This document provides guidance on typical methods for applying self-regulating heat tape to maintain fluid and ambient temperatures above 40 Fahrenheit. It includes tables specifying the maximum circuit length, insulation thickness, and heat tape rating based on pipe/tubing size and material. The document also illustrates proper positioning, attachment, splicing, and end cap methods for the heat tracing elements. General notes cover testing requirements, allowable overlapping, and approved product part numbers. This guidance is relevant to the attached federal contract opportunity for 100T Critical Chiller Rental, solicitation number N3904024R0137, issued by the Department of the Navy Naval Sea Systems Command.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 100 Ton Critical Chiller System SOW.pdf | ||
| N3904024R0137 RFQ.pdf | ||
| Enclosure 2 PNSY OPSEC Contract Requirements 24-065.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Typical Methods for Applying Self-Regulating Heat Tape
Design Criteria (Apply to All Tables):
1. Maintain fluid above 40° Fahrenheit.
2. Maintain minimum ambient temperature above 40° Fahrenheit.
3. Insulate using tubular foam plastic (Rubber-Tex or equivalent).
4. Quick disconnects are to be freeze protected by using removable heat trace across the joints, and by insulating the joint with a removable insulated joint cover.
5. Energize heat tape from heat tape control panels.
Table 1: Typical Maximum Circuit Length
HEAT TAPE RATING
(WATTS/FT)
CIRCUIT BREAKER SIZE VS MAXIMUM CIRCUIT
LENGTH (FEET)
10A 15A 20A 8 125 150 200
NOTES:
1. Service voltage - 120 VAC, Ground Fault Circuit Interrupter (GFCI) protected.
2. Table values are for system startup temperature of 40° F.
3. Heat tapes do not have a minimum circuit length.
4. All installations must be per the National Electric Code.
5. For any clarification of the National Electric Code, contact cognizant technical code.
Table 2: Metal Pipe
PIPE SIZE
(OD)
INSULATION
THICKNESS (IN)
HEAT TAPE
RATING (WATTS/FT)
STRAIGHT SPIRALED
1/4 1/2 - 1 8 N/A 1/2 1/2 - 1 8 N/A 3/4 1/2 - 1 8 N/A 1 1/2 - 1 8 N/A
1-1/4 1/2 - 1 8 N/A 1-1/2 1/2 - 1 8 N/A
2 1/2 - 1 8 8 2-1/2 1/2 - 1 8 8
NOTE: Spiral factor is 1.32 feet of heat tape per 1 foot of pipe.
Table 3: Metal Tubing
INSULATION
THICKNESS (IN)
HEAT TAPE
RATING (WATTS/FT)
STRAIGHT SPIRALED
3/8 1/2 8 N/A 1/2 1/2 - 1 8 N/A 3/4 1/2 - 1 8 N/A 1 1/2 - 1 8 N/A
1-1/4 1/2 - 1 8 N/A
Table 4: Non-Metallic Pipe and Tubing
INSULATION
THICKNESS (IN)
HEAT TAPE
RATING (WATTS/FT)
STRAIGHT SPIRALED
1/4 1/2 - 1 8 N/A 3/8 1/2 - 1 8 N/A 1/2 1/2 - 1 8 N/A 3/4 1/2 - 1 8 N/A 1 1/2 - 1 8 8
1-1/4 1/2 - 1 8 8 1-1/2 1/2 - 1 8 8
2 1/2 - 1 8 8 2-1/2 1/2 -1 8 8
4 1 8 8
NOTE: Spiral factor is 1.32 feet of heat tape per 1 foot of pipe. Secure heat tape to hose every 2 to 3 feet.
Positioning and Attachment of Heating Elements (Typical)
Figure 1
Allowable Methods for Applying End Caps
Manufacturer's Kit (Long Sleeve Version)
Figure 2
Heat Shrink End Caps
Figure 3
NOTE: Methods differing from these shown may be used, if approved by cognizant technical code.
Typical Splice and Tee Connection Kits
Figure 4
Heat Tracing Pressure Regulators and Other Complex Components with Several Tubes
Figure 5
Heat Tracing Cutoff Valves for Bleeder Protected Systems
Figure 6
1. Exact configuration may vary.
2. For removable components, leave a loop of tracing long enough to make breaking the circuit unnecessary.
3. Take care to keep the flat side of the heater in as good physical contact with the body as possible.
4. Fully insulate and weather protect.
Heat Tracing 8" Diameter Fresh Water Manifolds
Figure 7
Table 5
HEATER CABLE RATING
(WATTS/FT)
REQUIRED LENGTH
(FT INCHES)
8 6' 3"
1. Length required to protect manifold is shown in table.
2. Take care to keep the flat side of the heater in as good physical contact with the manifold body as possible.
3. Fully insulate and weather protect.
GENERAL NOTES:
1. Heat tapes do not have a minimum length restriction.
2. Heat tapes may be overlapped. Wrap valves and flanges as shown.
3. Run heat tape along pipe or tubing.
4. Test each circuit after thermal insulation installation. Testing with a 500-volt D.C.
megger is acceptable. Minimum insulation resistance reading should be 20 megohms, regardless of length. If insulation resistance falls below the minimum reading:
a. Determine the cause of the insulation resistance drop, and take corrective action.
b. If damaged, remove the entire damaged section of heat tape and splice in a new section of heat tape, using approved splice kits.
5. Use stock numbers listed in table 6 for specific heat tape, or use one that meets the requirements of this PI.
Table 6
HEATER CABLE
RATING
(WATTS/FT)
STOCK NUMBER FOR
INDUSTRIAL GRADE
HEAT TAPE
RAYCHEM INDUSTRIAL
GRADE HEAT TAPE
PART NUMBER
8 LLDM10259EL 8BTV1-CR
Table 7
WOODHEAD CONNECTORS
MALE 24W47
FEMALE 25W47
END CAP 50W50
| Typical Methods for Applying Self-Regulating Heat Tape |
| NOTES: |
| Figure 1 |
| Figure 2 |
| Figure 3 |
| Figure 4 |
| Figure 5 |
| Figure 6 |
| NOTES: |
| Figure 7 |
| NOTES: |
| GENERAL NOTES: |