USNS JOSHUA HUMPHREYS

(T-AO 188)

ELECTRICAL

JULY 2016

SERVICE
CATEGORY "A"
MSFSC/HR/WP

GENERATOR MAINTENANCE (CASREP 16-017)

1.0 ABSTRACT:

1.1 Perform bearing checks on the PORT PTO Generator. Replace PTO bearings and seals as necessary.

2.0 REFERENCE/ENCLOSURES:

2.1 References (On board during bidder survey)

2.1.1 NAVSEA Tech Manual T9311-AX-MMC-010, "Generators Sets"

2.2 Enclosure

2.2.1 None

3.0 ITEM LOCATION/DESCRIPTION:

3.1 Location/Quantity

3.1.1 Lower Level, Engine Room (4-60-0)/ One (1) PTO Generator

3.2 Description/Quantity

3.2.1 PTO Generator Sets.

Unit

Qty PTO (Generator) (1)

Manufacturer
ACEO
Model
PA125G70/8P
Type
Synchronous
Excitation
Brushless
Rated Power
2500 KW

450 V, 60 Hertz, 3phase

KVA
3.125 kVA
Speed (max)
1200 rpm
Power Factor
0.8 lagging
Insulation
Class ‘F’

3.3 Contractor Furnished Material:

3.3.1 NONE

4.0 GOVERNMENT FURNISHED MATERIAL:

4.1 Material: None

5.0 NOTES:

5.1 USNS JOSHUA HUMPHREYS

POP: July 9-10

LOCATION: PHILLIPINES

POC Wesley Payne 757-443-0892 / 757-449-6924

Wesley.Payne2@navy.mil

6.0 QUAILITY ASSURANCE REQUIREMENTS:

6.1 None Additional

7.0 STATEMENT OF WORK REQUIRED:

7.1 USNS JOSHUA HUMPHREYS

7.1.1 Provide the services of an OEM Renk Bearing representative to perform the following:

7.1.2 Open, clean, and inspect the PTO drive end (DE) and non-drive (NDE) end bearing assemblies, condition and clearances. (2 total bearing assemblies) provide and replace sealant.

7.2 After inspection by the Manufacturer’s Technical Representative and the Chief Engineer. Submit an “As Found” Condition Report to the MSCREP

7.3 Recommended Tech Rep. Sources:

RENK Corp 304 Tucapau Rd Duncan, SC 29334

Phone (864) 433-0069

7.4 All test and inspections to be witnessed by Chief Engineer or MSC Representative.

8 GENERAL REQUIREMENTS:

8.1 None additional.

305-2