19R0404_MWD_Amend_0003.pdf
PDF 166 KB Posted
- Solicitation number
- N3319119R0404
About this file
19R0404_MWD_Amend_0003.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 19R0404_MWD_Amend_0004.pdf | ||
| Perf_Bond_Sample.docx | DOCX document | |
| N3319119R0404_19R0404_Plovdiv_MWD__-_Pre_sol.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ACQR5613515
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
N3319119R0404 D-B Construct Military Working Dog (MWD) Facility, Plovdiv, Bulgaria
1. CONTRACT ID CODE PAGE OF PAGES
J 1 5
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY 02-Apr-2019
16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X N3319119R0404
X 9B. DATED (SEE ITEM 11)
13-Mar-2019
10B. DATED (SEE ITEM 13)
9A. AMENDMENT OF SOLICITATION NO.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN
REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
02-Apr-2019
CODE
NAVFAC EUROPE AFRICA SOUTHWEST ASIA
VIALE PORTO CAPODICHINO
NAPOLI 80144
N33191 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODECODE
EMAIL:TEL:
N3319119R0404
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
SECTION SF 30 - BLOCK 14 CONTINUATION PAGE
The following have been added by full text:
1. The purpose of this modification is to responsd to Pre-Proposal Inquiries.
PRE-PROPOSAL INQUIRY 007
PTS states in 3.6 Requirements for Obedience Course 3.6.2 Requirements Fence must have no ground clearance. No ground clearance means that the fencing extends the whole way to the ground so that dogs cannot crawl or easily dig under it.
QUESTION: Is it possible the clearance to be avoided by reinforcement concrete structure 30cm in the soil and the fence dived in it.
PRE-PROPOSAL INQUIRY RESPONSE 007
Yes, it is required to provide a reinforced concrete structure minimum 30 cm deep into the ground to avoid dogs digging under the fences.
PRE-PROPOSAL INQUIRY 008
The PTS states in 3.4.11 Sewer System Minimum size for sewer piping outside of the footprint of the new buildings shall be 250 mm (internal diameter) even if Bulgarian regulations allow for smaller diameter piping. Concrete manholes shall be placed at every change of direction, at each connection between piping outside the footprint of the new buildings and at every 40 linear meters of straight sewer line. Minimum slope to be 0.5%.
QUESTION: Because lack of distance to the old buildings south of the site and problematic compacting is it possible the material of the pipes to be fiberglass (GRP). Is it possible the shaft of the manholes to be in modules of fiberglass too?
PRE-PROPOSAL INQUIRY RESPONSE 008
Yes, it is possible to use fiberglass or GRP (Glass Reinforced Plastic) piping, which must comply with all size requirements described in the contract specifications and the corresponding certificate for proper use in city gravity sewage systems must be provided.
PRE-PROPOSAL INQUIRY 009
3.4.3 Electrical Service Connection. “The Contractor must develop the power supply contract and coordinate all work to connect to the existing substation.”
QUESTION: Please inform us on the current power feed capacity of the existing substation. Based on our site visit our understanding is that the additional electrical installation /street lights included/ will need additional power supply to be added by the Electrical Distribution Company.
PRE-PROPOSAL INQUIRY RESPONSE 009
The street lamps mentioned are 50 Watts each and solar powered. These 8 street lights would consume a maximum of 400 Watts which is the same power as would be consumed by a standard to small refrigerator. For estimating purposes, the contractor shall follow the requirements of paragraph 3.4.3 and connect to the substation shown in first picture in page 24. The contract includes the necessary works inside the substation in order to connect the new electrical feeder to the existing transformer, but not providing a new high voltage transformer.
PRE-PROPOSAL INQUIRY 010
3.4.5 Backup Power. “The Contractor must develop the power supply contract and coordinate all work to connect to the existing substation./…/ Generator set (generator and diesel engine) and the automatic transfer switch shall be a complete package provided by the same manufacturer, designed for exterior/outdoor use.”
QUESTION: According to the Bulgarian legislation, the diesel engine shall be installed under the ground based to the written recommendations of the Fire Agency regulations. Is it acceptable to install it on the ground and provide a special fire protection?
PRE-PROPOSAL INQUIRY RESPONSE 011
The generator shall be as described in the contract specifications. There is no need to provide an underground generator and all work shall be done in compliance with Bulgarian regulations.
PRE-PROPOSAL INQUIRY 011
3.7.2 Requirements. The PTS requires “Grass covered and free of trees, rocks, holes, etc.”
QUESTION: Please specify if the contractor shall provide an irrigation system for grass maintenance.
PRE-PROPOSAL INQUIRY RESPONSE 011
An irrigation system is not part of the contract. The contract includes seeding the areas specified to be provided with grass and to irrigate it and to maintain it as long as necessary until it can be mowed at least 3 times and providing a full coverage of at least 99% of the area with the soil not visible, as it would be completely covered with the new grass.
PRE-PROPOSAL INQUIRY 012
PTS states in 3.3 General Design / Construction Requirements for Structures “, Exterior Enclosure: Use traditional solid natural stone bricks or other concrete masonry units (CMU) authorized by Bulgarian construction standards.
Provide masonry walls, with rigid thermal insulation, mesh, plaster, and paint.
QUESTION: Is it possible the rigid thermal insulation to be integrated into the bricks or to be replaced with the masonry blocks fulfilling the requirements for heat protection and 3.4.15 Thermal Facade.
PRE-PROPOSAL INQUIRY RESPONSE 012
Thermal insulation is part of the contract. Any other technical solution or alternatives that provides the equivalent thermal insulation of 8 cm of wool rock, which complies with Bulgarian regulations and fulfills all technical requirements of the contract specifications is technically acceptable as part of this design-build contract.
PRE-PROPOSAL INQUIRY 013
PTS states in 3.6 Requirements for Obedience Course 3.6.2 Requirements. Enclose with a 2.5m tall stainless-steel chain link fence, 316 grade, 4mm diameter. Do not use galvanized or PVC coated chain link fence.
QUESTION: Is it possible the fence to be made by welded stainless panes and adequate steel structure and fastening.
PRE-PROPOSAL INQUIRY RESPONSE 013
Any technical alternatives that provides the same or better technical features to that provided in the contract specifications may be technically acceptable. Welded stainless steel grid is acceptable. Welded steel solid panes is not acceptable as it would not allow wind and would create an unnecessary barrier.
PRE-PROPOSAL INQUIRY 014
3.10 Requirements for CCTV Security System and Installation. The PTS states: “All equipment and installation to constitute a fully operational CCTV surveillance system, including but not limited to: o DVR /o CCTV cameras (indoor/outdoor, day/night (IR) capability)”
QUESTION: Based on our site visit we need to provide cameras for security surveillance and for dog behavior supervision. We need to provide cameras with a resolution higher than a standard security camera. Please confirm.
PRE-PROPOSAL INQUIRY RESPONSE 014
The contractor shall provide high resolution color cameras as described in the contract specifications.
PRE-PROPOSAL INQUIRY 015
SF 1442, Page 1, Item 12:
This block states that both a Performance and Payment bond will be required. The work “bond” is mentioned three times in the SF 1442 and none of these times is there any elaboration on the requirement except that the bond(s) are due within 30 days of contract award.
QUESTION: a). is there really a requirement for Performance and a Payment bond, b.) if such a requirement does exist, what are the details applicable to this requirement? Letter of Guaranty? Letter of Assurance? Terms and Conditions?
PRE-PROPOSAL INQUIRY RESPONSE 015
Yes, bonds are required for this project
Subject solicitation is amended to add the following language:
“Performance Guarantee Requirements: The offeror shall provide a performance guarantee as referenced in NFAS 5252.228-9306 for the duration of the contract. See sample performance guarantee letter provided as an attachment to this amendment.”
NFAS Clause 5252.228-9306 is provided in its entirety.
SECTION 00700 - CONTRACT CLAUSES
The following have been added by full text:
5252.228-9306 PERFORMANCE GUARANTEE (JUN 1994)
Submittal Time. The bidder whose bid is accepted shall furnish a performance guarantee within ten (10) days after the contract forms are presented to him for signature. If he fails to give such guarantee within ten (10) days, his contract may be terminated for default. In such event he shall be liable for any cost of procuring the work which exceeds the amount of his bid and the bid guarantee shall be available toward offsetting such difference.
Form of Performance Guarantee. The bidder whose bid is accepted shall furnish a performance guarantee in the form of a cashier's check to the order of the (Office Designated for Contract Administration) in the amount of eight percent (8%) of the contract price, which will be cashed and deposited in the account of the U. S. Government. The performance guarantee shall take effect upon the date of signature of the contract and remain valid and irrevocable until one (1) year after the work has been finally inspected and accepted by the Government. However, upon acceptance of all work by the Government, the Contractor may, with the approval of the Contracting Officer, replace this guarantee with a reduced guarantee in the amount of four percent (4%) of the then existing contract price, with modifications, if any. Such replacement guarantee will then remain in effect for one year after the final acceptance of the work by the Government.
Optional Performance Bond. In lieu of a performance guarantee in the above stated form of a cashier's check, the Contractor may submit a performance bond in which the Contractor and the surety obligate themselves in the amount of ten percent (10%) of the contract price, that the Contractor shall undertake the performance of the contract and that said performance bond ensures the fulfillment of all agreements contained in the contract.
a. The bond shall be from a registered bank, bonding firm, or registered insurance firm approved by the Contracting Officer.
b. The bond shall be of the U. S. standard type or of another approved type and shall include the following concepts: (1) name of Surety and name of agent signing in behalf of Surety; (2) name of Principal; (3) a statement that the Principal and Surety are firmly bound on the United States of America in the penal sum of the bond; (4) Contract number; (5) Penal sum of bond and the statement "This bond will be in force until the Contracting Officer of the above-cited Contract authorized cancellation of the bond"; and (6) date of issuance of bond and signature of Surety's agent.
(End of Summary of Changes)