This document is an amendment to a government design solicitation for the installation of fire alarm equipment at multiple buildings on Naval Station Norfolk and Craney Island in Virginia. The work includes modifying design notes and drawings, adding demolition notes for master boxes, and revising specification sections. The solicitation is specifically for the 8(a) Multiple Award Construction Contract (MACC) contractors in the Hampton Roads area of Virginia under Contract Nos. N40085-23-D-0030 through N40085-23-D-0038 and N40085-24-N0052. The amendment includes details on the work to be performed at each building, such as removing existing master boxes and associated conduit, patching walls, and reseeding disturbed areas. The amendment also lists the revised drawings and specification sections accompanying the design changes.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PWD Norfolk, Facilities Engineering and Acquisition Division Page 1 of 2

Design Revision 01 eProjects Work Order Number: 1793709

Construction Contract Number: N/A

Building: Multiple Buildings

Project Title: Install Fire Alarm Equipment

Date: August 2, 2024

Design Revision Purpose

1. Modifying notes and dimensions for walls sections and roof details.

2. Adding demolition notes for master boxes.

3. Revising spec sections.

Drawing Revisions

SECTION 00 01 15 LIST OF DRAWINGS

1.2 CONTRACT DRAWINGS

On drawing 12,911,697 (FD100) add the following notes:

1. At wall mounted master box, cut existing metal conduit 4” below existing ground surface and remove exposed wiring at Building CI-87. Remove loose debris and clean before infilling holes at existing wall after master box removal. Prep existing wall at master box removal area and provide 1 coat prime, and 2 coats of exterior finish matching existing (for bidding purposes assume 20 square feet). (Typical of 1 master box).

2. At wall mounted master box, cut existing metal conduit flush with existing hard surface and remove exposed wiring at building CI-72. Remove loose debris and clean before infilling holes at existing wall after master box removal. Prep existing wall at master box removal area, provide 1 coat prime, and 2 coats of exterior finish matching existing (for bidding purposes assume 35 square feet). (Typical of 1 master box).

3. At pole mounted master box, cut existing metal conduit 4” below existing ground surface and remove exposed wiring. Remove 6” ± diameter timber pole. Backfill timber pole excavation with crushed stone or sand. Refer to keynote No. 2 on drawing FD100 for approximate location. (Typical of 1 master box).

4. At pedestal type master boxes, remove 3’ x 3’ x 6” ± concrete pedestal. Cut existing metal conduit 4” below existing ground surface and remove exposed wiring. Provide topsoil to fill void and then reseed. Refer to keynote No. 1 on drawing FD100 for approximate locations of master boxes. (Typical of 14 master boxes).

PWD Norfolk, Facilities Engineering and Acquisition Division Page 2 of 2

The following drawings are revised as of August 2, 2024, and accompany this Design Revision:

NAVFAC Dwg. No. Title

General

12,911,641 (GI003) General Notes and Symbols

Architectural

12,911,670 (AE301) CI-288 Wall Sections 12,911,671 (AE302) CI-294 Wall Sections 12,911,673 (AE304) A-58 Wall Sections 12,911,674 (AE305) CEP-177 Wall Sections 12,911.675 (AE306) CEP-156 Wall Sections 12,911,676 (AE307) WB-200 Wall Sections 12,911,677 (AE308) P-1 Wall Sections 12,911,678 (AE309) CEP-204 Wall Sections 12,911,679 (AE310) Z-140 Wall Sections 12,911,680 (AE311) Z-144 Wall Sections 12,911,682 (AE313) N-26 Wall Sections 12,911,683 (AE501) CI-288 Roof Details 12,911,684 (AE502) CI-294 Roof Details 12,911,685 (AE503) SP-313 Roof Details 12,911,686 (AE504) A-58 Roof Details 12,911,687 (AE505) CEP-177 Roof Details 12,911,688 (AE506) CEP-156 Roof Details 12,911,689 (AE507) WB-200 Roof Details 12,911,690 (AE508) P-1 Roof Details 12,911,691 (AE509) CEP-204 Roof Details 12,911,692 (AE510) Z-140 Roof Details 12,911,693 (AE511) Z-144 Roof Details 12,911,694 (AE512) DS-31 Roof Details 12,911,695 (AE513) N-26 Roof Details

Specification Revisions

PROJECT TABLE OF CONTENTS

Remove spec section “01 42 00 Sources for Reference Publication” from contract documents.

The following spec sections are revised as of August 2, 2024, and accompany this Design Revision:

Spec Number Title

01 35 26 General Safety Requirements 01 45 00.00 20 Quality Control 01 50 00 Temporary Construction Facilities and Controls

DOOR NUMBER

(REFER TO DOOR SCHEDULE)

DOOR TAG

GENERAL PROJECT SYMBOLS

WINDOW TYPE LETTER

WINDOW TYPE TAG

SPECIALITY ITEM NUMBER

SPECIALITY ITEM TAG

PARTITION TYPE DESIGNATION

(REFER TO PARTITION SCHEDULE)

PARTITION TYPE

INDICATOR

PARTITION IN PLAN

A1

A-301

A-401 INTERIOR ELEVATION

INDICATOR

INTERIOR ELEVATION NUMBER

SHEET WHERE DRAWN

EXTERIOR ELEVATION

INDICATOR

ELEVATION NUMBER

DIRECTION OF VIEW

SHEET WHERE DRAWN

A1

A-301

WALL / PARTIAL

BUILDING SECTION

INDICATOR

SECTION NUMBER

SHEET WHERE DRAWN

A1

A-301

BUILDING SECTION

INDICATOR

A1

A-301

BUILDING

A1

A1

A1

B

A1

ROOM

ROOM IDENTIFIER

DETAIL NUMBER

SHEET WHERE DRAWN

DETAIL

INDICATOR

ROOM NAME

ROOM NUMBER

A-901 PHOTOGRAPH

INDICATOR

PHOTOGRAPH NUMBER

SHEET WHERE SHOWN

A1

A-501

VIEW NUMBERSHEET

BACK-REFERENCE

VIEW BACK-REFERENCE

ENLARGED PLAN NUMBERSHEET

BACK-REFERENCE

VIEW BACK-REFERENCE

KEYNOTE INDICATOR

KEYNOTE NUMBER

PLAN NUMBER

A1

SCALE: 1/8" = 1'-0"

PLAN TITLE

A1

A1

A-101

ENLARGED PLAN

SCALE: 1/4" = 1'-0"

A1

DETAIL/SECT/ELEV

SCALE: 1/8" = 1'-0"

A1

A-101

SECTION NUMBER

SHEET WHERE DRAWN

WILLOUGHBY BAY

NAVAL SUPPORT

ACTIVITY

U.S. NAVAL STATION

SEWELLS POINT

NORFOLK

U.S. NAVAL

AIR STATION

CHESAPEAKE BAY

LITTLE CREEK

U.S. NAVAL

AMPHIBIOUS BASE

VA BEACH

OCEANA

NAVAL AIR

STATION

CHESAPEAKE

SOUTHERN BRANCH

EASTERN BRANCH

ST. JULIEN'S CREEK

U.S. NAVAL ANNEX

ELIZABETH RIVER

PORTSMOUTH

U.S. ARMY CRANEY

ISLAND DISPOSAL AREA

NANSEMOND RIVER

WESTERN BRANCH

CRANEY

ISLAND NAVY

DEPOT

PROJECT SITE

NORTH

VICINITY MAP

PROJECT SITE

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

/2

/2

:4

:2

P M

C R e v it

L o c a l F ile s \C

I2

A

R k e s h a w n .s k in n e r.

rv t

GI003

M U

LT

IP

LE

B

U

IL

D

IN

G F

IR

E

A

LA

R M

E Q

U

IP

M E

N T

IN

S

TA

LL

A T

IO

N

G E

N E

R A

L N

O T

E S

A N

D S

Y M

B O

LS

ALP

12,911,641

KES KES

05/24/2024

HAI HUYNH

KESHAWN SKINNER

1793709

N/A

N O

R F

O

LK

, V

IR

G

IN

IA

N

A V

A L

S T

A T

IO

N

N O

R F

O

LK

J. MILLER P.E.

A. PILLO, RA

M

ID

L A

N T

D C

C O

R E

G I0

1 WHERE EXISTING CONSTRUCTION IS DAMAGED BY CONSTRUCTION REQUIRED

BY THESE DOCUMENTS. REPAIR THE DAMAGED ITEM(S) WITH MATERIALS TO

MATCH THE ADJACENT MATERIAL, TEXTURE AND COLOR.

2 FIELD VERIFY EXISTING DIMENSIONS, PRIOR TO ORDERING MATERIALS OR

BEGINNING DEMOLITION.

3 ALL ITEMS NOT SHOWING AS "EXISTING" MUST BE PROVIDED AND INSTALLED

UNDER THE REQUIREMENTS OF THIS CONTRACT.

4 COORDINATE LAY DOWN AREA WITH THE CONTRACTING OFFICER PRIOR TO

THE PRECONSTRUCTION MEETING. THE ALLOWABLE AREA SIZE MUST BE

ESTABLISHED BY THE CONTRACTING OFFICER.

5 MANUFACTURER'S TRADE NAMES LISTED ARE NOT INTENDED TO BE

PROPRIETARY. PRODUCTS OF OTHER MANUFACTURERS WILL BE ACCEPTABLE

PROVIDED THEY MATCH THE COLOR, FINISHES, TEXTURES AND PATTERNS OF

THE MANUFACTURER LISTED, AND MEET THE TECHNICAL REQUIREMENTS OF

THE SPECIFICATIONS.

6 OBSERVE AND MAINTAIN BUILDING AND COMPOUND SECURITY

REQUIREMENTS AS DIRECTED BY THE CONTRACTING OFFICER.

7 CONSTRUCTION WILL BE ACCOMPLISHED IN AND AROUND AREAS WHICH WILL

REMAIN OPERATIONAL. AVOID INTERFERENCE WITH THE OPERATIONAL WORK

ROUTINE. ESCORTS TO BE PROVIDED BY EACH COMMAND.

8 ALL SUBMITTALS REQUIRED BY THESE DRAWINGS OR SPECIFICATIONS MUST

BE SUBMITTED TO THE CONTRACTING OFFICER FOR APPROVAL TO

COMMENCEMENT OF RELATED WORK.

BUILDING CODE:

UNIFIED FACILITIES CRITERIA (UFC) 1-200-01 (20 JUNE 2016)

UNIFIED FACILITIES CRITERIA (UFC) 1-200-02 (01 DEC. 2016)

UNIFIED FACILITIES CRITERIA (UFC) 3-110-03 (01 MAY 2012)

ACCESSIBILITY CODE:

UNIFORM ACCESSIBILITY STANDARDS (UFAS)

AMERICANS WITH DISABILITIES ACT (ADA)

ACCESSIBILITY GUIDELINES FOR BUILDINGS AND FACILITIES

(ADAAG)

MECHANICAL CODE:

INTERNATIONAL MECHANICAL CODE (IMC) 2009

ELECTRICAL CODE:

NFPA 70, NATIONAL ELECTRIC CODE

PLUMBING CODE:

INTERNATIONAL PLUMBING CODE (IPC) 2009

FIRE PREVENTION & LIFE SAFETY CODE:

UNIFIED FACILITIES CRITERIA (UFC) 3-600-01 (15 DEC. 2009)

NFPA 101, LIFE SAFETY CODE

GENERAL NOTES

GOVERNING REGULATIONS

BUILDING LOCATIONS

CRANEY ISLAND

CI-288, CI-294, CI-72, CI-87

NAVAL STATION

SP-313, A-58, CEP-177,

CEP-156, WB-200, P-1,

CEP-204, Z-140,

Z-144, N-26, DS-31*

* = REQUIRES WATER TRANSPORTATION

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

D es ig n R e v is io ns

/0 2/

K E

S

SECOND FLOOR

16'-8"

FIRST FLOOR

0'-0"

HIGH ROOF

32'-8"

VEST

LUNCHROOM

OFFICE

EXISTING ROOF TO REMAIN

EXISTING SUSPENDED ACOUSTICAL

CEILING 8'-0"± AFF

EXISTING SUSPENDED ACOUSTICAL

CEILING 8'-0"± AFF

COAX CABLE IN

METAL CONDUIT

CORE DRILL EXISTING FLOOR

TO ACCOMODATE CONDUIT

INSTALLATION, SEAL PENETRATION

WITH CONTINUOUS

INTUMESCENT SEALANT

RADIO TRANSMITTER,

REFER TO FIRE PROTECTION

DRAWINGS

EXISTING WALL TO REMAIN

AE501

A1

3"

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

/2

/2

:4

:2

P M

C R e v it

L o c a l F ile s \C

I2

A

R k e s h a w n .s k in n e r.

rv t

AE301

M U

LT

IP

LE

B

U

IL

D

IN

G F

IR

E

A

LA

R M

E Q

U

IP

M E

N T

IN

S

TA

LL

A T

IO

N

C I-2

W

A

LL

S E

C T

IO

N

S

ALP

12,911,670

KES KES

05/24/2024

HAI HUYNH

KESHAWN SKINNER

1793709

N/A

N O

R F

O

LK

, V

IR

G

IN

IA

N

A V

A L

S T

A T

IO

N

N O

R F

O

LK

J. MILLER P.E.

A. PILLO, RA

M

ID

L A

N T

D C

C O

R E

A E

3/4" = 1' - 0" 0 1' 5'6" 2' 3' 4'

GRAPHIC SCALE(S)

GENERAL SHEET NOTES

1 REFER TO FIRE PROTECTION & ELECTRICAL DWGS FOR MORE INFORMATION.

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

D es ig n R e v is io ns

/0 2/

K E

S

SCALE: 3/4" = 1'-0"

A1

CI-288 THRU-ROOF PENTRATION

T.O. CMU WALL

12'-0"

FIRST FLOOR

0'-0"

CONTROL ROOM

CORRIDOR

EXISTING ROOF TO REMAIN

EXISTING

SUSPENDED

ACOUSTICAL

CEILING 8'-0"± AFF

COAX CABLE IN

METAL CONDUIT

RADIO

TRANSMITTER,

REFER TO

FIRE PROTECTION

DRAWINGS

EXISTING WALL

TO REMAIN

AE502

A1

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

/2

/2

:5

:5

P M

C R e v it

L o c a l F ile s \C

I2

A

R k e s h a w n .s k in n e r.

rv t

AE302

M U

LT

IP

LE

B

U

IL

D

IN

G F

IR

E

A

LA

R M

E Q

U

IP

M E

N T

IN

S

TA

LL

A T

IO

N

C I-2

W

A

LL

S E

C T

IO

N

S

ALP

12,911,671

KES KES

05/24/2024

HAI HUYNH

KESHAWN SKINNER

1793709

N/A

N O

R F

O

LK

, V

IR

G

IN

IA

N

A V

A L

S T

A T

IO

N

N O

R F

O

LK

J MILLER P.E.

A PILLO. RA

M

ID

L A

N T

D C

C O

R E

A E

3/4" = 1' - 0" 0 1' 5'6" 2' 3' 4'

GRAPHIC SCALE(S)

GENERAL SHEET NOTES

1 REFER TO FIRE PROTECTION & ELECTRICAL DWGS FOR MORE INFORMATION.

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

D es ig n R e v is io ns

/0 2/

K E

S

SCALE: 3/4" = 1'-0"

CI-294 THRU-ROOF PENTRATION

EXISTING CEILING

8'-5"

FIRST FLOOR

0'-0"

LAUNDRY

HALLWAY

EXISTING ROOF

TO REMAIN

COAX CABLE IN

METAL CONDUIT

CORE DRILL

EXISTING CEILING

TO ACCOMODATE

CONDUIT INSTALLATION,

SEAL PENETRATION

WITH CONTINUOUS

INTUMESCENT SEALANT

RADIO TRANSMITTER,

REFER TO FIRE PROTECTION

DRAWINGS

EXISTING WALL TO REMAIN

ROOF RIDGE

15'-0"

ATTIC SPACE

EXISTING SUSPENDED

ACOUSTICAL CEILING

TO REMAIN

AE504

A1

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

/2

/2

:0

:4

P M

C R e v it

L o c a l F ile s \A

A

R k e s h a w n .s k in n e r.

rv t

AE304

M U

LT

IP

LE

B

U

IL

D

IN

G F

IR

E

A

LA

R M

E Q

U

IP

M E

N T

IN

S

TA

LL

A T

IO

N

A -5

W

A

LL

S E

C T

IO

N

S

ALP

12,911,673

KES KES

05/24/2024

HAI HUYNH

KESHAWN SKINNER

1793709

N/A

N O

R F

O

LK

, V

IR

G

IN

IA

N

A V

A L

S T

A T

IO

N

N O

R F

O

LK

J MILLER P.E.

A. PILLO, RA

M

ID

L A

N T

D C

C O

R E

A E

3/4" = 1' - 0" 0 1' 5'6" 2' 3' 4'

GRAPHIC SCALE(S)

GENERAL SHEET NOTES

1 REFER TO FIRE PROTECTION & ELECTRICAL DWGS FOR MORE INFORMATION.

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

D es ig n R e v is io ns

/0 2/

K E

S

SCALE: 3/4" = 1'-0"

A-58 THRU-ROOF PENTRATION

ROOF

12'-0"

FIRST FLOOR

0'-0"

ENTRY

101B

ELECTRICAL ROOM

EXISTING ROOF

TO REMAIN

EXISTING SUSPENDED

ACOUSTICAL

CEILING 8'-0"± AFF

COAX CABLE IN

METAL CONDUIT

RADIO TRANSMITTER,

REFER TO FIRE PROTECTION

DRAWINGS

EXISTING WALL TO REMAIN

AE505

A1

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

/2

/2

:0

:5

P M

C R e v it

L o c a l F ile s \C

E P

A

R k e s h a w n .s k in n e r.

rv t

AE305

M U

LT

IP

LE

B

U

IL

D

IN

G F

IR

E

A

LA

R M

E Q

U

IP

M E

N T

IN

S

TA

LL

A T

IO

N

C E

P -1

W

A

LL

S E

C T

IO

N

S

ALP

12,911,674

KES KES

05/24/2024

HAI HUYNH

KESHAWN SKINNER

1793709

N/A

N O

R F

O

LK

, V

IR

G

IN

IA

N

A V

A L

S T

A T

IO

N

N O

R F

O

LK

J MILLER P.E.

A. PILLO, RA

M

ID

L A

N T

D C

C O

R E

A E

3/4" = 1' - 0" 0 1' 5'6" 2' 3' 4'

GRAPHIC SCALE(S)

GENERAL SHEET NOTES

1 REFER TO FIRE PROTECTION & ELECTRICAL DWGS FOR MORE INFORMATION.1 REFER TO FIRE PROTECTION & ELECTRICAL DWGS FOR MORE INFORMATION.

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

D es ig n R e v is io ns

/0 2/

K E

S

SCALE: 3/4" = 1'-0"

CEP-177 THRU-ROOF PENTRATION

FIRST FLOOR

0'-0"

LOW ROOF

20'-5"

CORRIDOR

EXISTING ROOF TO REMAIN

EXISTING SUSPENDED

ACOUSTICAL

CEILING 8'-0"± AFF

COAX CABLE IN

METAL CONDUIT

RADIO TRANSMITTER,

REFER TO FIRE PROTECTION

DRAWINGS

EXISTING WALL TO REMAIN

AE506

A1

EXISTING WALL TO REMAIN

BREAK ROOM

MEN'S LOCKER ROOM

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

/2

/2

:0

:0

P M

C R e v it

L o c a l F ile s \C

E P

A

R k e s h a w n .s k in n e r.

rv t

AE306

M U

LT

IP

LE

B

U

IL

D

IN

G F

IR

E

A

LA

R M

E Q

U

IP

M E

N T

IN

S

TA

LL

A T

IO

N

C E

P -1

W

A

LL

S E

C T

IO

N

S

ALP

12,911,675

KES KES

05/24/2024

HAI HUYNH

KESHAWN SKINNER

1793709

N/A

N O

R F

O

LK

, V

IR

G

IN

IA

N

A V

A L

S T

A T

IO

N

N O

R F

O

LK

J MILLER P.E.

A. PILLO, RA

M

ID

L A

N T

D C

C O

R E

A E

3/4" = 1' - 0" 0 1' 5'6" 2' 3' 4'

GRAPHIC SCALE(S)

GENERAL SHEET NOTES

1 REFER TO FIRE PROTECTION & ELECTRICAL DWGS FOR MORE INFORMATION.

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

D es ig n R e v is io ns

/0 2/

K E

S

SCALE: 3/4" = 1'-0"

CEP-156 THRU-ROOF PENTRATION

0'-0"

ROOF RIDGE

28'-1"

CORRIDOR

EXISTING ROOF TO REMAIN

EXISTING SUSPENDED

ACOUSTICAL CEILING 8'-0"± AFF

COAX CABLE IN

METAL CONDUIT

RADIO TRANSMITTER,

REFER TO FIRE PROTECTION

DRAWINGS

EXISTING WALL TO REMAINEXISTING WALL TO REMAIN

LAUNDRY

PRE-SCHOOL

AE507

A1

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

/2

/2

:0

:2

P M

C R e v it

L o c a l F ile s \W

B

A

R k e s h a w n .s k in n e r.

rv t

AE307

M U

LT

IP

LE

B

U

IL

D

IN

G F

IR

E

A

LA

R M

E Q

U

IP

M E

N T

IN

S

TA

LL

A T

IO

N

W B

-2

W A

LL

S

E C

T

IO

N S

ALP

12,911,676

KES KES

05/24/2024

HAI HUYNH

KESHAWN SKINNER

1793709

N/A

N O

R F

O

LK

, V

IR

G

IN

IA

N

A V

A L

S T

A T

IO

N

N O

R F

O

LK

J MILLER P.E.

A. PILLO, RA

M

ID

L A

N T

D C

C O

R E

A E

3/4" = 1' - 0" 0 1' 5'6" 2' 3' 4'

GRAPHIC SCALE(S)

GENERAL SHEET NOTES

1 REFER TO FIRE PROTECTION & ELECTRICAL DWGS FOR MORE INFORMATION.

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

D es ig n R e v is io ns

/0 2/

K E

S

SCALE: 3/4" = 1'-0"

WB-200 THRU-ROOF PENTRATION

16'-8"

THIRD FLOOR

28'-1"

ROOF

51'-7"

313311

EXISTING ROOF

TO REMAIN

EXISTING SUSPENDED

ACOUSTICAL CEILING

8'-0"± AFF

COAX CABLE IN

METAL CONDUIT

RADIO TRANSMITTER,

REFER TO FIRE PROTECTION

DRAWINGS

EXISTING WALL TO REMAIN

AE508

A1

EXISTING WALL TO REMAIN

EXISTING PARAPET

TO REMAIN

3"

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

/2

/2

:4

:3

P M

C R e v it

L o c a l F ile s \P

A

R k e s h a w n

.s k in n e r.

rv t

AE308

M U

LT

IP

LE

B

U

IL

D

IN

G F

IR

E

A

LA

R M

E Q

U

IP

M E

N T

IN

S

TA

LL

A T

IO

N

P -1

W A

LL

S

E C

T

IO

N S

ALP

12,911,677

KES KES

05/24/2024

HAI HUYNH

KESHAWN SKINNER

1793709

N/A

N O

R F

O

LK

, V

IR

G

IN

IA

N

A V

A L

S T

A T

IO

N

N O

R F

O

LK

J. MILLER P.E.

A. PILLO, RA

M

ID

L A

N T

D C

C O

R E

A E

3/4" = 1' - 0" 0 1' 5'6" 2' 3' 4'

GRAPHIC SCALE(S)

GENERAL SHEET NOTES

1 REFER TO FIRE PROTECTION & ELECTRICAL DWGS FOR MORE INFORMATION.

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

D es ig n R e v is io ns

/0 2/

K E

S

SCALE: 3/4" = 1'-0"

P-1 THRU-ROOF PENTRATION

10'-0"

FIRST FLOOR

0'-0"

ROOF

20'-0"

100101

EXISTING ROOF TO REMAIN

EXISTING SUSPENDED

ACOUSTICAL CEILING

8'-0"± AFF

COAX CABLE IN

METAL CONDUIT

CORE DRILL EXISTING FLOOR

TO ACCOMODATE CONDUIT

INSTALLATION, SEAL PENETRATION

WITH CONTINUOUS

INTUMESCENT SEALANT

RADIO TRANSMITTER,

REFER TO FIRE PROTECTION

DRAWINGS

EXISTING WALL TO REMAIN

EXISTING SUSPENDED

ACOUSTICAL CEILING

8'-0"± AFF

AE509

A1

3"

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

/2

/2

:4

:2

P M

C R e v it

L o c a l F ile s \C

E P

A

R k e s h a w n .s k in n e r.

rv t

AE309

M U

LT

IP

LE

B

U

IL

D

IN

G F

IR

E

A

LA

R M

E Q

U

IP

M E

N T

IN

S

TA

LL

A T

IO

N

C E

P -2

W

A

LL

S E

C T

IO

N

S

ALP

12,911,678

KES KES

05/24/2024

HAI HUYNH

KESHAWN SKINNER

1793709

N/A

N O

R F

O

LK

, V

IR

G

IN

IA

N

A V

A L

S T

A T

IO

N

N O

R F

O

LK

J. MILLER P.E.

A. PILLO, RA

M

ID

L A

N T

D C

C O

R E

A E

3/4" = 1' - 0" 0 1' 5'6" 2' 3' 4'

GRAPHIC SCALE(S)

GENERAL SHEET NOTES

1 REFER TO FIRE PROTECTION & ELECTRICAL DWGS FOR MORE INFORMATION.

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

D es ig n R e v is io ns

/0 2/

K E

S

SCALE: 3/4" = 1'-0"

CEP-204 THRU-ROOF PENTRATION

0' - 0"

SECOND FLOOR

16' - 0"

RADIO TRANSMITTER,

REFER TO FIRE

PROTECTION

DRAWINGS

EXISTING WALL TO REMAIN

ENTRY

ENTRY

EXISTING SUSPENDED ACOUSTICAL

CEILING 8'-0"± AFF

EXISTING SUSPENDED ACOUSTICAL

CEILING 8'-0"± AFF

CORE DRILL EXISTING FLOOR

TO ACCOMODATE CONDUIT

INSTALLATION, SEAL PENETRATION

WITH CONTINUOUS

INTUMESCENT SEALANT

3"

ROOF

39' - 0"

THIRD FLOOR

27' - 5"

AE510

A1

EXISTING SUSPENDED ACOUSTICAL

CEILING 8'-0"± AFF

COAX CABLE IN

METAL CONDUIT

EXISTING ROOF TO REMAIN

CORE DRILL EXISTING FLOOR

TO ACCOMODATE CONDUIT

INSTALLATION, SEAL PENETRATION

WITH CONTINUOUS

INTUMESCENT SEALANT

3"

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

/2

/2

:5

:3

P M

C R e v it

L o c a l F ile s \Z

A

R k e s h a w n .s k in n e r.

rv t

AE310

M U

LT

IP

LE

B

U

IL

D

IN

G F

IR

E

A

LA

R M

E Q

U

IP

M E

N T

IN

S

TA

LL

A T

IO

N

Z -1

W

A

LL

S E

C T

IO

N

S

ALP

12,911,679

KES KES

05/24/2024

HAI HUYNH

KESHAWN SKINNER

1793709

N/A

N O

R F

O

LK

, V

IR

G

IN

IA

N

A V

A L

S T

A T

IO

N

N O

R F

O

LK

J. MILLER P.E.

A. PILLO, RA

M

ID

L A

N T

D C

C O

R E

A E

3/4" = 1' - 0" 0 1' 5'6" 2' 3' 4'

GRAPHIC SCALE(S)

GENERAL SHEET NOTES

SCALE: 3/4" = 1'-0"

A1

Z-140 THRU-ROOF PENETRATION - LOWER

1 REFER TO FIRE PROTECTION & ELECTRICAL DWGS FOR MORE

INFORMATION.

SCALE: 3/4" = 1'-0"

B3

Z-140 THRU-ROOF PENETRATION - UPPER

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

D es ig n R e v is io ns

/0 2/

K E

S

SECOND FLOOR

15' - 4"

ROOF

29' - 4"

AE511

A1

EXISTING ROOF TO REMAIN

EXISTING SUSPENDED ACOUSTICAL

CEILING 8'-0"± AFF

CORE DRILL EXISTING FLOOR

TO ACCOMODATE CONDUIT

INSTALLATION, SEAL PENETRATION

WITH CONTINUOUS

INTUMESCENT SEALANT

EXISTING SUSPENDED ACOUSTICAL

CEILING 8'-0"± AFF

103 119

COAX CABLE IN

METAL CONDUIT

RADIO TRANSMITTER,

REFER TO FIRE PROTECTION

DRAWINGS

EXISTING WALL TO REMAIN

3"

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

/2

/2

:2

:1

P M

C R e v it

L o c a l F ile s \Z

A

R k e s h a w n .s k in n e r.

rv t

AE311

M U

LT

IP

LE

B

U

IL

D

IN

G F

IR

E

A

LA

R M

E Q

U

IP

M E

N T

IN

S

TA

LL

A T

IO

N

Z -1

W

A

LL

S E

C T

IO

N

S

ALP

12,911,680

KES KES

05/24/2024

HAI HUYNH

KESHAWN SKINNER

1793709

N/A

N O

R F

O

LK

, V

IR

G

IN

IA

N

A V

A L

S T

A T

IO

N

N O

R F

O

LK

J. MILLER P.E.

A. PILLO, RA

M

ID

L A

N T

D C

C O

R E

A E

3/4" = 1' - 0" 0 1' 5'6" 2' 3' 4'

GRAPHIC SCALE(S)

GENERAL SHEET NOTES

SCALE: 3/4" = 1'-0"

A1

Z-144 THRU-ROOF PENETRATION

1 REFER TO FIRE PROTECTION & ELECTRICAL DWGS FOR MORE

INFORMATION.

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

D es ig n R e v is io ns

/0 2/

K

SECOND FLOOR

13' - 0"

RADIO TRANSMITTER,

REFER TO FIRE PROTECTION

DRAWINGS

EXISTING WALL TO REMAIN

EXISTING SUSPENDED ACOUSTICAL

CEILING 8'-0"± AFF

EXISTINGSUSPENDED ACOUSTICAL

CEILING 8'-0"± AFF

CORE DRILL EXISTING FLOOR

TO ACCOMODATE CONDUIT

INSTALLATION, SEAL PENETRATION

WITH CONTINUOUS

INTUMESCENT SEALANT

VEST

RECEPTION

200202

3"

ROOF

37' - 0"

THIRD FLOOR

24' - 0"

AE513

A1

EXISTING SUSPENDED ACOUSTICAL

CEILING 8'-0"± AFF

CORE DRILL EXISTING FLOOR

TO ACCOMODATE CONDUIT

INSTALLATION, SEAL PENETRATION

WITH CONTINUOUS

INTUMESCENT SEALANT

EXISTING ROOF TO REMAIN

COAX CABLE IN

METAL CONDUIT

300301

3"

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

/2

/2

:3

:1

P M

C R e v it

L o c a l F ile s \N

A

R k e s h a w n .s k in n e r.

rv t

AE313

M U

LT

IP

LE

B

U

IL

D

IN

G F

IR

E

A

LA

R M

E Q

U

IP

M E

N T

IN

S

TA

LL

A T

IO

N

N -2

W

A

LL

S E

C T

IO

N

S

ALP

11,911,682

KES KES

05/24/2024

HAI HUYNH

KESHAWN SKINNER

1793709

N/A

N O

R F

O

LK

, V

IR

G

IN

IA

N

A V

A L

S T

A T

IO

N

N O

R F

O

LK

J. MILLER P.E.

A. PILLO, RA

M

ID

L A

N T

D C

C O

R E

A E

3/4" = 1' - 0" 0 1' 5'6" 2' 3' 4'

GRAPHIC SCALE(S)

GENERAL SHEET NOTES

SCALE: 3/4" = 1'-0"

A1

N-26 THRU-ROOF PENETRATION - LOWER

1 REFER TO FIRE PROTECTION & ELECTRICAL DWGS FOR MORE

INFORMATION.

SCALE: 3/4" = 1'-0"

B3

N-26 THRU-ROOF PENETRATION - UPPER

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

D es ig n R e v is io ns

/0 2/

K

TWO-PART LIQUID APPLIED FABRIC

REINFORCED FLASHING

CONDUIT, REFER TO

ELECTRICAL DRAWINGS

EXISTING ROOFING MEMBRANE

EXISTING COVER BOARD

EXISTING ROOF INSULATION

EXISTING METAL ROOF DECK

ANTENNA

8" M

IN

8"

8" MIN

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

/2

/2

:4

:2

P M

C R e v it

L o c a l F ile s \C

I2

A

R k e s h a w n .s k in n e r.

rv t

AE501

M U

LT

IP

LE

B

U

IL

D

IN

G F

IR

E

A

LA

R M

E Q

U

IP

M E

N T

IN

S

TA

LL

A T

IO

N

C I-2

R

O O

F D

E T

A

IL

S

ALP

12,911,683

KES KES

05/24/2024

HAI HUYNH

KESHAWN SKINNER

1793709

N/A

N O

R F

O

LK

, V

IR

G

IN

IA

N

A V

A L

S T

A T

IO

N

N O

R F

O

LK

J. MILLER P.E.

A. PILLO, RA

M

ID

L A

N T

D C

C O

R E

A E

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

D es ig n R e v is io ns

/0 2/

K E

S

SCALE: 3" = 1'-0"

A1

CI-288 ROOF DETAIL

3" = 1' - 0" 0 3" 6" 1'

GRAPHIC SCALE(S)

EXISTING STANDING

SEAM ROOFING

EXISTING RIGID INSULATION

STAINLESS STEEL CLAMP

PROVIDE CONTINUOUS SEALANT

RUBBERIZED ASPHALT

MEMBRANE AROUND PIPE

ANTENNA

VENT PIPE FLASHING

EXISITNG STEEL

DECK

CONDUIT, REFER TO

ELECTRICAL DRAWINGS

5"±

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

/2

/2

:5

:5

P M

C R e v it

L o c a l F ile s \C

I2

A

R k e s h a w n .s k in n e r.

rv t

AE502

M U

LT

IP

LE

B

U

IL

D

IN

G F

IR

E

A

LA

R M

E Q

U

IP

M E

N T

IN

S

TA

LL

A T

IO

N

C I-2

R

O O

F D

E T

A

IL

S

ALP

12,911,684

KES KES

05/24/2024

HAI HUYNH

KESHAWN SKINNER

1793709

N/A

N O

R F

O

LK

, V

IR

G

IN

IA

N

A V

A L

S T

A T

IO

N

N O

R F

O

LK

J MILLER P.E.

A PILLO. RA

M

ID

L A

N T

D C

C O

R E

A E

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

D es ig n R e v is io ns

/0 2/

K E

S

SCALE: 3" = 1'-0"

A1

CI-294 ROOF DETAIL

3" = 1' - 0"

CONDUIT, REFER TO

ELECTRICAL DRAWINGS

EXISTING ROOFING MEMBRANE

EXISTING COVER BOARD

EXISTING ROOF INSULATION

EXISTING METAL ROOF DECK

ANTENNA

8" M

IN

8" MIN

7"

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

/2

/2

:5

:5

P M

C R e v it

L o c a l F ile s \S

P

A

R k e s h a w n .s k in n e r.

rv t

AE503

M U

LT

IP

LE

B

U

IL

D

IN

G F

IR

E

A

LA

R M

E Q

U

IP

M E

N T

IN

S

TA

LL

A T

IO

N

S P

-3

R O

O F

D E

T A

IL

S

ALP

12,911,685

KES KES

05/24/2024

HAI HUYNH

KESHAWN SKINNER

1793709

N/A

N O

R F

O

LK

, V

IR

G

IN

IA

N

A V

A L

S T

A T

IO

N

N O

R F

O

LK

J. MILLER P.E.

A. PILLO, RA

M

ID

L A

N T

D C

C O

R E

A E

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

D es ig n R e v is io ns

/0 2/

K E

S

3" = 1' - 0" 0 3" 6" 1'

GRAPHIC SCALE(S)

SCALE: 3" = 1'-0"

SP-313 ROOF DETAIL

EXISTING ASPHALT

SHINGLE ROOFING

EXISTING PLYWOOD, SHEATHING

STAINLESS STEEL CLAMP

PROVIDE CONTINUOUS SEALANT

RUBBERIZED ASPHALT

MEMBRANE AROUND PIPE

ANTENNA

VENT PIPE FLASHING

EXISTING ROOF STRUCTURE

CONDUIT, REFER TO

ELECTRICAL DRAWINGS

8"±

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

/2

/2

:0

:4

P M

C R e v it

L o c a l F ile s \A

A

R k e s h a w n .s k in n e r.

rv t

AE504

M U

LT

IP

LE

B

U

IL

D

IN

G F

IR

E

A

LA

R M

E Q

U

IP

M E

N T

IN

S

TA

LL

A T

IO

N

A -5

R

O O

F D

E

TA

IL

S

ALP

12,911,686

KES KES

05/24/2024

HAI HUYNH

KESHAWN SKINNER

1793709

N/A

N O

R F

O

LK

, V

IR

G

IN

IA

N

A V

A L

S T

A T

IO

N

N O

R F

O

LK

J MILLER P.E.

A. PILLO, RA

M

ID

L A

N T

D C

C O

R E

A E

SCALE: 3" = 1'-0"

A1

A-58 ROOF DETAIL

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

D es ig n R e v is io ns

/0 2/

K E

S

3" = 1' - 0"

CONDUIT, REFER TO

ELECTRICAL DRAWINGS

EXISTING ROOFING MEMBRANE

EXISTING COVER BOARD

EXISTING ROOF INSULATION

EXISTING METAL ROOF DECK

ANTENNA

8" M

IN

8" MIN

8"

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

/2

/2

:0

:5

P M

C R e v it

L o c a l F ile s \C

E P

A

R k e s h a w n .s k in n e r.

rv t

AE505

M U

LT

IP

LE

B

U

IL

D

IN

G F

IR

E

A

LA

R M

E Q

U

IP

M E

N T

IN

S

TA

LL

A T

IO

N

C E

P -1

R

O O

F D

E T

A

IL

S

ALP

12,911,687

KES KES

05/24/2024

HAI HUYNH

KESHAWN SKINNER

1793709

N/A

N O

R F

O

LK

, V

IR

G

IN

IA

N

A V

A L

S T

A T

IO

N

N O

R F

O

LK

J MILLER P.E.

A. PILLO, RA

M

ID

L A

N T

D C

C O

R E

A E

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

D es ig n R e v is io ns

/0 2/

K E

S

3" = 1' - 0" 0 3" 6" 1'

GRAPHIC SCALE(S)

SCALE: 3" = 1'-0"

CEP-177 ROOF DETAIL

CONDUIT, REFER TO

ELECTRICAL DRAWINGS

EXISTING ROOFING MEMBRANE

EXISTING COVER BOARD

EXISTING ROOF INSULATION

EXISTING METAL ROOF DECK

ANTENNA

8" M

IN

8" MIN

8"

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

/2

/2

:0

:0

P M

C R e v it

L o c a l F ile s \C

E P

A

R k e s h a w n .s k in n e r.

rv t

AE506

M U

LT

IP

LE

B

U

IL

D

IN

G F

IR

E

A

LA

R M

E Q

U

IP

M E

N T

IN

S

TA

LL

A T

IO

N

C E

P -1

R

O O

F D

E T

A

IL

S

ALP

12,911,688

KES KES

05/24/2024

HAI HUYNH

KESHAWN SKINNER

1793709

N/A

N O

R F

O

LK

, V

IR

G

IN

IA

N

A V

A L

S T

A T

IO

N

N O

R F

O

LK

J MILLER P.E.

A. PILLO, RA

M

ID

L A

N T

D C

C O

R E

A E

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

D es ig n R e v is io ns

/0 2/

K E

S

3" = 1' - 0" 0 3" 6" 1'

GRAPHIC SCALE(S)

SCALE: 3" = 1'-0"

CEP-156 ROOF DETAIL

EXISTING STANDING

SEAM ROOFING

EXISTING RIGID INSULATION

STAINLESS STEEL CLAMP

PROVIDE CONTINUOUS SEALANT

RUBBERIZED ASPHALT

MEMBRANE AROUND PIPE

ANTENNA

VENT PIPE FLASHING

EXISITNG STEEL

ROOF DECK

EXISTING 15LB BUILDING FELT

CONDUIT, REFER TO

ELECTRICAL DRAWINGS

4"±

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

/2

/2

:0

:2

P M

C R e v it

L o c a l F ile s \W

B

A

R k e s h a w n .s k in n e r.

rv t

AE507

M U

LT

IP

LE

B

U

IL

D

IN

G F

IR

E

A

LA

R M

E Q

U

IP

M E

N T

IN

S

TA

LL

A T

IO

N

W B

-2

R O

O F

D E

T A

IL

S

ALP

12,911,689

KES KES

05/24/2024

HAI HUYNH

KESHAWN SKINNER

1793709

N/A

N O

R F

O

LK

, V

IR

G

IN

IA

N

A V

A L

S T

A T

IO

N

N O

R F

O

LK

J MILLER P.E.

A. PILLO, RA

M

ID

L A

N T

D C

C O

R E

A E

SCALE: 3" = 1'-0"

A1

WB-200 ROOF DETAIL

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

D es ig n R e v is io ns

/0 2/

K E

S

3" = 1' - 0"

CONDUIT, REFER TO

ELECTRICAL DRAWINGS

EXISTING ROOFING MEMBRANE

EXISTING COVER BOARD

EXISTING ROOF INSULATION

EXISTING METAL ROOF DECK

ANTENNA

8" M

IN

8" MIN

8"

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

/2

/2

:1

:1

P M

C R e v it

L o c a l F ile s \P

A

R k e s h a w n

.s k in n e r.

rv t

AE508

M U

LT

IP

LE

B

U

IL

D

IN

G F

IR

E

A

LA

R M

E Q

U

IP

M E

N T

IN

S

TA

LL

A T

IO

N

P -1

R O

O F

D E

TA

IL

S

ALP

12,911,690

KES KES

05/24/2024

HAI HUYNH

KESHAWN SKINNER

1793709

N/A

N O

R F

O

LK

, V

IR

G

IN

IA

N

A V

A L

S T

A T

IO

N

N O

R F

O

LK

J. MILLER P.E.

A. PILLO, RA

M

ID

L A

N T

D C

C O

R E

A E

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

D es ig n R e v is io ns

/0 2/

K E

S

3" = 1' - 0" 0 3" 6" 1'

GRAPHIC SCALE(S)

SCALE: 3" = 1'-0"

P-1 ROOF DETAIL

INSULATED METAL

ROOF PANELS ON

STEEL PURLINS

INSULATION

STAINLESS STEEL CLAMP

PROVIDE CONTINUOUS SEALANT

RUBBERIZED ASPHALT

MEMBRANE AROUND PIPE

ANTENNA

VENT PIPE FLASHING

STEEL PURLINS

CONDUIT, REFET TO

ELECTRICAL DRAWINGS

8"±

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

/2

/2

:2

:4

P M

C R e v it

L o c a l F ile s \C

E P

A

R k e s h a w n .s k in n e r.

rv t

AE509

M U

LT

IP

LE

B

U

IL

D

IN

G F

IR

E

A

LA

R M

E Q

U

IP

M E

N T

IN

S

TA

LL

A T

IO

N

C E

P -2

R

O O

F D

E T

A

IL

S

KES

12,911,691

KES KES

05/24/2024

HAI HUYNH

KESHAWN SKINNER

1793709

N/A

N O

R F

O

LK

, V

IR

G

IN

IA

N

A V

A L

S T

A T

IO

N

N O

R F

O

LK

J. MILLER P.E.

A. PILLO, RA

M

ID

L A

N T

D C

C O

R E

A E

SCALE: 3" = 1'-0"

A1

CEP-204 ROOF DETAIL

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

D es ig n R e v is io ns

/0 2/

K E

S

3" = 1' - 0"

CONDUIT, REFER TO

ELECTRICAL DRAWINGS

EXISTING ROOFING MEMBRANE

EXISTING STEEL PLATE

EXISTING ROOF INSULATION

EXISTING CONCRETE ROOF DECK

ANTENNA

8" MIN

8" M

IN

7"

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

/2

/2

:2

:4

P M

C R e v it

L o c a l F ile s \Z

A

R k e s h a w n .s k in n e r.

rv t

AE510

M U

LT

IP

LE

B

U

IL

D

IN

G F

IR

E

A

LA

R M

E Q

U

IP

M E

N T

IN

S

TA

LL

A T

IO

N

Z -1

R

O O

F D

E

TA

IL

S

ALP

12,911,692

KES KES

05/24/2024

HAI HUYNH

KESHAWN SKINNER

1793709

N/A

N O

R F

O

LK

, V

IR

G

IN

IA

N

A V

A L

S T

A T

IO

N

N O

R F

O

LK

J. MILLER P.E.

A. PILLO, RA

M

ID

L A

N T

D C

C O

R E

A E

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

D es ig n R e v is io ns

/0 2/

K E

S

SCALE: 3" = 1'-0"

A1

Z-140 ROOF DETAIL

3" = 1' - 0"

CONDUIT, REFER TO

ELECTRICAL DRAWINGS

EXISTING ROOFING MEMBRANE

EXISTING COVER BOARD

EXISTING ROOF INSULATION

EXISTING METAL ROOF DECK

ANTENNA

8" MIN

8" M

IN

7"

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

/2

/2

:2

:1

P M

C R e v it

L o c a l F ile s \Z

A

R k e s h a w n .s k in n e r.

rv t

AE511

M U

LT

IP

LE

B

U

IL

D

IN

G F

IR

E

A

LA

R M

E Q

U

IP

M E

N T

IN

S

TA

LL

A T

IO

N

Z -1

R

O O

F D

E

TA

IL

S

ALP

12,911,693

KES KES

05/24/2024

HAI HUYNH

KESHAWN SKINNER

1793709

N/A

N O

R F

O

LK

, V

IR

G

IN

IA

N

A V

A L

S T

A T

IO

N

N O

R F

O

LK

J. MILLER P.E.

A. PILLO, RA

M

ID

L A

N T

D C

C O

R E

A E

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

D es ig n R e v is io ns

/0 2/

K E

S

SCALE: 3" = 1'-0"

A1

Z-144 ROOF DETAIL

3" = 1' - 0"

EXISTING ASPHALT

SHINGLE ROOFING

EXISITNG 2 LAYERS

BUILDING PAPER

STAINLESS STEEL CLAMP

PROVIDE CONTINUOUS SEALANT

RUBBERIZED ASPHALT

MEMBRANE AROUND PIPE

VENT PIPE FLASHING

EXISTING ROOF STRUCTURE

CONDUIT, REFER TO

ELECTRICAL DRAWINGS

ANTENNA

5"±

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

/2

/2

:3

:2

P M

C R e v it

L o c a l F ile s \D

S

A

R k e s h a w n .s k in n e r.

rv t

AE512

M U

LT

IP

LE

B

U

IL

D

IN

G F

IR

E

A

LA

R M

E Q

U

IP

M E

N T

IN

S

TA

LL

A T

IO

N

D S

-3

R O

O F

D E

T A

IL

S

ALP

12,911,694

KES KES

05/24/2024

HAI HUYNH

KESHAWN SKINNER

1793709

N/A

N O

R F

O

LK

, V

IR

G

IN

IA

N

A V

A L

S T

A T

IO

N

N O

R F

O

LK

J. MILLER P.E.

A. PILLO, RA

M

ID

L A

N T

D C

C O

R E

A E

SCALE: 3" = 1'-0"

A1

DS- 31 ROOF DETAIL

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

D es ig n R e v is io ns

/0 2/

K E

S

3" = 1' - 0"

CONDUIT, REFER TO

ELECTRICAL DRAWINGS

EXISTING ROOFING MEMBRANE

EXISTING COVER BOARD

EXISTING ROOF INSULATION

EXISTING METAL ROOF DECK

ANTENNA

8" MIN

8" M

IN

8"

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

TI

C

N A

V A

L S

T A

T

IO

N

N O

R F

O L

K V

A

AS NOTED

/2

/2

:3

:1

P M

C R e v it

L o c a l F ile s \N

A

R k e s h a w n .s k in n e r.

rv t

AE513

M U

LT

IP

LE

B

U

IL

D

IN

G F

IR

E

A

LA

R M

E Q

U

IP

M E

N T

IN

S

TA

LL

A T

IO

N

N -2

R

O O

F D

E

TA

LS

ALP

11,911,695

KES KES

05/24/2024

HAI HUYNH

KESHAWN SKINNER

1793709

N/A

N O

R F

O

LK

, V

IR

G

IN

IA

N

A V

A L

S T

A T

IO

N

N O

R F

O

LK

J. MILLER P.E.

A. PILLO, RA

M

ID

L A

N T

D C

C O

R E

A E

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

D es ig n R e v is io ns

/0 2/

K E

S

SCALE: 3" = 1'-0"

A1

N-26 ROOF DETAIL

3" = 1' - 0"

SECTION 01 35 26

GOVERNMENTAL SAFETY REQUIREMENTS

11/20, CHG 3: 02/22

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME)

ASME B30.3 (2020) Tower Cranes

ASME B30.5 (2021) Mobile and Locomotive Cranes

ASME B30.7 (2021) Winches

ASME B30.8 (2020) Floating Cranes and Floating Derricks

ASME B30.9 (2018) Slings

ASME B30.20 (2018) Below-the-Hook Lifting Devices

ASME B30.22 (2016) Articulating Boom Cranes

ASME B30.23 (2022) Personnel Lifting Systems Safety Standard for Cableways, Cranes, Derricks, Hoists, Hooks, Jacks, and Slings

ASME B30.26 (2015; R 2020) Rigging Hardware

AMERICAN SOCIETY OF SAFETY PROFESSIONALS (ASSP)

ASSP A10.22 (2007; R 2017) Safety Requirements for Rope-Guided and Non-Guided Workers’ Hoists

ASSP A10.34 (2021) Protection of the Public on or Adjacent to Construction Sites

ASSP A10.44 (2020) Control of Energy Sources (Lockout/Tagout) for Construction and Demolition Operations

ASSP Z244.1 (2016) The Control of Hazardous Energy Lockout, Tagout and Alternative Methods

ASSP Z359.0 (2018) Definitions and Nomenclature Used for Fall Protection and Fall Arrest

ASSP Z359.1 (2020) The Fall Protection Code

ASSP Z359.2 (2017) Minimum Requirements for a Comprehensive Managed Fall Protection Program

ASSP Z359.3 (2019) Safety Requirements for Lanyards and Positioning Lanyards

ASSP Z359.4 (2013) Safety Requirements for Assisted-Rescue and Self-Rescue Systems, Subsystems and Components

ASSP Z359.6 (2016) Specifications and Design Requirements for Active Fall Protection Systems

ASSP Z359.7 (2019) Qualification and Verification Testing of Fall Protection Products

ASSP Z359.11 (2014) Safety Requirements for Full Body Harnesses

ASSP Z359.12 (2019) Connecting Components for Personal Fall Arrest Systems

ASSP Z359.13 (2013) Personal Energy Absorbers and Energy Absorbing Lanyards

ASSP Z359.14 (2014) Safety Requirements for Self-Retracting Devices for Personal Fall Arrest and Rescue Systems

ASSP Z359.15 (2014) Safety Requirements for Single Anchor Lifelines and Fall Arresters for Personal Fall Arrest Systems

ASSP Z359.16 (2016) Safety Requirements for Climbing Ladder Fall Arrest Systems

ASSP Z359.18 (2017) Safety Requirements for Anchorage Connectors for Active Fall Protection Systems

ASSP Z490.1 (2016) Criteria for Accepted Practices in Safety, Health, and Environmental Training

ASTM INTERNATIONAL (ASTM)

ASTM F855 (2019) Standard Specifications for Temporary Protective Grounds to Be Used on De-energized Electric Power Lines and Equipment

INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)

IEEE 1048 (2016) Guide for Protective Grounding of Power Lines

IEEE C2 (2023) National Electrical Safety Code

NATIONAL AERONAUTICS AND SPACE ADMINISTRATION (NASA)

NASA NPR 8621.1 (2020d) NASA Procedural Requirements for Mishap and Close Call Reporting, Investigating, and Recordkeeping

NASA NPR 8715.3 (2017d; Change 1) NASA General Safety Program Requirements

NASA-STD 8719.12 (2021a; Change 2) Safety Standard for Explosives, Propellants, and Pyrotechnics

NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

NEMA Z535.2 (2011; R 2017) Environmental and Facility Safety Signs

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

NFPA 10 (2022; ERTA 1 2021) Standard for Portable Fire Extinguishers

NFPA 51B (2019; TIA 20-1) Standard for Fire Prevention During Welding, Cutting, and Other Hot Work

NFPA 70 (2023; ERTA 4 2023) National Electrical Code

NFPA 70E (2021) Standard for Electrical Safety in the Workplace

NFPA 241 (2022) Standard for Safeguarding Construction, Alteration, and Demolition Operations

NFPA 306 (2019) Standard for the Control of Gas Hazards on Vessels

TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA)

TIA-222 (2018H; Add 1 2019) Structural Standard for Antenna Supporting Structures and Antennas and Small Wind Turbine Support Structures

TIA-1019 (2012; R 2016) Standard for Installation, Alteration and Maintenance of Antenna Supporting Structures and Antennas

U.S. ARMY CORPS OF ENGINEERS (USACE)

EM 385-1-1 (2014) Safety -- Safety and Health Requirements Manual

U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)

10 CFR 20 Standards for Protection Against Radiation

29 CFR 1910 Occupational Safety and Health Standards

29 CFR 1910.146 Permit-required Confined Spaces

29 CFR 1910.147 The Control of Hazardous Energy (Lock Out/Tag Out)

29 CFR 1910.333 Selection and Use of Work Practices

29 CFR 1915 Confined and Enclosed Spaces and Other Dangerous Atmospheres in Shipyard Employment

29 CFR 1915.89 Control of Hazardous Energy (Lockout/Tags-Plus)

29 CFR 1919 Gear Certification

29 CFR 1926 Safety and Health Regulations for Construction

29 CFR 1926.16 Rules of Construction

29 CFR 1926.450 Scaffolds

29 CFR 1926.500 Fall Protection

29 CFR 1926.552 Material Hoists, Personal Hoists, and Elevators

29 CFR 1926.553 Base-Mounted Drum Hoists

29 CFR 1926.1400 Cranes and Derricks in Construction

49 CFR 173 Shippers - General Requirements for Shipments and Packagings

CPL 02-01-056 (2014) Inspection Procedures for Accessing Communication Towers by Hoist

CPL 2.100 (1995) Application of the Permit-Required Confined Spaces (PRCS) Standards, 29 CFR 1910.146

1.2 DEFINITIONS

1.2.1 Competent Person (CP)

The CP is a person designated in writing, who, through training, knowledge and experience, is capable of identifying, evaluating, and addressing existing and predictable hazards in the working environment or working conditions that are dangerous to personnel, and who has authorization to take prompt corrective measures with regards to such hazards.

1.2.2 Competent Person, Confined Space

The CP, Confined Space, is a person meeting the competent person requirements as defined EM 385-1-1 Appendix Q, with thorough knowledge of OSHA’s Confined Space Standard, 29 CFR 1910.146, and designated in writing to be responsible for the immediate supervision, implementation and monitoring of the confined space program, who through training, knowledge and experience in confined space entry is capable of identifying, evaluating and addressing existing and potential confined space hazards and, who has the authority to take prompt corrective measures with regard to such hazards.

1.2.3 Competent Person, Cranes and Rigging

The CP, Cranes and Rigging, as defined in EM 385-1-1 Appendix Q, is a person meeting the competent person requirements, who has been designated in writing to be responsible for the immediate supervision, implementation and monitoring of the Crane and Rigging Program, who through training, knowledge and experience in crane and rigging is capable of identifying, evaluating and addressing existing and potential hazards and, who has the authority to take prompt corrective measures with regard to such hazards.

1.2.4 Competent Person, Excavation/Trenching

A CP, Excavation/Trenching, is a person meeting the competent person requirements as defined in EM 385-1-1 Appendix Q and 29 CFR 1926, who has been designated in writing to be responsible for the immediate supervision, implementation and monitoring of the excavation/trenching program, who through training, knowledge and experience in excavation/trenching is capable of identifying, evaluating and addressing existing and potential hazards and, who has the authority to take prompt corrective measures with regard to such hazards.

1.2.5 Competent Person, Fall Protection

The CP, Fall Protection, is a person meeting the competent person requirements as defined in EM 385-1-1 Appendix Q and in accordance with ASSP Z359.0, who has been designated in writing by the employer to be responsible for immediate supervising, implementing and monitoring of the fall protection program, who through training, knowledge and experience in fall protection and rescue systems and equipment, is capable of identifying, evaluating and addressing existing and potential fall hazards and, who has the authority to take prompt corrective measures with regard to such hazards.

1.2.6 Competent Person, Scaffolding

The CP, Scaffolding is a person meeting the competent person requirements in EM 385-1-1 Appendix Q, and designated in writing by the employer to be responsible for immediate supervising, implementing and monitoring of the scaffolding program. The CP for Scaffolding has enough training, knowledge and experience in scaffolding to correctly identify, evaluate and address existing and potential hazards and also has the authority to take prompt corrective measures with regard to these hazards. CP qualifications must be documented including experience on the specific scaffolding systems/types being used, assessment of the base material that the scaffold will be erected upon, load calculations for materials and personnel, and erection and dismantling. The CP for scaffolding must have a documented minimum of 8-hours of scaffold training to include training on the specific type of scaffold being used (e.g. mast-climbing, adjustable, tubular frame), in accordance with EM 385-1-1 Section 22.B.02.

1.2.7 Competent Person (CP) Trainer

A competent person trainer as defined in EM 385-1-1 Appendix Q, who is qualified in the training material presented, and who possesses a working knowledge of applicable technical regulations, standards, equipment and systems related to the subject matter on which they are training Competent Persons. A competent person trainer must be familiar with the typical hazards and the equipment used in the industry they are instructing. The training provided by the competent person trainer must be appropriate to that specific industry. The competent person trainer must evaluate the knowledge and skills of the competent persons as part of the training process.

1.2.8 High Risk Activities

High Risk Activities are activities that involve work at heights, crane and rigging, excavations and trenching, scaffolding, electrical work, and confined space entry.

1.2.9 High Visibility Accident

A High Visibility Accident is any mishap which may generate publicity or high visibility.

1.2.10 Load Handling Equipment (LHE)

LHE is a term used to describe cranes, hoists and all other hoisting equipment (hoisting equipment means equipment, including crane, derricks, hoists and power operated equipment used with rigging to raise, lower or horizontally move a load).

1.2.11 Medical Treatment

Medical Treatment is treatment administered by a physician or by registered professional personnel under the standing orders of a physician. Medical treatment does not include first aid treatment even when provided by a physician or registered personnel.

1.2.12 Near Miss

A Near Miss is a mishap resulting in no personal injury and zero property damage, but given a shift in time or position, damage or injury may have occurred (e.g., a worker falls off a scaffold and is not injured; a crane swings around to move the load and narrowly misses a parked vehicle).

1.2.13 Operating Envelope

The Operating Envelope is the area surrounding any crane or load handling equipment. Inside this "envelope" is the crane, the operator, riggers and crane walkers, other personnel involved in the operation, rigging gear between the hook, the load, the crane's supporting structure (i.e. ground or rail), the load's rigging path, the lift and rigging procedure.

1.2.14 Qualified Person (QP)

The QP is a person designated in writing, who, by possession of a recognized degree, certificate, or professional standing, or extensive knowledge, training, and experience, has successfully demonstrated their ability to solve or resolve problems related to the subject matter, the work, or the project.

1.2.15 Qualified Person, Fall Protection (QP for FP)

A QP for FP is a person meeting the definition requirements of EM 385-1-1 Appendix Q, and ASSP Z359.2 standard, having a recognized degree or professional certificate and with extensive knowledge, training and experience in the fall protection and rescue field who is capable of designing, analyzing, and evaluating and specifying fall protection and rescue systems.

1.2.16 Recordable Injuries or Illnesses

Recordable Injuries or Illnesses are any work-related injury or illness that results in:

a. Death, regardless of the time between the injury and death, or the length of the illness;

b. Days away from work (any time lost after day of injury/illness onset);

c. Restricted work;

d. Transfer to another job;

e. Medical treatment beyond first aid;

f. Loss of consciousness; or

g. A significant injury or illness diagnosed by a physician or other licensed health care professional, even if it did not result in (a) through (f) above

1.2.17 Government Property and Equipment

Interpret "USACE" property and equipment specified in USACE EM 385-1-1 as Government property and equipment.

1.2.18 Load Handling Equipment (LHE) Accident or Load Handling Equipment Mishap

A LHE accident occurs when any one or more of the eight elements in the operating envelope fails to perform correctly during operation, including operation during maintenance or testing resulting in personnel injury or death; material or equipment damage; dropped load; derailment;

two-blocking; overload; or collision, including unplanned contact between the load, crane, or other objects. A dropped load, derailment, two-blocking, overload and collision are considered accidents, even though no material damage or injury occurs. A component failure (e.g., motor burnout, gear tooth failure, bearing failure) is not considered an accident solely due to material or equipment damage unless the component failure results in damage to other components (e.g., dropped boom, dropped load, or roll over).