MC AE CivilMech-OCO Attachments.pdf
PDF 875 KB Posted
- Attached to
- A&E Projects - JC Multi-Center East
- Solicitation number
- 12970224R0055
- Issued by
-
Department of Agriculture Forest Service
About this file
This document is a solicitation for Architectural and Engineering (A&E) services from the Department of Agriculture Forest Service for the "A&E Projects - JC Multi-Center East" project. The solicitation is requesting Standard Form (SF) 330 submissions from qualified A&E firms by August 27, 2024 in order to select the most highly rated firms for potential discussions.
The project consists of five base items across five different Job Corps Civilian Conservation Center locations: Jacobs Creek (JAC), Lyndon B. Johnson (LBJ), Oconaluftee (OCO), Schenck (SCH), and Frenchburg (FRE). The work includes tasks such as egress improvements, gym and drainage, HVAC upgrades, and lift station generator installations. This is a 100% Total Small Business Set-Aside solicitation under NAICS code 541310 - Architectural Services. Interested firms are instructed to submit questions via email no later than five calendar days prior to the closing date.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CHEROKEE, NORTH CAROLINA
OCONALUFTEE
CCC
OCONALUFTEE
CIVILIAN CONSERVATION CENTER
20 MI10 0
Building Descriptions Date: 06/27/2018Center : Oconaluftee (00423) Page: 2 of 90
Building: 0001 - ADMINISTRATION
INTERIOR FINISH
Carpet Ceramic Tile Concrete Wood
Ceramic Tile Drywall Plaster Wood Paneling
Storefront - Aluminum Frame Wood Unit - Metal Frame
Wood Unit - Wood Frame
Mechanical Restroom
Ventilation Area Served
VERTICAL CIRCULATION
Ramp Comments: There are concrete ramps leading to the entries.
Fixed - Wood Frame; Single Glazing; Sliding - Wood Frame; Single Glazing;
Acoustical Tile Gypsum Board
Exhaust Ventilation
Number of Deficiencies = 2
Number of Deficiencies = 1
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Heating and cooling is provided by a Trane 10 ton packaged, rooftop heat pump, with electric backup heat model #WSC120ER0A08 with R410A refrigerant, manufactured in 01/2011
Comments:
HVAC
Heat1.
Packaged Heat Pump (Air
Source)
Single Duct None Electric Mechanical None Entire Building
Ventilation2. Number of Deficiencies = 2
Ceilings
Page: 3 of 90
Building: 0001 - ADMINISTRATION
Domestic hot water is provided by a tankless electric water heater, Marley model # ECO110, with 11kW heating element.
Comments:
Cast Iron None None
Electric Water Cooler Hose Bibb Lavatory Sink Water Closet (Tank)
None
None None ABC Type Fire Extinguisher
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Split Direct Expansion (Air
Source)
Packaged Heat Pump (Air
Source)
Fan Coil
Single Duct
Refrigerant
None
Electronic
Electric
Natural
Mechanical
None
None
Equipment Room
Entire Building
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Mitsubishi, 1-1/2 ton mini-split, cooling only system, model MSY-GE18, serves IT data room.
Heating and cooling is provided by a Trane 10 ton packaged, rooftop heat pump, with electric backup heat model #WSC120ER0A08 with R410A refrigerant, manufactured in 01/2011
Comments:
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
3. Air Conditioning
Page: 7 of 90
Building: 0002 - DORMITORY A
Comments: Fixed, single pane windows are interior windows.
INTERIOR FINISH
Carpet Ceramic Tile Concrete
Ceramic Tile Drywall
Metal Unit - Metal Frame
Mechanical
Mechanical
Entire Building
Toilet/Shower
Comments:
Comments:
The building is equipped with air intakes at the eaves. There are two exhaust fans on the roof to exhaust the space under the roof. They are manufactured by Loren Cook.
The exhaust fan for the toilet/shower is Loren Cook Co. model 120C10D.
Ventilation Area Served
VERTICAL CIRCULATION
Ramp Comments: There are concrete ramps leading to the entries.
Fixed - Aluminum Frame; Double Glazing; Fixed - Aluminum Frame; Single Glazing;
Single Hung - Aluminum Frame; Double Glazing;
Gypsum Board
Exhaust Ventilation
Number of Deficiencies = 3
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Cooling and heating are provided by two split system heat pumps. The outdoor units are Carrier 38YC048560 and Carrier 38YC060560. The indoor units are Carrier FB4AN048 and FB4AN060 respectively. The systems include an outdoor air intake fans, Cook # 105-KSPD and use R22 refrigerant.
Comments:
HVAC
Heat1.
Split Heat Pump (Air
Source)
Single Duct Refrigerant Electric Mechanical None Entire Building
Page: 8 of 90
Building: 0002 - DORMITORY A
Hot water is provided by a gas-fired, Rheem-Ruud water heater, model G91-300A, rated at 300 MBH input and equipped with 91 gallon storage.
Comments:
Cast Iron None None
Electric Water Cooler Hose Bibb Lavatory Shower Sink Water Closet (Flush Valve)
Comments: There is one clothes washer and one clothes dryer in the toilet/shower room.
Gas (Propane)
Wet None ABC Type Fire Extinguisher
Comments: Data from Hydraulic Design Card, posted at the sprinkler valve: Design water density: 0.10 gallons per minute per square foot. Design area: 999 square feet. Design water flow 244 gallons per minute.
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Split Heat Pump (Air
Source)
Single Duct Refrigerant Electric Mechanical None Entire Building
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Cooling and heating are provided by two split system heat pumps. The outdoor units are Carrier 38YC048560 and Carrier 38YC060560. The indoor units are Carrier FB4AN048 and FB4AN060 respectively. The systems include an outdoor air intake fans, Cook # 105-KSPD and use R22 refrigerant.
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
Number of Deficiencies = 2FIRE PROTECTION
Page: 18 of 90
Building: 0003 - DORMITORY B
Comments: Fixed, single pane windows are interior windows.
INTERIOR FINISH
Carpet Ceramic Tile Concrete
Ceramic Tile Drywall
Metal Unit - Metal Frame
Mechanical
Mechanical
Entire Building
Toilet/Shower
Comments:
Comments:
The building is equipped with air intakes at the eaves. There are two exhaust fans on the roof to exhaust the space under the roof. They are Loren Cook Co. 100C10DL.
The exhaust fan for the toilet/shower is Loren Cook Co. model 120C10D.
Ventilation Area Served
VERTICAL CIRCULATION
Ramp Comments: There are concrete ramps leading to the entries.
Fixed - Aluminum Frame; Double Glazing; Fixed - Aluminum Frame; Single Glazing;
Single Hung - Aluminum Frame; Double Glazing;
Gypsum Board
Exhaust Ventilation
Number of Deficiencies = 3
Windows6.
Floors1. Number of Deficiencies = 1
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Cooling and heating are provided by two split system heat pumps. The outdoor units are Carrier 38YC048560 and Trane (no available information of the unit). The indoor units are Carrier FB4AN048 and Trane 4FWCA061A1000B built in 05/2013 respectively. The systems include an outdoor air intake fans, Cook # 105-KSPD and use R22 refrigerant for Carrier and 410A for Trane.
Comments:
HVAC
Heat1.
Split Heat Pump (Air
Source)
Single Duct Refrigerant Electric Mechanical None Entire Building
Page: 19 of 90
Building: 0003 - DORMITORY B
Hot water is provided by a gas-fired, Rheem-Ruud hot water heater, model G91-300A, rated at 300 MBH and equipped with 91 gallons storage.
Comments:
Cast Iron None None
Electric Water Cooler Hose Bibb Lavatory Shower Urinal Water Closet (Flush Valve)
Comments: There is one clothes washer and one clothes dryer in the toilet/shower room.
Gas (Propane)
Wet None ABC Type Fire Extinguisher
Comments: Data from Hydraulic Design Card, posted at the sprinkler valve: Design water density: 0.10 gallons per minute per square foot. Design area: 999 square feet. Design water flow 244 gallons per minute.
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Split Heat Pump (Air
Source)
Single Duct Refrigerant Electric Mechanical None Entire Building
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Cooling and heating are provided by two split system heat pumps. The outdoor units are Carrier 38YC048560 and Trane (no available information of the unit). The indoor units are Carrier FB4AN048 and Trane 4FWCA061A1000B built in 05/2013 respectively. The systems include an outdoor air intake fans, Cook # 105-KSPD and use R22 refrigerant for Carrier and 410A for Trane.
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
Number of Deficiencies = 1FIRE PROTECTION
Page: 28 of 90
Building: 0005 - VACANT DORMITORY D
Comments: Fixed, single pane windows are interior windows.
INTERIOR FINISH
Carpet Ceramic Tile Concrete
Ceramic Tile Drywall
Metal Unit - Metal Frame
Mechanical
Mechanical
Entire Building
Toilet/Shower
Comments:
Comments:
The building is equipped with air intakes at the eaves. There are two exhaust fans on the roof to exhaust the space under the roof. They are Loren Cook Co. 100C10DL.
The exhaust fan for the toilet/shower is Loren Cook Co. model 120C10D.
Ventilation Area Served
VERTICAL CIRCULATION
Ramp Comments: There is concrete ramp leading to the entrance.
Fixed - Aluminum Frame; Double Glazing; Fixed - Aluminum Frame; Single Glazing;
Single Hung - Aluminum Frame; Double Glazing;
Gypsum Board
Exhaust Ventilation
Number of Deficiencies = 2
Windows6.
Floors1. Asbestos: Yes
Interior Walls2.
3. Asbestos: Yes
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Cooling and heating are provided by two split system heat pumps. The outdoor units are Carrier 38YC048560 and Carrier 38YC060560. The indoor units are Carrier FB4AN048 and FB4AN060 respectively. The systems include an outdoor air intake fans, Cook # 105-KSPD and use R22 refrigerant.
Comments:
HVAC
Heat1. Asbestos: Yes
Split Heat Pump (Air
Source)
Single Duct Refrigerant Electric Mechanical None Entire Building
Page: 29 of 90
Building: 0005 - VACANT DORMITORY D
Hot water is provided by a gas-fired, Rheem-Ruud water heater, model G100-310A, rated at 310 MBH input and equipped with 100 gallon storage.
Comments:
Cast Iron None None
Electric Water Cooler Hose Bibb Lavatory Service Sink Shower Urinal Water Closet (Flush Valve)
Comments: There is one clothes washer and one clothes dryer in the toilet/shower room.
Gas (Propane)
Wet None ABC Type Fire Extinguisher
Comments: Data from Hydraulic Design Card, posted at the sprinkler valve: Design water density: 0.10 gallons per minute per square foot. Design area: 999 square feet. Design water flow 244 gallons per minute.
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Split Heat Pump (Air
Source)
Single Duct None Electric Mechanical None Entire Building
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Cooling and heating are provided by two split system heat pumps. The outdoor units are Carrier 38YC048560 and Carrier 38YC060560. The indoor units are Carrier FB4AN048 and FB4AN060 respectively. The systems include an outdoor air intake fans, Cook # 105-KSPD and use R22 refrigerant.
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
Page: 33 of 90
Building: 0006 - VACANT DORMITORY E
Comments: Fixed, single pane windows are interior windows.
INTERIOR FINISH
Carpet Ceramic Tile Concrete
Ceramic Tile Drywall
Metal Unit - Metal Frame
Mechanical
Mechanical
Entire Building
Toilet/Shower
Comments:
Comments:
The building is equipped with air intakes at the eaves. There are two exhaust fans on the roof to exhaust the space under the roof. They are Loren Cook Co. 100C10DL.
The exhaust fan for the toilet/shower is Loren Cook Co. model 120C10D.
Ventilation Area Served
VERTICAL CIRCULATION
Ramp Comments: There is concrete ramp leading to the entry.
Fixed - Aluminum Frame; Double Glazing; Fixed - Aluminum Frame; Single Glazing;
Single Hung - Aluminum Frame; Double Glazing;
Gypsum Board
Exhaust Ventilation
Number of Deficiencies = 4
Windows6.
Floors1. Asbestos: Yes
Interior Walls2.
3. Number of Deficiencies = 1
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Cooling and heating are provided by two split system heat pumps. The outdoor units are Carrier 38YC048560 and Goodman GSZ140601KE. The indoor units are Carrier FB4AN048 and Goodman AVPTC61D14AC built in 05/2013 respectively. The systems include an outdoor air intake fans, Cook # 105-KSPD and use R22 refrigerant for Carrier and 410A for Goodman. The Carrier system has failed.
Comments:
HVAC
Heat1.
Split Heat Pump (Air
Source)
Single Duct None Electric Mechanical None Entire Building
Ventilation2. Number of Deficiencies = 1
Page: 34 of 90
Building: 0006 - VACANT DORMITORY E
Hot water is provided by a gas-fired, Rheem-Ruud hot water heater, model G91-300A, rated at 300,000 BTU/hr input, 272 gallons per hour recovery at 100F rise, and equipped with 91 gallons storage.
Comments:
Cast Iron None None
Electric Water Cooler Hose Bibb Lavatory Shower Sink Urinal Water Closet (Flush Valve)
Gas (Propane)
Wet None ABC Type Fire Extinguisher
Comments: Data from Hydraulic Design Card, posted at the sprinkler valve: Design water density: 0.10 gallons per minute per square foot. Design area: 999 square feet. Design water flow 244 gallons per minute.
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Split Heat Pump (Air
Source)
Single Duct Refrigerant Electric Mechanical None Entire Building
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Cooling and heating are provided by two split system heat pumps. The outdoor units are Carrier 38YC048560 and Goodman GSZ140601KE. The indoor units are Carrier FB4AN048 and Goodman AVPTC61D14AC built in 05/2013 respectively. The systems include an outdoor air intake fans, Cook # 105-KSPD and use R22 refrigerant for Carrier and 410A for Goodman. The Carrier system has failed.
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2. Number of Deficiencies = 1
Fixtures3. Number of Deficiencies = 1
Fuel Distribution4.
Page: 38 of 90
Building: 0007 - EDUCATION
INTERIOR FINISH
Carpet Ceramic Tile Concrete Quarry Tile
CMU Ceramic Tile Plaster Plywood Wood Paneling
Storefront - Aluminum Frame Metal Unit - Metal Frame
Wood Unit - Metal Frame Metal Unit - Wood Frame
Wood Unit - Wood Frame
VERTICAL CIRCULATION
Ramp Comments: There are concrete ramps leading to the entries.
Fixed - Aluminum Frame; Double Glazing; Fixed - Wood Frame; Single Glazing;
Sliding - Aluminum Frame; Double Glazing; Sliding - Aluminum Frame; Single Glazing;
Acoustical Tile Gypsum Board
Windows6.
Floors1.
Interior Walls2. Number of Deficiencies = 1
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Heating and cooling are provided by three, packaged, rooftop, heat pumps with electric back-up heat.
One is a Carrier model 50HJQ012, 10 ton capacity, manufactured in December 2009, and utilizing R- 22 refrigerant.. One is a Trane model WSC090E3, 7-1/2 ton capacity, manufactured in November 2010, and utilizing R-410A refrigerant. One is a Trane model WSC090E3, 7-1/2 ton capacity, manufactured in June 2012, and utilizing R-410A refrigerant.
Comments:
HVAC
Heat1.
Packaged Heat Pump (Air
Source)
Single Duct None Electric Mechanical None Entire Building
Page: 39 of 90
Building: 0007 - EDUCATION
Mechanical Restroom
Domestic hot water is provided by an instantaneous type electric hot water heater manufactured by Titan # N-120, 11.8 kW and located in the mechanical room.
Comments:
Cast Iron None None
Electric Water Cooler Hose Bibb Lavatory Sink Urinal Water Closet (Tank)
None
None None ABC Type Fire Extinguisher
Ventilation Area Served
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Packaged Heat Pump (Air
Source)
Single Duct None Electric Mechanical None Entire Building
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Exhaust Ventilation
Heating and cooling are provided by three, packaged, rooftop, heat pumps with electric back-up heat.
One is a Carrier model 50HJQ012, 10 ton capacity, manufactured in December 2009, and utilizing R- 22 refrigerant.. One is a Trane model WSC090E3, 7-1/2 ton capacity, manufactured in November 2010, and utilizing R-410A refrigerant. One is a Trane model WSC090E3, 7-1/2 ton capacity, manufactured in June 2012, and utilizing R-410A refrigerant.
Comments:
Ventilation2.
System Type
Number of Deficiencies = 1
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2. Number of Deficiencies = 2
Fixtures3. Number of Deficiencies = 2
Fuel Distribution4.
Page: 72 of 90
Building: 0015 - WELLNESS CENTER
INTERIOR FINISH
Carpet Vinyl Tile
Drywall Wood Paneling
Metal Unit - Metal Frame Wood Storefront - Wood Frame
Wood Unit - Wood Frame
Mechanical Restroom
Ventilation Area Served
VERTICAL CIRCULATION
Ramp Comments: There is concrete ramp leading to the entry.
Casement - Aluminum Frame; Double Glazing; Fixed - Wood Frame; Single Glazing;
Gypsum Board
Exhaust Ventilation
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Heating and cooling are provided by a Trane split-system heat pump. The indoor unit is Trane model 4FWCA061. The outdoor unit is Trane model 4TWB3048. The 4 ton system was manufactured in May, 2013, and utilizes R-410A refrigerant.
Comments:
HVAC
Heat1.
Packaged Heat Pump (Air
Source)
Split Heat Pump (Air
Source)
Through-The- Wall Unit
Single Duct
None
Refrigerant
Electric
Electric
Mechanical
Mechanical
None
None
Offices
Entire Building
Page: 73 of 90
Building: 0015 - WELLNESS CENTER
Domestic hot water is provided by a 40 gallon electric water heater with upper and lower elements rated at 4500W each, model AOS-EES-40-910.
Comments:
Cast Iron None None
Electric Water Cooler Hose Bibb Lavatory Sink Urinal Water Closet (Tank)
None
None None ABC Type Fire Extinguisher
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Packaged Heat Pump (Air
Source)
Split Direct Expansion (Air
Source)
Through-The- Wall Unit
Single Duct
None
Refrigerant
Electric
Electric
Mechanical
Mechanical
None
None
Offices
Entire Building
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Heating and cooling are provided by a Trane split-system heat pump. The indoor unit is Trane model 4FWCA061. The outdoor unit is Trane model 4TWB3048. The 4 ton system was manufactured in May, 2013, and utilizes R-410A refrigerant.
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2. Number of Deficiencies = 1
Fixtures3.
Fuel Distribution4.
3. Number of Deficiencies = 1Air Conditioning
OCO Deficiencies
124666-Vacant Dorm D Bldg 5
Two air intake fans that require service are located within 10 feet of a roof edge (or open side of a walking surface) more than 30 inches above the floor, roof, or grade below. (IBC, 2015, 1015.6 and IMC, 2015, 304.11)
Provide a guard that extends at least 42 inches above the edge of the elevated surface and extends at least 30 inches beyond end of each fan. The guard will be constructed so as to prevent the passage of a 21 inch diameter sphere. Guards will be constructed to resist a load of 50 pounds per linear foot applied in any direction at the top and to transfer this load through the supports to the building structure. The guard will also be designed to resist a 200 pound concentrated load applied in any direction at the top and to transfer this load through the supports to the building structure. Design for the 200 pound concentrated load is not concurrent with the distributed load. Properly seal and waterproof any roofing membrane penetrations.
124668-Vacant Dorm 8 Bldg 6
Two air intake fans that require service are located within 10 feet of a roof edge (or open side of a walking surface) more than 30 inches above the floor, roof, or grade below. (IBC, 2015, 1015.6 and IMC, 2015, 304.11)
Provide a guard that extends at least 42 inches above the edge of the elevated surface and extends at least 30 inches beyond end of each fan. The guard will be constructed so as to prevent the passage of a 21 inch diameter sphere. Guards will be constructed to resist a load of 50 pounds per linear foot applied in any direction at the top and to transfer this load through the supports to the building structure. The guard will also be designed to resist a 200 pound concentrated load applied in any direction at the top and to transfer this load through the supports to the building structure. Design for the 200 pound concentrated load is not concurrent with the distributed load. Properly seal and waterproof any roofing membrane penetrations.
124952-Administration Bldg 1
The packaged rooftop HVAC unit was installed without the outdoor air intake kits typically installed on them. This is in violation of the building code. Furthermore, it does not provide make-up air to equipment such as shower/restroom exhaust fans, and clothes dryers that are required to exhaust air to the outdoors.
(IMC, 2018, 403.2)
The packaged rooftop HVAC unit was installed without the outdoor air intake kits typically installed on them. This decreases indoor air quality in this highly occupied building. This is in violation of the building code. Furthermore, it does not provide make-up air to equipment such as shower/restroom exhaust fans, and clothes dryers that are required to exhaust air to the outdoors. (IMC, 2018, 403.2)
124959-Administration Bldg 1
Indoor air quality is poor because of a lack of adequate ventilation. Natural ventilation is not introducing sufficient outdoor air because the building is very tightly constructed and it is not practical to open the windows during extreme conditions. The building's mechanical ventilation is not operational. (IMC 2018, 403.2)
Retain a licensed HVAC design-build consultant to calculate the building outdoor air requirement and provide outdoor air to the return air plenum by making the outdoor air fan functional. Rebalance the fan to provide the required code approved outdoor air to the building.
124965-Dormitory B Bldg 3
Indoor air quality is poor because of a lack of adequate ventilation. Natural ventilation is not introducing sufficient outdoor air because the building is very tightly constructed and it is not practical to open the windows during extreme conditions. The building's mechanical ventilation is not operational. (IMC 2018, 403.2)
Retain a licensed HVAC design-build consultant to calculate the building outdoor air requirement and provide outdoor air to the return air plenum by making the outdoor air fan functional. Rebalance the fan to provide the required code approved outdoor air to the building.
124970-Dormitory B Bldg 3
Indoor air quality is poor because of a lack of adequate ventilation. Natural ventilation is not introducing sufficient outdoor air because the building is very tightly constructed and it is not practical to open the windows during extreme conditions. The building's mechanical ventilation is not operational. (IMC 2018, 403.2)
Retain a licensed HVAC design-build consultant to calculate the building outdoor air requirement and provide outdoor air to the return air plenum by making the outdoor air
124973-Dormitory E Bldg 6
Indoor air quality is poor because of a lack of adequate ventilation. Natural ventilation is not introducing sufficient outdoor air because the building is very tightly constructed and it is not practical to open the windows during extreme conditions. The building's mechanical ventilation is not operational. (IMC 2018, 403.2)
Retain a licensed HVAC design-build consultant to calculate the building outdoor air requirement and provide outdoor air to the return air plenum by making the outdoor air
124979-Education Bldg 7
The packaged rooftop HVAC units ware installed without the typically included outdoor air intake kits. This condition decreases indoor air quality in this frequently occupied building which is a violation of the building code. Furthermore, the units do not provide make-up air to standard equipment pieces such as shower/restroom exhaust fans, and clothes dryers that are required to exhaust air to the outdoors. (IMC 2018, 403.2)
Retain a certified consulting HVAC design firm to calculate the building outside air requirement. Contact the unit manufacturer, purchase and install the outdoor air kits on the RTU. Rebalance unit to have the code approved quantity of outdoor air in the system.
124994-Wellness Bldg 15
The packaged rooftop HVAC units ware installed without the typically included outdoor air intake kits. This condition decreases indoor air quality in this frequently occupied building which is a violation of the building code. Furthermore, the units do not provide make-up air to standard equipment pieces such as shower/restroom exhaust fans, and clothes dryers that are required to exhaust air to the outdoors. (IMC 2018, 403.2)
Procure the services of a licensed mechanical design build contractor to calculate the building outside air requirement and provide outdoor air to the return air plenum.
Rebalance fan to provide the required code approved outdoor air to the building.
| Vicinity Map-OCO |
| SitePlan-OCO |
| OconalufteeFloorPlans |
| OconalufteeEquipment Sheets |