This is a technical specification and requirements document for a mobile communications platform project in Maine. The document outlines requirements for a comprehensive mobile communication system, including tower infrastructure, network deployment, and related telecommunications services. The project scope encompasses the design, construction, and implementation of mobile communication tower facilities to support statewide connectivity. The document specifies technical standards, equipment requirements, and operational parameters for the platform deployment. Key deliverables include site assessment reports, tower construction documentation, network configuration specifications, and system integration plans. The project timeline includes phased implementation stages with specific milestones for site preparation, equipment procurement, installation, and system testing. The contract term extends through the full deployment phase with provisions for ongoing maintenance and system support.
The procurement establishes performance standards for network coverage, signal quality, and system reliability across designated service areas. The document includes technical specifications for equipment compatibility, safety compliance requirements, and industry standard adherence. Funding for the project derives from state appropriations allocated for telecommunications infrastructure development. The specification requires bidders to demonstrate technical expertise in tower construction, network installation, and mobile communications platform deployment. Qualified vendors must provide evidence of relevant experience with similar-scale telecommunications projects and certification in applicable industry standards. The document addresses redundancy requirements, backup power systems, and failover protocols to ensure continuous network operation.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Conditions and Instructions to Bidders.doc | DOC document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Mobile Communications Platform Required specifications
The State of Maine OIT Radio Communications Services Division is seeking to purchase a self-sustaining mobile communications platform for deployment in emergency situations.
The following list of features and specifications should be included in any proposal that is to be considered for evaluation and / or subsequent purchase.
Physical Limitations
· Overall Length:
No more than 32 feet
(384”)
· Overall Width:
No more than 8 feet
( 96”)
· Overall Transport Height:
No more than 13 feet
(156”)
· Vehicle Platform Height:
No more than 3 feet, 6 inches ( 42”) Transport Platform Requirements
· Gross Vehicle Weight Rating:
No more than 20,000 pounds
· Stabilizing Outriggers:
Minimum number (4), adjustable height, Static capacity no less than 15,000 pounds EACH
· Leveling Jacks:
Minimum (5 degree) ground slope accommodation
· Leveling Platforms:
Minimum (5), sand/marsh compatible, Removable and stowable on deck with lanyard(s)
· Leveling Bubbles:
Minimum (3) on perimeter plus (1) at tower base
· Brakes:
All-Wheel Electric, self-adjusting, battery backup
· Wheels:
Minimum number (8), minimum size 16 inches With full-size, full capacity spare
· Bumpers:
As necessary to provide typical protection
· Towing Connection:
3” Pintle Eye with height adjustment
· Landing Gear:
Single, drop-leg, adjustable, Static capacity no less than 15,000 pounds
· Safety Chains / Hooks:
P-70 Style, no less than 3/8 inch
· Lashing Rings:
Minimum number (6), 10,000 pounds rating, identified with specific markings
· Lighting / Wiring:
DOT approved, weather-sealed LED lamps, weather-sealed wiring, SAE-7 vehicle plug
· Decals:
DOT approved, includes perimeter reflector tape
All labels UV resistant
Transport Platform Requirements (con’t)
· Finish:
Operating Platform – painted and heavy-duty weather resistant, impact resistant rubberized coating drain holes for water removal
· Ground Lugs:
Minimum number (4), NFPA 780 compliant
· Storage Box:
Deck mounted, sufficient size for typical tool and anchor storage.
Trailer Transport Capabilities
· Air Transport
MIL–STD 1791
· Land Transport
· First class roads:
No less than 65 mph maximum speed
· Unpaved, graded roads:
No less than 25 mph maximum speed
· Unpaved, ungraded roads:
No less than 5 mph maximum speed
· G-load factors:
Longitudinal
1.5 G minimum
Vertical Upward
2.0 G minimum
Vertical Downward
1.5 G minimum
6.0 G potential
Tower System Specifications
· General Conformance Codes:
UBC, TIA-EIA 222-G
· Extended Height:
No less than 105 feet above ground level
· Nested Height:
No more than 30 feet (horizontal & vertical)
· Maximum Payload:
No less than 500 pounds raising & tilting
· Support Configurations:
Self-Supporting AND Guy-capable
· Self-support Wind Speed Limit:
No less than 70 mph
· Guyed Wind Speed Limit:
No less than 120 mph
· Material Specifications
ASTM
· Legs
DOM 1036 Alloy A513
· Structural Shapes
A-36
· Structural Square Tubing
A-500
· Flat Bar
A-36
· Galvanizing
A513, Hot Dipped
· Bolts and Accessories
A307 (Galvanized), A316SS
· Lift / Support Cables:
Stainless steel, galvanized, aircraft quality
Breaking strength – no less than 7,200 lbs.
Redundant tower cabling
Mechanical tower lock with safety switch
· Lifting Functions:
Automatic with electronic limiting switch(es)
Control system in NEMA enclosure, Weatherproof with protective outside panel
Environmental Considerations
· Temperature - Operational:
- 30º to +100 º F (continuous duty)
- 30º to +130 º F (intermittent duty)
· Temperature – Storage:
- 30º to +140 º F
· Humidity – Storage:
20% to 90%
· Solar Radiation Tolerance:
No less than 1,100 w / m2
· Altitude – Operational:
No less than 3,000 m
· Altitude – Storage:
No less than 7,000 m
· Sand / Dust Tolerance:
No more than 1.0 g / m3 at 40 km/h & 3m Particle size – 75 to 500 µm average
· Rain Leakage Limit:
None with 5 cm/hr rain & 80 km/hr wind Equipment Shelter Specifications
· Outside Dimensions:
No single dimension more than 8 feet
· Walls and Ceilings:
Minimum 4” thick, R-28 insulation Minimum 2.4 lb / ft2 panel surface
· Floor:
No single dimension more than 8 feet Minimum 3.5 lb / ft2 panel surface
· Design Floor Load:
No less than 250 pounds / foot 2
· Roof:
Rain roof, PVC with min. 6” termination bar
· Door:
3.0’ X 6.0’, 20 gauge steel construction, Stainless steel hinges & deadbolt
· HVAC:
Minimum 24,000 BTU cooling, 3 kW heat, Single-phase, supply / return capability, Alarm relay(s), automatic thermostat
· Steps:
Building access, detachable
· Ladder:
Roof access, fixed Electrical Requirements
· Service Capacity:
No less than 100 amperes
· Circuit Breakers:
Main – 100A, Loads – 20A, minimum of 8
· Receptacles:
Minimum (2) duplex, (2) four-plex
· Lighting (Interior):
(1) Fluorescent Fixture, 2-bulb, 40-watt, T-12 rapid-start, ceiling surface mounted
(1) Emergency, battery backup, 2-bulbs
· Lighting (Exterior):
(2) Sodium lights, Hubble NRG-307PC, 220 VAC, 70 watt
(1) Emergency, battery backup, 2-bulbs
· Light Switches:
(1) Interior, (1) exterior
· GFCI Outlet:
(1) Exterior inside weatherproof enclosure
· Alarms:
(1) Terminal Block with:
Door Open Low Temperature
High Temperature
Smoke / Fire Electrical Requirements (con’t)
· Transfer Panel:
100 Ampere, manual, interior mounted
· LB Entrances:
(2) 2” with galvanized nipples
· Ground Complement:
(1) 24” X 4” X ¼” interior buss bar,
(1) 24” X 4” X ¼” exterior buss bar, Isolator Standoffs
Halo system, #2 Cu, green perimeter, Minimum (7) #2 Tinned Cu drops
· Coaxial Entry Point:
(1) 4-hole 4” diameter each, WX covers
· Telco Board:
No less than 2’ X 4’, white FRP Generator Requirements
· Rated Output:
No less than 15 kW (continuous duty)
· Power Factor:
1.0
· Voltage:
120 / 240 VAC Single Phase
· Regulation:
At least +/- 0.5% at rated output
· Sound Level:
No more than 80 dBa
· Fuel Consumption:
No more than 1.5 Gal / hr at rated output
· Run Time without Refueling:
No less than 48 hours at rated output, with platform-mounted external fuel tank
· External Tank:
Aluminum with adequate supply & return lines for full rated power operation
· Enclosure:
All weather, locking
END OF SPECIFICATIONS