MC AE CivilMech-OCO Attachments.pdf

PDF 875 KB Posted

Attached to
A&E Projects - JC Multi-Center East
Solicitation number
12970224R0055
Issued by

About this file

This document is a solicitation for Architectural and Engineering (A&E) services from the Department of Agriculture Forest Service for the "A&E Projects - JC Multi-Center East" project. The solicitation is requesting Standard Form (SF) 330 submissions from qualified A&E firms by August 27, 2024 in order to select the most highly rated firms for potential discussions.

The project consists of five base items across five different Job Corps Civilian Conservation Center locations: Jacobs Creek (JAC), Lyndon B. Johnson (LBJ), Oconaluftee (OCO), Schenck (SCH), and Frenchburg (FRE). The work includes tasks such as egress improvements, gym and drainage, HVAC upgrades, and lift station generator installations. This is a 100% Total Small Business Set-Aside solicitation under NAICS code 541310 - Architectural Services. Interested firms are instructed to submit questions via email no later than five calendar days prior to the closing date.

View the file

Other files

File Type Posted
MC AE CivilMech-JAC Attachments.pdf PDF
MC AE CivilMech-LBJ Attachments.pdf PDF
Location Map.pdf PDF
MC AE CivilMech-SCH Attachments.pdf PDF
MC AE CivilMech-FRE Attachments.pdf PDF
010150_SOW_MC_AE_Civil-Mech.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CHEROKEE, NORTH CAROLINA

OCONALUFTEE

CCC

OCONALUFTEE

CIVILIAN CONSERVATION CENTER

20 MI10 0

Building Descriptions Date: 06/27/2018Center : Oconaluftee (00423) Page: 2 of 90

Building: 0001 - ADMINISTRATION

INTERIOR FINISH

Carpet Ceramic Tile Concrete Wood

Ceramic Tile Drywall Plaster Wood Paneling

Storefront - Aluminum Frame Wood Unit - Metal Frame

Wood Unit - Wood Frame

Mechanical Restroom

Ventilation Area Served

VERTICAL CIRCULATION

Ramp Comments: There are concrete ramps leading to the entries.

Fixed - Wood Frame; Single Glazing; Sliding - Wood Frame; Single Glazing;

Acoustical Tile Gypsum Board

Exhaust Ventilation

Number of Deficiencies = 2

Number of Deficiencies = 1

Windows6.

Floors1.

Interior Walls2.

3.

Interior Doors4.

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Heating and cooling is provided by a Trane 10 ton packaged, rooftop heat pump, with electric backup heat model #WSC120ER0A08 with R410A refrigerant, manufactured in 01/2011

Comments:

HVAC

Heat1.

Packaged Heat Pump (Air

Source)

Single Duct None Electric Mechanical None Entire Building

Ventilation2. Number of Deficiencies = 2

Ceilings

Page: 3 of 90

Building: 0001 - ADMINISTRATION

Domestic hot water is provided by a tankless electric water heater, Marley model # ECO110, with 11kW heating element.

Comments:

Cast Iron None None

Electric Water Cooler Hose Bibb Lavatory Sink Water Closet (Tank)

None

None None ABC Type Fire Extinguisher

Copper Copper Electric None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Split Direct Expansion (Air

Source)

Packaged Heat Pump (Air

Source)

Fan Coil

Single Duct

Refrigerant

None

Electronic

Electric

Natural

Mechanical

None

None

Equipment Room

Entire Building

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

Mitsubishi, 1-1/2 ton mini-split, cooling only system, model MSY-GE18, serves IT data room.

Heating and cooling is provided by a Trane 10 ton packaged, rooftop heat pump, with electric backup heat model #WSC120ER0A08 with R410A refrigerant, manufactured in 01/2011

Comments:

Comments:

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

FIRE PROTECTION

3. Air Conditioning

Page: 7 of 90

Building: 0002 - DORMITORY A

Comments: Fixed, single pane windows are interior windows.

INTERIOR FINISH

Carpet Ceramic Tile Concrete

Ceramic Tile Drywall

Metal Unit - Metal Frame

Mechanical

Mechanical

Entire Building

Toilet/Shower

Comments:

Comments:

The building is equipped with air intakes at the eaves. There are two exhaust fans on the roof to exhaust the space under the roof. They are manufactured by Loren Cook.

The exhaust fan for the toilet/shower is Loren Cook Co. model 120C10D.

Ventilation Area Served

VERTICAL CIRCULATION

Ramp Comments: There are concrete ramps leading to the entries.

Fixed - Aluminum Frame; Double Glazing; Fixed - Aluminum Frame; Single Glazing;

Single Hung - Aluminum Frame; Double Glazing;

Gypsum Board

Exhaust Ventilation

Number of Deficiencies = 3

Windows6.

Floors1.

Interior Walls2.

3.

Interior Doors4.

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Cooling and heating are provided by two split system heat pumps. The outdoor units are Carrier 38YC048560 and Carrier 38YC060560. The indoor units are Carrier FB4AN048 and FB4AN060 respectively. The systems include an outdoor air intake fans, Cook # 105-KSPD and use R22 refrigerant.

Comments:

HVAC

Heat1.

Split Heat Pump (Air

Source)

Single Duct Refrigerant Electric Mechanical None Entire Building

Page: 8 of 90

Building: 0002 - DORMITORY A

Hot water is provided by a gas-fired, Rheem-Ruud water heater, model G91-300A, rated at 300 MBH input and equipped with 91 gallon storage.

Comments:

Cast Iron None None

Electric Water Cooler Hose Bibb Lavatory Shower Sink Water Closet (Flush Valve)

Comments: There is one clothes washer and one clothes dryer in the toilet/shower room.

Gas (Propane)

Wet None ABC Type Fire Extinguisher

Comments: Data from Hydraulic Design Card, posted at the sprinkler valve: Design water density: 0.10 gallons per minute per square foot. Design area: 999 square feet. Design water flow 244 gallons per minute.

Copper Copper Gas-Fired None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Split Heat Pump (Air

Source)

Single Duct Refrigerant Electric Mechanical None Entire Building

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

Cooling and heating are provided by two split system heat pumps. The outdoor units are Carrier 38YC048560 and Carrier 38YC060560. The indoor units are Carrier FB4AN048 and FB4AN060 respectively. The systems include an outdoor air intake fans, Cook # 105-KSPD and use R22 refrigerant.

Comments:

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

Number of Deficiencies = 2FIRE PROTECTION

Page: 18 of 90

Building: 0003 - DORMITORY B

Comments: Fixed, single pane windows are interior windows.

INTERIOR FINISH

Carpet Ceramic Tile Concrete

Ceramic Tile Drywall

Metal Unit - Metal Frame

Mechanical

Mechanical

Entire Building

Toilet/Shower

Comments:

Comments:

The building is equipped with air intakes at the eaves. There are two exhaust fans on the roof to exhaust the space under the roof. They are Loren Cook Co. 100C10DL.

The exhaust fan for the toilet/shower is Loren Cook Co. model 120C10D.

Ventilation Area Served

VERTICAL CIRCULATION

Ramp Comments: There are concrete ramps leading to the entries.

Fixed - Aluminum Frame; Double Glazing; Fixed - Aluminum Frame; Single Glazing;

Single Hung - Aluminum Frame; Double Glazing;

Gypsum Board

Exhaust Ventilation

Number of Deficiencies = 3

Windows6.

Floors1. Number of Deficiencies = 1

Interior Walls2.

3.

Interior Doors4.

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Cooling and heating are provided by two split system heat pumps. The outdoor units are Carrier 38YC048560 and Trane (no available information of the unit). The indoor units are Carrier FB4AN048 and Trane 4FWCA061A1000B built in 05/2013 respectively. The systems include an outdoor air intake fans, Cook # 105-KSPD and use R22 refrigerant for Carrier and 410A for Trane.

Comments:

HVAC

Heat1.

Split Heat Pump (Air

Source)

Single Duct Refrigerant Electric Mechanical None Entire Building

Page: 19 of 90

Building: 0003 - DORMITORY B

Hot water is provided by a gas-fired, Rheem-Ruud hot water heater, model G91-300A, rated at 300 MBH and equipped with 91 gallons storage.

Comments:

Cast Iron None None

Electric Water Cooler Hose Bibb Lavatory Shower Urinal Water Closet (Flush Valve)

Comments: There is one clothes washer and one clothes dryer in the toilet/shower room.

Gas (Propane)

Wet None ABC Type Fire Extinguisher

Comments: Data from Hydraulic Design Card, posted at the sprinkler valve: Design water density: 0.10 gallons per minute per square foot. Design area: 999 square feet. Design water flow 244 gallons per minute.

Copper Copper Gas-Fired None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Split Heat Pump (Air

Source)

Single Duct Refrigerant Electric Mechanical None Entire Building

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

Cooling and heating are provided by two split system heat pumps. The outdoor units are Carrier 38YC048560 and Trane (no available information of the unit). The indoor units are Carrier FB4AN048 and Trane 4FWCA061A1000B built in 05/2013 respectively. The systems include an outdoor air intake fans, Cook # 105-KSPD and use R22 refrigerant for Carrier and 410A for Trane.

Comments:

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

Number of Deficiencies = 1FIRE PROTECTION

Page: 28 of 90

Building: 0005 - VACANT DORMITORY D

Comments: Fixed, single pane windows are interior windows.

INTERIOR FINISH

Carpet Ceramic Tile Concrete

Ceramic Tile Drywall

Metal Unit - Metal Frame

Mechanical

Mechanical

Entire Building

Toilet/Shower

Comments:

Comments:

The building is equipped with air intakes at the eaves. There are two exhaust fans on the roof to exhaust the space under the roof. They are Loren Cook Co. 100C10DL.

The exhaust fan for the toilet/shower is Loren Cook Co. model 120C10D.

Ventilation Area Served

VERTICAL CIRCULATION

Ramp Comments: There is concrete ramp leading to the entrance.

Fixed - Aluminum Frame; Double Glazing; Fixed - Aluminum Frame; Single Glazing;

Single Hung - Aluminum Frame; Double Glazing;

Gypsum Board

Exhaust Ventilation

Number of Deficiencies = 2

Windows6.

Floors1. Asbestos: Yes

Interior Walls2.

3. Asbestos: Yes

Interior Doors4.

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Cooling and heating are provided by two split system heat pumps. The outdoor units are Carrier 38YC048560 and Carrier 38YC060560. The indoor units are Carrier FB4AN048 and FB4AN060 respectively. The systems include an outdoor air intake fans, Cook # 105-KSPD and use R22 refrigerant.

Comments:

HVAC

Heat1. Asbestos: Yes

Split Heat Pump (Air

Source)

Single Duct Refrigerant Electric Mechanical None Entire Building

Page: 29 of 90

Building: 0005 - VACANT DORMITORY D

Hot water is provided by a gas-fired, Rheem-Ruud water heater, model G100-310A, rated at 310 MBH input and equipped with 100 gallon storage.

Comments:

Cast Iron None None

Electric Water Cooler Hose Bibb Lavatory Service Sink Shower Urinal Water Closet (Flush Valve)

Comments: There is one clothes washer and one clothes dryer in the toilet/shower room.

Gas (Propane)

Wet None ABC Type Fire Extinguisher

Comments: Data from Hydraulic Design Card, posted at the sprinkler valve: Design water density: 0.10 gallons per minute per square foot. Design area: 999 square feet. Design water flow 244 gallons per minute.

Copper Copper Gas-Fired None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Split Heat Pump (Air

Source)

Single Duct None Electric Mechanical None Entire Building

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

Cooling and heating are provided by two split system heat pumps. The outdoor units are Carrier 38YC048560 and Carrier 38YC060560. The indoor units are Carrier FB4AN048 and FB4AN060 respectively. The systems include an outdoor air intake fans, Cook # 105-KSPD and use R22 refrigerant.

Comments:

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

Page: 33 of 90

Building: 0006 - VACANT DORMITORY E

Comments: Fixed, single pane windows are interior windows.

INTERIOR FINISH

Carpet Ceramic Tile Concrete

Ceramic Tile Drywall

Metal Unit - Metal Frame

Mechanical

Mechanical

Entire Building

Toilet/Shower

Comments:

Comments:

The building is equipped with air intakes at the eaves. There are two exhaust fans on the roof to exhaust the space under the roof. They are Loren Cook Co. 100C10DL.

The exhaust fan for the toilet/shower is Loren Cook Co. model 120C10D.

Ventilation Area Served

VERTICAL CIRCULATION

Ramp Comments: There is concrete ramp leading to the entry.

Fixed - Aluminum Frame; Double Glazing; Fixed - Aluminum Frame; Single Glazing;

Single Hung - Aluminum Frame; Double Glazing;

Gypsum Board

Exhaust Ventilation

Number of Deficiencies = 4

Windows6.

Floors1. Asbestos: Yes

Interior Walls2.

3. Number of Deficiencies = 1

Interior Doors4.

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Cooling and heating are provided by two split system heat pumps. The outdoor units are Carrier 38YC048560 and Goodman GSZ140601KE. The indoor units are Carrier FB4AN048 and Goodman AVPTC61D14AC built in 05/2013 respectively. The systems include an outdoor air intake fans, Cook # 105-KSPD and use R22 refrigerant for Carrier and 410A for Goodman. The Carrier system has failed.

Comments:

HVAC

Heat1.

Split Heat Pump (Air

Source)

Single Duct None Electric Mechanical None Entire Building

Ventilation2. Number of Deficiencies = 1

Page: 34 of 90

Building: 0006 - VACANT DORMITORY E

Hot water is provided by a gas-fired, Rheem-Ruud hot water heater, model G91-300A, rated at 300,000 BTU/hr input, 272 gallons per hour recovery at 100F rise, and equipped with 91 gallons storage.

Comments:

Cast Iron None None

Electric Water Cooler Hose Bibb Lavatory Shower Sink Urinal Water Closet (Flush Valve)

Gas (Propane)

Wet None ABC Type Fire Extinguisher

Comments: Data from Hydraulic Design Card, posted at the sprinkler valve: Design water density: 0.10 gallons per minute per square foot. Design area: 999 square feet. Design water flow 244 gallons per minute.

Copper Copper Gas-Fired None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Split Heat Pump (Air

Source)

Single Duct Refrigerant Electric Mechanical None Entire Building

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

Cooling and heating are provided by two split system heat pumps. The outdoor units are Carrier 38YC048560 and Goodman GSZ140601KE. The indoor units are Carrier FB4AN048 and Goodman AVPTC61D14AC built in 05/2013 respectively. The systems include an outdoor air intake fans, Cook # 105-KSPD and use R22 refrigerant for Carrier and 410A for Goodman. The Carrier system has failed.

Comments:

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Water Distribution1.

Sanitary Distribution2. Number of Deficiencies = 1

Fixtures3. Number of Deficiencies = 1

Fuel Distribution4.

Page: 38 of 90

Building: 0007 - EDUCATION

INTERIOR FINISH

Carpet Ceramic Tile Concrete Quarry Tile

CMU Ceramic Tile Plaster Plywood Wood Paneling

Storefront - Aluminum Frame Metal Unit - Metal Frame

Wood Unit - Metal Frame Metal Unit - Wood Frame

Wood Unit - Wood Frame

VERTICAL CIRCULATION

Ramp Comments: There are concrete ramps leading to the entries.

Fixed - Aluminum Frame; Double Glazing; Fixed - Wood Frame; Single Glazing;

Sliding - Aluminum Frame; Double Glazing; Sliding - Aluminum Frame; Single Glazing;

Acoustical Tile Gypsum Board

Windows6.

Floors1.

Interior Walls2. Number of Deficiencies = 1

3.

Interior Doors4.

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Heating and cooling are provided by three, packaged, rooftop, heat pumps with electric back-up heat.

One is a Carrier model 50HJQ012, 10 ton capacity, manufactured in December 2009, and utilizing R- 22 refrigerant.. One is a Trane model WSC090E3, 7-1/2 ton capacity, manufactured in November 2010, and utilizing R-410A refrigerant. One is a Trane model WSC090E3, 7-1/2 ton capacity, manufactured in June 2012, and utilizing R-410A refrigerant.

Comments:

HVAC

Heat1.

Packaged Heat Pump (Air

Source)

Single Duct None Electric Mechanical None Entire Building

Page: 39 of 90

Building: 0007 - EDUCATION

Mechanical Restroom

Domestic hot water is provided by an instantaneous type electric hot water heater manufactured by Titan # N-120, 11.8 kW and located in the mechanical room.

Comments:

Cast Iron None None

Electric Water Cooler Hose Bibb Lavatory Sink Urinal Water Closet (Tank)

None

None None ABC Type Fire Extinguisher

Ventilation Area Served

Copper Copper Electric None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Packaged Heat Pump (Air

Source)

Single Duct None Electric Mechanical None Entire Building

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

Exhaust Ventilation

Heating and cooling are provided by three, packaged, rooftop, heat pumps with electric back-up heat.

One is a Carrier model 50HJQ012, 10 ton capacity, manufactured in December 2009, and utilizing R- 22 refrigerant.. One is a Trane model WSC090E3, 7-1/2 ton capacity, manufactured in November 2010, and utilizing R-410A refrigerant. One is a Trane model WSC090E3, 7-1/2 ton capacity, manufactured in June 2012, and utilizing R-410A refrigerant.

Comments:

Ventilation2.

System Type

Number of Deficiencies = 1

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Water Distribution1.

Sanitary Distribution2. Number of Deficiencies = 2

Fixtures3. Number of Deficiencies = 2

Fuel Distribution4.

Page: 72 of 90

Building: 0015 - WELLNESS CENTER

INTERIOR FINISH

Carpet Vinyl Tile

Drywall Wood Paneling

Metal Unit - Metal Frame Wood Storefront - Wood Frame

Wood Unit - Wood Frame

Mechanical Restroom

Ventilation Area Served

VERTICAL CIRCULATION

Ramp Comments: There is concrete ramp leading to the entry.

Casement - Aluminum Frame; Double Glazing; Fixed - Wood Frame; Single Glazing;

Gypsum Board

Exhaust Ventilation

Windows6.

Floors1.

Interior Walls2.

3.

Interior Doors4.

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Heating and cooling are provided by a Trane split-system heat pump. The indoor unit is Trane model 4FWCA061. The outdoor unit is Trane model 4TWB3048. The 4 ton system was manufactured in May, 2013, and utilizes R-410A refrigerant.

Comments:

HVAC

Heat1.

Packaged Heat Pump (Air

Source)

Split Heat Pump (Air

Source)

Through-The- Wall Unit

Single Duct

None

Refrigerant

Electric

Electric

Mechanical

Mechanical

None

None

Offices

Entire Building

Page: 73 of 90

Building: 0015 - WELLNESS CENTER

Domestic hot water is provided by a 40 gallon electric water heater with upper and lower elements rated at 4500W each, model AOS-EES-40-910.

Comments:

Cast Iron None None

Electric Water Cooler Hose Bibb Lavatory Sink Urinal Water Closet (Tank)

None

None None ABC Type Fire Extinguisher

Copper Copper Electric None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Packaged Heat Pump (Air

Source)

Split Direct Expansion (Air

Source)

Through-The- Wall Unit

Single Duct

None

Refrigerant

Electric

Electric

Mechanical

Mechanical

None

None

Offices

Entire Building

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

Heating and cooling are provided by a Trane split-system heat pump. The indoor unit is Trane model 4FWCA061. The outdoor unit is Trane model 4TWB3048. The 4 ton system was manufactured in May, 2013, and utilizes R-410A refrigerant.

Comments:

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Water Distribution1.

Sanitary Distribution2. Number of Deficiencies = 1

Fixtures3.

Fuel Distribution4.

3. Number of Deficiencies = 1Air Conditioning

OCO Deficiencies

124666-Vacant Dorm D Bldg 5

Two air intake fans that require service are located within 10 feet of a roof edge (or open side of a walking surface) more than 30 inches above the floor, roof, or grade below. (IBC, 2015, 1015.6 and IMC, 2015, 304.11)

Provide a guard that extends at least 42 inches above the edge of the elevated surface and extends at least 30 inches beyond end of each fan. The guard will be constructed so as to prevent the passage of a 21 inch diameter sphere. Guards will be constructed to resist a load of 50 pounds per linear foot applied in any direction at the top and to transfer this load through the supports to the building structure. The guard will also be designed to resist a 200 pound concentrated load applied in any direction at the top and to transfer this load through the supports to the building structure. Design for the 200 pound concentrated load is not concurrent with the distributed load. Properly seal and waterproof any roofing membrane penetrations.

124668-Vacant Dorm 8 Bldg 6

Two air intake fans that require service are located within 10 feet of a roof edge (or open side of a walking surface) more than 30 inches above the floor, roof, or grade below. (IBC, 2015, 1015.6 and IMC, 2015, 304.11)

Provide a guard that extends at least 42 inches above the edge of the elevated surface and extends at least 30 inches beyond end of each fan. The guard will be constructed so as to prevent the passage of a 21 inch diameter sphere. Guards will be constructed to resist a load of 50 pounds per linear foot applied in any direction at the top and to transfer this load through the supports to the building structure. The guard will also be designed to resist a 200 pound concentrated load applied in any direction at the top and to transfer this load through the supports to the building structure. Design for the 200 pound concentrated load is not concurrent with the distributed load. Properly seal and waterproof any roofing membrane penetrations.

124952-Administration Bldg 1

The packaged rooftop HVAC unit was installed without the outdoor air intake kits typically installed on them. This is in violation of the building code. Furthermore, it does not provide make-up air to equipment such as shower/restroom exhaust fans, and clothes dryers that are required to exhaust air to the outdoors.

(IMC, 2018, 403.2)

The packaged rooftop HVAC unit was installed without the outdoor air intake kits typically installed on them. This decreases indoor air quality in this highly occupied building. This is in violation of the building code. Furthermore, it does not provide make-up air to equipment such as shower/restroom exhaust fans, and clothes dryers that are required to exhaust air to the outdoors. (IMC, 2018, 403.2)

124959-Administration Bldg 1

Indoor air quality is poor because of a lack of adequate ventilation. Natural ventilation is not introducing sufficient outdoor air because the building is very tightly constructed and it is not practical to open the windows during extreme conditions. The building's mechanical ventilation is not operational. (IMC 2018, 403.2)

Retain a licensed HVAC design-build consultant to calculate the building outdoor air requirement and provide outdoor air to the return air plenum by making the outdoor air fan functional. Rebalance the fan to provide the required code approved outdoor air to the building.

124965-Dormitory B Bldg 3

Indoor air quality is poor because of a lack of adequate ventilation. Natural ventilation is not introducing sufficient outdoor air because the building is very tightly constructed and it is not practical to open the windows during extreme conditions. The building's mechanical ventilation is not operational. (IMC 2018, 403.2)

Retain a licensed HVAC design-build consultant to calculate the building outdoor air requirement and provide outdoor air to the return air plenum by making the outdoor air fan functional. Rebalance the fan to provide the required code approved outdoor air to the building.

124970-Dormitory B Bldg 3

Indoor air quality is poor because of a lack of adequate ventilation. Natural ventilation is not introducing sufficient outdoor air because the building is very tightly constructed and it is not practical to open the windows during extreme conditions. The building's mechanical ventilation is not operational. (IMC 2018, 403.2)

Retain a licensed HVAC design-build consultant to calculate the building outdoor air requirement and provide outdoor air to the return air plenum by making the outdoor air

124973-Dormitory E Bldg 6

Indoor air quality is poor because of a lack of adequate ventilation. Natural ventilation is not introducing sufficient outdoor air because the building is very tightly constructed and it is not practical to open the windows during extreme conditions. The building's mechanical ventilation is not operational. (IMC 2018, 403.2)

Retain a licensed HVAC design-build consultant to calculate the building outdoor air requirement and provide outdoor air to the return air plenum by making the outdoor air

124979-Education Bldg 7

The packaged rooftop HVAC units ware installed without the typically included outdoor air intake kits. This condition decreases indoor air quality in this frequently occupied building which is a violation of the building code. Furthermore, the units do not provide make-up air to standard equipment pieces such as shower/restroom exhaust fans, and clothes dryers that are required to exhaust air to the outdoors. (IMC 2018, 403.2)

Retain a certified consulting HVAC design firm to calculate the building outside air requirement. Contact the unit manufacturer, purchase and install the outdoor air kits on the RTU. Rebalance unit to have the code approved quantity of outdoor air in the system.

124994-Wellness Bldg 15

The packaged rooftop HVAC units ware installed without the typically included outdoor air intake kits. This condition decreases indoor air quality in this frequently occupied building which is a violation of the building code. Furthermore, the units do not provide make-up air to standard equipment pieces such as shower/restroom exhaust fans, and clothes dryers that are required to exhaust air to the outdoors. (IMC 2018, 403.2)

Procure the services of a licensed mechanical design build contractor to calculate the building outside air requirement and provide outdoor air to the return air plenum.

Rebalance fan to provide the required code approved outdoor air to the building.

Vicinity Map-OCO