)
1. CONTRACT ID CODE PAGE OF PAGES
J 1 7
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY 15-Nov-2022
16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X N4215823Q0002
X 9B. DATED (SEE ITEM 11)
27-Oct-2022
10B. DATED (SEE ITEM 13)
9A. AMENDMENT OF SOLICITATION NO.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer X is extended, is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE
RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN
REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
15-Nov-2022
CODE
NORFOLK NAVAL SHIPYARD
ATTN: KIMBERLY RETTINGER
CVN FLEET SUPPORT BRANCH
C400, BLDG 65, 2ND FLOOR, RM 201
PORTSMOUTH VA 23709-1122
N42158 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODECODE
EMAIL:TEL:
N4215823Q0002
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
SECTION SF 1449 - CONTINUATION SHEET
SOLICITATION/CONTRACT FORM
The required response date/time has changed from 18-Nov-2022 05:00 PM to 21-Nov-2022 05:00 PM.
The following have been added by full text:
AMENDMENT 0001 Q&A
Question 1: Would the government accept four 20ft long containers instead of the two 40ft?
Answer 1: Yes, the government will accept four 20-foot long containers.
The following have been modified:
ADDENDUM
Quotations shall be emailed to Kim Rettinger (email: kimberly.rettinger@navy.mil) and to
USFF_NNSY_C432@NAVY.MIL by November 21st 2022 5:00PM Eastern.
Questions relating to this notice shall be submitted in writing via the above email address no later than November 4, 2022 4:00PM Eastern.
Quotation will consist of the following documents submitted together in Adobe Acrobat .pdf format:
1. Completed FAR 52.212-3 Representations and Certification unless otherwise completed in SAM;
2. Completed SF 1449 with pricing for each line item being quoted in accordance with the Contract Line Item
Numbers listed in this notice. Provide cost by day, week, and month.
3. Manufacturer’s specifications manual to reflect the proposed equipment is in compliance with all specifications of the SOW.
4. Completed Technical Capabilities Certification
5. Completed and signed amendments to all documents attached to Solicitation
Award will be made to the offeror whose quote reflects a technically acceptable item or combination of technically acceptable items that result in the lowest aggregate price to the Government.
Price:
The estimated amount for each line item will be added together to determine the total estimated price which will become the evaluate price.
The vendor’s proposed price will be evaluated on the basis of price reasonableness. All prices must be considered fair and reasonable as determined by the Government. Price quote shall be held firm and valid for sixty (60) days.
The completion and submission of the above items will constitute a quote and will be considered the vender’s unconditional assent to the terms and conditions of this Solicitation and any attachments and/or exhibits.
Failure to provide all of these documents by the required date and time may preclude a quotation from award consideration at the discretion of the Government.
STATEMENT OF WORK
mailto:kimberly.rettinger@navy.mil mailto:USFF_NNSY_C432@NAVY.MIL
1. Scope:
1.1 Title: WALK-IN REFRIGERATED BOX
1.2 Quantity of four (4) for twenty feet long units or Quantity of two (2) forty feet long units Self-contained walk-in refrigerated box (electric) for acceptable space for food and medicine storage.
1.3 Location of work:
1.3.1 NORFOLK NAVAL SHIPYARD (NNSY) Inside NNSY waterfront CIA area in support of the
Truman Project at Pier 5A.
2. Reference and Guiding Documents:
2.1 Refrigerated boxes shall comply with all governing codes and Naval Standards including the most recent Unified Facilities Criteria, International Building Code 2012, ADA and Requirements for
Lifting Equipment.
2.2 United Facilities Criteria (UFC) 1-200-01, 3-301-01, 3-600-01.
2.3 National Fire Protection Association (NFPA) 1, Fire Code.
2.4 National Fire Protection Association (NFPA) 70, National Electrical Code (NEC).
2.5 Federal Specification RR-C-271H.
2.6 Hazardous Energy Control (HEC) procedures as identified in NAVSEA’s Occupational Safety, Health, and Environment Corporate Manual (OSHECM) Chapter 250 (latest revision) (See web site in section 8.1.(b)).
3. General Specifications and Requirements:
3.1 Equipment Requirements:
3.1.1 Unit(s) will be cleaned, disinfected, and ready to store food or medicine prior to delivery.
3.1.2 Each unit shall be a minimum of 8’ wide x 8’ high (not including refrigeration unit) x 20’ long or
8’ wide x 8’ high (not including refrigeration unit) x 40’ long.
3.1.3 Units shall be electrically powered and capable of running 24 hours a day / 7 days a week. See attached enclosures (1), (2), (3) and (4).
3.1.4 Units shall be rated at 200 amps or less. See attached enclosures (1), (2), (3) and (4).
3.1.5 Unit shall be capable of keeping a constant temperature of -3 degrees to 42 degrees (Fahrenheit).
3.1.6 Each unit shall be hurricane proof to 110 MPH winds and also must be water resistant.
3.1.7 Each unit that has forklift connections in lieu of overhead rigging equipment and associated gear shall have forklift channels 5”x10” inside dimension the full width of the unit and enclosed on sides.
3.1.8 There shall be no windows in the units.
3.1.9 Each unit shall have exterior camlok connections to box feeding a 600 Volt, 40A (amp) 2-pole circuit breaker enclosed in a NEMA 3R enclosure feeding a 15kva, 440/240V primary:240/120V secondary, single-phase transformer. This is to feed a 15 kva, 480/240 volt primary, 240/120 volt secondary single phase transformer (see enclosure (2)). See enclosure (4) for a list of exterior equipment. Equivalent material may be substituted. Power cable end fittings (camlok) will be lugged and color coded to indicate proper phasing. See attached enclosures (1), (2), (3) and (4).
3.1.10 Each unit shall be in compliance with applicable NFPA and NEC requirements.
3.1.11 Each unit shall comply with the applicable OSHA regulations.
3.1.12 Provide a decal on each unit with the following information: Contractor company name, contract number and a unique number. The unique number must be different on each unit. The decal shall have the following: minimum of 8.5” x 11” in size, white in color with black writing. The decal is to be located on one of the doors of the unit. If the half of the unit does not have a door, an 11/3” x 4” at minimum label shall be placed on the electrical panel on the inside of the unit.
3.1.13 Each unit doors are to swing outward and the doors must be capable of being locked.
3.1.14 Units shall be capable of being moved via forklift and/or lifting pad eyes. Unit shall have weight clearly marked for lifting purposes.
3.1.15 The equipment shall be outfitted with suitable attachments for overhead lifting (if applicable).
This is not applicable for forklift lifting.
3.1.16 Each lifting attachment shall be capable of supporting one half the gross weight of the equipment with a design factor of five to one based on ultimate strength.
3.1.17 Each lifting attachment shall be designed to accept a standard anchor shackle (Federal
Specification RR-C-271D, type IVA) which is capable of supporting one half the gross weight of the equipment.
3.1.18 Design of the lifting attachments shall be such that the shackles are not side loaded. This is not applicable for forklift lifting.
3.1.19 Each lifting attachment shall be conspicuously marked in a contrasting color “Lift Here”. Letters shall have a minimum height of 1”.
3.1.20 The equipment shall be provided with a lifting sketch / rigging diagram.
3.1.21 The lifting sketch shall detail any specific requirements and / or configurations that must be meet prior to lifting (i.e. “engage swing lock”, “Tilt mast back fully”, “Rotate lifting basket over side”, “Utilize 10’ minimum length slings”, “Spreader beam required”, etc.). This is not applicable for forklift lifting.
3.2 One row of surface mount fluorescent twin tube strip type interior light fixtures with energy efficient electronic ballast and 32 watt fluorescent bulbs. Mount in center of enclosure. Light fixtures shall be blast proof.
3.3 All Wire must be THHN or THWN, 75 degrees Celsius (min), size as indicated. Do not substitute wiring type/temperature rating unless the ampacity of wire and conduit fill requirements are evaluated to ensure NEC compliance.
3.4 Electrical Metallic Tubing (EMT) is specified on drawings. The NEC requires EMT to be supported within 3 ft of each box or conduit body and supported every 10 ft (min).
3.5 Liquid Tight Flexible Metal Conduit (LFMC) may be used on the exterior instead of EMT. The NEC requires LFMC to be supported within 1 ft of each box or conduit body and supported every 4.5 ft
(min).
3.6 The NEC requires the following color code for electrical wires:
3.6.1 Neutral (grounded conductor) = white
3.6.2 Note: may be phased taped white if larger than #6 AWG.
3.6.3 Ground (Equipment grounding conductor) = green
3.7 Contractor may use a fusible disconnect switch, NEMA 3R with current limiting fuses rated the same size as the circuit breaker in the enclosure (2) (PC-4 and PC-5).
3.8 Receptacles: 120 volt, 20 Amp Quad type receptacle wired on a #12 AWG (min of two Quad
Receptacles per circuit). Provide (1) ea 120 volt, 15 amp duplex GFCI test type receptacle wired on a dedicated circuit mounted on the exterior in a weatherproof box beside the unit.
3.9 A typical transformer wiring diagram is shown in enclosure (3) in the drawing, use the manufacturers wiring schematic to connect transformer (schematic usually located on front panel of transformer).
Transformer size may be adjusted depending on load demand of walk in refrigerated box enclosure.
3.10 Transformer frame shall be bonded to unit frame using appropriate size bonding jumper from NEC table 250.122, per NEC.
3.11 Markings:
3.11.1 The equipment shall be marked in a prominent location with vendor Point Of Contact information (i.e. Name and cell phone number) and date of end of contract.
3.11.2 The equipment shall be marked in a prominent location with the gross weight. Marking shall be upper case letters of a contrasting color, with a minimum height of 1”. Marking shall include the units (i.e. “pounds”, “long tons”, etc.).
4. Period of Performance:
4.1 The Government reserves the right to return the unit(s) at any time prior to the expiration of the rental period. The contractor agrees to prorate costs for the time the refrigerated boxes are in use by NNSY only. The Government agrees to give the contractor twenty-four (24) hours-notice for the return of the refrigerated box(es) if the return is prior to the expiration of rental period.
5. Contractor Requirements:
5.1 Provide POC information (name and phone number) on the equipment for NNSY to notify contractor of equipment failures.
5.2 Delivery crew security clearance request is required for shipment offload within the Controlled
Industrial Area at NNSY. Contractor shall arrange the Security clearance request with the pass office at NNSY. See DBIDS section 10.1 through 10.14 for DBIDS participants.
5.2.1 One-Day Passes, Contact (OPZM) POC and fill out visit request form, NNSY 5512/104, also this request form must be presented to Pass Office by (OPZM) POC at least one day (M-F) prior to the visit or earlier. Prior to visit contact delivery POC to assist in one day pass at the pass office and delivery POC will provide shipyard site (escort). Participation in the DBIDS is not mandatory, and if the Contractor chooses to not participate, the Contractor’s personnel will have to obtain daily passes, be subject to daily mandatory vehicle inspection, and will have limited access to the installation. The Government will not be responsible for any cost or lost time associated with obtaining daily passes or added vehicle inspections incurred by non-participants in the DBIDS.
5.3 Deliver and retrieve the walk-in refrigerated box to Norfolk Naval Shipyard, Portsmouth Virginia, inside the Controlled Industrial Area. (Exact location to be shown upon delivery by escort or
(OPZM)).
5.4 Connect the accessory equipment that is not integral to the walk-in refrigerated box. See attached enclosures (1), (2), (3) and (4).
5.5 Contractors and Non-NNSY Government Agencies (NNGAs) are hereby informed that their employees or representatives present on property under Norfolk Naval Shipyard (NNSY) cognizance must adhere to Federal OSHA requirements for hazardous energy control lAW 29 CFR 1915.89 and must follow Hazardous Energy Control (HEC) procedures as identified in NAVSEA's Occupational
Safety, Health, and Environment Corporate Manual (OSHECM) Chapter 250 (latest revision), when performing work under NNSY contract. All HEC work to be performed by Contractors and NNGAs requires that NNSY (OPZM) Points of Contact (TPOCs) and/or Contracting Officer's Representatives
(CORs) be notified of the HEC scope of work prior to starting work. Any changes or deviations in the initial scope of HEC work require the NNSY TPOCs and/or CORs be informed of the change/deviation. Appendix 250.8-1 through B-3 of OSHECM Chapter 250 for multiple employer work identifies when Contractors and NNGAs are required to assign their Lockout/Tags-Plus
Coordinator (LOTC) to coordinate HEC work with the cognizant NNSY LOTC. HEC locks shall be provided by the contractor or NNGA for their employees use. The HEC locks shall have red bodies with name labels or name tags affixed, identifying who installed the HEC lock(s) and a point of contact telephone number. HEC lock name labels and tags must be made of materials that will hold up to the environment to which they are exposed. HEC tags used for Tags-Plus HEC work shall be provided by the cognizant NNSY LOTC to the contractor or NNGA for their use if machinery, equipment, or systems (MES) cannot be locked out. OSHECM Chapter 250 Tags-Plus procedures will be strictly followed.
5.6 Provide commercial operating instruction manuals for the walk-in refrigerated box to (OPZM) POC.
5.7 Provide 24 hour a day, seven-day a week on-call repair service during the rental period. The vendor will be responsible for initiating repairs on-site, at Norfolk Naval Shipyard, within 12 hours of verbal or written notification that the equipment has malfunctioned. The contractor will replace the malfunctioning component if the system cannot be returned to service within 16 hours of being notified of the original malfunction.
5.8 Before any leased/purchased temporary production facility will be accepted by the government an inspection at NNSY will be performed to ensure that the contractor has provided a product that conforms to the agreed specifications. If the inspection is not satisfactory, the contractor has 3 business days to correct the discrepancies (at contractor’s cost) or the temporary production facility will not be accepted the government.
5.9 Contractor provide representative within 24 hours in order to modify units in the event the customer determines the units do not meet contract specifications.
5.10 Contractor personnel shall notify the Operations Zone Manager (OPZM) POC for authorization prior to any work or maintenance on rental unit.
5.11 Lost items by Government personnel and equipment damaged beyond normal wear and tear
Contractor must submit a claim separate from rental. This is to be submitted within 30 days of the end of the rental period.
5.12 Contractor to contact (OPZM) prior to the end of rental period to confirm pickup date.
6. Government Responsibility:
6.1 Government shall provide contractor ready access to the job location during contractor’s working hours
(i.e., weekdays between the hours of 7:30 AM and 4:00 PM). Emergent services outside these hours will require government approval and will be no cost to the government. The government is responsible for the cost of all additional approved or requested maintenance and repairs not specifically covered under this
Agreement or any applicable warranties. The government will prevent anyone other than contractor from maintaining, repairing or modifying its product.
6.2 The government agrees to, upon satisfactory delivery and installation; connect walk in refrigerated boxes to temporary services. The government will also have temporary services disconnected upon completion of the contract in order to allow the contractor to remove the container or equipment from the shipyard.
6.3 The government will provide a COR, from code 400, to this project to maintain the contract is being completed and a C400/COR representative will be the point of contact to escort, if needed, once the contract is award.
7. Points Of Contact:
7.1 Invoice Certifying POC: TBD
7.2 Delivery POC: TBD
8. Safety Requirements:
8.1 "Per FAR 22.102-1(a) entitled "Safety", Contractors are hereby informed that their employees or representatives present on property under Naval Base Norfolk must follow Federal and State OSHA requirements OSHE OSHECM Chapter Hazardous Energy Control (HEC) requirements or safety requirements for site specific location of the contract.
a. Contractors and Non-NNSY Government Agencies (NNGAs) are hereby informed that their employees or representatives present on property under Norfolk Naval Base must adhere to
Federal OSHA requirements for hazardous energy control IAW 29 CFR 1915.89 and must follow Hazardous Energy Control (HEC) procedures as identified in NAVSEA’s Occupational
Safety, Health, and Environment Corporate Manual (OSHECM) Chapter 250 (latest revision), when performing work under NNSY contract. All HEC work to be performed by Contractors and NNGAs requires that NNSY (OPZM) Points of Contact (TPOCs) and/or Contracting
Officer’s Representatives (CORs) be notified of the HEC scope of work prior to starting work.
Any changes or deviations in the initial scope of HEC work requires the NNSY TPOCs and/or
CORs be informed of the change/deviation. Appendix 250.B-1 through B-3 of OSHECM
Chapter 250 for multiple employer work identifies when Contractors and NNGAs are required to assign their Lockout/Tags-Plus Coordinator (LOTC) to coordinate HEC work with the cognizant NNSY LOTC. HEC locks shall be provided by the contractor or NNGA for their employees use. The HEC locks shall have red bodies with name labels or name tags affixed, identifying who installed the HEC lock(s) and a point of contact telephone number. HEC lock name labels and tags must be made of materials that will hold up to the environment to which they are exposed. HEC tags used for Tags-Plus HEC work shall be provided by the cognizant
NNSY LOTC to the contractor or NNGA for their use if machinery, equipment, or systems
(MES) cannot be locked out. OSHECM Chapter 250 Tags-Plus procedures will be strictly followed.
b. Contractors and NNGAs may obtain electronic copies of OSHECM Chapter 250 (latest revision) and access the OSHA 1915.89 web site by using the following link to NNSY’s public access web site: “http://www.navsea.navy.mil/Home/Shipyards/Norfolk/NNSY-
Forms/default.aspx”
c. Names and contact information for NNSY LOTCs and/or the Building Monitor will be provided by NNSY TPOC and/or CORs set forth elsewhere in this award document.
9. DBIDS:
9.1 Any new contractor, vendor or supplier requesting base access AFTER 31 MAY 2017 will be required to obtain a DBIDS credential. NCACS credentials will no longer be issued.
9.2 Only DBIDS credentials will be issued to ALL contractors, vendors and suppliers seeking base access
AFTER 14 August 2017.
9.3 Defense Biometric Identification System (DBIDS) increases installation security and communications by receiving frequent database updates on changes to personnel/credential status, law enforcement warrants, lost/stolen cards, and force protection conditions. The system provides a continuous vetting anytime the
DBIDS card is scanned at an installation entry point.
If you currently have a Navy Commercial Access Control System (NCACS) card, The following is required to get a DBIDS credential:
9.4 Present your NCACS Card and completed copy of the SECNAV FORM 5512/1 to the base Visitor Control
Center representative.
9.5 The VCC will pull up your information in the computer, ensuring all information is current and correct.
9.6 Once your information is validated, a temporary DBIDS credential is provided.
9.7 Your temporary credential will have an expiration date, prior to which you will need to obtain your permanent DBIDS credential (~90 days)
9.8 For each additional U.S Navy installation to which you need access, the first time you visit you only need to bring your DBIDS credential and statement of purpose for base access when arriving at the Visitor
Control Center.
9.9 The representative will enter base access authorization and then you may proceed to work.
If you do NOT have an NCACS Card, the following is required to obtain a DBIDS credential:
9.10 Present a letter or official document from my government sponsoring organization that provides the purpose for your access.
9.11 Present valid identification, such as a passport of Real ID Act – compliant state driver’s license.
9.12 Present a completed copy of the SECNAV 5512/1 form to obtain your background check.
9.13 Upon completion of the background check, the Visitor Control Center representative will complete the
DBIDS enrollment process, which includes your photo, finger prints, base restrictions, and several other assessments: after all this is done, you will be provided with your new DBIDS credential.
9.14 The representative will enter base access authorization and then you may proceed to work.
FOR ADDITIONAL QUESTIONS ABOUT OBTAINING A DBIDS CARD, CONTACT YOUR
LOCAL BASE VISITOR CONTROL CENTER, INFORMTAION IS ALSO PROVIDED AT:
www.cnic.navy.mil/om/dbids.html Participation in the DBIDS is not mandatory, and if the Contractor chooses to not participate, the Contractor’s personnel will have to obtain daily passes (One-Day Passes), be subject to daily mandatory vehicle inspection, and will have limited access to the installation. The
Government will not be responsible for any cost or lost time associated with obtaining daily passes (One-
Day Passes) or added vehicle inspections incurred by non-participants in the DBIDS.
One-Day Passes, See paragraph 5.2
(End of Summary of Changes) http://www.cnic.navy.mil/om/dbids.html