SECTION 00100, ATTACHMENT A

PRE-PROPOSAL INQUIRY FORM

SOLICITATION NUMBER

N33191-19-T-0825

OFFEROR

INQUIRY NO.

GOVERNMENT

INQUIRY NO.

Bldg.. 273 PHARMACY UPGRADE RQMT, NAS I, SIGONELLA, ITALY

DATE OF INQUIRY:

INQUIRY: (Please type or print clearly) (Include RFP Section, page number, and paragraph if applicable) QUESTION N.1: “Repair the floor surfaces after vinyl flooring removal (paragraph 3 above). Prepare and apply new industrial type floor surfacing to be used for storage spaces”(Page n.2 Paragraph 1,3(I).5.)

Technical characteristics of the industrial floor

QUESTION N.2:”Remove and dispose of existing floating floor in room 1A-55. Fill the void in the floor using plastic domes filled with light concrete and welded wire fabric, for floor continuity with room 1A-54. Provide new PVC flooring (approx. 16m2) to match type, color and quality of existing floor in room 1A-54”(Page n.3, Paragraph 1,3(II)4.)

What kind of fabric in welded wire

QUESTION N.3 “Modify the existing fire suppression sprinkler system and HVAC system in accordance with the new storage space layout (in accordance with all current NFPA and Italian codes and regulations). Modify/relocate grids, hatches and other equipment parts from suspended ceiling where conflicting with new walls. Ensure all utility lines penetrations between different areas are properly sealed, and install fire dampers if air ductworks run across the wall, for fire protection rating continuity”(Page n.2 Paragraph 1,3(I)9) Fire protection and configuration drawings are required?

QUESTION N.4 “Reconfigure existing HVAC system to have negative pressure in the new three spaces, all three externally exhausted. New hood in room 1A-55 shall be externally exhausted through a HEPA filter. Room 1A-55 must be at a negative pressure with regard to the area from which it is entered of 0.01 - 0.03 inches of water. Room 1A-55 needs to have 30 or more air changes per hour (ACPH). Room 1A55 floors and walls need to be of uniform color, and completely without texture. Variegated surfaces can conceal stains and spills; even slight texture increases the difficulty of deactivation, cleaning and disinfection. Room 1A-55 flooring to be “coved” up the walls of the C-SEC to simplify cleaning. The ante room, 1A-54b MUST be at a 0.02 or greater inches of water positive pressure to the area from which it is entered. All rooms must be ISO Class 7 air. 13” (Page n. 3 Paragraph 1,3(II)12) Drawing and system configuration required HVAC?

QUESTION N.5 “Reconfigure the existing electrical lighting system to serve the new 3 spaces, each with independent dedicated light switches in the room. Reconfigure electrical system and install new 110/220V electrical outlets, fed by the closest electrical panel, in the new 3 spaces (the Contracting Officer will indicate the exact locations of outlets)(Page n.3, Paragraph 1,3(II)11) Where the outlets for the electrical sockets will be placed?

ANSWER PROVIDED: (For Government Use Only)

N.1: Please follow UFC 4-510-01 Design: Military Medical Facilities, Appendix B-4 Architectural notes, Appendix B-3.1.1 and Table B-1 Architectural and Engineering Design Criteria to choose the type of floor specific for Pharmacy space;

N.2: Shall be determine by DOR;

N.3: The Design and the Certification for the modified HVAC system and fire protection system are required;

N.4: The Design and the Certification for the modified HVAC system and fire protection system are required;

N.5: Exactly location of the electrical sockets will be determined during the design phase.

GOVERNMENT RESPONDER’S SIGNATURE: ______________________ DATE: ___________