0002.docx
DOCX document 26 KB Posted
- Attached to
- USNS PATUXENT (T-AO 201) MID-TERM AVAILABILITY
- Solicitation number
- N32205-16-R-4003
About this file
RFC Response 0002
View the file
Other files
| File | Type | Posted |
|---|---|---|
| J A_Patuxent_P00003_Aug_2016_Redacted.pdf | ||
| J-3_CAT_B_Amendment_0004.xlsx | XLSX spreadsheet | |
| Amendment_0004.pdf | ||
| Amendment_0003.pdf | ||
| J-3_CAT_B_Amendment_0003.xlsx | XLSX spreadsheet | |
| Amendment_0002.pdf | ||
| 0005.docx | DOCX document | |
| 0006.docx | DOCX document | |
| 0004.docx | DOCX document | |
| Amd_0001.pdf | ||
| 0003.doc | DOC document | |
| 0001.docx | DOCX document | |
| J-8_Request_for_Spec_Clarification.doc | DOC document | |
| J-2_CAT_A.xlsx | XLSX spreadsheet | |
| Solicitation_N32205-16-R-4003.doc | DOC document | |
| J-7_MSC_Ship_Repair_Facility_Survey.doc | DOC document | |
| J-9_Disclosure_of_Lobbying_Activities_SF-LLL.doc | DOC document | |
| J-14_NON_DISCLOSRE_AGREEMENT_FOR_GOVN'T_TECHNICAL_DATA_(V1_1_2-27-14).docx | DOCX document | |
| J-6_CDRLs.PDF | ||
| J-4_Scheduled_Government_Furnished_Property.xls | XLS spreadsheet | |
| J-3_CAT_B.xlsx | XLSX spreadsheet | |
| J-12_Past_Performance_Data.docx | DOCX document | |
| J-10_Interport_Differential.doc | DOC document | |
| J-13__PAST_PERFORMANCE_QUESTIONNAIRE.docx | DOCX document | |
| PATUXENT_Avail_JA_Redacted.pdf |
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N32205-16-R-4003
USNS PATUXENT (T-AO 201)
RFC 0002
REQUEST FOR SPECIFICATION CLARIFICATION
NAME OF CONTRACTOR: ___
SPECIFICATION ITEM NO.: __302___________________
PARAGRAPH / SECTION NO:__3.3.1, 7.1.23__________________
TITLE: _Air Circuit Breaker Annual Maintenance______________
QUESTION:
In item 0302 paragraph 3.3.1 calls for three breakers to be provided (1 at 800 amps, 1 at 1600 amps and 1 at 2000 amps), but in paragraph 7.1.23 the item calls for four breakers to be provided (the three listed in para 3.3.1 plus 1 at 4000 amp). Please clarify how many breakers are to be provided.
ANSWER:
Paragraph 3.3.1 is correct; only three breakers are to be provided. Paragraph 7.1.23.1 numbering was incorrect, what should have been 7.1.23.5 is to be deleted.
Paragraph 7.1.23 should read as follows;
| 7.1.23 | In additional to the work above contractor shall accomplish and provide the following; |
| 7.1.23.1 | The contacts on the three (3) 800 AMP circuit breakers in the EDG room needs to be taken out, cleaned, sand blasted, re-plated, re-assembled and re-install. |
| 7.1.23.2 | One (1) 800 AMP SPB 100 for 120 Volts Lighting, Forward Emergency Lighting and Forward Load Centre L-C7 |
| 7.1.23.3 | One (1) 1600 AMP frame SPB 150 with 800 AMP Sensors for 120 Volts Lighting and Forward Lighting. |
| 7.1.23.4 | One (1) 2000 AMP frame SPB 150 with 2000 AMP Sensors for Vitals A&C. |
| 7.1.23.5 | One (1) 4000 AMP frame SPB 150 with 4000 AMP sensors for PTO & SSDG. |