Attachment F PPI Spreasheet Argus with NAVFAC response.pdf
PDF 11 KB Posted
- Solicitation number
- N4008524R2776
About this file
This document appears to be a set of Questions and Answers related to a federal contract opportunity to Replace Chiller, Building 382, Dam Neck Annex, Virginia Beach, VA. The solicitation number is N4008524R2776.
The key details are:
- The scope of work involves removing an existing 40-ton air cooled chiller, demolishing associated piping, and installing a new 40-ton air cooled chiller with associated chilled water piping, including emergency chiller connections.
- The existing chiller will be turned over to the Government.
- Only contractors on the MACC Group (ML-C00075) can submit a proposal.
- The cut-off date for Requests for Information is August 14, 2024.
- The document provides responses to 8 specific questions from the offeror Argus CJW JV 3, LLC, covering topics such as geotechnical investigation requirements, access to as-built drawings, quality control staffing, and potential structural engineering needs.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| PPI Spreadsheet MIG GOV with NAVFAC response.pdf | ||
| 24R2776 AMENDMENT 0002.pdf | ||
| 24R2776 AMENDMENT 0001.pdf | ||
| 125_0323.JPG | JPG image | |
| Site Visit Sheet.pdf | ||
| 125_0327.JPG | JPG image | |
| 125_0322.JPG | JPG image | |
| 125_0329.JPG | JPG image | |
| 125_0328.JPG | JPG image | |
| 125_0325.JPG | JPG image | |
| 125_0324.JPG | JPG image | |
| 125_0326.JPG | JPG image | |
| BASE ACCESS INSTRUCTION.pdf | ||
| Attachment F PPI Spreasheet.xlsx | XLSX spreadsheet | |
| va167 (1).txt | TXT text file | |
| 1779363 Final DB_RFP.pdf | ||
| SECNAV 5512.pdf | ||
| Oceana IDIQ Front End SPECS - 20220602.pdf | ||
| N4008524R2776 GENERAL REQUIREMENTS .pdf | ||
| BLANK SPONSOR VERIFICATION SPREADSHEET.xls | XLS spreadsheet | |
| PROVISION 52.204-24.pdf | ||
| DEVGRU SPREADSHEET.xlsx | XLSX spreadsheet |
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Page Section Para. Dwg #
Argus CJW JV 3, LLC
08/13/24
Confirm that no geotechnical investigation is required during design A geotechnical investigation is not required during design. During construction, prior to foundation placement, the geotechnical engineer must verify that the subgrade has the stated bearing capacity as indicated in the
RFP, Part 3, Section 6, Paragraph A10
Foundation. ~Response by J. Picano
Argus CJW JV 3, LLC
08/13/24 Please share the as built drawings.
Reference drawings have already been provided in the RFP.
3 Argus CJW JV 3, LLC 08/13/24 Please share a sign in sheet. This was provided with Amendment 0001.
Argus CJW JV 3, LLC
08/13/24
Can a single person be a
QC/SSHO/Super?
See RFP, Part 2, 01 30 00.05 20
Administrative Requirements, 1.1
Supervision and 01 45 00.05 20 Design and
Construction Quality Control, 1.2 Quality
Control Manager Qualifications.
Argus CJW JV 3, LLC
08/13/24 Is US citizen is mandatory in job site? See RFP, Part 2, 01 14 00.05 20 Work
Restrictions, 1.2 Work Hours, Access and
Passes.
Argus CJW JV 3, LLC
08/13/24
Will we have access to the offices to run this pipe and will the offices be cleaned out This question does not apply to this project.
Argus CJW JV 3, LLC
08/13/24
Can we get an Existing 2nd Floor Plan that has the Room Numbers shown? Will
"new CMU wall at North End of Room
215" require structural engineer or any special reinforcing? If so we will need structural engineer for that small portion, assuming, right now we cannot determine where Room 215 is located exactly.
Otherwise, we should not require structural engineer on this project.
This question does not apply to this project.
Argus CJW JV 3, LLC
08/13/24 Would they consider alternate routing This question is not specific enough to be answered.
Project Title: REPLACE CHILLER, B382, DNA Solicitation / RFP#: N4008524R2776 - PPI Cut Off Date: 14 AUG 2024
Amend No.
GOVERNMENT RESPONSE
PPI No.
Offeror
Date
Submitted
REFERENCE
QUESTION
File details come from the government source that posted it. Updated .