NAVFAC
SPECIFICATION
6839560, B-4389 INSTALL
UPS IN HOSPITAL
SERVER ROOM
MCAS Cherry Point, NC
AMENDMENT #0001
IMPORTANT
This amendment should be acknowledged when your proposal is submitted. Failure to acknowledge the amendment may constitute grounds for rejection of the proposal.
If your proposal has been submitted prior to the receipt of this amendment, acknowledgement should be made by telegram, which should state whether the price contained in your proposal is to remain unchanged, is to be decreased by an amount, or is to be increased by an amount. The acknowledgement must be received prior to proposal opening time.
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE PAGE OF PAGES
1 2
2. AMENDMENT/MODIFICATION NO. 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQ. NO. 5. PROJECT NO. (If applicable)
0001 08/21/2020 6839560
6. ISSUED BY Code N40085 7. ADMINISTERED BY (If other than item 6.) Code
CG MCAS Cherry Point
FACILITIES, ROICC
B-163, CURTIS ROAD
PSC BOX 8006
CHERRY POINT, NC 28533
8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code) 9A. AMENDMENT OF SOLICITATION
B-4389 INSTALL UPS IN HOSPITAL
SERVER ROOM
9B. DATED (SEE ITEM 11)
AMENDMENT MUST BE ACKNOWLEDGED WITH YOUR PROPOSAL 10A. MODIFICATION OF CONTRACT/ORDER NO.
10B. DATED (SEE ITEM 13)
CODE FACILITY CODE
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
The above numbered solicitation is amended as set forth in item 14. The hour and date specified for receipt of Offers is extended is not extended. Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods: (a) By completing items 8 and 15, and returning 1 copy of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (if required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14. ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATION CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103 (b).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER: (specify type of modification and authority)
E. IMPORTANT: Contractor is not is required to sign this document and return original to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
6970450 B-4389 Install UPS in Hospital Server Room, NHC, Marine Corps Air Station Cherry Point, NC
This amendment is being issued to provide corrected specs and drawings.
The deadline to submit pre-award RFIs remains 26 August 2020 by 0900.
The proposal due date of 8 September 2020 at 1200 local times remains UNCHANGED.
See Attached.
15A. NAME AND TITLE OF SIGNER (Type or print) 16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
15B. CONTRACTOR/OFFEROR (Same as Item 8) 15C. DATE SIGNED 16B. UNITED STATES OF AMERICA 16C. DATE SIGNED
BY
(Signature of person authorized to sign) (Signature of Contracting Officer)
NSN 7540-01-152-8070 30-105 STANDARD FORM 30 (REV.1-83) 0224-3(10-90)
PREVIOUS EDITION UNUSABLE Prescribed by GSA
CONTINUATION SHEET
PROJECT TABLE OF CONTENTS
SECTION 26 33 53 Static Uninterruptible Power Supply (UPS) is deleted and SECTION 26 33 53 Static Uninterruptible Power Supply (UPS), dated
08/20/2020, as shown in the footer, is added to the Project Table of
Contents and accompanies this Amendment.
SECTION 00 01 15 – LIST OF DRAWINGS
1.2 CONTRACT DRAWINGS
The following drawings are revised as of August 20, 2020:
NAVFAC DWG NO. TITLE
12798980 GENERAL NOTES, ABBREVIATION, AND LEGEND
12798982 NEW ONE LINE DIAGRAM TO PANEL 2CLC
These drawings accompany this Amendment.
Install UPS, HOSP, Server Room, B4389
SECTION 26 33 53
STATIC UNINTERRUPTIBLE POWER SUPPLY (UPS)
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM B173 (2017) Standard Specification for Rope-Lay-Stranded Copper Conductors Having Concentric-Stranded Members, for Electrical Conductors
ASTM D709 (2017) Standard Specification for Laminated Thermosetting Materials
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE 100 (2000; Archived) The Authoritative Dictionary of IEEE Standards Terms
IEEE 450 (2010) Recommended Practice for Maintenance, Testing, and Replacement of Vented Lead-Acid Batteries for Stationary Applications
IEEE 485 (2010) Recommended Practice for Sizing Lead-Acid Batteries for Stationary Applications
IEEE C2 (2017; Errata 1-2 2017; INT 1 2017) National Electrical Safety Code
IEEE C62.41 (1991; R 1995) Recommended Practice on Surge Voltages in Low-Voltage AC Power Circuits
IEEE C62.41.1 (2002; R 2008) Guide on the Surges Environment in Low-Voltage (1000 V and Less) AC Power Circuits
IEEE C62.41.2 (2002) Recommended Practice on Characterization of Surges in Low-Voltage (1000 V and Less) AC Power Circuits
INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)
NETA ATS (2017; Errata 2017) Standard for Acceptance Testing Specifications for Electrical Power Equipment and Systems
SECTION 26 33 53 Page 1 08/20/2020
INTERNATIONAL ORGANIZATION FOR STANDARDIZATION (ISO)
ISO 9001 (2008; Corr 1 2009) Quality Management Systems- Requirements
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA 250 (2018) Enclosures for Electrical Equipment (1000 Volts Maximum)
NEMA PE 1 (2012; R 2017) Uninterruptible Power Systems (UPS) - Specification and Performance Verification
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2017; ERTA 1-2 2017; TIA 17-1; TIA 17-2;
TIA 17-3; TIA 17-4; TIA 17-5; TIA 17-6;
TIA 17-7; TIA 17-8; TIA 17-9; TIA 17-10;
TIA 17-11; TIA 17-12; TIA 17-13; TIA
17-14; TIA 17-15; TIA 17-16; TIA 17-17 )
National Electrical Code
U.S. DEPARTMENT OF ENERGY (DOE)
Energy Star (1992; R 2006) Energy Star Energy Efficiency Labeling System (FEMP)
U.S. FEDERAL COMMUNICATIONS COMMISSION (FCC)
FCC Part 15 Radio Frequency Devices (47 CFR 15)
UNDERWRITERS LABORATORIES (UL)
UL 1778 (2014; Reprint Sep 2017) UL Standard for Safety Uninterruptible Power Systems
1.2 DEFINITIONS
Unless otherwise specified or indicated, electrical and electronics terms used in these specifications, and on the drawings, are as defined in
IEEE 100.
1.3 SUBMITTALS
Government approval is required for submittals. the Government. Submit in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
UPS Drawings;
UPS Installation;
SD-03 Product Data
UPS Module;
Technical Requirements UPS System
SECTION 26 33 53 Page 2
Spare Parts;
SD-06 Test Reports
Work Plan;
Factory Test Plan;
Factory Test Report;
SD-09 Manufacturer's Field Reports
Initial Inspection and Tests;
Performance Tests;
Performance Test Plan;
Performance Test Report;
SD-10 Operation and Maintenance Data
UPS Operation and Maintenance, Data Package 5;
Submit operation and maintenance data in accordance with Section 01 78 23 OPERATION AND MAINTENANCE DATA and as specified herein.
SD-11 Closeout Submittals
Installation
1.4 OPERATION AND MAINTENANCE MANUALS
1.4.1 Additions to UPS Operation and Maintenance Manuals
In addition to requirements of SD-10 Data Package 5, include the followings on the actual UPS system provided:
a. An outline drawing, front, top, and side views.
b. Prices for spare parts and supply list.
c. Routine and field acceptance test reports.
d. Date of Purchase.
e. Corrective maintenance procedures.
1.5 QUALITY ASSURANCE
The manufacturer must have a documented quality assurance program including:
a. Inspections of incoming parts, modular assemblies and final product.
b. Final test procedure for the product including proof of performance specifications.
SECTION 26 33 53 Page 3
c. The on-site test procedure includes an inspection of controls and indicators after installation of the equipment.
d. ISO 9001 quality certification.
1.5.1 UPS Drawings
Drawings are to include the following: Detail drawings consisting of a complete list of equipment and materials, manufacturer's descriptive and technical literature, battery sizing calculations per IEEE 485, installation instructions, single-line diagrams, elevations, layout drawings, and details required to demonstrate that the system has been coordinated and will function properly as a unit.
a. One-line diagram.
b. Outline drawings including front elevation, section views, footprints, and overall dimensions.
c. Manufacturer's descriptive and technical literature.
d. Markings and NEMA nameplate data.
e. Battery sizing calculations per IEEE 485.
f. Wiring and control diagrams with terminals identified, and indicating prewired interconnections between items of equipment and interconnection between the items.
g. Complete list of materials and equipment covering major components.
Ensure the bill of material and the schematic have a direct correlation between items in order to easily identify the various components.
h. Details required to demonstrate that the system has been coordinated and will function properly as a unit.
1.5.2 UPS Installation
Include wiring diagrams and installation details of equipment indicating proposed location, layout and arrangement, control panels, accessories, piping, ductwork, and other items that must be shown to ensure a coordinated installation. Wiring diagrams are to identify circuit terminals and indicate the internal wiring for each item of equipment and the interconnection between each item of equipment. Drawings are to indicate adequate clearance for operation, maintenance, and replacement of operating equipment devices. Submittals include the nameplate data, size, and capacity. Submittals also include applicable federal, military, industry, and technical society publication references.
1.5.3 Work Plan
Submit schedules of dates for factory tests, installation, field tests, and operator training for the UPS system. Furnish a list of instrumentation equipment for factory and field test reports.
1.5.4 Factory Test Plan
Submit factory test plans and procedures at least 21 calendar days prior to
SECTION 26 33 53 Page 4 the tests being conducted. Provide detailed description of test procedures, including test equipment and setups, to be used to ensure the UPS meets the performance specification and explain the test methods to be used. Provide test procedures that include the test required under the paragraph entitled "Factory Testing."
1.5.5 Factory Test Report
Submit a factory test report within 21 calendar days after completion of tests. Receive approval of test prior to shipping unit. Factory test reports are to be signed by an official authorized to certify on behalf of the UPS manufacturer of that the system meets specified requirements in accordance with the requirements set forth in paragraph entitled "Factory Testing". Provide test reports in booklet form tabulating factory tests and measurements performed, upon completion and testing of the installed system. Reports are to state the Contractor's name and address, the name of the project and location, and list the specific requirements which are being certified.
1.5.6 Performance Test Plan
Submit test plans and procedures at least 15 calendar days prior to the start of field tests. Provide detailed description and dates and times scheduled for performance of tests, and detailed description of test procedures, including test equipment (list make and model and provide functional description of the test instruments and accessories) and setups of the tests to be conducted to ensure the UPS meets the performance specification. Explain the test methods to be used. Provide test procedures that include the tests required under the paragraph entitled "Performance Tests."
1.5.7 Performance Test Report
Submit report of test results as specified by paragraph entitled "Performance Tests" within 15 calendar days after completion of tests.
Field test reports are to be signed by an official authorized to certify on behalf of the UPS manufacturer that the system meets specified requirements in accordance with the requirements set forth in paragraph entitled "Performance Tests". Provide test reports in in booklet form tabulating factory tests and measurements performed, upon completion and testing of the installed system. Reports are to state the Contractor's name and address, the name of the project and location, and list the specific requirements which are being certified.
1.5.8 Regulatory Requirements
In each of the publications referred to herein, consider the advisory provisions to be mandatory, as though the word, "shall" had been substituted for "should" wherever it appears. Interpret references in these publications to the "authority having jurisdiction," or words of similar meaning, to mean the Contracting Officer. Provide equipment, materials, installation, and workmanship in accordance with the mandatory and advisory provisions of NFPA 70 unless more stringent requirements are specified or indicated.
1.5.8.1 Reference Standard Compliance
Where equipment or materials are specified to conform to industry and technical society reference standards of the organizations such as American
SECTION 26 33 53 Page 5
National Standards Institute (ANSI), American Society for Testing and Materials (ASTM), National Electrical Manufacturers Association (NEMA), Underwriters Laboratories (UL), and Association of Edison Illuminating Companies (AEIC), submit proof of such compliance. The label or listing by the specified organization will be acceptable evidence of compliance.
1.5.8.2 Independent Testing Organization Certificate
In lieu of the label or listing, submit a certificate from an independent testing organization, competent to perform testing, and approved by the Contracting Officer. The certificate is to state that the item has been tested in accordance with the specified organization's test methods and that the item complies with the specified organization's reference standard.
1.5.9 Standard Products
Provide materials and equipment that are products of manufacturers regularly engaged in the production of such products which are of equal material, design and workmanship and:
a. Have been in satisfactory commercial or industrial use for 2 years prior to bid opening including applications of equipment and materials under similar circumstances and of similar size.
b. Have been on sale on the commercial market through advertisements, manufacturers' catalogs, or brochures during the 2-year period.
c. Where two or more items of the same class of equipment are required, provide products of a single manufacturer; however, the component parts of the item need not be the products of the same manufacturer unless stated in this section.
d. The service organization is to be, in the opinion of the Contracting Officer, reasonably convenient to the site.
e. Provide new parts and materials comprising the UPS system from the current manufacture, of a high grade and free of defects and imperfections, and has not been in prior service except as required during aging and factory testing.
1.5.9.1 Alternative Qualifications
Products having less than a 2-year field service record will be acceptable if a certified record of satisfactory field operation for not less than 6000 hours, exclusive of the manufacturers' factory or laboratory tests, is furnished.
1.5.9.2 Material and Equipment Manufacturing Date
Products manufactured more than 6 months prior to date of delivery to site are not acceptable.
1.6 DELIVERY AND STORAGE
Protect equipment placed in storage from humidity and temperature variations, moisture, water intrusion, dirt, airborne corrosives, or other contaminants. In harsh environments where temperatures exceed non-operational parameters established within this specification, provide an environmentally controlled equipment storage facility to ensure
SECTION 26 33 53 Page 6 temperature parameters are within equipment specification. Provide documentation of same to the Government when storage is implemented.
PART 2 PRODUCTS
2.1 SYSTEM DESCRIPTION
Provide continuous duty, three-phase, solid state, on-line double conversion reverse transfer static UPS(s). The UPS by means of solid state conversion techniques, must provide continuous regulated AC power to its output terminals, while operating from an input power source, cabinet or rack-mounted direct current (DC) storage battery or other approved means.
The performance of the UPS must not be degraded when operating without a system battery, provided the input AC source is within tolerance. Provide an UPS system that conforms to UL 1778 and consists of UPS module, battery system, battery protective device, system cabinet, controls and monitoring, system protective devices, means of isolating the UPS system from the critical load, and remote monitoring interfaces. Connect input ac power the normal source ac input of the UPS module. Connect battery to the dc input of the UPS module through the battery protective device. The following configuration is used:
a. Non-Redundant.
(1) Single Module. On-line, single module UPS configuration capable of supplying power to the total load, with bypass availability.
(2) Parallel Multi-Module. Two or more UPS modules, of the same size, on-line, operating in parallel, with enough capacity to supply the total load.
b. Redundant System.
(1) Isolated Redundant System (Segmented Redundant or Hot Standby).
One unit on-line supporting the load, while the other unit is operating to provide the bypass source.
(2) Parallel Redundant System. Two or more UPS modules, of the same size, on-line, operating in parallel, with more capability than is required to support the total load. If any unit fails, the remaining unit or units is able to support the critical load.
(3) Split Bus System. Two parallel redundant systems that may be operated separately or through a tie breaker for increased redundancy. Each UPS system on either side of the split bus is able to support the total critical load.
(4) Distributed Redundant System. Distributed redundant configurations is also called tri-redundant. The basis of this design uses three or more UPS modules with independent input and output feeders. The independent output buses are connected to the critical load via multiple PDUs.
c. Scalable Units.
(1) Scalable Unit Non-Redundant. Non-redundant:scalable unit consists of a UPS system module with one or more power modules. The power modules provided are all required to handle the critical load.
(2) Scalable Unit Internal Redundant. Internal Redundant: scalable
SECTION 26 33 53 Page 7 unit consists of a UPS system module with more than one power module. There is at least one additional power module that is not required to handle the load within the system. The additional power module or power modules can be sized to handle only part of the critical load or all the critical load. This is not a true parallel redundant system system since it still uses one UPS system module.
(3) Scalable Unit Redundant. Redundant:scalable unit consists of a UPS system module with one or more power modules. The number of power modules can be to just support the load or also have at least one extra power module to internal redundancy. This UPS system module is parallel with a matching scalable unit previously discussed under "Redundant System".
2.2 MODES OF OPERATION
2.2.1 Normal
The UPS module rectifier/charger must convert the incoming ac input power to dc power for the inverter and for float charging the battery. The inverter continuously coverts the dc power to ac power to supply the critical load. The inverter output must synchronize with the bypass ac power source, provided that the bypass ac power source is within the specified voltage and frequency range.
2.2.2 Battery - Emergency Operation (Loss or deviation of AC Input Power)
Whenever the ac input power source deviates from the specified tolerances including complete failure, the inverter must draw power from the battery system and supply AC power to the critical load without any interruption or switching transient. The battery system must supply power to the inverter for a minimum protection time of 30 minutes or until return of ac input source. Provide an audible alarm to indicate the UPS is on battery and provide provisions for a remote alarm signal to be sent via the communication network and a relay output, allowing startup of a secondary power source or orderly shutdown of the critical load.
2.2.3 Failure of AC Input Power to Return
If the ac input power fail to return before the battery voltage reaches the discharge limit, then the UPS system must disconnect from the critical load to safeguard the battery.
2.2.4 Recharge
Upon restoration of normal power to the UPS unit, the input converter and output inverter must simultaneously recharge the batteries and provide regulated power to the critical load.
2.2.5 Transfer to Static Bypass AC Power Source
When the UPS controller senses an overload, two or more inverter shutdown signals or degradation of the inverter output, the static bypass switch automatically transfers the critical load from the inverter output to the bypass ac power source without an interruption of power. If the static bypass ac power source is outside of specified tolerance limits, the UPS and the critical load shut down. Transfer to static bypass can also be done manually (requested bypass). Transfer to bypass does not take place
SECTION 26 33 53 Page 8 under these conditions: 100% stepload; and, loss or return of input power, momentary sags, surges or spikes on the input to the UPS.
When the UPS controller senses an overload, two or more inverter shutdown signals or degradation of the inverter output, the static bypass switch automatically transfers the critical load from the inverter output to the bypass ac power source without an interruption of power only if the connected load exceeds the capacity of the remaining on-line modules. If the static bypass ac power source is outside of specified tolerance limits, the UPS and the critical load shut down. Transfer to static bypass can also be done manually (requested bypass). Transfer to bypass does not take place under these conditions: 100% stepload; and, loss or return of input power, momentary sags, surges or spikes on the input to the UPS.]
2.2.6 Transfer to Inverter
Provide a static bypass switch that is capable of automatically transferring the load back to the inverter output after the inverter overload condition has returned to normal conditions. Transfer only occurs once the two sources are synchronized. UPS system logic is to monitor the number of retransfer's within any one-hour period and is to allow 1 to 3 transfers in order to prevent cyclical transfers caused by overloads.
2.2.7 Maintenance Bypass
Provide the system with an external make-before-break maintenance bypass cabinet/panel to electrically isolate the UPS during routine maintenance and service. Manual transfer to the maintenance bypass circuit transfers the critical load from the inverter output to the bypass ac power source without disturbing the critical load bus.
2.2.8 Off-Battery (Battery Maintenance)
Provide a battery protective device which disconnects the battery from the rectifier/charger and inverter for maintenance. The device may be located external to the UPS cabinet. The UPS module continues to function and meet the performance criteria specified except for the battery back-up time function.
2.2.9 Failure of a Module
In a redundant configuration, failure of one module causes that module to be disconnected from the system critical load bus by its internal protective devices and its individual output protective device. Remaining module(s) are to continue to carry the load.
2.2.10 UPS Module Servicing
Provide a means the manually disconnect the UPS modules from the critical load bus for maintenance without disturbing the critical load bus.
2.2.11 Component Performance
Do not exceed 75% of the working voltage and current ratings as established by the manufacturer on solid-state power components and electronic devices. Do not exceed 75% of the operating temperature of solid-state component sub-assemblies. Use computer grade electrolytic capacitors and operate at no more than 95% of the voltage rating at the rectifier charging voltage.
SECTION 26 33 53 Page 9
2.3 GENERAL UPS SYSTEM COMPONENTS AND FABRICATION
2.3.1 Semiconductor Fusing
Protect power semiconductors with fast-acting fuses to prevent cascaded or sequential semiconductor failures. Bolt fuses at both ends to bus bars to ensure mechanical and electrical integrity. Indicator lamp or display panel denoting blown fuse conditions must be readily observable by the operator without removing panels or opening cabinet doors.
2.3.2 EMI/RFI Protection
Provide an UPS that complies with and is labeled compliant, with FCC Part 15, Subclass B, Class A.
2.3.3 Internal Wiring
Wiring practices, materials, and coding must be in accordance with the requirements of NFPA 70, OSHA, UL 1778, and other applicable standards.
Protect wire runs in a manner which separates power and control wiring.
Provide control cabling that is at least No. 16 AWG extra-flexible stranded copper. Logic-circuit wiring may be smaller. Provide ribbon cables that are at least minimum No. 22 AWG. Provide control wiring with permanently attached wire numbers.
2.3.4 Internal Assembly
The printed circuit board (PCB) subassemblies are to be mounted in pull-out swing-out trays where feasible. Provide cable connections to the trays that are sufficiently long to allow easy access to all components.
Where not feasible to mount PCB subassemblies in pull-out or swing-out trays, then mount them firmly mounted inside the enclosure. Monitor every PCB subassembly. Include self-test and diagnostic circuitry in the logic circuits such that a fault can be isolated down to the PCB subassembly level. When used, control logic cards are to have test points or logic indicators on the front edge of the control logic card and be labeled.
2.3.5 Cable Lugs and Terminations
2.3.5.1 Cable Lugs
Provide appropriate compression type lugs or pre-drilled bus bars on all ac and dc power connections to the UPS system and battery as required.
Aluminum or bare copper cable lugs are not suitable.
2.3.5.2 Terminations
Supply terminals for making power and control connections. Provide terminal block for field wiring terminals. Provide terminal blocks that are the heavy-duty, strap-screw type or screw terminals that are integrated into removable plugs. Locate terminal blocks for field wiring in one place in each module. Extend control wiring to the terminal block location. Any terminal point is limited to land a maximum of two wires. Where control wiring is attached to the same point as power wiring, Provide a separate terminal where control wiring is attached to the same point as power wiring, . If bus duct is used, provide bus stubs where bus duct enters cabinets.
SECTION 26 33 53 Page 10
2.3.6 Cabinets
Install the UPS system in cabinets of heavy-duty structure meeting the NEMA PE 1 standards for floor mounting. Provide a structurally adequate UPS module that can be forklift handled and lifted. Provide removable lifting eyes on top of each cabinet. Provide the UPS module cabinet with hinged and key lockable doors on the front only and with assemblies and components accessible from the front. Provide dead-front construction behind the door for those UPS module cabinets that are not lockable. Operating controls are to be located outside the locked doors. Install input, output, and battery cables through the top or bottom of the cabinet.
2.3.6.1 Factory Applied Finish
Provide electrical equipment with a factory-applied painting systems which, as a minimum, meets the requirements of NEMA 250 corrosion-resistance test.
2.3.6.2 Drawout Assemblies
Provide a means of lifting, either and overhead device or a hoisting device for drawout assemblies weighing 50 lbs or more. Device can either be part of the UPS or a separate portable device that can be used to perform the lifting.
2.3.7 Manufacturer's Nameplates
Provide a nameplate for each item of equipment bearing the manufacturer's name, address, model number, and serial number securely affixed in a conspicuous place; the nameplate of the distributing agent will not be acceptable.
2.3.8 Field Fabricated Nameplates
ASTM D709. Provide laminated plastic nameplates for each equipment enclosure, relay, switch, and device; as specified or as indicated on the drawings. Provide an inscription on each nameplate that identifies the name of the item, calculated short circuit rating with date, and source of power e.g. 'Panel A in Electrical Room 103'. Provide nameplates that are made of melamine plastic, 0.125 inch thick, white with blackcenter core.
Provide the nameplate with a surface that is matte finished and that has square corners.. Accurately align lettering and engrave into the core.
Provide nameplates that are at least 1.0 by 2.5 inches with a minimum lettering size of 0.25 inch high normal block style.
2.3.9 Safety
Provide UPS with instruction plates including warnings and cautions, suitably located, and describing any special or important procedures to be followed in operating and servicing the equipment. Provide control panel displays, which also provide warning messages prior to performing a critical function.
2.3.9.1 Maintenance Isolation
All energized terminals, both AC and DC, and control voltage exposed points are to be insulated or enclosed to ensure the safety of maintenance personnel. Provide the system with the ability to isolate the static switch to enable repair when the UPS is bypassed.
SECTION 26 33 53 Page 11
2.3.9.2 Remote Emergency Power Off (REPO) Switch
Provide a remote emergency power off switch that is separate from the UPS.
Provide a red, pushbutton with a cover with a label indicating "UPS Emergency Power Off". The switch disconnects all breakers or contactors including battery, input, output, and bypass breakers when activated.
2.4 TECHNICAL REQUIREMENTS UPS SYSTEM RATINGS
Unless stated otherwise, the parameters listed are under full output load over the range of 0.9 lagging power factor to 0.9 leading power factor, with batteries fully charged and floating on the dc bus and with nominal input voltage.
2.4.1 UPS SYSTEM LOAD PROFILE
Provide an UPS system that is compatible with the load characteristics defined in the LOAD PROFILE below and load configuration. The UPS system is to provide compensation for UPS/load interaction problems resulting from nonlinear loads or transformer and motor inrush.
LOAD PROFILE
Type of load:
Data processing equipment. Size of load: 60kVA, _208voltage, 0.9power factor.
2.4.2 System Requirements
The UPS is to support and maintain full battery charging under the following conditions: indicated environmental conditions, a.c input voltage range, air filters blocked up to 50% and a single failed fan. The UPS size and configuration is indicated below.
Scalable Units. Each UPS power module is rated 20 kVA. Provide at least 3 bank of UPS power modules to handle the system load.
2.4.3 Battery Capacity
Discharge time to end voltage: 30 minutes, at 77 degrees F. Provide a battery that is capable of delivering 125 percent of full rated UPS kW load at 0.9 power factor at initial start-up.
2.4.4 Static Switch
150 amperes (continuous duty)
2.4.5 Short Circuit Withstand Rating
Braced for at least 20000 amperes symmetrical interrupting capacity.
2.4.6 AC Input
a. Voltage 480 volts line-to-line.
b. Number of phases: Three-phase + neutral configuration..
c. Voltage Range: Plus 10 percent, minus 15 percent nominal (no battery discharge), without affecting battery float voltage or output voltage.
SECTION 26 33 53 Page 12
d. Frequency: 60 Hz, plus or minus 5 percent.
e. Total harmonic current distortion (THD) reflected into the primary line: 5 percent maximum at full load.
f. Input surge protection: per IEEE C62.41.1 and IEEE C62.41.2, meeting IEEE C62.41 requirement of Category B3 6kV, 100k Hz ring wave and 6kV, combined wave.
g. Input power factor: Lagging from 1-100 percent load.
2.4.7 AC Output
a. Voltage 208 volts line-to-line, 120 volts line-to-neutral.
b. Number of phases: Three-phase + neutral configuration.
c. Voltage regulation:
(1) Balanced load: Plus or minus 1.0 percent.
(2) 50 percent load imbalance, phase-to-phase: Plus or minus 2 percent.
(3) 100 percent load imbalance, phase-to-phase Plus or minus 3 percent.
(4) Voltage drift: Plus or minus 1 percent over any 30 day interval (or length of test) at stated ambient conditions found in paragraph Environmental Conditions.
d. Voltage adjustment: Plus or minus 5 percent.
e. Frequency: 60 Hz.
f. Frequency regulation: Plus or minus 0.1 percent, when on internal oscillator. Internal oscillator is to be temperature compensated.
g. Frequency drift: Plus or minus 0.1 percent over any 24 hour interval (or length of test) at stated ambient conditions when on internal oscillator.
h. Harmonic content (RMS voltage): Provide a system that meets the following voltage THD levels: maximum of 4% RMS total,2 percent total with 100 percent on any single harmonic (linear load) and 5 percent RMS total for up to 100 percent nonlinear load.
i. Load power factor operating range (without derating): 0.9 leading to
0.9 lagging.
j. Phase angle displacement/imbalance:
(1) Balanced load: 120 degrees plus or minus 0.5 degree of bypass input.
(2) 50 percent load imbalance phase-to-phase: 120 degrees plus or minus 3 degrees of input.
SECTION 26 33 53 Page 13
k. Inverter overload capability (at full voltage with plus or minus 2 percent regulation) (excluding battery):
(1) 125 percent load for 10 minutes.
(2) 150 percent load for 60 seconds.
(3) Fault clearing. Provide an UPS that is able to maintain output current during a fault condition for 20 cycles if bypass is unavailable or 1 cycle with bypass available. If the fault is not cleared and a bypass is available, the UPS is to transfer to bypass without interruption to clear the fault.
l. Load sharing of parallel modules: Plus or minus 5 percent at full rated system load.
m. Bypass Overload Capability.
2.4.8 Transient Response
2.4.8.1 Voltage Transients
a. 100 percent load step: Plus or minus 5 percent.
b. Loss or return of ac input: Plus or minus 1 percent.
c. Automatic transfer of load from UPS to bypass: Plus or minus 1 percent.
d. Manual retransfer of load from bypass to UPS: Plus or minus 5 percent.
e. Response time: Recovery to 1 percent of nominal within 20 milliseconds where there was a maximum deviation from nominal system output of volts plus or minus 5 percent.
2.4.8.2 Frequency
a. Transients: Plus or minus 0.6 Hz maximum.
b. Slew Rate: under all conditions of operation, provide 0.4 to 1.0 Hz per second.
2.4.9 Efficiency
a. Minimum Single-Module Efficiency: 94 percent at full load kW and 92 percent at 50 percent load.
b. Minimum System Efficiency: 93 percent at full system load kW.
c. Provide Energy Star labeled battery charging systems and AC-DC/AC-AC power supplies. Provide proof of Energy Star label for battery charging systems and AC-DC/AC-AC power supply products.
2.4.10 Energy Saving Mode
Provide the UPS with an energy saving mode that operates by having the
SECTION 26 33 53 Page 14 inverter charged and batteries on at all times, while the main power to the output is through the static bypass switch. When a power problem is sensed, the system is to operate in double-conversion mode and revert to energy saving mode after a pre-set period of time. Maximum transition time is 2 miliseconds.
2.5 UPS MODULE
2.5.1 General Description
UPS module consists of an input converter, output converter, with associated transformers, synchronizing equipment, protective devices, surge suppression, and accessories as required for operation.
2.5.1.1 Interchangeability
The subassemblies in one UPS module are to be interchangeable with the corresponding modules within the same UPS, and from one UPS system to another of identical systems.
2.5.1.2 Rectifier/Charger Unit
Scalable, expandable modular input converts for the system are to be housed within removable power modules. Input converters control the power from the mains input of the system, provide the necessary UPS power for precise regulation of the DC bus voltage, battery charging, and main inverter regulated output power.
2.5.1.2.1 Input Protective Device
Provide the rectifier/charger unit with an input protective device. Size the protective device to accept simultaneously the full-rated load and the battery recharge current. Provide a protective device that is capable of shunt tripping and has an amperes symmetrical interrupting rating of 20000.
Provide the protective device with an under-voltage release to open automatically when the control voltage is lost.
2.5.1.2.2 Power Walk-In
Input convert is to have an adjustable soft-start (either by manufacturer or owner), capable of limiting the input current form 0 percent to 100 percent of the input over a default 10 second period when returning to ac input bus from battery operation. The change in current over time is to be done in a linear manner.
2.5.1.2.3 Sizing
Size the rectifier/charger unit for the following two simultaneous operating conditions:
a. Supplying the full rated load current to the inverter.
b. Recharging a fully-discharged battery to 90 percent of rated ampere-hour capacity within ten times the discharge time after normal ac power is restored.
2.5.1.2.4 AC Input Current Limiting
Provide a circuit to the input converter that controls and limits the
SECTION 26 33 53 Page 15 current draw form utility to 130 percent of the rated UPS output. During conditions where input current limit is active, the UPS system is to be able to support 100 percent of the load, charge the batteries at 10 percent of the UPS output rating, and provide voltage regulation with mains deviation of +15/-5 percent.
Second step current limiting: Provide the rectifier/charger unit with a second-step input current limit. Provide a separately adjustable second-step current limit that is adjustable from 85 percent to 125 percent of the maximum discharge current with initial setting at 100 percent.
Activate the second-step current-limit circuit by a dry contact signal from the generator.
2.5.1.2.5 Battery Charging Current
a. Primary current limiting: Battery-charging current is to be voltage regulated and current limited. Provide a separately adjustable battery-charging current limit that is adjustable from 1 percent to 20 percent of the maximum discharge current. Set the limit at the factory to 10 percent. After the battery is recharged, the rectifier/charger unit maintains the battery at full float charge until the next operation under input power failure. Battery charger is capable of providing equalizing charge to the battery.
b. Second step current limiting: The rectifier/charger unit is also to have a second-step battery current limit. Provide a separately adjustable second-step current limit that is adjustable from 0 percent to 20 percent of the maximum discharge current with initial setting at 1 percent. The second-step current-limit circuit is activated by a dry contact signal from the generator set controls and it will prevent normal rate battery recharging until utility power is restored.
2.5.1.2.6 DC Ripple (Output Filter)
Rectifier/charger unit is to minimize ripple current and voltage supplied to the battery; the ripple voltage into the battery is not to exceed 1 percent RMS of the float voltage. Ensure the AC ripple voltage of the rectifier DC output does not exceed 0.5 percent of the float voltage.
2.5.1.2.7 DC Voltage Adjustment
Provide a manual means at the rectifier/charger unit that allows for adjusting the dc voltage for battery equalization in order to provide voltage within plus 10 percent of nominal float voltage.
2.5.1.2.8 Battery Isolation Protective Device
Provide the module or external battery system with a dc protective device to isolate the module from the battery system. The protective device size and interrupting rating are as required by system capacity and is to incorporate the trip required by circuit design. Provide the protective device with a provision for locking in the "off" position.
2.5.1.2.9 Battery Equalize Charge
Equalize charge timer is to provide an equalizing charge automatically to the battery after a 30 second or longer utility outage. The equalize charging time is to be adjustable form 0-72 hours. Provide a manual override for the automatic equalize circuit.
SECTION 26 33 53 Page 16
2.5.2 General Description
UPS module consists of a rectifier/charger unit and a 3-phase inverter unit with their associated transformers, synchronizing equipment, protective devices, surge suppression, input isolation transformer, and accessories as required for operation.
2.5.2.1 Interchangeability
The subassemblies in one UPS module are to be interchangeable with the corresponding modules within the same UPS, and from one UPS system to another of identical systems.
2.5.2.2 Rectifier/Charger Unit
Provide a solid state rectifier/charger unit that converts alternating current to direct current, and provides regulated direct current to the dc bus, supplying power to the inverter and charging the battery plant.
2.5.2.2.1 Input Protective Device
Provide the rectifier/charger unit with an input protective device. Size the protective device to accept simultaneously the full-rated load and the battery recharge current. Provide a protective device that is capable of shunt tripping and has an amperes symmetrical interrupting rating of 20000.
Provide the protective device with an under-voltage release to open automatically when the control voltage is lost.
2.5.2.2.2 Input Isolation Transformer
The rectifier unit is to use a dry-type, isolated-winding power transformer. The transformer's hottest spot winding temperature must not exceed the temperature limit of the transformer insulation material when operating at full load. Provide a transformer with Class H, 150 degrees C rise insulation. Transformer connections are to be accessible from the front. If there is a separate transformer cabinet, it is is to match the UPS cabinet and attach to it. Provide a Department of Energy CSL-3 transformer.
2.5.2.2.3 Power Walk-In
Protect the rectifier/charger unit with a power walk-in feature such that when ac power is returned to the ac input bus, the total initial power requirement will not exceed 20 percent of the rated full load current. This demand is to gradually increase to 100 percent of the rated full load current plus the battery charging current over the specified time interval.
2.5.2.2.4 Sizing
Size the rectifier/charger unit for the following two simultaneous operating conditions:
a. Supplying the full rated load current to the inverter.
b. Recharging a fully-discharged battery to 90 percent of rated ampere-hour capacity within ten times the discharge time after normal ac power is restored.
2.5.2.2.5 AC Input Current Limiting
Provide a circuit on the rectifier/charger to limit AC input current to an adjustable level of 100 percent to 125 percent with a factory setting at 100
SECTION 26 33 53 Page 17 percent.
Second step current limiting: Provide the rectifier/charger unit with a second-step input current limit. Provide a separately adjustable second-step current limit that is adjustable from 85 percent to 125 percent of the maximum discharge current with initial setting at 100 percent.
Activate the second-step current-limit circuit by a dry contact signal from the generator.
2.5.2.2.6 Battery Charging Current
a. Primary current limiting: Battery-charging current is to be voltage regulated and current limited. Provide a separately adjustable battery-charging current limit that is adjustable from 1 percent to 20 percent of the maximum discharge current. Set the limit at the factory to 10 percent. After the battery is recharged, the rectifier/charger unit maintains the battery at full float charge until the next operation under input power failure. Battery charger is capable of providing equalizing charge to the battery.
b. Second step current limiting: The rectifier/charger unit is also to have a second-step battery current limit. Provide a separately adjustable second-step current limit that is adjustable from 0 percent to 20 percent of the maximum discharge current with initial setting at 1 percent. The second-step current-limit circuit is activated by a dry contact signal from the generator set controls and it will prevent normal rate battery recharging until utility power is restored.
2.5.2.2.7 DC Ripple (Output Filter)
Rectifier/charger unit is to minimize ripple current and voltage supplied to the battery; the ripple voltage into the battery is not to exceed 1 percent RMS of the float voltage. Ensure the AC ripple voltage of the rectifier DC output does not exceed 0.5 percent of the float voltage.
2.5.2.2.8 DC Voltage Adjustment
Provide a manual means at the rectifier/charger unit that allows for adjusting the dc voltage for battery equalization in order to provide voltage within plus 10 percent of nominal float voltage.
2.5.2.2.9 Battery Isolation Protective Device
Provide the module or external battery system with a dc protective device to isolate the module from the battery system. The protective device size and interrupting rating are as required by system capacity and is to incorporate the trip required by circuit design. Provide the protective device with a provision for locking in the "off" position.
2.5.2.2.10 Battery Equalize Charge
Equalize charge timer is to provide an equalizing charge automatically to the battery after a 30 second or longer utility outage. The equalize charging time is to be adjustable form 0-72 hours. Provide a manual override for the automatic equalize circuit.
2.5.3 Inverter Unit
Provide a solid-state inverter with sinusoidal output deriving its power from the dc bus (rectifier or battery source) and providing ac power within
SECTION 26 33 53 Page 18 specified limits to the critical load. Inverter is to utilize microprocessor controlled solid state Pulse Width Modulation (PWM) controlled insulated gate bipolar transistor (IGBT) power transistor technology to shape the ac output.
Provide an output converter that constantly develops the UPS output voltage waveform by converting the dc voltage to ac voltage through a set of semiconductor power converters. In both normal operation and battery operation, the output inverters are creating and output voltage independent of the mains input voltage. Input anomalies such as brown-outs, spikes, surges, sags and outages do not affect the amplitude or sinusoidal nature of the output voltage sine wave of the inverters.
Include a bypass phase synchronization window adjustment to optimize compatibility with local engine-generator-set power source.
2.5.3.1 Output Overload
Provide an inverter that is able to sustain an overload as specified across its output terminals. The inverter is to remain on and continue to operate within rated parameters, with inverse-time overload shutdown protection.
If the overload condition persists beyond the rated parameters of the inverter, the load is to be transferred to the bypass source where the inverter disconnects automatically from the critical load bus. If the bypass source is not available and the overload/fault condition continues, the inverter is to current limit for the time as determined by the manufacturer and then shut down to protect the internal components.
Provide the output inverter with overload capabilities that allows steady state overload conditions of up to 150 percent of system capacity to be sustained by for 30 seconds in normal and battery operation. If the overload condition persists beyond the rated parameters of the inverter, the load is to be transferred to the bypass source where the inverter disconnects automatically from the critical load bus.
2.5.3.2 Output Protective Device
Provide an output protective device that is capable of opening on an applied control signal and has the proper frame size and trip rating to supply overload current as specified. Provide the external output protective device with provision for locking in the "off" position. The inverter output protective device works in conjunction with the bypass protective device for both manual and automatic load transfers to and from bypass power.
2.5.3.3 Output Transformer
The inverter output transformer is harmonic mitigating transformer type.
capable of handling up to K-13 nonlinear loads as described in IEEE C57.110.
Provide a transformer that meets the requirements for Department of Energy CSL-3.
2.5.4 External Protection
Provide the UPS module with built-in self-protection against undervoltage, overvoltage, overcurrent and surges introduced on the ac input source and/or the bypass source. Provide the UPS with built-in self-protection against overvoltage and voltage surges introduced at the output terminals by paralleled sources, load switching, or circuit breaker operation in the critical load distribution system.
SECTION 26 33 53 Page 19
2.5.5 Internal Protection
Provide the UPS module with the ability to be self-protected against overcurrent, sudden changes in output load and short circuits at the output terminals.