This document is a Part 3 Project Program section for a Request for Proposal (RFP) for the Secure Electromagnetic Research Facility (SERF) at Naval Support Facility Dahlgren in Virginia. The project involves designing and constructing a state-of-the-art facility for the Naval Surface Warfare Center Dahlgren Division to test future radio frequency (RF) equipment. The facility will feature a large anechoic chamber with specific dimensional requirements (250'-0" x 90'-0" x 60'-0"), designed to support simultaneous radar testing on the ground floor and equipment platform, with integrated dynamic and static instrumentation walls.

The facility will include utility rooms, telecommunications infrastructure for unclassified and classified networks, fire protection systems, and will be designed to meet various federal standards including Unified Facilities Criteria (UFC). The building will have a steel superstructure, insulated metal panel exterior, standing seam metal roof, and concrete floors. The project emphasizes cybersecurity, sustainable design, and will provide an Open Storage Secret (OSS) environment. The facility is intended to support the development of future x-band radar capabilities and will be occupied by fewer than 10 people, with loading areas for equipment deliveries located on the southeast and northwest corners of the building.

View the file

Other files

File Type Posted
N4008025SP402.pdf PDF
N4008025SP402.pdf PDF
Attachment B_Project Data Sheet.docx DOCX document
Attachment D_Identified Vendor List.pdf PDF
N4008025SP402.pdf PDF
Attachment A_Contractor Information Form.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

P402 Secure Electromagnetic Research Facility (SERF) NSF Dahlgren, VA

PART 3 – PROJECT PROGRAM - Page 1

1.0 PROJECT DESCRIPTION

The Contractor shall design, deliver, and construct a Secure Electromagnetic Research Facility (SERF) for the Naval Surface Warfare Center Dahlgren Division (NSWCDD). This facility is situated at the intersection of Bronson Road and McVay Road south of Building 1580 at Naval Support Facility (NSF) Dahlgren. This project will primarily include ground-up construction of a state-of-the art facility that will provide the U.S.

Navy with a new means of testing future radio frequency (RF) equipment for deployment to the fleet. This test facility shall include the following rooms: a high-bay, indoor anechoic chamber, a control room, material lift, shop rooms, passageways, restrooms, and the dynamic/static instrumentation walls. The utility rooms shall include the following: chamber electrical, telecommunications, electrical, mechanical, and the fire pump room. The facility will be occupied by less than 10 people for design purposes.

The facility design shall incorporate a steel superstructure with insulated metal panel exterior membrane, standing seam metal roof, and concrete deck floors and slab. The building components shall also include a foundation, and mechanical, electrical and informational systems appropriate for the supported command and design to meet applicable Unified Facilities Criteria (UFC).

The anechoic chamber is the operational centerpiece that will comprise a significant footprint within this facility. Most, if not all, of the technical requirements within the facility are driven from the operational design criteria from the chamber itself. The Design-Build (DB) Contractor and the anechoic chamber subconsultant/contractor shall have a close working relationship throughout the design and construction of this facility. The anechoic chamber design criteria is largely provided by the Government and supported command and will require close collaboration to ensure that the dimensional, material, and RF design criteria is strictly adhered to. The anechoic chamber design shall have interior absorber tip-to-tip dimensions of 250’-0” (L) x 90’-0” (W) x 60’-0” (H) at the target end wall, sloping down to 46’-0” (H) at the transmit/radar end wall. There will also be an equipment platform at the 15 ft level off the ground extending back another 23’-0” bringing the total effective length for test items located on the equipment platform to at least 270’-0”. The chamber shall be designed to support two (2) radars operating simultaneously in various configurations on the ground floor and on the equipment platform. The static and dynamic instrumentation walls and associated equipment shall be incorporated into the chamber design and construction.

The facility shall include telecommunications infrastructure to support unclassified and classified networks for purposes of radar testing, building management facility services, and voice/video collaboration. Building telecommunication systems shall comply with UFC 3-580-01 Information and Communications Technology Infrastructure Planning and Design. Premium information systems include Intrusion Detection System (IDS) and CCTV infrastructure supporting safety monitoring within the anechoic chamber (i.e. no external connectivity).

The building shall be outfitted with appropriate fire alarm control panels and smoke detection systems per UFC 3-600-01 Fire Protection Engineering for Facilities. Due to the radar equipment susceptibility during an emergency, the anechoic chamber shall also be equipped with a clean agent system per NFPA 2001 Standard on Clean Agent Fire Extinguishing Systems. Outside of the chamber itself, the facility shall have a combination of dry- and wet-pipe sprinklers.

The project shall implement minimum Anti-Terrorism requirements per UFC 4-010-01 DoD Minimum Antiterrorism Standards for Buildings and physical security measures in accordance with UFC 4-026-01 Design to Resist Forced Entry.

Built-in equipment shall include the anechoic chamber, material lift, and static/dynamic instrumentation walls. Barrier-free design in accordance with UFC 1-200-01, DOD Building Code, and the Architectural Barriers Act (ABA) Standards shall be followed for the first level of the building. All other levels are not public spaces and will have 5 or fewer occupants in accordance with ABA section F206.2.3, Exception 1.

DRAFT

PART 3 – PROJECT PROGRAM - Page 2

Department of Defense and Department of Navy principles for High Performance and Sustainable Building Requirements shall be included in the design and construction of the project in accordance with federal laws, Executive Orders, and UFC 1-200-02 High Performance and Sustainable Building Requirements.

Site preparation shall include minimal site clearing on a flat 5.7-acre lot. Site development shall include earthwork, site utilities, parking for 5 vehicles, access roads to building and mechanical equipment, sidewalks, detention/retention facilities, landscaping, and other site improvements.

Electrical utilities shall include electrical distribution, site communications, and new transformer. The building point of connection has been identified as the existing 13.8kV, pad-mounted switch located on the northeast corner of the site that is fed from Substation 2.

Mechanical utilities shall include water supply, sanitary sewer, fire protection, and storm sewer.

Coordination with the NSF Dahlgren Master Plan and permitting with the Virginia Department of Environmental Quality (DEQ) is necessary for the stormwater management and erosion control design/construction. The site design shall be consistent with the Stormwater Pollution Prevention Plan

(SWPPP).

The facility shall be designed to meet or exceed the useful life specified in DoD Unified Facilities Criteria (UFC). It shall incorporate features that provide the lowest practical life cycle cost solutions satisfying the facility requirements with the goal of maximizing energy efficiency.

1.1 Facility Development

Construction of the P402 Anechoic Chamber shall utilize sound and efficient construction practices in compliance with the current issue dates of the following design guides and building codes.

A. Applicable Codes and Standards

Federal projects must comply with the Unified Facilities Criteria regulations and design criteria. For site and facility design, these include:

**NOTE: The current edition is to be used if not explicitly stated.

IBC International Building Code, Current Edition

NFPA 13 Standard for the Installation of Sprinkler Systems

NFPA 20 Standard for the Installation of Stationary Pumps for Fire Protection

NFPA 24 Standard for the Installation of Private Fire Service Mains and Their Appurtenances

NFPA 70 National Electrical Code, Current Edition

NFPA 72 National Fire Alarm and Signaling Code

NFPA 90A Standard for the installation of Air-Conditioning and Venting Systems

NFPA 101 Life Safety Code, Current Edition

NFPA 2001 Standard on Clean Agent Fire Extinguishing Systems

PART 3 – PROJECT PROGRAM - Page 3

FM Data Sheet 1-53 Anechoic Chambers

UFC 1-200-01 DoD Building Code, Current Edition

UFC 1-200-02 High Performance and Sustainable Building Requirements, Current Edition

UFC 1-300-02 Unified Facilities Guide Specifications (UFGS) Format Standard, Current Edition

UFC 3-101-01 Architecture, Current Edition

UFC 3-110-03 Roofing, Current Edition

UFC 3-120-01 Design: Sign Standards, Current Edition

UFC 3-120-10 Interior Design, Current Edition

UFC 3-190-06 Protective Coatings and Paints, Current Edition

UFC 3-201-01 Civil Engineering, Current Edition

UFC 3-201-02 Landscape Architecture, Current Edition

UFC 3-210-10 Low Impact Development, Current Edition

UFC 3-220-01 Geotechnical Engineering, Current Edition

UFC 3-230-01 Water Storage and Distribution, Current Edition

UFC 3-240-01 Wastewater Collection and Treatment, Current Edition

UFC 3-250-01 Pavement Design for Roads and Parking Areas, Current Edition

UFC 3-250-04 Standard Practice for Concrete Pavements, Current Edition

UFC 3-301-01 Structural Engineering, Current Edition

UFC 3-401-01 Mechanical Engineering, Current Edition

UFC 3-400-02 Design: Engineering Weather Data, Current Edition

UFC 3-410-01 Heating, Ventilating and Air Conditioning (HVAC), Current Edition

UFC 3-410-02 Direct Digital Control for HVAC & Other Building Control Systems, Current Edition

UFC 3-501-01 Electrical Engineering, Current Edition

PART 3 – PROJECT PROGRAM - Page 4

UFC 3-520-01 Interior Electrical Systems, Current Edition

UFC 3-530-01 Interior and Exterior Lighting Systems, Current Edition

UFC 3-550-01 Exterior Electrical Power Distribution, Current Edition

UFC 3-560-01 Operation and Maintenance: Electrical Safety, Current Edition

UFC 3-575-01 Lightning and Static Electricity Protection Systems, Current Edition

UFC 3-580-01 Information and Communications Technology Infrastructure Planning and Design, Current Edition

UFC 3-600-01 Fire Protection Engineering for Facilities, Current Edition

UFC 4-010-01 DoD Minimum Antiterrorism Standards for Buildings, Current Edition

UFC 4-010-06 Cybersecurity of Facility-Related Control Systems

UFC 4-026-01 Design to Resist Forced Entry, Current Edition

UFC 4-440-01 Warehouses and Storage Facilities, Current Edition

FC 1-300-09N Navy and Marine Corps Design Procedures, Current Edition

FC 2-000-05N Facility Planning Criteria for Navy and Marine Corps Shore Installations, Current Edition

ABA Architectural Barriers Act Accessibility Standards, Current Edition

ASHRAE 90.1 ANSI/ASHRAE/IES Energy Standards for Buildings Except Low Rise, Commercial Buildings, Current Edition

NAVFAC Interior Design Procedures – FF&E, Current Edition

FMDS 1-53 Anechoic Chambers, Current Edition

NFPA 13 Standard for the Installation of Sprinkler Systems, 2025 Edition

NFPA 72 National Fire Alarm and Signaling Code, 2025 Edition

NFPA 2001 Standard on Clean Agent Fire Extinguishing Systems, 2025 Editionas

2.0 PROJECT OBJECTIVES

2.1 Mission Statement

The P402 Secure Electromagnetic Research Facility (SERF) is to meet the emerging far field radar testing requirements of the Supported Command, the Naval Surface Warfare Center Dahlgren Division (NSWCDD). It will enable the specialized radio frequency testing of developmental and production radar systems required for deploying to the Fleet. This facility will further assess these specialized weapon systems that will serve to deter and defeat our adversaries.

PART 3 – PROJECT PROGRAM - Page 5

2.2 Facility Function

The SERF will be utilized to support the development of future x-band radar (FXR) capabilities that cannot be fully exercised in an open-air environment. The 256-ft x 96-ft (nominal dimensions) anechoic chamber will be encircled by passageways and support areas. More detailed dimensions are listed in Section 2.3 below. The anechoic chamber will have the ability to have radar testing capabilities on both the ground floor and equipment platform on the second level which will be accessible via the 30-ft x 30-ft material lift.

Loading areas on the southeast and northwest corners of the building will be the main exterior access areas for radar and equipment deliveries. The north target wall within the anechoic chamber will also have provisions for the dynamic and static instrumentation systems. The entire space will be Open Secret Storage (OSS).

2.3 Project Specific Priorities

An anechoic chamber design consultant/subcontractor is required for the design and construction of this project. This chamber contractor shall have a minimum of ten (10) years of experience in collaborating with architects, clients, contractors, and measurement system vendors. This chamber contractor shall provide full design-build capabilities including pre-design project planning, custom engineering design, and BIM modeling. Lastly, the chamber contractor shall provide assurance that the final chamber design will meet the agreed upon performance, quality, and schedule requirements established by the Supported Command and NAVFAC. The anechoic chamber required minimum dimensions are listed below and reflected in the RF concept drawings in Part 6 of this document.

• Chamber Enclosure at Ground Floor o Inside Face of Shield (Wall-to-Wall): 256’-0” (L) x 96’-2” (W) o Absorber Tip-to-Tip: 250’-0” (L) x 90’-2” (W)

• Equipment Platform o Wall-to-Leading Edge: 23’-2” (D) x 96’-2” (W) o Absorber Tip-to-Leading Edge: 20’-2” (L) x 90-2”(W)

• Chamber Enclosure at Level 2 Elevation o Inside Face of Shield (Wall-to-Wall): 279’-0” (L) x 96’-2” (W)

Absorber Tip-to-Tip: 273’-0” (L) x 90’-2” (W)

• Wall Heights o Radar Wall: 43’-0” Height o Target Wall: 66’-0” Height

2.3.1 Sustainable Design and Construction

Design and construct project to comply with sustainability requirements identified in Part 2 UFGS Section 01 33 29, Sustainability Requirements and Reporting. Additional specific sustainability requirements are found in RFP Part 2, Part 3, and Part 4 sections.

PART 3 – PROJECT PROGRAM - Page 6

Design and construct project in accordance with UFC 1-200-02, High Performance and Sustainable Building Requirements.

2.3.2 Storm Water Management - Low Impact Development (LID)

Comply with UFC 3-210-10, Low Impact Development and FC 1-300-09N Navy and Marine Corps Design Procedures. Additional specific LID and stormwater management requirements are found in RFP Parts 3 and 4, Section G30. In addition to LID, comply with State and Local stormwater regulations.

2.3.3 Energy Efficiency

The building’s energy efficiency shall be in accordance with UFC 1-200-02, High Performance Sustainable and Building Requirements.

2.3.4 Building Commissioning

Provide commissioning to meet requirements identified in Section 01 91 00.15 Building Commissioning, and UFC 1-200-02 High Performance and Sustainable Building Requirements.

2.3.5 Accessibility Requirements

Provide barrier-free design in accordance with UFC 1-200-01 , DoD Building Code (General Building Requirements).

2.3.6 Antiterrorism Criteria

Facility will have an occupancy designated as low occupancy and UFC 4-010-01 does not apply.

Facility will be less than 3 stories and will not be required to meet the progressive collapse avoidance standards.

Structural components and assemblies do not meet the conventional construction parameters in UFC 4-010-01,Table 2-3 or are not listed in UFC 4-010-01, Table B-2.

2.3.7 Cybersecurity

Design, acquire and execute all control systems (including systems separate from management utility monitoring and control system) in accordance with UFC 4-010-06 Cybersecurity of Facility- Related Control Systems and as required by individual Facilities Engineering Command (FEC) or Installation implementation policy.

Incorporate ICS Security Controls located in NIST 800-82, Appendix G, Table G-1. Design the project using UFGS 25 05 11, Cybersecurity for Facility-Related Control Systems. Incorporate elements of the NAVFAC Cybersecurity Hygiene Checklist into contract specifications by using

SECTION 25 05 11, CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS. CIO4

Point of Contact to be utilized in SECTION 25 05 11 is: TO BE DETERMINED. Contact information shall include: Office code, usually CIO4, contact phone number, and address of NAVFAC CIO POC]. Submit Cybersecurity Plan and Cybersecurity Hygiene Report in accordance with SECTION 25 05 11."

The following are the steps to perform for the full Cybersecurity design:

http://www.wbdg.org/ffc/dod/unified-facilities-criteria-ufc/ufc-1-200-01

PART 3 – PROJECT PROGRAM - Page 7

Step 1 - Determine the Confidentiality, Integrity, and Availability (C-I-A) impact levels (Low, Moderate, or High) for each of the Facility-Related Control System. (HVAC, FLS, UCS, ESS, ES)

1. Facility Related Controls Systems (FRCS): Develop the FRCS matrix during the Design Phase of the project.

Step 2: Use impact levels to select the proper list of controls per the National Institute of Standards and Technology - NIST SP 800-82.

1. Facility Related Controls Systems (FRCS): Update the FRCS matrix, identifying specific project requirements to incorporate, and identifying components that are outside of the Design-Build Contractor scope of work.

2. Note: The RMF Knowledge Service (https://rmfks.osd.mil) contains guidance on determining controls from C-I-A ratings, including an Excel Spreadsheet that generates a control list based on the impact ratings and the NIST SP 800-82 guidance. This website is CAC-enabled; designers without a CAC must request assistance from the Service if tables and information were not provided.

Step 3 – CCI’s & Diagrams: Using the DoD master Control Correlation Identifier (CCI) list, create a list of relevant CCIs based on step 2.

1. This list of CCIs identifies cybersecurity requirements to be included in control system design.

2. Create a cybersecurity level 1-5 (if requested by end-user) control system architecture diagrams for each facility-related control system.

Step 4 – Categorize CCIs for each FRCS

1. Identify CCIs that require input from the designer.

Step 5 – Specifications UFGS 25 05 11 for each FCRS : Incorporate cybersecurity requirements into project specifications.

2.3.8 Secured Areas

Provide an Open Storage Secret (OSS) environment within the building that complies with the SECNAV M-5510.36 Department of Navy Information Security Program, 32 CFR 2001.53, 32 CFR Part 117, and all requirements included within this document.

Provide secured area(s) as required by the Part 3, Chapter 5 - Room Requirements table of this

RFP.

2.4 Appropriate Design

Not Used.