This document is an amendment to a Request for Proposal (RFP) for the replacement of four rooftop HVAC units at Building 310 at the Naval Air Station Oceana, Dam Neck Annex in Virginia Beach, Virginia. The amendment clarifies that complete demolition of the existing rooftop unit support structures is required, and provides instructions to design and install a new curb support system. It also states that the reference drawings may not accurately reflect current conditions, and the contractor must field verify all existing conditions. The amendment specifies that a single person cannot serve as the Quality Control Manager, Site Safety and Health Officer, and Superintendent. It confirms that US citizenship is mandatory for all contractor personnel working on this project, as access to the Naval Special Warfare Development Group compound is restricted. Only contractors in the specified MACC group are eligible to submit proposals for this project.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Page Section Para. Dwg #
Confirm that demolition of the existing unit support frames is required, or if refurbishment and reuse may be considered.
Complete demolition of existing rooftop air-handling unit support structures are required.
Refer to RFP Part 3 paragraph 6.0
ENGINEERING SYSTEMS
REQUIREMENTS (ESR) sub-paragraph B10 SUPERSTRUCTURE, including the following:
- Demolish existing unit support beams complete, existing unit support posts to base plate, do not damage existing steel joists, repair existing deck penetration
- Design and provide new curb unit support system underneath existing deck, check existing joists and distribute the load to not overstress existing joists, reinforce as necessary at connection points.
Please share the as built drawings. Refer to RFP Part 6 for: -
BLDG. 310 AIR OPS AND GYM FIELD
VERIFICATION DRAWINGS
- BLDG. 310 PT REHAB AND DIVE OPS
FIELD VERIFICATION DRAWINGS
- STRUCTURAL REFERENCE
DRAWINGS OPERATIONS FACILITIES
1981 .
The remainder of the 1981 drawing set will be forwarded.
As stated in RFP Part 3 Section 4.0
BUILDING/GENERAL REQUIREMENTS:
Reference drawings must be used for informational purposes only, and may not accurately reflect current as-built conditions.
The Design Build Contractor must not solely rely on the reference drawings to determine existing conditions, but must field verify all existing conditions pertinent to the project.
Can a single person be QC/SSHO/Super?
NO. PART 2 GENERAL REQUIREMENTS,
01 30 00.05 20 1.1 ADMINISTRATIVE
REQUIREMENTS ALLOWS THE
SUPERINTENDENT TO SERVE AS THE
SSHO. 1.2 QUALITY CONTROL MANAGER
QUALIFICATIONS STATES THE
SUPERINTENDENT MAY NOT SERVE AS
THE QC MANAGER.
Project Title: Replace Four Rooftop Units, B310, Dam Neck Annex, Virginia Beach, Virginia
Solicitation / RFP#: N4008524R2767
Amend No.
GOVERNMENT RESPONSE
PPI No.
Offeror Date
Submitted
REFERENCE QUESTION
Is US Citizen is mandatory in Job Site? YES, Non-US citizens will not be granted access to the NSWDG compound Refer Part 2 01 14 00.05 20 WORK RESTRICTIONS paragraph 1.3.f.
Special security requirements apply to this contract. All Contractor personnel associated with this contract must obtain clearance to the NSWDG compound from the Activity's Security Officer in order to perform work in Building 310. Contractor personnel must submit full name, social security number and confirmation of US citizenship to Activity POC. Non-US citizens will not be granted access to the compound.
Strict adherence to the rules and regulations, as set forth by the Activity’s Security Officer, must be complied with at all times.
File details come from the government source that posted it. Updated .