Motor_Control_Center_-_BOM_2.pdf
PDF 200 KB Posted
- Attached to
- LANDSAT TRI-BAND ANTENNA PROJECT
- Solicitation number
- DOIGFBO260032
About this file
This document is a Bill of Materials (BOM) for two Motor Control Centers (MCCs) designated as MCC-11 and MCC-31, which are CR8000 series low-voltage electrical distribution units manufactured to NEMA 1 specifications with gasketing for industrial applications.
MCC-11 is a 1200-amp, 3-phase, 480V, 60Hz unit comprising 3 sections with a total lineup dimension of 90 inches high by 60 inches wide by 20 inches deep. It features a 42kA minimum interrupt rating, fully rated copper tin-plated buses, a main circuit breaker rated at 1200A with 1000A trip capacity, two magnetic starters (2 hp and 0.5 hp), multiple feeders with varying amperage ratings (ranging from 15A to 400A), seismic certification to IBC-2018/CBC-2019, UL 845 certification, and ANSI-61 light gray enclosure paint. The unit includes control power transformers, auxiliary contacts, pilot devices with hand/off/auto switches, and customer-available blank space units.
MCC-31 is a 600-amp, 3-phase, 480V, 60Hz unit comprising 4 sections with a total lineup dimension of 90 inches high by 80 inches wide by 20 inches deep. It shares similar certifications and specifications as MCC-11 but includes a 600A main circuit breaker with thermal magnetic adjustable trip unit, four 20 hp starters, three 15 hp starters, two 5 hp starters, two 10 hp starters, one 25 hp starter, one 7.5 hp starter with soft-start capability, and one standard Modbus RTU communication module. Both units are configured for front-only mounting with top incoming feeds and factory-tested for 600 hours humidity and salt spray resistance.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment_E_-_L10_Spacecraft_to_Ground__Interface_Req_Document_(SC_to_GND_IRD)_Rev_2.pdf | ||
| RFI_Q_A_2.xlsx | XLSX spreadsheet | |
| Landsat_Tri-Band_Antenna_Industry_Brief_2.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
JM060424 EROS Buckets - Original Version | UM8-00013254 4 of 14
Bill of Material(s)
Item No. Quantity Description 1 1 Motor Control Center, Low Voltage
Marks: MCC-11
3 Section(s), NEMA 1 with Gasketing Not Suitable for Service Entrance 1200 Amps, 3 Phase 3 Wire, 480 V ac, 60 Hz Minimum Interrupt Rating: 42kA Fully Rated; Bus Bracing Rating: 65 kA Incoming Feed: Top Incoming Left Feeding Right Front Only Mounting NEMA Wiring Classification I-BD "Class 1-BD (Independent units with NO Factory interconnecting wires, load wiring to device)" UL 845 Certified for US and Canada, NEMA ICS 18, NEC Seismic Certified (non-OSHPD) to IBC-2018/CBC-2019 Enclosure Paint: ANSI-61 (Light Gray) tested to minimum withstand of 600 hours humidity and salt spray test.
Customer will NOT provide Specifications or Drawings to the Factory.
Dimensions and Weight (Estimated) Section 1 "AA":
Height=90 in; Width=20 in; Depth=20 in Section 2 "AB":
Height=90 in; Width=20 in; Depth=20 in Section 3 "AC":
Height=90 in; Width=20 in; Depth=20 in Lineup Total:
Height=90 in; Width=60 in; Depth=20 in List of Materials
1 NEMA 1 With Gasketing Enclosure 20W 2 NEMA 1 With Gasketing Enclosure 20W 3 Fully Rated COPPER Standard Tin plated Bus 1200A 20 Wide 3 Ground COPPER Standard Tin plated Bus 300A 20 Wide 1 Vertical COPPER Standard Tin plated Bus 300A 36 High 1 Vertical COPPER Standard Tin plated Bus 850A 72 High 1 Vertical COPPER Standard Tin plated Bus 300A 72 High
Options 1 Seismic Rating 3 Double-Bolted Main Bus 3 Standard Catalog Renewal Parts Book 19 Engraved Nameplates Black with White Text
NEMA Wiring Classification: I-BD "Class 1-BD (Independent units with NO Factory interconnecting wires, load wiring to device)"
2 Control Wire Type: MTW VW1 (Standard) 2 Control Wire Markers: None (Standard) 2 Control Wire Terminal: Stripped Wire (Standard) 2 Control Terminal Board: Hi Density Standard 14 Power Wire Type: MTW VW1 (Standard) 14 Power Wire Markers: None (Standard) 14 Power Wire Terminal: Stripped Wire (Standard) 14 Power Wire Terminal Board: Standard
Main Circuit Breaker 1 Circuit Breaker, 1200 A Frame, 1000 A Trip, 3 Pole, Thermal Magnetic XT7S1200
Electronic Ekip Dip LSI Trip Unit Manually Operated Circuit Breaker
JM060424 EROS Buckets - Original Version | UM8-00013254 5 of 14
4/0 AWG - 500 MCM Mechanical (1-Hole) ALUMINUM Line Lugs (4) Cables Per Phase Starter
1 Full Voltage Non-Reversing, 300 Contactor Type 2 hp; 1.49 kW, Nema Size 1, Magnetic Starter
1 Circuit Breaker, 10 A Trip, 3 Pole, Magnetic, XT2H125 Stationary Stab Ekip Dip I Trip Unit
1 AMBIENT Overload Relay 1 Control Power Type: Control Power Transformer - 150VA 1 Aux Contacts
Used Contacts: (1) Normally Open Contact (0) Normally Closed Contact 1 Pilot Devices
Switches / Pushbuttons : Hand / Off / Auto (SW) (Black), Non Illuminated Starter
1 Full Voltage Non-Reversing, 300 Contactor Type
0.5 hp; 0.37 kW, Nema Size 1, Magnetic Starter
1 Circuit Breaker, 10 A Trip, 3 Pole, Magnetic, XT2H125 Stationary Stab Ekip Dip I Trip Unit
1 AMBIENT Overload Relay 1 Control Power Type: Control Power Transformer - 150VA 1 Aux Contacts
Used Contacts: (1) Normally Open Contact (0) Normally Closed Contact 1 Pilot Devices
Switches / Pushbuttons : Hand / Off / Auto (SW) (Black), Non Illuminated Feeder
2 Circuit Breaker, 125 A Frame, 30 A Trip, 3 Pole, Thermal Magnetic, XT2H125 Manually Operated Circuit Breaker Stationary Stab
6 #14 - 1/0 AWG Mechanical Aluminum Load Lugs Thermal Magnetic Fixed Trip Unit Feeder
1 Circuit Breaker, 125 A Frame, 60 A Trip, 3 Pole, Thermal Magnetic, XT2H125 Manually Operated Circuit Breaker Stationary Stab
3 #14 - 1/0 AWG Mechanical Aluminum Load Lugs Thermal Magnetic Fixed Trip Unit Feeder
2 Circuit Breaker, 400 A Frame, 400 A Trip, 3 Pole, Thermal Magnetic, XT5S400 Manually Operated Circuit Breaker Stationary Stab
6 2/0 AWG - 500 kcmil Mechanical Aluminum Load Lugs Thermal Magnetic Adjustable Trip Unit Feeder
1 Circuit Breaker, 125 A Frame, 40 A Trip, 3 Pole, Thermal Magnetic, XT2H125 Manually Operated Circuit Breaker Stationary Stab
3 #14 - 1/0 AWG Mechanical Aluminum Load Lugs Thermal Magnetic Fixed Trip Unit Feeder
1 Circuit Breaker, 125 A Frame, 100 A Trip, 3 Pole, Thermal Magnetic, XT2H125 Manually Operated Circuit Breaker Stationary Stab
JM060424 EROS Buckets - Original Version | UM8-00013254 6 of 14
3 #14 - 1/0 AWG Mechanical Aluminum Load Lugs Thermal Magnetic Adjustable Trip Unit Feeder
1 Circuit Breaker, 250 A Frame, 200 A Trip, 3 Pole, Thermal Magnetic, XT4H250 Manually Operated Circuit Breaker Stationary Stab
3 #4 AWG - 300 kcmil Mechanical Aluminum Load Lugs Thermal Magnetic Fixed Trip Unit Feeder
3 Circuit Breaker, 125 A Frame, 80 A Trip, 3 Pole, Thermal Magnetic, XT2H125 Manually Operated Circuit Breaker Stationary Stab
9 #14 - 1/0 AWG Mechanical Aluminum Load Lugs Thermal Magnetic Adjustable Trip Unit Feeder
1 Circuit Breaker, 125 A Frame, 15 A Trip, 3 Pole, Thermal Magnetic, XT2H125 Manually Operated Circuit Breaker Stationary Stab
3 #14 - 1/0 AWG Mechanical Aluminum Load Lugs Thermal Magnetic Fixed Trip Unit Space Unit
4 Customer Available Spaces Height=12 in
2 1 Motor Control Center, Low Voltage
Marks: MCC-31
4 Section(s), NEMA 1 with Gasketing Not Suitable for Service Entrance 600 Amps, 3 Phase 3 Wire, 480 V ac, 60 Hz Minimum Interrupt Rating: 42kA Fully Rated; Bus Bracing Rating: 65 kA Incoming Feed: Top Incoming Left Feeding Right Front Only Mounting NEMA Wiring Classification I-BD "Class 1-BD (Independent units with NO Factory interconnecting wires, load wiring to device)" UL 845 Certified for US and Canada, NEMA ICS 18, NEC Seismic Certified (non-OSHPD) to IBC-2018/CBC-2019 Enclosure Paint: ANSI-61 (Light Gray) tested to minimum withstand of 600 hours humidity and salt spray test.
Customer will NOT provide Specifications or Drawings to the Factory.
Dimensions and Weight (Estimated) Section 1 "AA":
Height=90 in; Width=20 in; Depth=20 in Section 2 "AB":
Height=90 in; Width=20 in; Depth=20 in Section 3 "AC":
Height=90 in; Width=20 in; Depth=20 in Section 4 "AD":
Height=90 in; Width=20 in; Depth=20 in Lineup Total:
Height=90 in; Width=80 in; Depth=20 in List of Materials
1 NEMA 1 With Gasketing Enclosure 20W
JM060424 EROS Buckets - Original Version | UM8-00013254 7 of 14
3 NEMA 1 With Gasketing Enclosure 20W 4 Fully Rated COPPER Standard Tin plated Bus 600A 20 Wide 4 Ground COPPER Standard Tin plated Bus 300A 20 Wide 1 Vertical COPPER Standard Tin plated Bus 600A 72 High 3 Vertical COPPER Standard Tin plated Bus 300A 72 High
Options 1 Seismic Rating 4 Double-Bolted Main Bus 3 Standard Catalog Renewal Parts Book 22 Engraved Nameplates Black with White Text
NEMA Wiring Classification: I-BD "Class 1-BD (Independent units with NO Factory interconnecting wires, load wiring to device)"
14 Control Wire Type: MTW VW1 (Standard) 14 Control Wire Markers: None (Standard) 14 Control Wire Terminal: Stripped Wire (Standard) 14 Control Terminal Board: Hi Density Standard 14 Power Wire Type: MTW VW1 (Standard) 14 Power Wire Markers: None (Standard) 14 Power Wire Terminal: Stripped Wire (Standard) 14 Power Wire Terminal Board: Standard
Main Circuit Breaker 1 Circuit Breaker, 600 A Frame, 600 A Trip, 3 Pole, Thermal Magnetic XT5S600
Thermal Magnetic Adjustable Trip Unit Stationary Stab
Manually Operated Circuit Breaker 2/0 AWG - 500 MCM Mechanical (1-Hole) ALUMINUM Line Lugs (2) Cables Per Phase
Starter 4 Full Voltage Non-Reversing, 300 Contactor Type
20 hp; 14.92 kW, Nema Size 2, Magnetic Starter 4 Circuit Breaker, 50 A Trip, 3 Pole, Magnetic, XT2H125
Stationary Stab Motor Circuit Protector Trip Unit
4 AMBIENT Overload Relay 4 Control Power Type: Control Power Transformer - 150VA 4 Aux Contacts
Used Contacts: (1) Normally Open Contact (0) Normally Closed Contact 4 Pilot Devices
Switches / Pushbuttons : Hand / Off / Auto (SW) (Black), Non Illuminated Starter
3 Full Voltage Non-Reversing, 300 Contactor Type 15 hp; 11.19 kW, Nema Size 2, Magnetic Starter
3 Circuit Breaker, 50 A Trip, 3 Pole, Magnetic, XT2H125 Stationary Stab Motor Circuit Protector Trip Unit
3 AMBIENT Overload Relay 3 Control Power Type: Control Power Transformer - 150VA 3 Aux Contacts
Used Contacts: (1) Normally Open Contact (0) Normally Closed Contact 3 Pilot Devices
Switches / Pushbuttons : Hand / Off / Auto (SW) (Black), Non Illuminated Starter
2 Full Voltage Non-Reversing, 300 Contactor Type 5 hp; 3.73 kW, Nema Size 2, Magnetic Starter
JM060424 EROS Buckets - Original Version | UM8-00013254 8 of 14
2 Circuit Breaker, 25 A Trip, 3 Pole, Magnetic, XT2H125 Stationary Stab Ekip Dip I Trip Unit
2 AMBIENT Overload Relay 2 Control Power Type: Control Power Transformer - 150VA 2 Aux Contacts
Used Contacts: (1) Normally Open Contact (0) Normally Closed Contact 2 Pilot Devices
Switches / Pushbuttons : Hand / Off / Auto (SW) (Black), Non Illuminated Starter
2 Full Voltage Non-Reversing, 300 Contactor Type 10 hp; 7.46 kW, Nema Size 2, Magnetic Starter
2 Circuit Breaker, 25 A Trip, 3 Pole, Magnetic, XT2H125 Stationary Stab Ekip Dip I Trip Unit
2 AMBIENT Overload Relay 2 Control Power Type: Control Power Transformer - 150VA 2 Aux Contacts
Used Contacts: (1) Normally Open Contact (0) Normally Closed Contact 2 Pilot Devices
Switches / Pushbuttons : Hand / Off / Auto (SW) (Black), Non Illuminated Starter
1 Full Voltage Non-Reversing, 300 Contactor Type 25 hp; 18.65 kW, Nema Size 2, Magnetic Starter
1 Circuit Breaker, 50 A Trip, 3 Pole, Magnetic, XT2H125 Stationary Stab Motor Circuit Protector Trip Unit
1 AMBIENT Overload Relay 1 Control Power Type: Control Power Transformer - 150VA 1 Aux Contacts
Used Contacts: (1) Normally Open Contact (0) Normally Closed Contact 1 Pilot Devices
Switches / Pushbuttons : Hand / Off / Auto (SW) (Black), Non Illuminated Starter
1 Full Voltage Non-Reversing, 300 Contactor Type
7.5 hp; 5.59 kW, Nema Size 1, Magnetic Starter
1 Circuit Breaker, 25 A Trip, 3 Pole, Magnetic, XT2H125 Stationary Stab Ekip Dip I Trip Unit
1 AMBIENT Overload Relay 1 Control Power Type: Control Power Transformer - 150VA 1 Aux Contacts
Used Contacts: (1) Normally Open Contact (0) Normally Closed Contact 1 Pilot Devices
Switches / Pushbuttons : Hand / Off / Auto (SW) (Black), Non Illuminated SoftStarter
1 SoftStarters
7.5 hp; 5.59 kW INTEGRATED BYPASS Feature
1 Circuit Breaker, 25 A Trip, 3 Pole, Thermal Magnetic, XT4H250 Stationary Stab Thermal Magnetic Fixed Trip Unit
1 Required Circuit Relays
JM060424 EROS Buckets - Original Version | UM8-00013254 9 of 14
Standard Modbus RTU 1 Control Power Type: Control Power Transformer - 150VA
Blank Pilot Device Bracket Not Provided Space Unit
6 Customer Available Spaces Height=12 in 1 Customer Available Spaces Height=6 in
Sections 1 2 3 4 5 blank RF-1 P-9 blank
12x15 BAD AHU-1 12X15 BCD 12x15 BDD 12x15 BED
AHU-2 18x15 BBE AHU-11 P-10 blank
12x15 BAF AHU-6 12X15 BCF 12x15 BDF 12x15 BEF
AHU-3 12x15 BBG RF-2 blank blank
12x15 BAH 12X15 BCH 12x15 BDH 12x15 BEH Amps
AHU-4 12X15 BBI 6x15 blank
BCI blank
12x15 BAJ AHU-9 6x15 blank
BCJ 12x15 BDJ blank
AHU-5 12X15 BBK 6x15 blank
BCK blank 12x15 BEK
12x15 BAL AHU-10 6x15 blank
BCL 12x15 BDL BEL blank 12X15 BBM blank blank Incoming Power Bus Baacing
12x15 BAN 6X15 blank
BBM 12x15 BCM 12x15 BDN
6x20 6x20 6x20 6x20 24x20
Sect WxD
Vert Bus
Nuet bus
42000 symmetrical
MCC Short CKT. Rating 42000 SYM.
AHU-8
Vert bus Copper TIN STD
GND bus 300 Copper TIN STD
Power Supply 480 volt 60HZ 3-Phase 3-Wire
Control 120 Volt INDVI. CPT
Material Plating
Main bus 600 Copper TIN STD
Outline -Summary
CR8000 Motor Control Center
MCC-31
Total Sections - 5
NEMA Class 1 Type B ENCL. 1 Gasketed
20x20 20x20
300 300 300 300 600
MCC-31
20x20 20x20
Front View
20x20
Unit
Location Nameplate Elem. Funct Size HP FLA
O.L
Heater
C.B.
SW
Trip
Fuse/Clip
H
O
A
OFF/
AUTO
FAST/
SLOW
PILOT
Photo links
BAD BLANK NP SP
BAF AHU-2 D049 FVNR 2 20 25.8 273B SEL1 50 1 3 1
BAH AHU-3 D049 FVNR 2 15 19.8 214B SEL1 30 1 3 1
BAJ AHU-4 D049 FVNR 2 20 25.8 273B SEL1 50 1 3 1
BAL AHU-5 D049 FVNR 2 20 25 273B SEL1 50 1 3 1
BAN BLANK NP SP
BBE AHU-1 ? 2S2W 1 7.5/3
10.3/
6.0 SOL ST SEL1 20 1 1 A G R 6 2 5131, 5300, 5343
BBG AHU-6 ? FUNK 1 5 7.1 SOL ST SEL1 15 G R 3 1 2707, 3946,3959
BBI AHU-8 D049 FVNR 2 20 25.8 273B SEL1 50 3 1
BBK AHU-9 D049 FVNR 1 10 13.6 163B SEL1 20 3 1
BBM AHU-10 D049 FVNR 2 25 31 303B SEL1 50 3 1
BBN BLANK NP SP
BCD RF-1 D049 FVNR 1 7.5 10.3 104B SEL1 2 3 1
BCF AHU-11 D049 FVNR 1 10 13.6 163B SEL1 20 3 1
BCH RF-2 D049 FVNR 1 5 7.1 778A SEL1 15 3 1
BCI BLANK SP
BCJ BLANK SP
BCK BLANK SP
BCN BLANK SP
BDD P-9 D049 FVNR 2 15 20.3 214B SEL1 30 3 1
BDF P-10 D049 FVNR 2 15 20.3 214B SEL1 30 3 1
BDH BLANK NP SP
BDJ BLANK NP SP
BDL BLANK NP SP
BDN BLANK NP SP
BED BLANK NP SP
BEF BLANK NP SP
BEH BLANK NP SP
BEK BLANK NP SP
BEL
Incoming
Power INC Line 600 amp
MCC-31
Total
INTLK
UL Sect No: 1 2 3 4 5 6 7
6x20 6x20 6x20 6x20 6x20 6x20 blank 12x20 blank blank
12x15 AAC 12x15 ADC blank 12x15 AGC
CHP-1
6x15
AAD blank blank 18 AED blank blank
CHP-2
6x15
AAE MAIN 24x15 ACE 12x15 ADE 24 AFE 12x15 AGE
CP-1
6x15
AAF 24x20
ABF
CU-1
AHU12
CWP-3
AGF
CP-2
6x15
AAG blank 18
AEG
MODIS
AGG Amps blank 12x15 ABH blank EF-2 blank
CWP-2
AGH
12x15 AAI 24x15 ACI 24
ADI 12x15 AEI 24 AFI
CWP-1
AGI
12x15
ABJ blank
AC-1
6 AEJ blank
12x15 ACK CP-1 12x15 AFK
CH-1A blank blank
New
L7UPS 12x15 AEL blank blank Bus Baacing
24x20
AAM 18x15 ABM 12x15 ACM 24
ADM 6
Spare
AEM 12x15 AFM 12x15 AGM
12x20 12x20 12x20 12x20 12x20 12x20 12x20
Sect WxD
Front View
42000 symmetrical
MCC Short CKT. Rating 42000 SYM.
Total Sections - 7
NEMA Class 1 Type B ENCL. 1 Gasketed
Power Supply 480 volt 60HZ 3-Phase 3-Wire
Control 120 Volt INDVI. CPT
Copper TIN STD
PlatingMaterial
Main bus 1000
Nuet bus
GND bus 300
Copper TIN STDAHU-12
MCC-11
CR8000 Motor Control Center
Outline -Summary
MCC-11
Vert bus
20x20 20x20 20x2020x20 20x20 20x20 20x20
Copper TIN STD
Unit
Location Nameplate Elem. Funct Size HP FLA
O.L
Heater
C.B.
SW
Trip
Fuse/Clip
H
O
A
OFF/
AUTO
FAST/
SLOW
PILOT
Photo links
AAC BLANK NP SP
AAD CHP-1 FDR 2 20 25.8 273B SEL1 50 1 3 1
AAE CHP-2 FDR 2 15 19.8 214B SEL1 30 1 3 1
AAF CP-1 FDR 2 20 25.8 273B SEL1 50 1 3 1
AAG CP-2 FDR 2 20 25 273B SEL1 50 1 3 1
AAI BLANK SP
AAM CH-1A FDR
ABF MAIN BKR 1000 Amp SOL ST SEL1 20 1 1 A G R 6 2 5131, 5300, 5343
ABH BLANK NP 1 5 7.1 SOL ST SEL1 15 G R 3 1 2707, 3946,3959
ABJ AHU-12 D049 FVNR 2 20 25.8 273B SEL1 50 3 1
ABM BLANK NP D049 FVNR 1 10 13.6 163B SEL1 20 3 1
ABM BLANK NP D049 FVNR 2 25 31 303B SEL1 50 3 1
ACE BLANK NP D049 FVNR 1 7.5 10.3 104B SEL1 2 3 1
ACI BLANK NP D049 FVNR 1 10 13.6 163B SEL1 20 3 1
ACK BLANK NP D049 FVNR 1 5 7.1 778A SEL1 15 3 1
ACM BLANK NP SP
ADC BLANK NP D049 FVNR 2 15 20.3 214B SEL1 30 3 1
ADE BLANK NP D049 FVNR 2 15 20.3 214B SEL1 30 3 1
ADI ? SP
ADM L7UPS
AED BLANK NP SP
AEG CU-1 AHU-12
AEI EF-1
AEJ AC-1
AEL CP-1
AEM BLANK NP
AFE BLANK NP SP 2 15 20.3 214B SEL1 30 3 1
AFI BLANK NP SP 2 15 20.3 214B SEL1 30 3 1
AFK BLANK NP SP
AFM BLANK NP SP
AGC BLANK NP SP
AGE BLANK NP SP 2 20 25.8 273B SEL1 50 1 3 1
AGF CWP-3 FDR 2 15 19.8 214B SEL1 30 1 3 1
AGG MODIS FDR 2 20 25.8 273B SEL1 50 1 3 1
AGH CWP-2 FDR 2 20 25 273B SEL1 50 1 3 1
AGI CWP-1 FDR
AGM BLANK NP SP
MCC-11
Total
INTLK
| Motor Control Center - BOM |
| MCC11_MCC31 Info 1 |
| MCC11_MCC31 Info 2 |
| MCC11_MCC31 Info 3 |
| MCC11_MCC31 Info 4 |
File details come from the government source that posted it. Updated .