This document is an Attachment of Responses to Questions Received for a solicitation involving Powerware 93PM-208v uninterruptible power supply (UPS) equipment. The questions and responses clarify specific technical details about battery and equipment replacement, including confirmation that replacement batteries should be sealed lead acid (93PM 208V-20-120 VRLA Sealed, 40), the required power module is a 20kw Power Module (744-A4606), and two UPS units are involved with serial numbers EN093UJJ01 and EN092UJJ08. Additional clarifications include that existing battery cabinets can be reused for new batteries, and that fans and capacitors on the existing power ware do not require replacement.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment 5 – Responses to Questions Received

Questions were received through the solicitation and the requesting agency has provided the following responses:

Question 1: It appears existing batteries are sealed lead acid. Please confirm replacement batteries can also be sealed lead acid.

Response 1: These are the required battery part numbers needed nothing diƯerent (93PM 208V-20- 120 VRLA Sealed, 40.

Question 2: Verbiage alludes to the replacement of quantity 2 power ware 93PM-208v. If the actual Powerware 93PM-208v itself needs to be replaced, please confirm what size (kilowatts) is required as the manufacturer has several diƯerent sizes within the 93PM-208v model designation.

Response 2: 20kw Power Module 744-A4606

Question 3: Requesting serial number of the 2nd existing power ware. We only see one serial number listed for the power ware Each power ware should have its own serial number.

Response 3: UPS 1 (EN093UJJ01) & UPS 3 (EN092UJJ08)

Question 4: Do the fans and capacitors need to be replaced on the existing power ware 93PM- 208v?

Response 4: Fans and Caps do not require replacement

Question 5: Are we permitted to re-use existing battery cabinet when existing batteries are replaced?

Response 5: Yes, existing cabinets will be reused for new batteries.