Statement of Work.pdf

PDF 149 KB Posted

Attached to
SELF-CONTAINED HAZMAT STORAGE CONTAINERS
Solicitation number
N00244-25-Q-S019
Issued by

About this file

This Statement of Work (SOW) details the procurement of one self-contained hazardous material (HAZMAT) storage container for Naval Base Coronado, Building 1206. The required container is a two-room unit with specific technical specifications, including two 48" fire-rated doors, electro-magnetic door hold open options, explosion-proof air conditioning, a pre-engineered fire suppression system, interior LED lighting, fume removal systems, and other specialized safety features compliant with DoD, NFPA, OSHA, and local regulatory standards.

The contractor's scope of work includes delivering a fully operational HAZMAT container with functioning fire suppression systems and air conditioning, completing delivery and activation at the designated location, providing written certification of system installation, and furnishing operation and maintenance manuals. The period of performance requires all units to be delivered and fully activated on the day of delivery, with the point of contact being Henry Grays, FLCSD Regional HAZMAT Director, who can be reached at 619-556-6209.

View the file

Other files

File Type Posted
4.02 Attachment -Q&A Government Responses.xlsx XLSX spreadsheet
COMBINED SYNOPSIS.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Statement of Work (SOW)

Project Title: Self-Contained HAZMAT Storage Container – Delivery and Activation Location: Naval Base Coronado, HAZMAT Compound Building 1206

1. Objective:

To procure, deliver, and activate One (1) self-contained hazardous material (HAZMAT) storage containers equipped with built-in fire suppression systems for safe and compliant material storage at Naval Base Coronado, Building 1206.

Specifications: ONE (1) 2 ROOM OPTION with Two (2) Doors w/ ExpProof A/C per room

Equipped with Electro Magnetic Door Hold Open Option “EGDM241-B2-2RM2DR-AC-HD- NASNI” – One Unit w/ an approximate Exterior Footprint of 23’6”L x 9’6”D x 8’8”H with I.D.

of 22’’L x 8’D approximate Interior Square Feet @ Single Level – One (1) Room – Factory Mutual “FM” Approved – “2-Hour” Fire-rated Welded Construction equipped w/ features Meets County and City of San Diego OFFSITE requirements for Fabrication and Offsite electrical requirements for Southern California Jurisdictions. Structure to carry Product Liability Insurance. Structure to have a TOTAL of Two (2) Wide 48” Doors “3-hour” Fire-Rated “UL Listed” COMPLETE VERTICAL WALL FIRE-RATING INCLUDING SUMP SILL HEIGHT

WALLS. FLOOR SUPPORT CHANNELS TO BE COMPLETELY REMOVEABLE

ADA Pultruded Fiberglass Floor grating (500 psf), LDPE sump liner Full Building,R20 INSULATON of doors walls and ceiling ,Seventy (70’) Lineal feet of Stainless Steel 16” Deep Adjustable Shelving,Pre-Engineered FM Approved & UL Listed Dry Chem Fire Suppression system meeting NFPA 17 reqs, Exterior UL Listed NEMA 3R Load Center – 1 Phase,Two (2) Interior LED 2’ Lighting Fixture Class I Div 1 Groups C&D w/ NON EP Ext UL Listed Weather Proof switch, Two (2) Electromechanically Fume Removal System ( Class I, Grps C&D, Div 1 ) with 3Hour Fire Rated UL Listed fire damper and Break Glass Exterior Fan Switch, One (1) 19K BTU Explosion Proof Air Conditioner ( Class I, Grps C&D , Div 2) with Interior EP Thermostat , 12’ of Interior Copper Clad Buss Bars. Six (6) 2’ sections Tare Weight and No Smoking Sign

2. Scope of Work:

The contractor shall:

• Provide One (1) new, fully self-contained HAZMAT storage containers.

• Equipped with an integrated fire suppression system appropriate for chemical and flammable material storage.

• Ensure containers meet or exceed DoD, NFPA, OSHA, and local/state regulatory standards for hazardous materials storage.

• Deliver all units to HAZMAT Compound 1206, Naval Base Coronado.

• Activate and test fire suppression systems in each unit upon delivery.

• Provide technical documentation and training on safe use and emergency procedures if applicable.

3. Deliverables:

• One (1) fully operational self-contained HAZMAT container with functioning fire suppression systems and Air Conditioning for temperature control

• Completed delivery and activation at designated location.

• Written certification of system installation and functionality.

• Operation and maintenance manuals for each unit.

4. Period of Performance:

All units must be delivered and fully activated on day of delivery