7371909 Amendment 0004.pdf
PDF 281 KB Posted
- Solicitation number
- N400857371909
About this file
This is Amendment 0004 to Solicitation N400857371909, issued by CG MCAS Cherry Point Facilities, ROICC on July 1, 2026, for construction work at Marine Corps Air Station Cherry Point, North Carolina. The amendment addresses pre-proposal inquiries (PPIs) regarding the project scope, with the deadline for submitting pre-award PPIs having passed.
The project involves constructing a wall/partition and doorway in Building 219, Station Legal. The amendment provides responses to ten RFI questions covering critical construction details: Wall Type 'A' extends to the existing GWB ceiling as specified in drawing details A1 and A3; the wall type is not fire-rated per drawings and specifications; Door 204B hardware specifications are detailed in Section 08 71 00; HVAC modifications are required for Room 204B including new supply/return diffusers and testing/balancing; electrical device relocation/replacement is necessary per Division 26 specifications; lead-containing paint abatement requirements are addressed in Division 02 and Hazard Report recommendations; work hour restrictions and noise limitations are covered in contractor access provisions 1.6.1 through 1.6.6; temporary protection requirements including dust partitions and negative air are specified in Division 02; door hardware must be keyed into the existing base master key system per Section 08 71 00; and sprinkler head removal and reinstallation procedures are clarified in drawing sheets AD101 and A-101. All technical specifications are contained in the 7371909 Streamlined MACC TechSect PDF document across relevant construction divisions.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 7371909 Amendment 0003.pdf | ||
| 7371909 Amendment 0002.pdf | ||
| 7371909 Amendment 0001.pdf | ||
| 7371909DrawingsAsOne.pdf | ||
| 7371909 Streamlined SOW.pdf | ||
| Master PPI Form.xlsx | XLSX spreadsheet | |
| 7371909 RFP.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE PAGE OF PAGES 1 3
2. AMENDMENT/MODIFICATION NO. 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQ. NO. 5. PROJECT NO. (If applicable)
0004 07/01/2026 7371909
6. ISSUED BY Code N40085 7. ADMINISTERED BY (If other than item 6.) Code CG MCAS Cherry Point
FACILITIES, ROICC
B-87, 748 Roosevelt Blvd.
PSC BOX 8006
MCAS CHERRY POINT NC 28533-0012
8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code) 9A. AMENDMENT OF SOLICITATION N400857371909
9B. DATED (SEE ITEM 11)
AMENDMENT MUST BE ACKNOWLEDGED WITH YOUR PROPOSAL 10A. MODIFICATION OF CONTRACT/ORDER NO.
10B. DATED (SEE ITEM 13)
CODE FACILITY CODE
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
The above numbered solicitation is amended as set forth in item 14. The hour and date specified for receipt of Offers is extended is not extended. Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods: (a) By completing items 8 and 15, and returning 1 copy of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (if required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14. ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATION CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103 (b).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER: (specify type of modification and authority)
E. IMPORTANT: Contractor is not is required to sign this document and return original to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
7371909 Construct Wall/ Partition and Doorway, B219, Station Legal, Station Marine Corps Air Station Cherry Point, NC
Amendment 0004 is being issued to answer pre-proposal inquiries (PPIs).
The deadline to submit pre-award PPIs has passed.
See attached.
15A. NAME AND TITLE OF SIGNER (Type or print) 16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
15B. CONTRACTOR/OFFEROR (Same as Item 8) 15C. DATE SIGNED 16B. UNITED STATES OF AMERICA 16C. DATE SIGNED
BY
(Signature of person authorized to sign) (Signature of Contracting Officer)
NSN 7540-01-152-8070 30-105 STANDARD FORM 30 (REV.1-83) 0224-3(10-90)
PREVIOUS EDITION UNUSABLE Prescribed by GSA
Amendment 0004 7371909 Construct Wall/ Partition and Doorway, B219, Station Legal
RFI Responses:
1. Wall Type ‘A’ indicates full-height construction with gypsum board and acoustical sealant;
however, the reflected ceiling plan shows a suspended ACT ceiling grid. Please confirm: Does the new partition extend to the structural deck above, or terminate at the ceiling grid? If full-height, are above-ceiling bracing, firestopping, and sealing at deck required?
Response: "Wall type 'A' extends to 'Existing GWB Ceiling' as called out in Details A1, A3 on Drawing Sheet A-301. Refer to Detail A1 on Drawing Sheet A-501 and Detail A1 on Drawing Sheet A-301 for answer to the next question. For wall requirements, refer to specification sections under Division 07 Thermal and Moisture Protection, Division 8 Openings, Division 9 Finishes in the 7371909 Streamlined MACC TechSect PDF document."
2. Wall Type ‘A’ assembly is shown but no fire-resistance rating is identified. Please confirm required fire rating (if any) and firestopping requirements at penetrations and head-of-wall conditions.
Response: Drawings and Specifications do not indicate wall type 'A' to be fire rated. For wall requirements, refer to Drawing Sheets A-301, A-501, A-601, and specification sections under Division 07 Thermal and Moisture Protection, Division 8 Openings, Division 9 Finishes in the 7371909 Streamlined MACC TechSect PDF document.
3. Door 204B is identified; however, hardware set is not defined. Please confirm lock function, closer requirement, and any special hardware (access control, keypad, etc.).
Response: Refer to Detail D1 on Drawing Sheet A-601, and Door Hardware Specifications Section 08 71 00 in the 7371909 Streamlined MACC TechSect PDF document.
4. With the new partition dividing Room 204, please confirm if HVAC modifications are required, including new supply/return diffusers for Room 204B and testing/balancing requirements.
Response: "MEP response: YES.
Arch response: Refer to Drawing Sheets AD101, A-101, A-301, M-001 through E-501 and all specifications sections in Division 23 Heating, Ventilating, and Air Conditioning (HVAC), and Division 26 Electrical in the 7371909 Streamlined MACC TechSect PDF document."
5. Please confirm scope for relocation or replacement of electrical devices impacted by new wall, including receptacles, switches, and data outlets.
Response: "MEP Response: YES Arch Response: Refer to Drawing Sheets AD101, A-101, E-001 up to E-501, and all specification sections in Division 26 Electrical in 7371909 Streamlined MACC TechSect PDF document."
6. Lead-containing paint has been identified. Please confirm whether full abatement is required or if lead-safe work practices are acceptable, and whether third-party monitoring is required.
Amendment 0004 7371909 Construct Wall/ Partition and Doorway, B219, Station Legal
Response: Refer to Drawing Sheets AD101, A-101, and Hazard Report recommendations, and all specifications sections in Division 02 - Existing Conditions in the 7371909 Streamlined MACC TechSect PDF document.
7. Please confirm work hour restrictions and whether off-hours work is required for entire project and noise-producing activities within this occupied facility.
Response: Refer to sub-sections 1.6.1 up to 1.6.6 under 1.6 Contractor Access and Use of Premises in the 7371909 Streamlined MACC TechSect PDF document.
8. Please clarify required level of temporary protection, including dust partitions, barriers, and negative air requirements during construction.
Response: Refer to Drawing Sheets AD101, M-001, MD101, E-001, ED101, and other drawings as referenced therein, and all specifications sections in Division 02 - Existing Conditions in the 7371909 Streamlined MACC TechSect PDF document.
9. Please confirm door hardware is to be keyed into existing base master key system and provide keying requirements.
Response: YES. Refer to Part 1 General, Part 2 Products, Part 3 Execution of the Door Hardware Specifications Section 08 71 00 in 7371909 Streamlined MACC TechSect PDF document.
10. Keynote 8 is pointing to a sprinkler head which I am assuming will need to be removed as part of the ceiling demolition(pipe to remain).and general note 3 states SEE FIRE PROTECTION DRAWINGS FOR FIRE - RATED CONSTRUCTION (however do not see any fire protection drawings) Please advise are we securing the system to remove heads and then putting back existing on line after reinstall?
Response: Yes. Refer to Drawing Sheets AD101, A-101.