N39040-15-T-0176_-_All_attachments.pdf
PDF 1 MB Posted
- Solicitation number
- N39040-15-T-0176
About this file
N39040-15-T-0176 - All attachments
View the file
Other files
| File | Type | Posted |
|---|---|---|
| N39040-15-T-0176_Solicitation.pdf | ||
| 15-T-0176_FBO_pre_solicitation_notice_4-14-15.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TABLE V: TVENT MACHINERY & EQUIPMENT SCHEDULE
NO
SWLIN
OR
SYS
LCTN
SUB/MACH
DD / PIER
IDENTIFIER
TYPE [STYLE]–SZ
CRITICAL CMPNT
ARRIVAL
DATE
FOOTNOTE A
RETURN
DATE
SEASON
TERM
FTNT B
(wks)
ID IDENT ZONE MACHINE / EQPT STD│OPTION STD│OPTION 1ST CYCLE
ITEM QTY Position PURPOSE │ALTNV ANNOTATION EXTENSION 2ND CYCLE
V01 TCHW TO SHIP CHLR [3"CAM]–N 16 Jun '15 Tu 14 Jun '16 Tu S 52 A1 1ST of 1 DD flr Port FOR SHIP'S TCHW 1 NON-SEASONAL 18 Oct '16 Tu U1618
V02 TCHW TO SHIP PUMP [3"CAM]–N 16 Jun '15 Tu 14 Jun '16 Tu S 52 B1 1ST of 1 DD flr Port FOR SUB CHLR–N 1 NON-SEASONAL 18 Oct '16 Tu U1618
V03 TSPLY FWD DDU [CMBD]–N 16 Jun '15 Tu 24 May '16 Tu S 49 C 1ST of 3 DD flr Port ALTERNATIVE IA 1ST ARR / 3RD RTN 27 Sep '16 Tu O a18 V04 TSPLY SAIL DDU [CMBD]–N 30 Jun '15 Tu 17 May '16 Tu S 46 C 2ND of 3 Stbd Platf ALTERNATIVE IA 3RD ARR / 2ND RTN 27 Sep '16 Tu O b19 V05 TSPLY AFT DDU [CMBD]–N 23 Jun '15 Tu 10 May '16 Tu S 46 C 3RD of 3 DD flr Port ALTERNATIVE IA 2ND ARR / 1ST RTN
V06 TSPLY PIER 13C DDU [HTG]–N 25 Oct '16 Tu 03 Jan '17 Tu U1710 C' LATER Post-Dock ALTERNATIVE IA 2 POST–DD#1 14 Mar '17 Tu O c10
V07 TSPLY FWD DDU [DSCC]–N 16 Jun '15 Tu 24 May '16 Tu S 49 C1 1ST of 3 DD flr Port ALTERNATIVE IB 1ST ARR / 3RD RTN 27 Sep '16 Tu O 18 V08 TSPLY SAIL DDU [DSCC]–N 30 Jun '15 Tu 17 May '16 Tu S 46 C1 2ND of 3 Stbd Platf ALTERNATIVE IB 3RD ARR / 2ND RTN 27 Sep '16 Tu O 19 V09 TSPLY AFT DDU [DSCC]–N 23 Jun '15 Tu 10 May '16 Tu S 46 C1 3RD of 3 DD flr Port ALTERNATIVE IB 2ND ARR / 1ST RTN V10 TSPLY PIER 13C DDU [DSCC]–N 25 Oct '16 Tu 03 Jan '17 Tu U1710 C1 LATER Post-Dock ALTERNATIVE IB 2 POST–DD#1 14 Mar '17 Tu O c10
V11 TSPLY FWD RHC [STM]–N/2M 16 Jun '15 Tu 24 May '16 Tu S 49 C2 1ST of 3 DD flr Port ALTERNATIVE IB 3 RHC CAPACITY 27 Sep '16 Tu O a18 V12 TSPLY SAIL RHC [STM]–N/2M 30 Jun '15 Tu 17 May '16 Tu O46 C2 2ND of 3 Stbd Platf ALTERNATIVE IB 4 FOOTPRINT SIZE 27 Sep '16 Tu O b19 V13 TSPLY AFT RHC [STM]–N/2M 23 Jun '15 Tu 10 May '16 Tu S 46 C2 3RD of 3 DD flr Port ALTERNATIVE IB 3 RHC CAPACITY
V14 TSPLY FWD HTGC [ELEC]–N 29 Sep '15 Tu 24 May '16 Tu S 34 C3 1ST of 3 DD flr Port ALTERNATIVE IB 5OVERLAP CLGC 1ST HTG SEASON V15 TSPLY SAIL HTGC [ELEC]–N 29 Sep '15 Tu 17 May '16 Tu S 33 C3 2ND of 3 Stbd Platf ALTERNATIVE IB 5OVERLAP CLGC 1ST HTG SEASON V16 TSPLY AFT HTGC [ELEC]–N 29 Sep '15 Tu 10 May '16 Tu S 32 C3 3RD of 3 DD flr Port ALTERNATIVE IB 5OVERLAP CLGC 1ST HTG SEASON V17 TSPLY PIER 13C HTGC [ELEC]–N 25 Oct '16 Tu 03 Jan '17 Tu U1710 C3' LATER Post-Dock ALTERNATIVE IB 2 POST–DD#1 14 Mar '17 Tu O c10
V18 TSPLY FWD CLGC [PRE]–N 16 Jun '15 Tu 29 Sep '15 Tu S 15 C4' 1ST of 6 DD flr Port ALTERNATIVE IB 6CLGC CAPACITY 1ST CLG SEASON V19 TSPLY FWD CLGC[POST]-N/M 16 Jun '15 Tu 29 Sep '15 Tu S 15 C4" 2ND of 6 DD flr Port ALTERNATIVE IB 6CLGC CAPACITY 1ST CLG SEASON V20 TSPLY SAIL CLGC [PRE]–N 30 Jun '15 Tu 29 Sep '15 Tu S 13 C4' 3RD of 6 Stbd Platf ALTERNATIVE IB 6CLGC CAPACITY 1ST CLG SEASON V21 TSPLY SAIL CLGC[POST]-N/M 30 Jun '15 Tu 29 Sep '15 Tu S 13 C4" 4TH of 6 Stbd Platf ALTERNATIVE IB 6CLGC CAPACITY 1ST CLG SEASON V22 TSPLY AFT CLGC [PRE]–N 23 Jun '15 Tu 29 Sep '15 Tu S 14 C4' 5TH of 6 DD flr Port ALTERNATIVE IB 6CLGC CAPACITY 1ST CLG SEASON V23 TSPLY AFT CLGC[POST]-N/M 23 Jun '15 Tu 29 Sep '15 Tu S 14 C4" 6TH of 6 DD flr Port ALTERNATIVE IB 6CLGC CAPACITY 1ST CLG SEASON V24 TSPLY FWD CLGC [PRE]–N 24 May '16 Tu 27 Sep '16 Tu O a18 C4' LATER DD flr Port ALTERNATIVE IB 7OVERLAP HTGC 2ND CLG SEASON V25 TSPLY FWD CLGC[POST]-N/M 24 May '16 Tu 27 Sep '16 Tu O a18 C4" LATER DD flr Port ALTERNATIVE IB 7OVERLAP HTGC 2ND CLG SEASON V26 TSPLY SAIL CLGC [PRE]–N 17 May '16 Tu 27 Sep '16 Tu O b19
N39040-15-T-0176 Attachment 1 - Specification
SWLIN
OR
SYS
LCTN
SUB/MACH
DD / PIER
IDENTIFIER
TYPE [STYLE]–SZ
CRITICAL CMPNT
ARRIVAL
DATE
FOOTNOTE A
RETURN
DATE
SEASON
TERM
FTNT B
(wks)
ID IDENT ZONE MACHINE / EQPT STD│OPTION STD│OPTION 1ST CYCLE
ITEM QTY Position PURPOSE │ALTNV ANNOTATION EXTENSION 2ND CYCLE
C4' LATER Stbd Platf ALTERNATIVE IB 7OVERLAP HTGC 2ND CLG SEASON V27 TSPLY SAIL CLGC[POST]-N/M 17 May '16 Tu 27 Sep '16 Tu O b19 C4" LATER Stbd Platf ALTERNATIVE IB 7OVERLAP HTGC 2ND CLG SEASON V28 TSPLY FWD-INTR TCC [H&C]–L 23 Jun '15 Tu 21 Jun '16 Tu S 52 D1 1ST of 2 Stbd Platf ALTERNATIVE IIA 1 NON-SEASONAL 04 Oct '16 Tu U1615 V29 TSPLY AFT-INTR TCC [H&C]–L 23 Jun '15 Tu 21 Jun '16 Tu S 52 D1 2ND of 2 Stbd Platf ALTERNATIVE IIA 1 NON-SEASONAL 04 Oct '16 Tu U1615
V30 TSPLY FWD-INTR TCC [H&C]–2N 23 Jun '15 Tu 21 Jun '16 Tu S 52 D2 1ST of 2 Stbd Platf ALTERNATIVE IIB 1 NON-SEASONAL 04 Oct '16 Tu U1615 V31 TSPLY AFT-INTR TCC [H&C]–2N 23 Jun '15 Tu 21 Jun '16 Tu S 52 D2 2ND of 2 Stbd Platf ALTERNATIVE IIB 1 NON-SEASONAL 04 Oct '16 Tu U1615
V32 TEXH FWD-EXT AHU [EXH]–N 30 Jun '15 Tu 24 May '16 Tu S 47 E1 1ST of 4 DD Floor FOR FWD MBTS-EXT 1 NON-SEASONAL 27 Sep '16 Tu O a18 V33 TEXH AFT-EXT AHU [EXH]–N 30 Jun '15 Tu 10 May '16 Tu S 45 E1 2ND of 4 DD Floor FOR AFT MBTS-EXT 1 NON-SEASONAL V34 TEXH FWD-INTR AHU [EXH]–N 30 Jun '15 Tu 28 Jun '16 Tu S 52 E1 3RD of 4 Stbd Platf FOR FWD COMPT-INTR 1 NON-SEASONAL 04 Oct '16 Tu U1614 V35 TEXH AFT-INTR AHU [EXH]–N 30 Jun '15 Tu 28 Jun '16 Tu S 52 E1 4TH of 4 Stbd Platf FOR AFT COMPT-INTR 1 NON-SEASONAL 04 Oct '16 Tu U1614
V36 TCOND BOW DOME ACU [H&C]–L 21 Jul '15 Tu 19 Jul '16 Tu S 52 F1 1ST of 1 DD flr Port FOR BOW DOME/MISC 1 NON-SEASONAL 04 Oct '16 Tu O 11
V37 TCHW FWD CHLR [4"CAM]–L 26 Apr '16 Tu 27 Sep '16 Tu O a22 A2 1ST of 1 DD flr Port FOR FWD (AFT) DDU 8FIF DDU REMAIN 2ND CLG SEASON V38 TCHW FWD PUMP [4"CAM]–L 26 Apr '16 Tu 27 Sep '16 Tu O a22 B2 1ST of 1 DD flr Port FOR DDU CHLR–L 8FIF DDU REMAIN 2ND CLG SEASON V39 TCHW INTERIOR CHLR [6"CAM]–X 19 Apr '16 Tu 04 Oct '16 Tu U16 24 A3 1ST of 1 Stbd Platf FOR TCC–L/2N 2ND CLG SEASON
V40 TCHW INTERIOR PUMP [6"CAM]–X 19 Apr '16 Tu 04 Oct '16 Tu U16 24 B3 1ST of 1 Stbd Platf FOR TCC CHLR–X 2ND CLG SEASON
V41 TCHW EXT/INTR CHLR [8"FLG]–G 16 Jun '15 Tu 20 Oct '15 Tu S 18 A4 1ST of 1 Caisson FOR TCCS & DDUS 9UNIQUE TO DD#1 1ST CLG SEASON V42 TCHW EXT/INTR PUMP [8"FLG]–G 16 Jun '15 Tu 20 Oct '15 Tu S 18 B4 1ST of 1 Caisson FOR CHLR–G 9UNIQUE TO DD#1 1ST CLG SEASON
V43 TCHW FWD
TCC MANF [4"╬ 6"]–U 23 Jun '15 Tu 20 Oct '15 Tu S 17
G 1ST of 5 UPR Loop ALTERNATIVE IIIA 1ST CLG SEASON V44 TCHW AFT TCC MANF [4"╬ 6"]–U 23 Jun '15 Tu 20 Oct '15 Tu S 17 G 2ND of 5 UPR Loop ALTERNATIVE IIIA 1ST CLG SEASON
V45 TCHW FWD
DDU MANF [4"╬ 6"]–U 23 Jun '15 Tu 20 Oct '15 Tu S 17 G 3RD of 5 LWR Loop ALTERNATIVE IIIA 1ST CLG SEASON
V46 TCHW SAIL
DDU MANF [4"╬ 6"]–U 23 Jun '15 Tu 20 Oct '15 Tu S 17 G 4TH of 5 UPR Loop ALTERNATIVE IIIA 1ST CLG SEASON V47 TCHW AFT DDU MANF [4"╬ 6"]–U 23 Jun '15 Tu 20 Oct '15 Tu S 17 G 5TH of 5 LWR Loop ALTERNATIVE IIIA 1ST CLG SEASON V48 TCHW 2 TCCS MANF [4"╬ 6"]–U 19 Apr '16 Tu 04 Oct '16 Tu U16 24 G LATER UPR Loop ALTERNATIVE IIIA 2ND CLG SEASON
V49 TCHW FWD
DDU MANF [4"╬ 6"]–U 19 Apr '16 Tu 04 Oct '16 Tu O a24 G LATER DD flr Port ALTERNATIVE IIIA 8FIF DDU REMAIN 2ND CLG SEASON
V50 TCHW SAIL
DDU MANF [4"╬ 6"]–U 19 Apr '16 Tu 04 Oct '16 Tu O b24 G LATER UPR Loop ALTERNATIVE IIIA 8SIF DDU REMAIN 2ND CLG SEASON
V51 TCHW FWD
DDU MANF [4":3"×2]–L 23 Jun '15 Tu 20 Oct '15 Tu S 17
G1 1ST of 3 LWR Loop ALTERNATIVE IIIB 1ST SEASON 1ST CLG SEASON
OR
SYS
LCTN
SUB/MACH
DD / PIER
IDENTIFIER
TYPE [STYLE]–SZ
CRITICAL CMPNT
ARRIVAL
DATE
FOOTNOTE A
RETURN
DATE
SEASON
TERM
FTNT B
(wks)
ID IDENT ZONE MACHINE / EQPT STD│OPTION STD│OPTION 1ST CYCLE
ITEM QTY Position PURPOSE │ALTNV ANNOTATION EXTENSION 2ND CYCLE
V52 TCHW SAIL
DDU MANF [4":3"×2]–L 23 Jun '15 Tu 20 Oct '15 Tu S 17
G1 2ND of 3 UPR Loop ALTERNATIVE IIIB 1ST SEASON 1ST CLG SEASON V53 TCHW AFT DDU MANF [4":3"×2]–L 23 Jun '15 Tu 20 Oct '15 Tu S 17 G1 3RD of 3 LWR Loop ALTERNATIVE IIIB 1ST SEASON 1ST CLG SEASON
V54 TCHW FWD
DDU MANF [4":3"×2]–L 19 Apr '16 Tu 04 Oct '16 Tu O a24 G1 LATER DD flr Port ALTERNATIVE IIIB 8FIF DDU REMAIN 2ND CLG SEASON
V55 TCHW SAIL
DDU MANF [4":3"×2]–L 19 Apr '16 Tu 04 Oct '16 Tu O b24 G1 LATER UPR Loop ALTERNATIVE IIIB 8SIF DDU REMAIN 2ND CLG SEASON
V30 TCHW FWD
TCC MANF [4":3"×2]–L 23 Jun '15 Tu 20 Oct '15 Tu S 17 G1 TCC–2N UPR Loop ALTERNATIVE IIB 1ST CLG SEASON V31 TCHW AFT TCC MANF [4":3"×2]–L 23 Jun '15 Tu 20 Oct '15 Tu S 17 G1 TCC–2N UPR Loop ALTERNATIVE IIB 1ST CLG SEASON
V30 TCHW FWD
TCC MANF [4":3"×2]–L 19 Apr '16 Tu 04 Oct '16 Tu U16 24 G1 TCC–2N UPR Loop ALTERNATIVE IIB 2ND CLG SEASON V31 TCHW AFT TCC MANF [4":3"×2]–L 19 Apr '16 Tu 04 Oct '16 Tu U16 24 G1 TCC–2N UPR Loop ALTERNATIVE IIB 2ND CLG SEASON
V56 TCHW 2 DDUS MANF [6":4"×2]–X' 23 Jun '15 Tu 20 Oct '15 Tu S 17 G2 1ST of 1 LWR Loop ALTERNATIVE IIIB 1ST CLG SEASON
V57 TCHW FWD
TCC MANF [4":6"×2]–X 23 Jun '15 Tu 20 Oct '15 Tu S 17 G3 1ST of 3 UPR Loop ALTERNATIVE IIIB 1ST CLG SEASON
V58 TCHW SAIL
DDU MANF [4":6"×2]–X 23 Jun '15 Tu 20 Oct '15 Tu S 17 G3 2ND of 3 UPR Loop ALTERNATIVE IIIB 1ST CLG SEASON V59 TCHW AFT TCC MANF [4":6"×2]–X 23 Jun '15 Tu 20 Oct '15 Tu S 17 G3 3RD of 3 UPR Loop ALTERNATIVE IIIB 1ST CLG SEASON
V60 TCHW FWD
TCC MANF [4":6"×2]–X 19 Apr '16 Tu 04 Oct '16 Tu U16 24 G3 LATER UPR Loop ALTERNATIVE IIIB 2ND CLG SEASON V61 TCHW AFT TCC MANF [4":6"×2]–X 19 Apr '16 Tu 04 Oct '16 Tu U16 24 G3 LATER UPR Loop ALTERNATIVE IIIB 2ND CLG SEASON
V62 TCHW SAIL
DDU MANF [4":6"×2]–X 19 Apr '16 Tu 04 Oct '16 Tu O b24 G3 LATER UPR Loop ALTERNATIVE IIIB 8SIF DDU REMAIN 2ND CLG SEASON
V63 TCHW 2 DDUS SP [6"CAM-FLG]-X 16 Jun '15 Tu 20 Oct '15 Tu S 18 G4 1ST of 1 LWR Loop FOR DD#1 CHLR–G 9UNIQUE TO DD#1 1ST CLG SEASON
V64 TCHW EXT/INTR MANF [8":6"×2]-G 16 Jun '15 Tu 20 Oct '15 Tu S 18 G5 1ST of 1 Caisson FOR DD#1 CHLR–G 9UNIQUE TO DD#1 1ST CLG SEASON V65 TCHW EXT/INTR HOSE [4"CAM]–L 16 Jun '15 Tu 20 Oct '15 Tu S 18 H1 1ST of 1 FWDAFT ALTERNATIVE IIIB 1ST CLG SEASON
V66 TCHW EXT/INTR HOSE [6"CAM]–X 16 Jun '15 Tu 20 Oct '15 Tu S 18 H2 1ST of 1 FWDAFT ALTERNATIVE IIIA 1ST CLG SEASON
V67 TCHW EXTERIOR HOSE [6"FLG]–X' 16 Jun '15 Tu 20 Oct '15 Tu S 18 H3 1ST of 1 LWR Loop FOR DD#1 CHLR–G 9UNIQUE TO DD#1 1ST CLG SEASON V68 TCHW EXT/INTR HOSE [8"FLG]–G 16 Jun '15 Tu 20 Oct '15 Tu S 18 H4 1ST of 1 Caisson FOR DD#1 CHLR–G 9UNIQUE TO DD#1 1ST CLG SEASON
V69 TSPLY EXT/INTR DUCT [FTGS]–G 23 Jun '15 Tu 21 Jun '16 Tu E NA J1 1ST of 1 SHIP FOR TCC / DDU / ACU 10 PNS ELECTIVE 04 Oct '16 Tu ALL-TIME
V70 TSPLY EXT/INTR DUCT [+FLEX]–G 23 Jun '15 Tu 21 Jun '16 Tu E NA J2 1ST of 1 SHIP FOR TCC / DDU / ACU 10 PNS ELECTIVE 04 Oct '16 Tu ALL-TIME V71 TEXH EXT/INTR DUCT [−FLEX]–X 30 Jun '15 Tu 28 Jun '16 Tu E NA J3 1ST of 1 SHIP FOR AHU [EXH]–N 10 PNS ELECTIVE 04 Oct '16 Tu ALL-TIME V72 TEXH EXT/INTR DUCT [−FLEX]–N 30 Jun '15 Tu 28 Jun '16 Tu E NA J4 1ST of 1 WYE FOR AHU [EXH]–N 10 PNS ELECTIVE 04 Oct '16 Tu ALL-TIME
V73 TVENT EXTERIOR E-STOP [D&E]–02 23 Jun '15 Tu ANYTIME AFTER S NA
OR
SYS
LCTN
SUB/MACH
DD / PIER
IDENTIFIER
TYPE [STYLE]–SZ
CRITICAL CMPNT
ARRIVAL
DATE
FOOTNOTE A
RETURN
DATE
SEASON
TERM
FTNT B
(wks)
ID IDENT ZONE MACHINE / EQPT STD│OPTION STD│OPTION 1ST CYCLE
ITEM QTY Position PURPOSE │ALTNV ANNOTATION EXTENSION 2ND CYCLE
K1 1ST of 1 Guard Area FOR 2 AHUS & TCCS 11PRE-SCHEDULE TBD BY TSZM TWO-TIME
V74 CALL EXTERIOR CALL [≤6HR]–16 16 Jun '15 Tu ANYTIME AFTER S NA K2 1ST of 1 Machinery FOR MACHINES A–F 12 E-MAIL CHECK TBD BY TSZM 16–TIMES
V75 TRNG EXTERIOR TRNG [≥4HR]–02 16 Jun '15 Tu ANYTIME AFTER S NA K3 1ST of 1 Machinery FOR MACHINES A–F 11PRE-SCHEDULE TBD BY TSDE TWO-TIME V76 TECH EXT/INTR TECH [≤8HR]–02 16 Jun '15 Tu ANYTIME AFTER S NA K4 1ST of 1 CHW Loop FOR DD#1 CHLR–G 11PRE-SCHEDULE TBD BY TSZM TWO-TIME V77 DATA E-MAIL EDS [A–F]–01 16 Jun '15 Tu 28 Jun '16 Tu S NA L 1ST of 1 Grossman FOR MACHINES A–F E-MAIL REQUEST TBD BY TSDE ONE-TIME
TABLE V: TVENT SWLINS
TITLE DEHUMIDIFIED AIR
(100% OUTSIDE AIR)
INDUSTRIAL AIR
(100% OUTSIDE AIR)
CHILLED WATER
(NON-SEASONAL)
CONDITIONED AIR
(MAINLY
RETURN
AIR)
RECYCLED AIR OR
CHILLED WATER
CHILLED WATER
(NCHW)
PURPOSE DRY AIR
FOR BLAST & PAINT
FRESH AIR
FOR SHIP'S INTERIOR
TEMPCHILLEDWATER
FOR SHIP'S PIPING
COMFORT AIR
FOR BOW DOME ETC.
TEMPERED AIR
FOR ENCLOSURES
SEASONAL
FOR NUCLEAR BLDG
SYSTEM TSPLY-TEXH-TCHW TSPLY-TEXH-TCHW TCHW [SHIP] TCOND for SHT-RSC-XCEL CHW [NUC]
TABLE V: TVENT FOOTNOTES WITH ANNOTATIONS
FOOTNOTE A:
1 NON-SEASONAL For the single Normal (–N) capacity Chiller with Pump that supplies chilled water directly to the ship, the machine(s) are continuously needed irrespective of the season and for the entire duration of the drydock period. The asterisk () further identifies the machine(s) as CRITICAL component(s) in which there are extra Contractual obligations as specified elsewhere in the Technical Specification (TS).
Other NON-SEASONAL type machinery and equipment are ITEM C: DDUs & RHCs; ITEM D: TCCs;
AHU, ACU, and DUCT. SEASONAL machinery and equipment (other than the CHLR w/ PUMP ???
identified above) are the HTGC, CLGC, CHLR, PUMP, MANF (includes SP for DD#1), and HOSE.
2 POST–DD#1 There is an unusual requirement for a dehumidifier at the post-dock Berth just prior to undocking from Drydock No. 1 only (POST DD#1). The dehumidified air is necessary for minor hull repair after removal of Buoyancy cans necessary to undock (UD) a submarine from DD#1. Accordingly: (i) the post-dock scheduled season is the autumn; (ii) the capacity for airflow and moisture removal is half of what is normally required; and (iii) there is NO steam utility at the Berths. Correspondingly:
(i) dependent on the actual schedule, the Contractor may either keep the last remaining Normal (–N) capacity dehumidifier (e.g. FWD DDU) on-site for reuse post-dock or schedule a later delivery of some other dehumidifier; (ii) the capacity of the dehumidifier can be anywhere from half (i.e. Medium –M) to the same as for the Normal (–N) capacity dehumidifier, but, the capacity for the post-heater cannot be less than its associated dehumidifier; and (iii) the dehumidifier will use electric Reactivation, i.e.
NO (steam) Reactivation Heating Coil (RHC) will be needed – thus, a combined [CMBD] dehumidifier will not require functioning pre-/post- cooling coils and will use only electric reactivation and the desiccant [DSCC] dehumidifier will not require a separate steam [STM] RHC.
3 RHC CAPACITY For ALTERNATIVE IB (desiccant type [DSCC] dehumidifier only – neither pre- nor post- air treatment), the Vendor has a choice of either a single Normal (–N) or a pair of Medium (–M) capacity steam [STM]
AND Reactivation Heating Coil(s) (RHCs) for all three dehumidifiers. However, subject to footprint, there is the possibility that the SAIL DDU may have insufficient space nearby to accommodate the steam RHC.
4 FOOTPRINT SIZE The Vendor must provide precise footprint dimensions of each capacity type of steam RHC, along with its other machinery, and be prepared to deliver the SAIL RHC as scheduled. Whereas the capacity type of RHC is a VENDOR CHOICE, the decision to deploy the SAIL RHC is a GOVERNMENT OPTION dependent on its footprint and available platform space. The Temporary Systems Design Engineer (C230.1RG) will evaluate as to whether the SAIL RHC could fit within the available space. Contracting will then inform the Vendor, sufficiently prior to shipment, as of whether to commence a lease of the SAIL RHC.
5OVERLAP CLGC For ALTERNATIVE IB (desiccant type [DSCC] dehumidifier only – neither pre- nor post- air treatment), the Vendor must provide an autumnal four week (4 wk) overlap between the previous pre-cool & post-cool coils and the following post-heat coil AT NO ADDITIONAL COST. Only by allowing for this overlap of pre-treatment and post-treatment coils can the Government equate the Bid offers between a Vendor offering the preferred ALTERNATIVE IA combined [CMBD] dehumidifier which integrates pre-cooling, post-cooling, & post-heating and the permitted ALTERNATIVE IB dehumidifier lacking such integrated coils. If the overlap should be greater than four weeks, then the Government is obligated for the additional duration of the previous coil(s) which in this case is the pair of cooling coils. For this particular autumnal four-week overlap, the succeeding post-heat coil must arrive by the scheduled ARRIVAL date and the preceding pre-cool and post-cool coils should depart within four weeks after its scheduled RETURN date so as to not incur any additional fee.
6CLGC CAPACITY As background, the needed chilled water cooling capacity for a post-cooler is only half of what is required for a pre-cooler. The pre-cooling coil uses about half of its energy to process the air (moisture removal – i.e. latent heat of condensation) and the other half to treat the air (temperature reduction – i.e. sensible heat). Whereas, the post-cooler, similar to a post-heater, is used for comfort control for temperature treatment only (i.e. sensible heat). Thus, a pre-cooler would be sized as a Normal (–N) capacity machine of approximately fifty (50) tons, but, the pre-cooler could be sized up to half as much similar to a Medium (–M) capacity machine of twenty-five (25) tons. Although the Vendor has a choice as to the cooling capacity for the post-cooler only as either Normal or Medium (–N/M) capacity, the advantage of making both the pre-cooler and the post-cooler machines the same would be their interchangeability.
TABLE V: TVENT FOOTNOTES WITH ANNOTATIONS (continued)
FOOTNOTE A (continuation):
7OVERLAP HTGC For ALTERNATIVE IB (desiccant type [DSCC] dehumidifier only – neither pre- nor post- air treatment), the Vendor must provide a springtime four week (4 wk) overlap between the previous post-heat coil and the following pre-cool & post-cool coils AT NO ADDITIONAL COST. Only by allowing for this overlap of pre-treatment and post-treatment coils can the Government equate the Bid offers between a Vendor offering the preferred ALTERNATIVE IA combined [CMBD] dehumidifier which integrates pre-cooling, post-cooling, & post-heating and the permitted ALTERNATIVE IB dehumidifier lacking such integrated coils. If the overlap should be greater than four weeks, then the Government is obligated for the additional duration of the previous coil(s) which in this case is the single heating coil. For this particular springtime four-week overlap, the succeeding pre-cool and post-cool coils must actually arrive at least four weeks prior to its scheduled ARRIVAL date and the preceding post-heat coil should depart by its scheduled RETURN date so as to not incur any additional fee.
8 IF DDU REMAIN The scheduled plan is for the Project to complete all Blast and Paint (B&P) operations in the late Spring of 2016 just prior to the requisite pre-cooling and post-cooling of dehumidified air for a second cooling season 2ND CLG SEASON. However, an OPTION has been included in this Technical Specification to allow for an extension (EXT) of the lease of either the 8F FWD DDU and/or the 8S SAIL DDU so that the applicable dehumidifier(s) can REMAIN throughout the second cooling season. Dependent on which dehumidifier remains, specific types of machinery and equipment will be leased as an OPTION to support that dehumidification process. In particular, the 8F FWD DDU, which because of its isolated location on the Drydock floor, would require the lease of a separate chiller (CHLR [4"CAM]–L) with pump (PUMP [4"CAM]–L) besides cooling coils (ALTERNATIVE IB only) and manifold(s). Whereas, the 8S SAIL DDU, because of its proximity between the FWD & AFT TCCS, would connect to the TCC chiller (CHLR [6"CAM]–X) with pump (PUMP [6"CAM]–X) during the second cooling season and would only require the lease of cooling coils (ALTERNATIVE IB only) and manifold(s).
9UNIQUE TO DD#1 Because of the non-existence of balcony platforms for the placement of machinery on the South (submarine Port) side of the drydock and the presence of a clearance zone for a forklift path also along the South (submarine Port) side of the drydock floor, Drydock No. 1 (DD#1) has severely restricted footprint space for machinery either in the drydock or on the North (submarine Starboard) balcony platforms. To resolve the limited footprint issue and during the overhaul evolution when machinery is in peak demand, the seasonal chilled water demand can only be met by a single Gigantic (–G) chiller and pump with other associated equipment located near the Caisson versus within the immediate drydock environs (i.e. drydock floor or balcony platforms). For this overhaul, the peak demand for seasonal chilled water is only for the first cooling season (1ST CLG SEASON).
10 PNS ELECTIVE Dependent on Shipyard availability, the lease of rigid duct fittings DUCT [FTGS]–G and both the positive and negative pressure flexible ducting DUCT [±FLEX]–G/–X/–N are a Government PNS ELECTIVE as to whether an ITEM shall be leased. Also, these lease items have a ONE-TIME fee TERM for the entire duration that its associated machinery are under lease and not subject to a weekly rental TERM. The officially issued Contract will inform the Vendor as to whether each of the subject ITEMs are to be leased. The rigid duct fittings and the positive pressure flexible ducting would be required on-site EARLIER by one week than the LATER negative pressure flexible ducting.
The Contract ARRIVAL DATE will be adjusted so as to provide the Vendor with a three week lead time for the EARLIER ITEMs and a four week lead time for the LATER ITEMs unless the Vendor initiates and/or indicates a desire for the original speculative calendar dates. As adjusted, this lead time should be sufficient for the Vendor to place an order after Contract award if it should have an insufficient supply of a particular lease product.
11PRE-SCHEDULE There are specific Contract Line Items requiring the services (labor) of the Vendor that are NOT of an emergent nature and are best coordinated in advance and initiated by the responsible Shipyard Party via communications with the Vendor. The Project's Temporary Systems Zone Manager [TSZM] is responsible for scheduling (a) Vendor installation of E-Stops (ITEM K: E-STOP [D&E]–02) and (b) DD#1 only, Vendor assistance for the (dis)connection of the 1ST CLG SEASON Chilled Water (CHW) Loops manifolds to include the standpipe and specialty hose assemblies (ITEMs G & ITEMs H).
The TSZM will endeavor to provide the Vendor at least three normal workdays advance notice. The Shipyard's Temporary Systems Design Engineer [TSDE] is responsible for coordinating with the Vendor Shipyard training (ITEM L3: TRNG [≥4HR]–02) and will provide the Vendor at least two calendar weeks prior notice of the training date(s).
FOOTNOTE B:
These initial STANDARD CLIN (S ) durations span a Leap Day (29th of February) for the Leap Year 2016. When using the GRAPHIC DATE FINDER / SCHEDULATOR, the actual date for a given duration is one day sooner than the date shown on the SCHEDULATOR.
The CRITICAL NON-SEASONAL Normal (–N) capacity Chiller with Pump is needed for the entire duration of the drydock period regardless of whether or not that duration exceeds one year. Other NON-SEASONAL type machinery required for the full or near full duration of the drydock period are just the two AHUs dedicated to the ship's Interior Compartments (FWD & AFT) and all TCCs which happen to also provide ventilation to the ship's Interior Compartments. The scheduled duration for the drydock period is sixteen (16) calendar months. These ITEMs are initially scheduled for fifty-two (52) weeks as an initial STANDARD (S) CLIN and require a semi-automatic extension UNFUNDED CLIN (U ) prior to their scheduled RETURN DATE.
The initial durations for each dehumidifier and its supporting machinery (STANDARD CLIN) reflect an aggressive programmed Blast and Paint (B&P) guesstimate by the C970 Operations Manager. The programmed EXTENSION reflected in TABLE V: TVENT MACHINERY & EQUIPMENT SCHEDULE are an extension OPTION(AL) CLIN meant to provide the necessary flexibility to defer the RETURN DATE for the FWD (O a), SAIL (O b), or POST-DOCK (O c) dehumidifiers and to obtain associated seasonal supporting machinery for that particular dehumidifier such as a chiller, pump, or manifold(s).
This initial STANDARD CLIN (S ) is for a POST-DOCK dehumidifier or for its associated seasonal support machinery.
This initial OPTION(AL) CLIN (O ) is for a machine (SAIL RHC) in which there has been insufficient platform footprint to deploy at Drydock No. 1 (DD#1) only. A temporary somewhat larger platform will be constructed after docking in lieu of the previous permanent platforms, so, there may be sufficient platform footprint. Also, this particular unit needs to be listed, regardless of intent to lease, so as to equate bids from Vendor(s) offering ALTERNATIVE IA dehumidification vice Vendor(s) offering ALTERNATIVE IB dehumidification. The Temporary Systems Design Engineer [TSDE] can determine the practicality of leasing the ALTERNATIVE IB SAIL RHC from the successful Bidder after obtaining the actual footprint(s) of the single Normal capacity or dual Medium capacity RHC unit(s) as well as the footprints of other adjoining machinery sharing the platform.
The duration for this initial STANDARD CLIN (S ) unit (ITEM F1: ACU) of one year happens to exactly match the planned duration. The extension OPTION(AL) CLIN (O ) is just in case the need for this Stand-Alone machine is greater than the planned duration.
The machinery and equipment unique to PNS Drydock No. 1 (DD#1) only in support of the deployment of a 400 ton chiller with a double chilled water loop (1ST CLG SEASON) are indicated in this initial STANDARD CLIN (S ).
The elective OPTION(AL) CLIN (E ) is for the gigantic size rigid Duct Fittings (DUCT [FTGS]–G) and for some sizes of Flexible Ducting (DUCT [±FLEX]–G/–X/–N). The proposal is for a FIXED FEE for the lease of ITEMS: J series that is not defined by a particular duration rate (i.e. $ / week), but, with the entire duration of the particular associated machinery (TCC–L/2N, DDU–N/M, ACU–L, & AHU–N as applicable) that the elective ITEMS are affixed to. The Government will make an election as to whether or not to lease such ITEMS prior to issuance of the Contract.
The initial STANDARD CLIN (S ) is for technical expertise with its associated labor and for data on machinery. The proposal is for a FIXED FEE for the lease of ITEMS: K series & L that is not defined by a particular duration rate (i.e. $ / week), but, with the entire duration of the drydock period. The E-STOP [D&E]–02 (ITEM K1) allows for up to two (–02) Contractor trips for connecting Emergency Stops on particular air-handling machinery ([D&E]) to permit partial installations. The CALL [≤6HR]–16 (ITEM K2) allows for up to sixteen (–16) Contractor trips (avg. one per month) of six hours or less onsite duration ([≤6HR]) as a response to Trouble Calls that are not the fault of the Contractor. The TRNG [≥4HR]–02 allows for up to two (–02) Contractor trips of four hours or more onsite duration ([≥4HR]) to perform Classroom and/or Field training other than routine Start-Ups. The TECH [≤8HR]–02 allows for up to two (–02) Contractor trips of eight hours or less onsite duration ([≤8HR]) to facilitate the installation and/or removal of the DD#1 double chilled water loop (1ST CLG SEASON) and its connection and/or disconnection to the 400 ton chiller. The EDS [A–F]–01 allows for the Vendor to provide a set of Equipment Data Sheets (EDS) of all deployed machinery ([A–F]) after Contract award. Further clarification of the above ITEMS are in Section C LEASE SPECIFICATION — TVENT MACHINERY & EQUIPMENT NOTES.
FOOTNOTE B (continuation):
CLIN (CONTRACT LINE ITEM NUMBER)
S STANDARD CLIN: This CLIN will most likely be a known lease for the duration indicated which would initially be limited to not exceed fifty-two weeks (52 wks) or one year (1 yr).
U UNFUNDED CLIN: This CLIN will is either: (a) a known extension for the duration indicated beyond and immediately following an initial known lease limited to one year or (b) a known lease for ITEMS that do not begin until a following Fiscal Year and unfunded until that applicable Fiscal Year begins (U16 = FY'16 & U17 = FY'17).
O OPTION(AL) CLIN: This CLIN is an unknown lease or unknown extension at present, indeterminate as to its necessity and, if necessary, also uncertain as to its precise duration if exercised. The reason for its unknown status is its dependency as to the ability of the Shipyard to achieve an aggressive programmed Blast and Paint (B&P) work schedule in light of manning limitations combined with the normal climatic changes in the season.
The first and majority group of these Optional Items are in the Spring (April or May) of 2016 and are associated with the need to extend the lease of the dehumidifiers and, if extended, the need to lease associated machinery and equipment to provide the necessary cooling. This listing would also vary dependent on the number of dehumidifiers to be extended. The second set of Optional Items are in the early winter (December) of 2016 and are associated with an extension of post-dock dehumidification.
E ELECTIVE CLIN: This CLIN is an elective lease / extension to be determined by the Government prior to issuance of the Contract and conveyed to the Vendor via whether or not those particular Items are listed as a CLIN. The CLIN ARRIVAL dates will automatically be adjusted to allow at least three (3) weeks for positive pressure (DUCT [FTGS]–G & DUCT [+FLEX]–G) and four (4) weeks for negative pressure (DUCT [+FLEX]–X & DUCT [+FLEX]–N) between contract issuance and their required delivery unless the Vendor indicates a sooner availability. This will allow the Contractor to obtain additional rigid ducts and/or flexible ducting assets in case the Vendor is temporarily short of a particular resource.
FOOTNOTE C:
The summation of the TOTAL Government ESTIMATE for the entire Contract to include all CLINs whether STANDARD (S), UNFUNDED (U), OPTIONAL (O), or ELECTIVE (E) is at the end of the TVENT MACHINERY & EQUIPMENT SCHEDULE.
However, some ITEMS are a Vendor's choice as to the machinery type being an ALTERNATIVE A (preferred) or an ALTERNATIVE B (currently acceptable). Whether ALTERNATIVE A or ALTERNATIVE B, the Government Estimate for that particular alternative is exactly the same. The alternative type is annotated in the (last) Government ESTIMATE column as IA or IB / IIA or IIB / IIIA or IIIB. The ALTERNATIVE B ITEMS are shown in a white font with a black background. Thus, the summation of the TOTAL Government ESTIMATE for the entire Contract to include all CLINs is the sum of all non-alternative ITEMS plus let's say ALTERNATIVE A ITEMS, and would not total both alternatives.
Hence, one can compute the TOTAL Government ESTIMATE by adding all line ITEMS with a white background.
TVENT DESIGN CRITERIA: [Non-IA & DD#1 @ PNSY]
[1a] [Non-IA] Single Non-Seasonal Normal capacity (–N) chiller and pump is required for the ship's TCHW system.
Only for an IA overhaul would a second similar, but seasonal chiller & pump be required for a nuclear complex.
[2a] [Non-IA @ PNSY] Three Temporary Desiccant Dehumidification (TDD) systems (FWD / SAIL / AFT) are required to support Blast and Paint (B&P) operations. The Vendor has a choice of either the combined dehumidifier (DDU [CMBD]–N) that integrates steam reactivation, post-heating, pre-cooling, and post-cooling (ALTERNATIVE IA: PREFERRED for now to be required in the future) or a dehumidification group consisting of separate machinery components (RHC [STM]–N/2M / HTGC [ELEC]–N / CLGC [PRE]–N / CLGC [POST]–N/M) (ALTERNATIVE IB: PERMITTED for now to be precluded in the future). The routine home station (PNSY) evolution requires dehumidification for close to an entire year or longer in which pre-cooling & post-cooling would be followed by post-heating and/or vice versa. The dehumidification machinery is supported by twenty inch nominal diameter rigid duct fittings (DUCT [FTGS]–G) and discharge (positive pressure) flexible ducting
(DUCT [+FLEX]–G).
[2b] [Post-DD#1 @ PNSY] Besides the dehumidification machinery to support the overhaul during the drydock evolution, a single Temporary Desiccant Dehumidification (TDD) system is only required post Drydock No. 1 [Post-DD#1] to support Blast and Paint (B&P) repairs after first removing the "Buoyancy Cans" for floating the ship of can cleats. This system does not require steam reactivation and is season specific (either just post-heat or just pre/post-cool as specified).
[3a] [Non-IA @ PNSY] Four (4) very powerful exhaust blowers (AHU [EXH]–N: ≥10K cfm @ 14" WG & ≥40 Hp) are required to support both exterior Blast and Paint (B&P) operations (Hull / Fwd & Aft MBTs / Mud Tank) and an interior healthy work environment (via Dirty Air Exhaust) in the Ship's Forward and Aft Compartments. Two units will be deployed near the Bow and likewise for the Stern. The Shipyard will designate each unit either solely for air exchange of the exterior to counterbalance the supply air from the dehumidification systems or solely for air exchange of the interior to counterbalance the supply air from temperature conditioning coils.
Each exhaust blower has a pair of fourteen inch nominal diameter suction inlets which wye to three each eight inch nominal diameter suction lines (Y = 14"Ø : 8"Ø × 3). The net effect is that each exhaust blower will provide six each exhaust lines of eight-inch nominal diameter (8"Ø) rated for a minimum of 1,600 cfm per exhaust branch run. The exhaust blowers are equipment supported by strong suction (negative pressure) semi-flexible ducting of fourteen inch (DUCT [−FLEX]–X) and eight inch (DUCT [−FLEX]–N) nominal diameters.
[4a] [PNSY] For industrial ventilation, two Temporary Temperature Conditioning (TTC) systems (FWD & AFT) support an interior healthy work environment (via Clean Air Supply) from all ambient (100% outside fresh) treated (cooled or heated, as necessary) air to the Ship's Forward and Aft (pressurized) Compartments. For each of the two TTC systems, the Vendor has a choice for Temperature Conditioning Coils (TCCs) of either a single Large (–L) capacity unit (TCC [H&C]–L) having four outlets (ALTERNATIVE IIA: PREFERRED for now to be required in the future) or a pair of Normal (–N) capacity units (TCC [H&C]–N) having two outlets each (ALTERNATIVE IIB: PERMITTED for now to be precluded in the future). Penetrations to the ship's interior are via the Submarine Hatch Ventilation Enclosures (SHVEs) on top of the hatches (WSH [FWD] / FEH [FWD] / AEH [AFT]) or the Hull Cut Ventilation Enclosures (HCVEs) surrounding the Hull Cuts (HC#1-1A [FWD] / HC#39A [FWD & AFT] / HC#49 [AFT]). There shall be four (4) supply air runs for each of the ship's interior Compartments for a total of eight (8) runs. The temperature conditioners are equipment supported by twenty inch nominal diameter rigid duct fittings (DUCT [FTGS]–G) and discharge (positive pressure) flexible ducting
(DUCT [+FLEX]–G).
[5a] [Non-IA @ PNSY] For comfort conditioning where treated air can be recycled (i.e. retreated with no or very little fresh air intake), [6a] [DD#1 @ PNSY] A single seasonal chilled water system is required.
[7] Emergency Stops (E-STOP [TCC & AHU]–02) will provide a certain measure of Fire Fighting security at the Watch Shack by permitting the instantaneous SHUTDOWN of air-handlers that either exhausts air from (AHU [EXH]–N) or supplies air to (TCC [H&C]–L/2N) the Forward and Aft Submarine Compartments.
[6b] [DD#2/3 @ PNSY] About half of the seasonal chilled water will run along the drydock floor on the submarine's Port side in support of the Temporary Blast and Paint (TB&P) systems' cooling coils at three locations (FWD / SAIL / AFT). The corresponding other half of the seasonal chilled water is to run along the drydock balcony on the submarine's Starboard side in support of the Temporary Ship's Ventilation (TSHIP) systems' cooling coils positioned on two balcony platforms with its accompanying chiller / pump on a third platform. Hence, this particular docking evolution is best resolved via the lease of two each duplicate capacity (200 ton) chillers.
A LEASE SPECIFICATION — MACHINERY & EQUIPMENT OVERVIEW
TABLE V1: TVENT REQUIREMENTS [ EQUIPMENT UNDERLINED / E-STOPS HIGHLIGHTED IN RED ]
ITEM ID QTY IDENTIFIER PERFORMANCE CAPACITY TRANSITION(S) REMARK / NOTE / COMMENT
A1 V01 1
EA
CHLR [3"CAM]–N
PRIMARY UNIT
compatible w/
PUMP [3"CAM]–N
COOL: ≥60 ton rating [nom] [ACTL] [≥57 ton @ 95°F amb]
HGB: V01: YES ▌V0#: YES
CRIT: V01: YES ▌V0#: YES
WTR: 3"Ø M&F CAM
PNSY OR NLON (V01):
FP SEASON START OCT 1
[reqt] HOT GAS BYPASS
RMK V1: CHILLED WATER SYSTEM
RMK V2: COOLANT-FREE
ID V01: CRITICAL
TCHW SYSTEM
HGB YES: ≥2 COMPRESSORS & ≥2 CKTS
A2 V37
EA
CHLR [4"CAM]–L
PRIMARY UNIT
compatible w/
PUMP [4"CAM]–L
COOL: ≥100 ton rating [nom] [ACTL] [≥97.5 ton @ 95ºF amb]
WTR: 4"Ø M&F CAM
CAM hose to
PUMP [4"CAM]-L
MANF–U/–L
RMK V1: CHILLED WATER SYSTEM
RMK V2: COOLANT-FREE
ITEM A2:
HGB NO: ≥2 COMPRESSORS & ≥2 CKTS
A3 V39
EA
CHLR [6"CAM]–X
STATEMENT #1
compatible w/
PUMP [6"CAM]–X
COOL: ≥200 ton rating [nom] [ACTL] [≥195 ton @ 95ºF amb] [PNSY] limit 380A continuous [NLON] no limit w/ MUSE eqpt
WTR: 6"Ø M&F CAM
CAM hose to
PUMP [6"CAM]-X
MANF–U/L/X ' /X
RMK V1: CHILLED WATER SYSTEM
RMK V2: COOLANT-FREE
ITEM A3:
HGB NO: ≥2 COMPRESSORS & ≥2 CKTS
A4 V41
EA
CHLR [8"FLG]–G
STATEMENT #1
compatible w/
PUMP [8"FLG]–G
COOL: ≥400 ton rating [nom] [ACTL] [≥385 ton @ 95ºF amb] [PNSY] limit 780A continuous w/ 800A Slow-Blow CB
WTR: 8"Ø FLANGE
FLG hose to
PUMP [ 8" ]–G &
MANF–G
RMK V1: CHILLED WATER SYSTEM
RMK V2: COOLANT-FREE
ITEM A4: L&H EXEMPTION
HGB NO: ≥4 COMPRESSORS & ≥4 CKTS
B1 V02 1
EA
PUMP [3"CAM]–N
SUPPORT UNIT
compatible w/
CHLR [3"CAM]–N
FLOW: ≥216 gpm @ 100' HD MOT: ≥7 Hp HS | ≥12 Hp LS
ELB: 3"Ø M & F CAM × 4 EA
HOSE: 3"Ø M & F CAM × 300'
WTR: 3"Ø M&F CAM
LFM: 3"Ø M&F CAM
IN-LINE W/ FLOW
(PREFERRED)
RMK V1: CHILLED WATER SYSTEM
RMK V2: COOLANT-FREE
ID V02: CRITICAL
TCHW SYSTEM
ADPTRS: 2½"M : 3"F + 2½"F : 3"M
B2 V38
EA
PUMP [4"CAM]–L
SUPPORT UNIT
compatible w/
CHLR [4"CAM]–L
FLOW: ≥360 gpm @ 100' HD MOT: ≥13 Hp HS | ≥23 Hp LS
ELB: 4"Ø M & F CAM × 4 EA
HOSE: 4"Ø M & F CAM × 300'
WTR: 4"Ø M&F CAM
CAM hose to
CHLR [ 4" ]–L &
MANF–U/–L
RMK V1: CHILLED WATER SYSTEM
RMK V2: COOLANT-FREE
ITEM B2:
ADPTRS: NONE
B3 V40
EA
PUMP [6"CAM]–X
STATEMENT #1
compatible w/
CHLR [6"CAM]–X
FLOW: ≥720 gpm @ 100' HD MOT: ≥20 Hp HS | ≥30 Hp LS
ELB: 6"Ø M & F CAM × 4 EA
HOSE: 6"Ø M & F CAM × 300'
WTR: 6"Ø M&F CAM
CAM hose to
CHLR [ 6" ]–X &
MANF–U/L/X ' /X
RMK V1: CHILLED WATER SYSTEM
RMK V2: COOLANT-FREE
ITEM B3:
ADPTRS: NONE
B4 V42
EA
PUMP [8"FLG]–G
STATEMENT #1
compatible w/
CHLR [8"FLG]–G
FLOW: ≥1440 gpm @ 100' HD MOT: ≥40 Hp HS | ≥60 Hp LS
ELB: 8"Ø FLG : FLG × 4 EA
HOSE: 6"Ø M & F CAM × 300'
WTR: 8"Ø FLANGE
FLG hose to
CHLR [ 8" ]–G &
MANF–G
RMK V1: CHILLED WATER SYSTEM
RMK V2: COOLANT-FREE
ITEM B4:
ADPTRS: NONE
STATEMENT {COMMENT}:
1. Although the Extra Large (–X) and Gigantic (–G) capacity chillers may include a built-in pump in which the pump may even be of the preferred Low Speed (LS) type, ITEM ID QTY IDENTIFIER PERFORMANCE CAPACITY TRANSITION(S) REMARK / NOTE / COMMENT
C {C'} C1
{ 1 }
EA
DESICCANT DRY
DDU [CMBD]–N
{ DDU [HTG]–N }
DDU [DSCC]–N
DRY: {230 lb/hr│ 662 gal/dy} [ ] (400 lb/hr│1152 gal/dy) [AGG] [300 lb/hr│ 864 gal/dy] [ U R ] ▌295 lb/hr│850 gal/dy▐
DESICCANT WHEEL:
Reactivation (reactvtn) via Electricity & Steam DH incl Elec Reactvtn
RMK V3: MOISTURE
REMOVAL
RATE
STATE MRR & BASIS
ALTNV IA DSCC WHEEL & SYSTEM
ALTNV IB DSCC WHEEL ONLY
C {C'}
V03 V04 V05
{V06}
{ 1 }
EA
DDU [CMBD]–N
{ DDU [HTG]–N }
ALTERNATIVE IA
OR C1 – C4
PROCESS AIR-HANDLER(S)
FAN: 2 EA at Discharge End MTR: ≥25Hp HS×2 EA w/ VFD FLOW: ≥10K cfm @ 12" ESP
AIR: ≤2 × 20"Ø
SPLY
≥2 × 20"Ø
RTN
(IN & OUT SAME SIDE)
MTR: TEFC
PREMIUM
ALTERNATIVE IA: DDU [CMBD]–N
RMK V4: TERMINATION COUPLING
ITEM C: ELECTRICAL POWER MGT
ITEM C: DISCHARGE YS (SH16 ¶1)
C1 V07 V08 V09
{V10}
{ 1 }
EA
DDU [DSCC]–N
ALTERNATIVE IB
(C1 THRU C4)
{STATEMENT #2}
PROCESS AIR-HANDLER(S)
FAN: ≥1 EA for Process Air MTR: ≥20Hp LS×1 EA w/ VFD FLOW: ≥10K cfm @ 7½" TSP
AIR: ≤2 × 20"Ø
SPLY
≥2 × 20"Ø
RTN
(ACCESS TO INLETS)
MTR: TEFC
PREMIUM
ALTERNATIVE IB: DDU [DSCC]–N
RMK V4: TERMINATION COUPLING
ITEM C#: RIGID DUCT (SH16 ¶1 & ¶2)
ITEM C#: SEPARATE UNITS (SH 17)
C C2
V11 V12 V13
EA
PR
RHC [STM]-N/2M
REACTVTN COIL
(VIA STEAM)
DETACHED UNIT:
REACTIVATION MODE
(STEAM: 100 PSIG = 338°F)
HEAT: ≥792K Btuh (232Kw)
AIR: DH
COMPATIBLE
STM: 1½" FNPT IN
[reqt] ¾" MNPT OUT
RMK V5: STEAM AS A UTILITY
ALTERNATIVE IB:
ITEM C2: STEAM REACTIVATION
(LABOR & MATÉRIEL)
C {C'} C3
V14 V15 V16
{V17}
{ 1 }
EA
HTGC [ELEC]–N
HEATING COIL
(POST-HEATER)
DETACHED UNIT:
POST-HEATING MODE
(ELECTRIC: 440 – 460 VAC)
C'/C3: ≥512K Btuh (150Kw) C: ≥792K Btuh (232Kw)
AIR: DH
COMPATIBLE
UTIL: ELECTRIC ONLY
CONT: THERMOSTAT
ALTERNATIVE IB:
RMK V6: FAN (BLOWER) CRITERIA
ITEM C#: RIGID DUCT (SH16 ¶1 & ¶2)
ITEM C#: SEPARATE UNITS (SH 17)
C C4'
V18 V20 V22
{V24} {V26}
{ 2 }
EA
CLGC [PRE]–N
COOLING COIL
(PRE-COOLER)
DETACHED UNIT:
PRE-COOLING MODE
COOL: ≥50 ton rating [nom] [ACTL] [≥42.8 ton @ ∆T=10°F]
COMPATIBLE
WTR: 3"Ø M&F CAM
UTIL: CHILLED
WATER
CONT: FLOWRATE
RMK V2: COOLANT-FREE
RMK V6: FAN (BLOWER) CRITERIA
ITEM C#: RIGID DUCT (SH16 ¶1 & ¶2)
ITEM C#: SEPARATE UNITS (SH 17)
C C4"
V19 V21 V23
{V25} {V27}
{ 2 }
EA
CLGC[POST]-N/M
COOLING COIL
(POST-COOLER)
DETACHED UNIT:
POST-COOLING MODE
COOL: ≥25 ton rating [nom] [ACTL] [≥24.6 ton @ ∆T=10°F]
COMPATIBLE
WTR: 3"Ø M&F CAM
UTIL: CHILLED
WATER
CONT: THERMOSTAT
RMK V2: COOLANT-FREE
RMK V6: FAN (BLOWER) CRITERIA
ITEM C#: RIGID DUCT (SH16 ¶1 & ¶2)
ITEM C#: SEPARATE UNITS (SH 17)
D1 V28 V29
EA
TCC [H&C]–L
WIRED
TO
E-STOP
ALTERNATIVE
IIA
OR D2
LOAD: {≥100 TN}&[≥800KBTUH]
MTR: ≥50HP LS×1 EA W/ VFD
FAN: ≥20K CFM @ 5–9" TSP
HOSE: 4"Ø M & F CAM × 100'
AIR: ≥4 × 20"Ø
SPLY
≥4 × 20"Ø
RTN
WTR: 4"Ø M&F CAM
RMK V2: COOLANT-FREE
RMK V7: FAN (BLOWER) CRITERIA
TCC–L: {COOLING} & [HEATING]
ALTNVIIA: PREFERRED FOR PNS
D2 V30a V30b V31a V31b
PR
TCC [H&C]–2N
WIRED TO E-STOP
ALTERNATIVE
IIB
STATEMENT #4
LOAD: {≥50 TN} & [≥400K BTUH]
MTR: ≥20HP LS×1 EA
W/ VFD
FAN: ≥10K CFM @ 5–9" TSP
HOSE: 3"Ø M & F CAM × 200'
AIR: ≥2 × 20"Ø
SPLY
≥2 × 20"Ø
RTN
WTR: 3"Ø M&F CAM
IIB: V30c & V31c
RMK V2: COOLANT-FREE
RMK V6: FAN (BLOWER) CRITERIA
TCC-2N: {COOLING} & [HEATING]
ALTNVIIB: PERMITTED FOR NOW
STATEMENT {COMMENT}:
2. {ITEM} / {ID} / { QTY } / { IDENTIFIER } are highlighted to demonstrate necessary machinery or equipment for a future or potential redeployment and should not be counted towards the total minimum inventory required by the Vendor. For the │C│{C'}│C1│ as an example, in the QTY column 3 dehumidifiers are indicated for the initial deployment with { 1 } dehumidifier to be redeployed Post-Dock after the RETURN of the original deployment of three dehumidifiers (although, at the election of the Vendor, one DH may remain on-site vice incurring the cost of round-trip transport). Thus, the total minimum inventory required by the Vendor is for only three dehumidifiers.
3. C: The functions described for each ALTNV IB machine unit │C2│C3│C4'│C4"│ under the column headings of:
C#: │PERFORMANCE CAPACITY│TRANSITION(S)│REMARK / NOTE / COMMENT│ shall also be applicable to the single ALTNV IA combined dehumidifier ITEM C: DDU [CMBD]–N unless annotated otherwise.
4. If Vendor elects both ALTNV IIB & ALTNV IIIB, additional large manifolds (V30c & V31c) are needed each season.
ITEM ID QTY IDENTIFIER PERFORMANCE CAPACITY TRANSITION(S) REMARK / NOTE / COMMENT
E1 V32 V33 V34 V35
EA
AHU [EXH]–N
WIRED
TO
E-STOP
STAND-ALONE
MTR: ≥40HP LS×1 EA W/ VFD
FAN: ≥10K CFM @ 14" TSP
MAX: ≥12K CFM @ 10" TSP
MIN: ≥08K CFM @ 17" TSP
AIR: =2 × 14"Ø RTN
AFFIXED TO
AHU
WYE: 14"Ø : 8"Ø × 3
2 DETACHABLE
AHU–N: VENDOR ID EQUIPMENT
(SUCTION WYES)
TS ¶ F4: SPECIFICATION
VARIANCE
REVIEWED BY ENGINEER
F1 V36
EA
ACU [H&C]–L
STATEMENT #5
STAND-ALONE
LOAD: {≥60
TN} & [≥250K
BTUH]
CONT: THERMOSTAT ON RETURN
[PNSY] limit 380A continuous [NLON] no limit w/ MUSE eqpt
AIR: ≥3 × 20"Ø
SPLY
≥4 × 20"Ø
RTN
[reqt] ALL RA OR OA
ACU–L: {COOLING} & [HEATING]
COMFORT
(∆T≥15°F WB)
G V43
THRU
{V50}
{ 3 }
PR
MANF [4"╬ 6"]–U
ALTERNATIVE IIIA
STATEMENT #6
OR G1 – G3
TYPE: Cross; 6" NOM; w/ dual 6" & dual 4" branches VALV: 4" each branch (qty 2)
HOSE: 3"Ø × 100' + 4"Ø × 100'
END CONNECTORS:
6"Ø F CAM W/ PLUG
6"Ø M CAM W/ CAP
4"Ø F CAM W/
PLUGS
MANF-U: UNIVERSAL MANIFOLD
RMK V9: HYDROSTATIC TESTING
ELBOW: 3"×90°×2 EA + 4"×90°×2 EA
6"×90°×2 EA + 6"×45°×2 EA
G1
V30c V31c V51
THRU
{V55}
+2 { 2 }
PR
MANF [4":3"×2]–L
ALTERNATIVE IIIB
STATEMENT #6
SUPPLY & RETURN
TYPE: Tee; 4" NOM; w/ single 4" to dual 3" branches VALV: 3" each branch (qty 2)
HOSE: 3"Ø × 200' + 4"Ø × 100'
FTG: 3" & 4"Ø CAM
F CAM INLETS
M CAM OUTLETS
IIB: V30c & V31c
MANF-L: LARGE MANIFOLD
RMK V9: HYDROSTATIC TESTING
ELBOW: 3" M & F CAM × 90° × 4 EA +
4" M & F CAM × 90° × 2 EA
G2 V56
PR
MANF [6":4"×2]–X'
ALTERNATIVE IIIB
STATEMENT #6
SUPPLY & RETURN
TYPE: Tee; 6" NOM; w/ single 6" to dual 4" branches VALV: 4" each branch (qty 2)
HOSE: 4"Ø × 200' + 6"Ø × 100'
FTG: 4" & 6"Ø CAM
F CAM INLETS
M CAM OUTLETS
MANF-X': EX LGE PRIME MANIFOLD
RMK V9: HYDROSTATIC TESTING
ELBOW: 4" M & F CAM × 90° × 4 EA +
6" M & F CAM × 90° × 2 EA
G3 V57
THRU
{V62}
{ 3 }
PR
MANF [4":6"×2]–X
ALTERNATIVE IIIB
STATEMENT #6
SUPPLY & RETURN
TYPE: Tee; 6" NOM; w/ single {STMT} 4" to dual 6" branches VALV: 4" on take-off (qty 1)
HOSE: 4"Ø × 100' + 6"Ø × 200'
FTG: 4" & 6"Ø CAM
F CAM INLETS
M CAM OUTLETS
MANF-X: EXTRA LARGE MANIFOLD
ELBOW: 4" M & F CAM × 90° × 2 EA +
6" M & F CAM × 90° × 4 EA
G4 V63
PR
SP[6"CAM:FLG]-X
STATEMENT #6
STATEMENT #7
SUPPLY & RETURN
TYPE: Elbow; 6" NOM; long sweep; stand mounted VALV: 6" just under FLG (qty 1)
HOSE: 6"Ø × 200'
FTG: 6"Ø CAM & FLG
CAM @ BOTTOM
FLG @ TOP
SP–X: EXTRA LARGE STANDPIPE
ELBOW: 6" M & F CAM × 90° × 2 EA +
6" FLG : FLG × 90° × 2 EA
G5 V64
PR
MANF [8":6"×2]–G
STATEMENT #6
STATEMENT #7
SUPPLY & RETURN
TYPE: Tee; 8" NOM; w/ single 8" to dual 6" branches VALV: 6" each branch (qty 2)
HOSE: 6"Ø × 200'
FTG: 8"Ø FLG
6"Ø FLG (LL)
6"Ø CAM (UL)
(3
UNIQUE END FTGS)
MANF-G: GIGANTIC MANIFOLD
RMK V9: HYDROSTATIC TESTING
ELBOW: 6" FLG : FLG × 90° × 2 EA +
8" FLG : FLG × 90° × 2 EA
STATEMENT {COMMENT}:
5. MINIMUM REQT – HEAT: [≥250K BTUH] ▌MTR: ≥20 HP LS × 1 EA FOR PA ▌FLOW: ≥20K CFM @ 2¼" TSP
PREFER REQT – HEAT: [≥350K BTUH] ▌MTR: ≥40 HP LS × 1 EA & VFD ▌FLOW: ≥20K CFM @ 8¼" TSP
6. For the Manifolds and Standpipe, the quantity of valves indicated under the PERFORMANCE CAPACITY column is for each individual manifold (double for the pair). But, the quantity of HOSE listed under the PERFORMANCE CAPACITY column and ELBOW(S) under the REMARK / NOTE / COMMENT column is for each pair of Manifolds / Standpipe. Of course, the ELBOWS for the Universal Manifolds have Male and Female cam-lock type end connection fittings.
7. All flange and bolt dimensions shall be ASME / ANSI B16.5, preferably, Class 150# (eight bolt pattern) and not Class 300# or greater (twelve bolt pattern). Vendor is to provide a sufficient quantity of correctly dimensioned hardware (bolts, nuts, washers, and gaskets) to make-up all of the potential flange to flange connection points.
Gaskets shall be new (virgin) and of the proper size, durometer, and quality for an environment exposed to ambient conditions. Two (2) each washers are normally required for each of the eight bolt holes. For Class 150# flanges, the eight each bolts are three-quarter inch diameter (¾"Ø × 8 EA). Hardware (bolts, nuts, and washers) shall be almost new or better and of a superior metallurgical quality as to not show any signs of rust after its first season of use. If agreed to by the Project, this hardware can remain in the possession of the Vendor's technician as long as it is all made available to the Project on the very first workday that the systems installation is to occur.
ITEM ID QTY IDENTIFIER PERFORMANCE CAPACITY TRANSITION(S) REMARK / NOTE / COMMENT
H1 V65
LT
HOSE [4"CAM]–L
ALTERNATIVE IIIB
1ST
CLG SEASON
TYPE: CHILLED WATER HOSE
ABBR: CHWH–4"–CAM (M&F)
QTY: 25'L × 32 EA
HOSE: 4"Ø M & F CAM × 800'
CHWH QUALITIES:
Collapsible Acceptable Insulated Exterior Camlocks on Ends
EQPT H: VENDOR ID EQUIPMENT
H2 V66
LT
HOSE [6"CAM]–X
ALTERNATIVE IIIA
1ST
CLG SEASON
TYPE: CHILLED WATER HOSE
ABBR: CHWH–6"–CAM (M&F)
QTY: 25'L × 32 EA
HOSE: 6"Ø M & F CAM × 800'
CHWH QUALITIES:
Collapsible Acceptable Insulated Exterior Camlocks on Ends
EQPT H: VENDOR ID EQUIPMENT
H3 V67
GP
HOSE [6"FLG]–X'
STATEMENT #7
{ON PRIOR SHEET}
TYPE: CARGODISCHARGEHOSE
ABBR: CDH–6"–FLG (150#)
QTY: 15'L × 4 EA + 25'L × 2 EA
HOSE: 6"Ø FLG × 110' (6 PC)
CDH QUALITIES:
Non-Collapsible Only Strong Exterior Cover Flanges on Ends
RMK V9: HYDROSTATIC TESTING
EQPT H: VENDOR ID EQUIPMENT
PNSY: TO CONNECT MANF–G
(DD#1) TO SP–X (LL)
H4 V68
GP
HOSE [8"FLG]–G
STATEMENT #7
{ON PRIOR SHEET}
TYPE: CARGODISCHARGEHOSE
ABBR: CDH–8"–FLG (150#)
QTY: 10'L × 3 EA + 20'L × 2 EA
HOSE: 8"Ø FLG × 70' (5 PC)
CDH QUALITIES:
Non-Collapsible Only Strong Exterior Cover Flanges on Ends
RMK V9: HYDROSTATIC TESTING
EQPT H: VENDOR ID EQUIPMENT
PNSY: TO CONNECT CHLR–G
(DD#1) TO MANF-G & PUMP-G
J1 V69
GP
DUCT [FTGS]–G
#1: TCC–L/2N × 2
#2: DDU–N × 3
TYPE: ELBOWS ▌COUPLINGS
SIZE: 20"Ø×90º ▌20"Ø×20"L
FTGS: 14 ELBOWS + 42 CPLGS
1L+3CPLG/RUN×14 RUNS
FITTING QUALITIES:
Heavy-Duty Aluminum Dimensions Correct Quantities Correct
EQPT J: VENDOR ID EQUIPMENT
#1-2×4=8: HC#1A, HC#39A, HC#49,
+ SHVES: WSH ± FEH / AEH
#2-3×2=6: MBTS (FWD & AFT) & SAIL
J2 V70
GP
DUCT [+FLEX]–G
STATEMENT #8
#1: TCC–L/2N × 2
#2: DDU–N × 3
TYPE: FLEXAUST FSP-5 W/ CUFF OR
ABC ENVIRODUCT 1899HD
CLMP: 20"Ø × 56 × 2 = 112 EA
DUCT: 4/RUN × 14 RUNS=56 EA
DUCTING QUALITIES:
Heavy-Duty 20"Ø×25'L PVC & Steel Wire Helix
UL94V-0 (–20—+160°F)
EQPT J: VENDOR ID EQUIPMENT
#1-2×4=8: HC#1A, HC#39A, HC#49,
+ SHVES: WSH ± FEH / AEH
#2-3×2=6: MBTS (FWD & AFT) & SAIL
J3 V71
GP
DUCT [−FLEX]–X
STATEMENT #9
#1: AHU-N×2 SHIP
#2: AHU-N×2 MBTs
TYPE: FLEXAUST FLEXADUX PV R–3
w/ cuff-like ends
CLMP: CW×14"Ø× 32 × 2=64 EA
DUCT: 4/RUN × 08 RUNS=32 EA
DUCTING QUALITIES:
PVC Matériel 14"Ø×24'L Blue Wall & Wire Helix
UL94V-0 (+20—+160°F)
EQPT J: VENDOR ID EQUIPMENT
#1-2×6=12: HC#1A [FWD] / HC#15 [FWD]
+ HC#49 [AFT]
#2-2×6=12: MBTS [FWD] & MBTS [AFT]
J4 V72
GP
DUCT [−FLEX]–N
STATEMENT #10
#1: AHU-N×2 SHIP
#2: AHU-N×2 MBTs
TYPE: FLEXAUST FLEX-TUBE TR/FR
CPLG: 08"Ø × 24 × 2 = 48 EA
CLMP: CCW×8"Ø×72×2=144 EA
DUCT: 3/RUN × 24 RUNS=72 EA
DUCTING QUALITIES:
Smooth Inner 8"Ø×24'L Black Wall & Blue Helix
UL94V-0 (–20—+275°F)
EQPT J: VENDOR ID EQUIPMENT
#1-2×6=12: HC#1A [FWD] / HC#15 [FWD]
+ HC#49 [AFT]
#2-2×6=12: MBTS [FWD] & MBTS [AFT]
STATEMENT {COMMENT}:
8. Since this product is available from both recommended manufacturers with cuffs, any newly ordered product must be manufactured with cuffs. Existing product (manufactured on or prior to May 2015) may not include cuffs.
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .