MIL-W-16878-11.pdf
PDF 53 KB Posted
- Attached to
- Cabling for TS-405 Controls and Instrumentation Federal contract opportunity
- Solicitation number
- 80JSC024CABLE
About this file
This document is a Request for Quotations (RFQ) for providing cabling for TS-405 Controls and Instrumentation at the NASA White Sands Test Facility. The solicitation is a Total Small Business Set-aside with a NAICS code of 423610 - Electrical Apparatus and Equipment and a size standard of 200 employees.
The RFQ requires the following quantities of Teflon-insulated, shielded cables in 1000 ft spools: 48 spools of 20AWG 6-conductor, 27 spools of 22AWG 6-conductor, and 8 spools of 12AWG 2-conductor. Offers are due by 2:00 PM MT on April 9, 2024 and must include pricing, delivery schedule, and other commercial terms. The Government will award a contract to the responsible offeror whose offer is most advantageous based on technical capability and price. Delivery is required within 12 weeks of order receipt, FOB Destination to the NASA White Sands Test Facility in New Mexico.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| TC122F.pdf | ||
| TC206F.pdf | ||
| Terms and Conditions.pdf | ||
| TC226F.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
30 Toll Free: (800) 423-5873 International: +1 (661) 295-3100www.thermaxconnects.com
MIL-W-16878/11 (Type K) equivalent wire—extruded FEP insulation
MIL-W-16878/11 (type K) equivalent wires have extruded FEP insulation (medium wall thickness) for high-temperature applications. These wires have tin-plated copper conductors for economy. MIL-spec versions (silver-plated conductors) are also available.
For heavy-wall (type KK) versions of these wires, see M16878/12 equivalent (following page); for thin-wall (type KT) versions, see M16878/13 equivalent (page 32).
Performance:
Voltage rating: 600V.
Temperature rating: Tin-plated conductor: -55 to 150˚ C;
Silver-plated conductor: -55 to 200˚ C;
Nickel-plated conductor: -55 to 200˚ C.
Construction Details Insulation: Extruded FEP, wall thickness .010 (.25 mm).
Conductor: Tin-plated copper.
Colors: Color coded to MIL-STD-104 (See page 26).
Options: Silver- or nickel-plated copper conductor;
silver or nickel-plated high-strength copper alloy conductor; sodium napthalene etched insulation for bondability. Also available to NEMA HP-4-K.
AWG Size Stranding Conductor Insulation Diameter
Weight Maximum Thermax
Diameter Minimum Maximum Resistance P/N
8 133/29 .162 (4.11) .185 (4.70) .199 (5.05) 63.6 (9.46) .658 (2.16) 8-DXZ-13329
10 37/26 .108 (2.74) .127 (3.23) .141 (3.58) 33.1 (4.93) 1.26 (4.13) 10-DXZ-3726
12 19/25 .084 (2.13) .107 (2.72) .121 (3.07) 23.7 (3.53) 1.92 (6.30) 12-DXZ-1925
14 19/27 .067 (1.70) .088 (2.24) .102 (2.59) 15.5 (2.31) 3.06 (10.0) 14-DXZ-1927
16 19/29 .053 (1.35) .073 (1.85) .087 (2.21) 10.1 (1.50) 4.81 (15.8) 16-DXZ-1929
18 19/30 .047 (1.19) .064 (1.63) .074 (1.88) 7.74 (1.15) 6.23 (20.4) 18-DXZ-1930
18 7/26 .048 (1.22) .064 (1.63) .074 (1.88) 7.70 (1.15) 6.70 (22.0) 18-DXZ-726
20 19/32 .038 (.97) .054 (1.37) .062 (1.57) 5.08 (.756) 9.88 (32.4) 20-DXZ-1932
20 7/28 .038 (.97) .054 (1.37) .062 (1.57) 5.97 (.740) 10.7 (35.1) 20-DXZ-728
20 SOLID .032 (.81) .048 (1.22) .056 (1.42) 4.18 (.622) 10.9 (35.1) 20-DXZ-120
22 19/34 .030 (.76) .046 (1.17) .054 (1.37) 3.42 (.509) 16.2 (53.1) 22-DXZ-1934
22 7/30 .030 (.76) .046 (1.17) .054 (1.37) 3.33 (.496) 17.1 (56.1) 22-DXZ-730
22 SOLID .025 (.64) .041 (1.04) .050 (1.27) 2.92 (.435) 17.7 (58.1) 22-DXZ-122
24 19/36 .024 (.61) .040 (1.02) .048 (1.22) 2.39 (.356) 26.2 (85.9) 24-DXZ-1936
24 7/32 .024 (.61) .040 (1.02) .048 (1.22) 2.35 (.350) 27.0 (88.6) 24-DXZ-732
24 SOLID .020 (.51) .036 (.91) .044 (1.12) 2.12 (.315) 27.8 (91.2) 24-DXZ-124
26 19/38 .019 (.48) .035 (.89) .043 (1.09) 1.70 (.253) 41.3 (135) 26-DXZ-1938
26 7/34 .019 (.48) .035 (.89) .043 (1.09) 1.66 (.247) 43.3 (142) 26-DXZ-734
26 SOLID .016 (.41) .032 (.81) .040 (1.02) 1.55 (.231) 45.3 (149) 26-DXZ-126
28 7/36 .015 (.38) .031 (.79) .039 (.99) 1.22 (.182) 68.6 (225) 28-DXZ-736
28 SOLID .013 (.33) .029 (.74) .037 (.94) 1.17 (.174) 71.6 (235) 28-DXZ-128
30 7/38 .012 (.31) .028 (.71) .036 (.91) .930 (.138) 114 (374) 30-DXZ-738
30 SOLID .010 (.25) .026 (.66) .034 (.86) .900 (.134) 116 (380) 30-DXZ-130
32 7/40 .009 (.23) .026 (.66) .034 (.86) .700 (.104) 189 (620) 32-DXZ-740
32 SOLID .008 (.20) .024 (.61) .032 (.81) .730 (.109) 178 (584) 32-DXZ-132
Dimensions, Resistance, and Weights—M16878/11 equivalent—tin plated conductor
Dimensions in inches (mm). Weights in pounds/1000 feet (Kg/1000 m). Resistance in Ω/1,000 feet (Ω/Km), @20˚ C.
All values are nominal unless otherwise indicated.
Ordering Information: Specify Thermax part number and color.
To order with optional conductor materials:
For silver-plated copper conductor, change DXZ in Thermax part number to DX.
For silver-plated high-strength copper conductor, change DXZ in Thermax part number to DXTF.
For nickel-plated copper conductor, change DXZ in Thermax part number to DXN.
For nickel-plated high-strength copper conductor, change DXZ in Thermax part number to DXTFN.
K060714-5_GUTS_090712_K060714-5 all pages.qxd 9/7/12 3:39 PM Page 30
File details come from the government source that posted it. Updated .