N42158-18-Q-0009 ATTACHMENT 4

REVISED TECHNICAL CAPABILITY CERTIFICATIONS

Vendor shall self-certify that the equipment and services proposed either meets or does not meet the Government’s minimum requirements specified in the associated Statement of Work (SOW) reference by initialing in the “YES” or “NO” area of the chart below.

Any deviation to the Government specifications shall be identified as such – A detailed explanation shall be provided for each negative response.

Note: In order to be considered for award, the table must be completed in its entirety and submitted with your quotation in accordance with FAR 52.212-1 Instructions of Offerors ADDENDUM.

Technical Capabilities Statement

Item #1 Specifications for Two (2) 200 Ton Air Cooled Chillers

Shall be provided with the following capabilities, features, and specifications:
YES
NO

· Provide and deliver a 200 Ton Air Cooled Chiller

· Unit must be electrically powered at less than 400 full load amps. Input: 440 volts, 60 Hz, 3 phase, 3 wire (ungrounded or neutral that can be isolated), capable of providing chilled water.

· Unit must be equipped with required Air cooling equipment for condenser. Self-contained air cooling system.

· Unit must be equipped with required chilled water pump capable of 300 gpm minimum and to provide approximately 500 gpm for normal operating flow at 100 psi minimum to 150 psi maximum.

· Safety Devices: Equipment controller with circuit breaker.

· Unit must provide water Inlet and Outlet six inch Cam-Lok male and female connections and associated adapters to connect to six inch NPS 150 PSI commercial flat face flanges including quantity of six hoses six inch NPS at ten foot long.

· Unit must be able to provide chilled water near 40 degree F.

· Trailer mounted. Lifting points shall have current capacity certifications.

· Outdoor enclosure; Electrical Panel in NEMA 4 metal enclosure with lockable disconnect and Cam-Lok Cords. Unit shall be equipped with rain-tight enclosure.

· The unit shall have refrigerant tested to verify the system is not low in refrigerant within two weeks of delivery and applicable test data sent with unit. NNSY point of contact is Shop 99 POC LASCELLES BOND 757-284-8817.

• Forklift pockets and four-point certified lift frame required.

· All repairs/replacements shall be handled by contractor if breakdown occurs within 4 hours of being notified by NNSY.

· All maintenance will be handled by contractor. This includes all services per the manufacturer’s specifications.

· Transportation to be handled by vendor until delivery destination of Bldg 298 at NNSY.

· Rental usage is intended for constant 24 hours at 7 days week.

· Electrical Connection Cable Pigtails required.

· Unit shall be compatible with Shipyard furnished “THOF-500”- T-500 lugged output cables (4 per phase). If mechanical lug connections are provided, they shall be sized for 750MCM (4 per phase).

· Unit required is based on the specified period of performance, with the option to extend. The unit shall be delivered to NNSY bldg. 298, Portsmouth, VA based on the specified period of performance. Delivery POC LASCELLES BOND 757-284-8817.

· Maximum footprint size not to exceed 32’ L x 9’ W x 10’-6”H.

· Rigging sketch provided by Vendor. Lifting and Rigging must conform to NAVFAC-P-307 Standard.

In order to be considered technically acceptable, this form must be completed in its entirety.