Attachment_C.pdf

PDF 27 KB Posted

Attached to
NAVFAC EXWC MUSE 1400 kW Power Plants Exchange of Equipment
Solicitation number
N39430-14-R-1401
Issued by

About this file

Description of OLD Government Owned Equipment Offered for Exchange.

View the file

Other files

File Type Posted
N39430-14-R-1401-Amend03.pdf PDF
N39430-14-R-1401-Amend02.pdf PDF
N39430-14-R-1401-Amend_01.pdf PDF
Attachment_E.pdf PDF
Attachment_D.pdf PDF
N39430-14-R-1401.pdf PDF
Attachment_H.pdf PDF
Attachment_G.pdf PDF
Attachment_F.pdf PDF
Attachment_I.pdf PDF
Attachment_E.pdf PDF
Attachment_D.pdf PDF
N39430-14-R-1401-Amend03.pdf PDF
Attachment_A.pdf PDF
Attachment_B.pdf PDF
Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1 Attachment C

ATTACHMENT C- Detailed Description of Old Power Plants for Exchange

Condition of All Items: “AS - IS”

THE GOVERNMENT DOES NOT WARRANT THE CONDITION OF THE POWER PLANTS AND

COLLATERAL EQUIPMENT

1.0 Nomenclature. Four (4) classes of OLD power plants are being offered in this exchange. See below listings of individual generators, collateral equipment, and spare parts. A description of power plants is provided below. Drawings of power plants are provided in enclosure (3).

a. 750kW (4160VAC/130Amp/60Hz) self-contained Mobile Utilities Support Equipment (MUSE) Diesel power plants and collateral equipment.

b. 1500kW (4160VAC/260Amp/60Hz) self-contained Mobile Utilities Support Equipment (MUSE) Diesel power plants and collateral equipment.

c. ds2000kW (4160VAC/347Amp/60Hz) self-contained Mobile Utilities Support Equipment (MUSE) Diesel power plants and collateral equipment.

d. ds2500kW (4160VAC/430Amp/60Hz) self-contained Mobile Utilities Support Equipment (MUSE) Diesel power plants and collateral equipment.

2.0 Quantity. Twenty-eight (28) total power plants. The government does not warrant that all items and quantities of collateral equipment are present within each power plant’s enclosure.

a. 750kW (4160VAC/130Amp/60Hz) 5 power plants

b. 1500kW (4160VAC/260Amp/60Hz) 10 power plants

(includes control skid)

c. 2000kW (4160VAC/347Amp/60Hz) 7 power plants

(includes control skid)

d. 2500kW (4160VAC/430Amp/60Hz) 6 power plants

(includes control skid)

3.0 Location. All twenty-eight (28) power plants and collateral equipment are stored at the Mobile Utilities Support Equipment (MUSE) yard at Naval Base Ventura County, Port Hueneme, CA, 93043, and are available for inspection by prospective Offerors.

4.0 Power plants and collateral equipment.

a. 750kW (4160VAC/130Amp/60Hz)

1) Electrical Output: 750kW @ 0.8 PF, 4160VAC/130Amp/60Hz at 720 RPM

2) Configuration: The power plants are housed, self-contained, transportable, skid-mounted electric power plants. Each power plant has an Electro-Motive Division (EMD) 12-645E1 diesel engine, Baylor or Kato synchronous generator with brushless exciter, Woodward UG8 governing system, Basler 125H voltage regulation control, metal enclosed indoor type switchgear with analog metering, and local engine/generator management/protection controls for synchronizing, paralleling/load sharing during isolated operation or in parallel with a utility. These EMD power plants are Model Number 12-645-E1, 750kW, 4160VAC, 60 Hz.

Engine Skid Overall Length: 469 inches Overall Width: 121 inches Overall Height: 138 inches Weight (Empty): 88,500 pounds

3) Identification Numbers for 750kW power plants

Power Plant ID Number USN Number Engine Serial Number

2 Attachment C

1 51-12190 67-C1-1189 2 51-14821 67-F1-1179 3 51-14822 67-F1-1150 4 51-12191 66-C1-1151 5 51-12019 66-A1-1088

NOTE: The government will obliterate USN numbers from each power plant before it is turned over to the contractor. Above numbers (1-5) will be used to identify these units.

4) History of power plants: Each power plant was originally produced by A. G. Schoonmaker and received a “zero-time” overhaul (including switchgear and controls) under one of three contracts:

Contract Number Contractor N62578-86-C-6038 Stewart and Stevenson of Houston, TX N47408-89-C-2011 MCII Generator and Electric of Dallas, TX N47408-92-D-3118 MCII Generator and Electric of Dallas, TX

Technical inspection reports for the power plants are NOT available.

5) List of power plant by USN, overhaul contract, and presence of polychlorinated biphenyls (PCBS):

NOTE: Provision by the Government of the following data does not constitute a warranty of the condition of any of the power plants.

USN Number CONTRACT (overhaul contract)

PCBs

51-12190 N62578-86-C-6038 NO

51-14821 N62578-86-C-6038 NO

51-14822 N62578-86-C-6038 NO

51-12191 N62578-86-C-6038 NO

51-12019 N62578-86-C-6038 NO

b. 1500kW (4160VAC/260Amp/60Hz)

1) Electrical Output: 1500kW @0.8 PF, 4160VAC/260Amp/60Hz at 900 RPM

2) Configuration: The power plants are housed, self-contained, transportable, skid-mounted electric power plants. Each power plant set has an Electro-Motive Division (EMD) 16-645E4 diesel engine, synchronous generator with brushless exciter, governing system, voltage regulation control, metal enclosed indoor type switchgear with analog metering, and local engine/generator management/protection controls for synchronizing, paralleling/load sharing during isolated operation or in parallel with a utility. These EMD power plants are Model Number 16-645-E4, 1500kW, 4160VAC, 60 Hz.

Engine Skid Control Skid Exhaust Silencer Overall Length: 540 inches 220 inches 175 inches Overall Width: 125 inches 125 inches 120 inches Overall Height: 138 inches 125 inches 107 inches Weight (Empty): 112,700 pounds 18,000 pounds 3,000 pounds

3) Identification Numbers for 1500kW power plants

Power Plant ID Number USN Number Engine Serial Number 6 51-17103 69-C1-1130 7 51-14618 67-F1-1123 8 51-15121 67-F1-1115

3 Attachment C

9 51-16141 69-B1-1040 10 51-16522 69-D1-1060 11 51-12041 66-H1-1043 12 51-17102 69-L1-1100 13 51-13428 67-B1-1126 14 51-12039 66-F1-1162 15 51-16132 81-G3-7503

NOTE: The government will obliterate USN numbers from each power plant before it is turned over to the contractor. Above numbers (6-15) will be used to identify these units

4) History of power plants: Each power plant set was originally produced by:

NBY 75776 A. G. Schoonmaker, Sausalito, CA NBY 75819 A. G. Schoonmaker, Sausalito, CA NBY 92457 A. G. Schoonmaker, Sausalito, CA

Each power plant received a “zero-time” overhaul (including switchgear and controls) under one of the following contracts:

N62472-80-C-1648 PSD

N62578-86-C-6001 Morris & Knudsen TSARCM 83-02ANJX Tooele Army Depot TSARCM 83-02ANJX-A Valley Detroit Diesel N47408-89-C-2011 MCII Generator and Electric of Dallas, TX

Technical inspection reports for the generators are NOT available.

5) List of power plants by USN, overhaul contract, and presence of polychlorinated biphenyls (PCBS):

NOTE: Provision by the Government of the following data does not constitute a warranty of the condition of any of the Generators.

USN Original Contract Number

Overhaul Contract Number PCB’s

51-14618 NBY 75819 TSARCM 83-02ANJX NO

51-15121 NBY 75819 TSARCM 83-02ANJX NO

51-16141 NBY 92457 N47408-89-C-2011 NO

51-16522 NBY 92457 TSARCM 83-02ANJX NO

51-17103 NBY 92457 N62578-86-C-6001 NO

51-12041 NBY 92457 N62578-86-C-6001 NO

51-17102 NBY 92457 N62578-86-C-6001 NO

51-13428 NBY 75819 TSARCM 83-02ANJX NO

51-12039 NBY 92457 N62578-86-C-6001 NO

51-16132 NBY 92457 N47408-89-C-2011 NO

c. 2000kW (4160VAC/347Amp/60Hz)

1) Electrical Output: 2000kW @0.8 PF, 4160VAC/347Amp/60Hz at 900 RPM.

2) Configuration: The power plants are housed, self-contained, transportable, skid-mounted electric power plants. Each power plant has an Electro-Motive Division (EMD) 16-645E4 diesel engine, synchronous generator with series boost static exciter, electric governing system, voltage regulation control, metal enclosed indoor type switchgear with analog metering, and local engine/generator management/protection

4 Attachment C controls for synchronizing, paralleling/load sharing during isolated operation or in parallel with a utility.

These EMD power plants are Model Number 16-645E4, 2000kW, 4160VAC, 60 Hz.

Engine Skid Control Skid Overall Length: 600 inches 223 inches Overall Width: 144 inches 144 inches Overall Height: 156 inches 128 inches Weight (Empty): 120,000 pounds 25,000 pounds

3) Identification Numbers for 2000kW power plants

Power Plant ID Number USN Number Engine Serial Number 16 51-19776 84-A1-1010 17 51-19777 83-F1-1031 18 51-19778 83-E1-1029 19 51-19779 83-E1-1014 20 51-19782 83-F1-1015 21 51-19783 83-F1-1011 22 51-20004 83-E1-1001

NOTE: The government will obliterate USN numbers from each power plant before it is turned over to the contractor. Above numbers (16-22) will be used to identify these units.

4) History of power plants: Each power plant was originally produced by:

N62472-83-C-1663 Williams and Lane East Energy System Corp.

Technical inspection reports for the generators are NOT available.

5) List of power plants by USN, overhaul contract, and presence of polychlorinated biphenyls (PCBs):

NOTE: Provision by the Government of the following data does not constitute a warranty of the condition of any of the generators.

PCBs

51-19776 N62578-83-C-1663 NO

51-19777 N62578-83-C-1663 NO

51-19778 N62578-83-C-1663 NO

51-19779 N62578-83-C-1663 NO

51-19782 N62578-83-C-1663 NO

51-19783 N62578-83-C-1663 NO

51-20004 N62578-83-C-1663 NO

d. 2500kW (4160VAC/430Amp/60Hz)

1) Electrical Output: 2500kW @0.8 PF, 4160VAC/430Amp/60Hz at 900 RPM.

2) Configuration: The power plants are housed, self-contained, transportable, skid-mounted electric power plants. Each power plant has an Electro-Motive Division (EMD) 20-645E4 diesel engine, synchronous generator with brushless exciter, electric governing system, voltage regulation control, metal enclosed indoor type switchgear with analog metering, and local engine/generator management/protection controls for synchronizing, paralleling/load sharing during isolated operation or in parallel with a utility. These EMD power plants are Model Number 20-645-E4, 2500kW, 4160VAC, 60 Hz.

Engine Skid Control Skid Exhaust Silencer

5 Attachment C

Overall Length: 604 inches 175 inches 210 inches Overall Width: 144 inches 129 inches 53 inches Overall Height: 153 inches 132 inches 63 inches Weight (Empty): 133,800 pounds 18,000 pounds 4,000 pounds

3) Identification Numbers for 2500kW generators

Power Plant ID Number USN Number Engine Serial Number 23 51-19050 76-J1-1099 24 51-19051 82-H1-1004 25 51-19052 77-F1-1048 26 51-19053 77-F1-1016 27 51-19043 76-J1-1088 28 51-19044 76-K1-1102

NOTE: The government will obliterate USN numbers from each power plant before it is turned over to the contractor. Above numbers (23-28) will be used to identify these units.

4) History of power plants: Each power plant was originally produced by:

N62578-76-C-0209 Morrison-Knudsen Co

Technical inspection reports for the power plants are NOT available.

5) List of power plants by USN, overhaul contract, and presence of polychlorinated biphenyls (PCBS):

NOTE: Provision by the Government of the following data does not constitute a warranty of the condition of any of the generators.

PCBs

51-19050 N62578-76-C-0209 NO

51-19051 N62578-76-C-0209 NO

51-19052 N62578-76-C-0209 NO

51-19053 51-19043 51-19044

N62578-76-C-0209 N62578-76-C-0209 N62578-76-C-0209

NO