Main Treasury 2453 New Office Drawings.pdf
PDF 12 MB Posted
- Attached to
- Main Treasury Demo Build Out 2453
- Solicitation number
- 2032H326R00020
About this file
This document is a 100% submission architectural drawing set for the renovation of Suite 2453 (second floor) in a federal office building located in Washington, DC. The project involves adding a private office, demolishing non-original partitions, repainting the entire suite, and replacing carpet.
The project scope includes constructing new partition walls using 3 5/8" 16 gauge steel studs with gypsum wall board and batt insulation, installing a new two-panel wood door with Frame Type F-1, and creating a vestibule addition. The building is listed on the National Register of Historic Places, requiring compliance with the Secretary of the Interior's Standards for historic preservation. All work must protect existing historic fabric including original plaster ceiling vaults, crown molding, and ceiling rib moldings. The drawings specify detailed wall framing elevations and sections, floor panel system alterations using Irvine-Tate Concore steel 24"x24" panels, door details, finishes schedules, and hardware specifications. Finishes include Benjamin Moore paint (Pure White, OC-17 for walls and ceilings; Semi-Gloss for FCU cabinets), 3/4" poplar baseboard, and Shaw Industries carpet tile (Style 24115 in Clay color). Hardware Type 1 includes Corbin Russwin locks (Series ML 2051, US 3 Bright Brass finish) with 4.5" hinges. The submission is dated April 28, 2026, with drawings prepared by Meridien Group, LLC under Prime A/E designation for GSA.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| MT 2453 QAs.xlsx | XLSX spreadsheet | |
| A001.pdf | ||
| Corporate Experience Worksheet.docx | DOCX document | |
| APU No. 26-01 - Attachment 2 - Fillable.pdf | ||
| 2032H326R00020.pdf | ||
| Wage Determination.pdf | ||
| Schedule MT2453.docx | DOCX document | |
| APU No. 26-01 - Attachment 1 - Fillable.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
G- 001
FEDERAL OFFICE BUILDING
DRAWING INDEX
GENERAL
ARCHITECTURAL
G-001 COVER SHEET 01 OF 21
G-002 NOTES, ABBREVIATIONS, AND SYMBOLS 02 OF 21
AD 101 EXISTING & DEMOLITION WALLS AND FLOOR SYSTEM FLOOR PLAN 03 OF 21
AD 102 EXISTING & DEMOLITION RCP 04 OF 21
AD 201 EXISTING & DEMOLITION SECTIONS/ INTERIOR ELEVATIONS 05 OF 21
AD 202 EXISTING & DEMOLITION SECTIONS/ INTERIOR ELEVATIONS 06 OF 21
A-101 NEW WORK FLOOR PLAN W/O AND W/ FURNITURE 07 OF 21
A-102 NEW WORK RCP 08 OF 21
A-103 NEW WORK FLOOR PANELS W/O AND W/ FURNITURE 09 OF 21
A-201 NEW WORK FRAMING ELEVATIONS AND SECTIONS 10 OF 21
A-202 NEW WORK FRAMING ELEVATIONS AND SECTIONS 11 OF 21
A-203 NEW WORK FRAMING ELEVATIONS AND SECTIONS 12 OF 21
A-204 NEW WORK FRAMING ELEVATIONS AND SECTIONS 13 OF 21
A-301 WALL TYPE A 14 OF 21
A-302 WALL TYPE B 15 OF 21
A-501 WALL FRAMING DETAILS 16 OF 21
A-502 FLOOR PANEL SYSTEM ALTERATIONS DETAILS 17 OF 21
A-503 DOOR DETAILS (DOOR FRAME F-1 & LEAF TYPE A) 18 OF 21
A-601 FINISHES NOTES AND SCHEDULE 19 OF 21
A-602 DOOR AND HARDWARE SCHEDULE, DOOR ELEVATIONS 20 OF 21
A-701 BASIS OF DESIGN CUT SHEETS DOOR AND HARDWARE 21 OF 21
COVER SHEET
100% submission
04-28-2026
FOR REVIEW
KEY PLAN
PROJECT ADDRESS:
OCCUPANCY CLASSIFICATION: B,
BUILDING SPRINKLERS: AUTOMATIC SPRINKLER SYSTEM
HISTORIC OVERVIEW: THE BUILDING IS IN THE NATIONAL REGISTER OF HISTORIC PLACES
A. ALL WORK NECESSARY TO ADD A PRIVATE OFFICE IN SUITE 2453 AFTER DEMOLISHING NON-ORIGINAL PARTITION
B. THE ENTIRE SUITE WILL BE REPAINTED AND THE CARPET WILL BE REPLACED AS WELL
N
W
PROJECT INFORMATION
WORK DESCRIPTION
REVIEW COMMENTS / NOTES
2ND FLOOR
NO
RT
H
RENOVATION OF SUITE 2453 AND ADDITION OF A NEW PRIVATE OFFICE
VESTIBULE 5436
E
S
OF
R
EV
IS
IO
N N
O
TE
S
GR
AP
HI
C
SC
AL
E
MARK DATE DESCRIPTION
AGF
CE
RT
IFI
CA
TIO
NS
SHEET SIZE:
SHEET
DISCIPLINE SHEET TYPE SEQUENCE
DRAWING NO.
DRAWING TITLE
FILE NAME
CHECKED BY
DRAWN BY DATE DRAFTED:
PROJECT NO.
GSA PM
SUB. DATE
SUBMISSION
DESCRIPTION
PROJECT
TITLE
BUILDING NOs.
OTHER
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
DR
AW
IN
G
PR
OJ
EC
T
BU
ILD
IN
G
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
CO
NT
RA
CT
OR
S
FLOOR NO.
FACILITY CODE
PROJECT
A/E TASK NO.
CONS. WORK
24 x 36
DC-
1 2 3 4 5
A
B
C
D
WASHINGTON, DC
MERIDIEN GROUP / CITADEL DCA
LSP
MERIDIEN GROUP, LLC
208 SOUTH KING ST. SUITE 303
LEESBURG, VA 20175
(703) 777-8285 www.meridiengroupllc.com
BARBARA CHOATE
100% SUBMISSION FOR REVIEW
KE
Y
PL
AN
1 2 3 4 5
04/14/2026
MT2453_26_004
28 APRIL 2026
FEDERAL OFFICE BUILDING
RENOVATION OF SECOND FLOOR SUITE
MT 2453 OFFICE RENOVATION
2ND FLOOR
SUITE
1. OMISSIONS FROM THE DRAWINGS OR SPECIFICATIONS OF THE DESCRIPTION OF DETAILS OF WORK WHICH ARE MANIFESTLY NECESSARY TO CARRY OUT THE INTENT OF THE DRAWINGS AND SPECIFICATIONS OR ARE CUSTOMARILY PERFORMED SHALL NOT RELIEVE THE CONTRACTOR FROM PERFORMING SUCH OMITTED OR MIS-DESCRIBED DETAILS OF WORK BUT SHALL BE PERFORMED AS IF FULLY AND CORRECTLY SET FROM AND
DESCRIBED IN THE DRAWINGS AND S SPECIFICATION
2. MANUFACTURER SPECIFIED WITHIN THE CONSTRUCTION DOCUMENTS ARE PROVIDED AS A MINIMUM PERFORMANCE CRITERIA, SUBSTITUTIONS WILL BE CONSIDERED IF COMPLAINT TO THE PERFORMANCE ESTABLISHED BY THE MANUFACTURER NOTED. BUILDING MATERIALS SUBSTANDARD TO THESE REQUIREMENTS WILL BE SUMMARILY REJECTED. ALL BUILDING COMPONENTS ARE TO BE HEAVY DUTY QUALITY AND BE FOR ABUSIVE RESISTANCE INSTALLATION. BUILDING COMPONENTS SPECIFIED HEREIN THAT DO NOT MEET THE HEAVY DUTY-ABUSIVE ENVIRONMENTAL CRITERIA MUST BE
BROUGHT TO THE ATTENTION OF THE BUILDING REPRESENTATIVE AND WILL BE RE-SPECIFIED
3. BY THE SUBMISSION OF A BID, THE SUB CONTRACTOR REPRESENTS THAT HE HAS VISITED THE SITE AND HAS FAMILIARIZED HIMSELF/HERSELF WITH
THE CONDITIONS UNDER WHICH THE WORK IS TO BE PERFORMED
4. DRAWINGS ARE NOT TO BE SCALED FOR DIMENSIONS AND/OR SIZE. VERIFY ALL DIMENSIONS BEFORE PROCEEDING AND OBTAIN MEASUREMENTS AT THE JOB FOR ALL WORK REQUIRED TO BE ACCURATELY FITTED TO THE BUILDING. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE ACCURACY OF
ALL SUCH MEASUREMENTS AND FOR THE PRECISE FITTING OF THE WORK
5. IF CONFLICTS ARE DISCOVERED AT ANY TIME BETWEEN THE ENGINEERING AND ARCHITECTURAL DRAWINGS, THE COR SHALL BE CONTACTED AT ONCE TO RESOLVE THE PROBLEM. IF THE COR IS NOT CONTACTED, THE CONTRACTOR SHALL ACCEPT THE RESPONSIBILITY TO CORRECT ANY AND ALL SUCH
WORK NOT IN A COORDINATE WITH THE ARCHITECTURAL DRAWINGS
6. CHANGES TO THE DRAWINGS (ADDITIONS, DELETIONS OR ALTERATIONS) THAT MIGHT CONSTITUTE A CHANGE ORDER MUST BE SUBMITTED IN WRITING TO THE COR FOR APPROVAL, OTHERWISE CONTRACTOR WOULD UNDERTAKE SUCH WORK AT HIS OWN RISK AND WORK MIGHT HAVE TO BE REVERSED
AT CONTRACTOR'S OWN COST
7. BEST PRACTICES, METHODS AND MATERIALS, MUST BE FOLLOWED AT ALL TIMES. ANY ITEM NOT SPECIFICALLY LISTED OR SHOWN ON THE CONTRACT DOCUMENTS BUT NECESSARY FOR THE COMPLETION OF THE PROJECT, SHALL BE CONSIDERED PART OF THE CONTRACT'S SCOPE OF WORK
8. THE G. C. & ALL SUB-CONTRACTOR SHALL SUBMIT TO COR SUBMITTALS AND SHOP DRAWINGS FOR REVIEW PRIOR TO START OF CONSTRUCTION.
9. UPON COMPLETION OF THE INSTALLATION, REMOVE ALL DEBRIS FROM THE BUILDING CREATED BY THE WORK PROVIDED UNDER THIS CONTRACT AND LEAVE ALL AREAS CLEAN. REMOVE ANY SOILED SPOTS FROM THE FACE OF THE CARPET OR OTHER FINISH SURFACES USING PROCESSES RECOMMENDED BY THE MANUFACTURER AND IN A MANNER ACCEPTABLE TO THE GOVERNMENT. REPLACE ANY AREAS OF CARPET OR FINISH SURFACES WHERE CLEANING HAS FAIL TO RESTORE THE APPEARANCE AND QUALITY SATISFACTORILY, AS DETERMINED BY THE GOVERNMENT.
10. WHERE THE G. C. IS INSTRUCTED TO ALIGN A PARTITION WITH TWO OR MORE COLUMNS AND THE COLUMNS ARE DISCOVE- RED TO BE OF UNEQUAL SIZE, THE LARGER OF THE COLUMNS SHALL DETERMINE THE LOCATION OF THE PARTITION. THIS WILL ALSO APPLY TO COLUMNS AND CORE WALLS.
11. AREA OF WORK MUST BE ISOLATED FROM THE REST OF THE FLOOR. PROTECT ALL SURFACES, EQUIPMENT& FURNITURE PRIOR TO START OF WORK
12. PROTECT ALL GOVERNMENT PROPERTY ENCOUNTERED AT THE JOB SITE AGAINST DAMAGE. ALL DAMAGE CAUSED BY THE GC OR HIS SUB-CONTRACTORS DURING CONSTRUCTION SHALL BE REPAIRED OR REPLACED TO MATCH EXISTING AND TO THE SATISFACTION AND APPROVAL OF THE COR. PRE-EXISTING DAMAGE MUST BE REVIEWED AND ACKNOWLEDGED, IN WRITING BY THE GOVERNMENT AND ARCHITECT PRIOR TO COMMENCEMENT OF WORK. DAMAGE NOT DOCUMENTED PRIOR TO CONSTRUCTION START SHALL BE REPAIRED TO LIKE NEW CONDITION WITHOUT ADDITIONAL CHARGE TO THE GOVERNMENT.
13. WHEN IN PLACE, REMOVE ALL HVAC COVERS AS NEEDED. SEAL EXPOSED DUCTS AND VENTS TO PREVENT INTRODUCING DUST INTO THE SYSTEM. (REMOVED COVERS
MUST BE REINSTALLED AT END OF THE JOB)
14. THE CONTRACTOR SHALL CLEAN UP ALL ACTIVE WORK AREAS AFTER EACH DAY’S WORK. THE CONTRACTOR IS RESPONSIBLE FOR THE REMOVAL AND PROPER
DISPOSAL OF ALL WORK RELATED TRASH AND DEBRIS.
15. THE G. C. SHALL ENSURE THAT ALL PAINT HAS BEEN REMOVED FROM ALL NON-SCHEDULE PAINTED SURFACES PRIOR TO DELIVERY OF THE SPACE.
16. THE G. C. SHALL COORDINATE ALL WORK WITH FIELD CONDITIONS AND ALL OTHER TRADES INVOLVED AS REQUIRED
17. IF THERE IS A QUESTION AS TO THE ACCEPTABLE LEVEL OF QUALITY FOR THE INSTALLATION OF ANY MATERIALS, THE COR DECISION WILL BE FINAL
18. NEW DOOR HARDWARE, INCLUDING HINGES AND LOCK SETS, ARE TO BE MOUNTED AT ABA HEIGHTS U. N. O.
19. ALL CEILING REGISTERS, GRILLES, VENTS AND DIFFUSERS SHALL BE FACTORY FINISHED. IF PAINTING IS REQUIRED, PROVIDE ENAMEL FINISH
20. ALL J-BENDS AND OTHER GYPSUM METAL TRIM SHALL BE SPACKLE-BLENDED INTO THE ADJACENT SURFACE.
21. WHERE TWO OR MORE WALL SWITCHES OR DIMMERS OCCUR IN THE SAME LOCATION, THEY ARE TO RECEIVE A COMMON GANG PLATE WHOSE FINISH
IS TO MATCH THE BUILDING STANDARD SWITCH PLATE.
22. ALL PAINTED WALLS SHALL BE HAVE A LEVEL 4 FINISH: WITH ONE ROLLER-APPLIED (1) PRIMER COAT AND (2) ROLLER- APPLIED FINISH COATS.
23. PROVIDE THRESHOLDS AT ALL DOORS & TRANSITION STRIPS WHERE CARPET MEETS A DIFFERENT TYPE OF FLOORING UNLESS NOTED OTHERWISE
24. REVIEW THE SCHEDULES, SPECIFICATIONS AND CUT SHEETS FOR ACCESSORIES, FIXTURES, ETC. THAT ACCOMPANY THE DRAWING SET PRIOR TO PLACING ORDERS. IF CONFLICTS ARE FOUND, INFORM THE COR OF SUCH FINDINGS AND TAKE NO ACTION UNTIL RESOLVED. IN THOSE CASES, IF AN ORDER FOR AN UNRESOLVED ITEM IS PLACED WITHOUT APPROVAL OF COR, THE CONTRACTOR ASSUMES ALL RESPONSIBILITY IF THE ITEM IS NOT ACCEPTED BY THE
GOVERNMENT
25. ALL WORK MUST BE COMPLETED CONFORMING TO CODES AND REGULATIONS WHICH INCLUDE, BUT ARE NOT LIMITED TO THE FOLLOWING ( LATEST EDITIONS AS PER 9/2025) : International Building Code (IBC), International Existing Building Code (IEBC), DT-DRM REV. 2.1, Architectural Barriers Act (ABA) Accessibility Standards, NFPA 1: Fire Code, NFPA 10: Standard for Portable Fire Extinguishers, NFPA 13: Standard for the Installation of Sprinkler Systems,NFPA 70 (NEC): National Electrical Code, NFPA 72: National Fire Alarm and Signaling Code, NFPA 80: Standard for Fire Doors and Other Opening Protectives, NFPA 90A: Standard for the Installation of Air-Conditioning and Ventilating SystemsNFPA 101: Life Safety Code, NFPA 241: Standard for Safeguarding Construction, Alteration, and Demolition Operations. WHERE A CONFLICT OCCURS IN OR BETWEEN THE AFOREMENTIONED CODES AND REGULATIONS, THE STRICTER SHALL APPLY UNLESS OTHERWISE INDICATED OR AGREED UPON.
26. THE INVESTIGATION FOR AND REMEDIATION OF ANY HAZARDOUS MATERIALS WITHIN THE PROJECT AREA ARE NOT A PART OF THESE CONSTRUCTION DOCUMENTS. ANY SUCH MATERIAL THAT IS ENCOUNTERED AND IMPACTS THE PROGRESS OF THE WORK INDICATED BY THESE DRAWINGS AND SPECIFICATIONS MUST BE DEALT WITH BY THE CONTRACTOR WITH THE OWNER UNDER SEPARATE CONTRACT. THIS REQUIREMENT SHALL IN NO WAY BE CONSTRUED AS REPRESENTATION BY THE ARCHITECT AS TO HOW TO IDENTIFY AND REMEDIATE SAID MATERIAL.
27. CONTACT DFM TO PERFORM INSPECTIONS PRIOR TO WALL AND CEILING CLOSE-INS, AS WELL AS FINAL OCCUPANCY INSPECTION.
28. PROVIDE DEMOLITION TO THE MINIMUM EXTENT REQUIRED FOR THE INSTALLATION OF FIRE ALARM, SECURITY SYSTEMS AND TELECOMMUNICATIONS WORK.
COORDINATE WITH EACH TRADES AND CONSULTANTS AND VERIFY THE EXTENT OF THE WORK REQUIRED. EXISTING FINISHES AND EQUIPMENT IN THE WORK AREAS ARE TO REMAIN AND SHOULD BE DISTURBED ONLY TO THE MINIMUM EXTENT TO PERFORM THE WORK.
29. COORDINATE ALL WORK REQUIRED ON FLOORS AND IN THE CEILINGS ABOVE AND BELOW THE PROJECT AREA W/ THE COR AND W/ THE USERS IN THE AFFECTED AREAS. REMOVE EXISTING CONSTRUCTION TO THE MINIMUM EXTENT REQUIRED FOR THE PERFORMANCE OF THE WORK AND REPLACE WITH LIKE-KIND AT THE CONCLUSION OF THE WORK. VERIFY THE TYPES AND AMOUNT OF EXISTING CONSTRUCTION TO BE AFFECTED. PROTECT ALL USER FURNITURE, FIXTURES AND EQUIPMENT WHILE PERFORMING THE WORK AND REPLACE ANY DAMAGED ARTICLES IN-KIND. CLEAN ALL AFFECTED USER AREAS AFTER THE COMPLETION OF THE WORK AND RETURN ALL FF&E ITEMS TO THEIR ORIGINAL LOCATIONS.
30. POWDER-ACTIVATED TOOLS REQUIRE WRITTEN APPROVAL BY THE PROJECT OFFICER AND PRESENTED UPON REQUEST WHEN IN USE. USE OF THESE TOOLS ALSO REQUIRES PROOF OF LICENSING AND TRAINING WHICH MUST ALSO BE PROVIDED UPON REQUEST. CONTRACTOR SHALL PROVIDE A LOG
OF “WHO, WHAT, WHERE AND WHEN” FOR ANY POWER OR POWDER ACTIVATED TOOLS THAT WILL BE USED. EXAMPLES OF SUCH TOOLS INCLUDE: AIR OR ELECTRICALLY POWERED TOOLS SUCH AS NAIL-GUNS, RAM TOOLS, OR ANY OTHER TOOL THAT CAN PROPEL A PROJECTILE AND MIGHT BE WEAPONIZED.
THE LOG SHALL BE CONTINUALLY UPDATED DURING CONSTRUCTION, MADE AVAILABLE UPON REQUEST, AND PROVIDED TO THE PROJECT OFFICER AT
WORK COMPLETION. (NOTE: GAS TOOLS ARE NOT ALLOWED AT TREASURY)
31. ALL MATERIALS MUST BE U.S.A. MADE
HISTORIC PRESERVATIONGENERAL CONSTRUCTION / WORK NOTES
ABBREVIATIONS
1. ANY PROJECT AFFECTING HISTORIC PROPERTIES MUST FOLLOW SECRETARY OF THE INTERIOR'S STANDARDS FOR THE TREATMENT OF HISTORIC PROPERTIES
2. ALL DESIGNS MUST FOLLOW APPLICABLE NIH TECHNICAL GUIDELINES AND REQUIREMENTS FOR HISTORICAL BUILDINGS
3. PROTECT ALL HISTORIC FABRIC DURING DEMOLITION AND CONSTRUCTION. DO NOT REMOVE HISTORIC FABRIC UNLESS NOTED ON DOCUMENTS. ANY HISTORIC FABRIC REMOVED MUST BE RETURNED TO COR. DO NOT DISPOSE.
EJ EXPANSION JOINT
EL ELEVATION (GRADE)
ELEC ELECTRICAL
EQ EQUAL
EQUIP EQUIPMENT
ETS EXPOSED TO STRUCTURE
EW EACH WAY
EWC ELECTRIC WATER COOLER
EXT EXTERIOR
EXTG EXISTING
EXTD EXTRUDED
FCU FAN COIL UNIT
FD FLOOR DRAIN
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FEX FIRE EXTINGUISHER (NO CAB)
FFA FURNITURE, FIXTURES &
ACCESSORIES
FFE FURNITURE, FIXTURES &
EQUIPMENT
FF FINISHED FLOOR
FHC FIRE HOSE CABINET
F&I FURNISH AND INSTALL
FIN FINISH
FLASH FLASHING
FLR FLOOR
FLUOR FLUORESCENT
FOF FACE OF FINISH
FP FIREPROOFING
FPHB FREEZE-PROOF HOSE BIB
FR FIRE RETARDANT/ RESISTANT
FRP FIBERGLASS REINFORCED
POLYMER
FT FOOT/FEET
FTG FOOTING
FURN FURNITURE
FURR FURRING
FV FIELD VERIFY
FWC FABRIC WALL COVERING
GA GAUGE
GALV GALVANIZED
GB GRAB BAR
GC GENERAL CONTRACTOR
GFI GROUND FAULT INTERRUPT
GFRC GOVERNMENT FURNISHED/
CONTRACTOR INSTALLED
GFRG GLASS FIBER REINFORCED
CONCRETE
GL GLASS
GND GROUND
GR GRADE
GWB GYPSUM WALL BOARD
GYP GYPSUM
GYP BD GYPSUM BOARD
H HIGH
HB HOSE BIB
HBD HARDBOARD
HC HOLLOW CORE
HCTLT HANDICAPPED ACCESSIBLE
TOILET
HD HOLD
HDR HEADER
HDW HARDWARE
HDWD HARDWOOD
IBC INTERNATIONAL BUILDING CODE
IEBC INTERNATIONAL EXISTING BUILDING CODE
IECC INTERNTL. ENERGY CONSERVATION CODE
IFC INTERNATIONAL FIRE CODE
ID INSIDE DIAMETER
IMC INTERNATIONAL MECHANICAL CODE
IN INCH
INCAN INCANDESCENT
INCL INCLUDING
INSUL INSULATION
INT INTERIOR
IPC INTERNATIONAL PLUMBING CODE
A
B
C
ABA ARCHITECT. BARRIERS ACT
AC ACOUSTICAL TILE
ACT ACOUSTIC CEILING TILE
AD AREA DRAIN
ADA AMER. W/ DISABILITIES ACT
ADJ ADJUSTABLE
AFF ABOVE FINISH FLOOR
ALT ALTERNATE
ALUM ALUMINUM
A&G ALUMINUM AND GLASS
ANCH ANCHOR
APPROX APPROXIMATE
AOR ARCHITECT OF RECORD
ARCH ARCHITECTURAL
ATT ATTENUATION
AU ASH URN
A/V AUDIO VISUAL
B & B BALLED AND BAGGED
BD BOARD
BET BETWEEN
BF BARRIER FREE
BIT BITUMINOUS
BLDG BUILDING
BLKG BLOCKING
BM BEAM
BMK BENCHMARK
BNG BEARING
BOD BOTTOM OF DECK
BTM BOTTOM
BR BACKER ROD
BRG BRIDGING
BUR BUILT UP ROOFING
BW BOTH WAYS
C COURSE
CAB CABINET
CEM CEMENT OR CEMENTITIOUS
CER CERAMIC
CG CORNER GUARD
CIP CAST IN PLACE
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLM COLUMN
cm CENTIMETER
CMU CNCRETE MASONRY UNIT
COMP COMPRESSION
CONC CONCRETE
CONT CONTINUOUS
CORR CORRIDOR
CPT CARPET
CSK COUNTERSINK
CT CERAMIC TILE
CTTA CERTIFIED TEMPEST TECHNICAL
AUTHORITY
D DEPTH OR DEEP
DBL DOUBLE
DBC DESIGN BUILD CONTRACTOR
DEG DEGREE
DEMO DEMOLITION
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIM DIMENSION
DN DOWN
DP DAMP PROOFING
DR DOOR
DS DOWN SPOUT
DW DISH WASHER
DWG DRAWING
DWR DRAWER
E EAST
EA EACH
EHB ELECTRIC HAND BLOWER
EHD ELECTRIC HAND DRYER
EIFS EXISTING INSULATING FINISH
JB JUNCTION BOX
JT JOINT
KD KNOCK DOWN
KO KNOCK OUT
L LONG
LAM LAMINATED
LAV LAVATORY
LB LAG BOLT OR LINEAR BOLT
LBP LEAD-BASED PAINT
LF LINEAR FEET
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LP LOW POINT
LT LIGHT OR LIGHTING
LW LIGHT WEIGHT
M METER
MACH MACHINE
MAS MASONRY
MAT MATERIAL
MAX MAXIMUM
MBH MOP & BROOM HOLDER
MBR MODIFIED BITUMINOUS ROOF
MC MEDICINE CABINET
MECH MECHANICAL
MEMB MEMBRANE
MEP MECHANICAL, ELECTRICAL &
PLUMBING
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MIR-F MIRROR-FRAMED EDGE
MIR-G MIRROR-GLASS EDGE
MISC MISCELLANEOUS
MLD MOULDING
MM MILIMITER
MNTD MOUNTED
MO MASONRY OPENING
MS MOP SINK
MSD MATERIAL SAFETY DATA
MTD MOUNTED
MTG MOUNTING
MTL METAL
N NORTH
N/A NOT APPLICABLE
NCOM NON-COMBUSTIBLE
NEC NATIONAL ELECTRICAL CODE
NIC NOT IN CONTRACT
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NOM NOMINAL
NPS NOMINAL PIPE SIZE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OFCI OWNER FURNISHED/
CONTRACTOR INSTALLED
OFD OVERFLOW DRAIN
OFOI OWNER FURNISHED/ OWNER
INSTALLED
OH OPPOSITE HAND OR OVERHEAD
OPG OPENING
OPP OPPOSITE
OPT OPTION OR OPTIONAL
OSSI OFFICE OF SECURITY &
STRATEGIC INFORMATION
OZ OUNCES
PA PUBLIC ADDRESS SYSTEM
PAF PRESSURE AIR FASTENER
PC PRECAST
PCEM PORTLAND CEMENT
PCF POUNDS PER CUBIC FOOT
PL PLATE
PLAM PLASTIC LAMINATE
PLBG PLUMBING
PLF POUNDS PER LINEAR FOOT
PLTR PLASTER
PLY PLYWOOD
PMR PROTECTED MEMBRANE ROOFING
PNL PANEL
PNT PAINT OR PAINTED
POE POINT OF ENTRY
POL POLISHED
PR PAIR
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT POINT
PTD PAPER TOWEL DISPENSER
PTN PARTITION
PVC POLYVINYL CHLORIDE
PVMT PAVEMENT
QT QUARRY TILE
QTR QUARTER
QTY QUANTITY
R RADIUS OR RISER
RA RETURN AIR
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
RE REFER
RECEP RECEPTACLE
REFL REFLECTED
REG REGISTER
REINF REINFORCEMENT
REQD REQUIRED
RES RESILIENT
REV REVERSE
RFI REQUEST FOR INFORMATION
RH ROBE HOOK
RM ROOM
RO ROUGH OPENING
ROW RIGHT OF WAY
RSF RESILIENT SHEET FLOORING
S SOUTH
SA SUPPLY AIR
SAN SANITARY
SB SPLASH BLOCK
SC SOLID CORE
SCC SECURITY COMMAND CENTER
SCHED SCHEDULE
SCIF SENSITIVE COMPARTMENTED
INFORMATION FACILITY
SCWD SOLID CORE WOOD DOOR
SD SOAP DISPENSER
SECT SECTION
SF SQUARE FEET
SFP SPRAYED FIREPROOFING
SH SPRINKLER HEAD
SHT SHEET
SHTG SHEATHING
SIM SIMILAR
SKLT SKYLIGHT
SP STANDPIPE
SPEC SPECIFIED OR SPECIFICATION
SQ SQUARE
SR SHOWER ROD
SR/SC SHOWER ROD / SHOWER CURTAIN
SS STAINLESS STEEL
ST SOAP TRAY
STC SOUND TRANSMISSION CLASS
STD STANDARD
STL STEEL
STOR STORAGE
STRL STRUCTURAL
STRU STRUCTURE
SUSP SUSPENDED
SYM SYMBOL
SYN SYNTHETIC
SYS SYSTEM
D
G
H
T TREAD OR TOP
TB TOWEL BAR
TBL TOP OF BRICK LEDGE
T&B TOP & BOTTOM
TC TOP OF CURB
TD TRENCH DRAIN
TEL TELEPHONE
TERR TERRAZZO
T&G TONGUE AND GROOVE
THK THICK
THRU THROUGH
TLT TOILET
TOC TOP OF CONCRETE
TOD TOP OF DECK
TOF TOP OF FOOTING
TOI TOP OF INSULATION
TOJ TOP OF JOIST
TOP TOP OF PARAPET
TOS TOP OF STEEL
TOW TOP OF WALL
TPH TOILET PAPER HOLDER
TR TELEPHONE RECEPTACLE
TTB TELEPHONE TERMINAL
BOARD
TV TELEVISION
TYP TYPICAL
UCL UNDER CABINET LIGHT
ULAY UNDERLAYMENT
UNFIN UNFINISHED
UNO UNLESS NOTED OTHERWISE
UON UNLESS OTHERWISE NOTED
UR URINAL
VB VAPOR BARRIER
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VIF VERIFY IN FIELD
VP VENT PIPE
VS VENT SHAFT
VT VINYL TILE
VWC VINYL WALL COVERING
W WEST OR WIDE OR WIDTH
W/ WITH
WB WIND BRACE
WC WATER COSET
WCOT WAINSCOT
WD WOOD
WDO WINDOW
WH WEEP HOLE
W/O WITHOUT
WO WINDOW OPENING
WP WATER PROOFING
WR WASTE RECEPTACLE
W/R WATER RESISTANT
WS WEATHERSRIPPING
WT WEIGHT
WWF WELDED WIRE FABRIC
YD YARD
& AND
@ AT
= EQUAL
± PLUS / MINUS
# POUNDS OR NUMBER
x TIMES
° DEGREES
∠ ANGLE
Ø DIAMETER
℄ CENTER LINE
' FEET
" INCHES
F
J
K
L
M
N
O
Q
R
S
T
U
V
W
Y
SYMBOLS AND MATERIALS LEGEND
E
I
P
ALIGN
X
X
X
ELEVATION NUMBER
SHEET NUMBER
X
X
XX
DETAIL / SECTION NUMBER
SHEET NUMBER
X FURNITURE / EQUIPMENT TAG
ALUMINUM
BATT INSULATION
CONCRETE
GYPSUM OR SAND
WOOD BLOCKING CONTINUOUS
WOOD BLOCKING NOT
CONTINUOUS
FINISH WOOD
PLYWOOD
STEEL STUD
STEEL RUNNER / TRACK
CARPET
XX
XXX
XXX
CL
XX
XX
G- 002
NOTES, SYMBOLS AND ABBREVIATIONS
OF
R
EV
IS
IO
N N
O
TE
S
GR
AP
HI
C
SC
AL
E
MARK DATE DESCRIPTION
AGF
CE
RT
IFI
CA
TIO
NS
SHEET SIZE:
SHEET
DISCIPLINE SHEET TYPE SEQUENCE
DRAWING NO.
DRAWING TITLE
FILE NAME
CHECKED BY
DRAWN BY DATE DRAFTED:
PROJECT NO.
GSA PM
SUB. DATE
SUBMISSION
DESCRIPTION
PROJECT
TITLE
BUILDING NOs.
OTHER
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
DR
AW
IN
G
PR
OJ
EC
T
BU
ILD
IN
G
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
CO
NT
RA
CT
OR
S
FLOOR NO.
FACILITY CODE
PROJECT
A/E TASK NO.
CONS. WORK
24 x 36
DC-
1 2 3 4 5
A
B
C
D
WASHINGTON, DC
MERIDIEN GROUP / CITADEL DCA
LSP
MERIDIEN GROUP, LLC
208 SOUTH KING ST. SUITE 303
LEESBURG, VA 20175
(703) 777-8285 www.meridiengroupllc.com
BARBARA CHOATE
100% SUBMISSION FOR REVIEW
KE
Y
PL
AN
1 2 3 4 5
04/14/2026
MT2453_26_004
28 APRIL 2026
FEDERAL OFFICE BUILDING
RENOVATION OF SECOND FLOOR SUITE
MT 2453 OFFICE RENOVATION
2ND FLOOR
EXISTING TATE STEEL 24"x 24"
FLOOR PANEL SYSTEM TO REMAIN
UNALTERED
MODIFIED EXISTING STEEL 24"x 24"
FLOOR PANEL
EXISTING STEEL 24"x 24" FLOOR
PANEL TO BE REMOVED AND MODIFIED
ALIGN SURFACES
GENERAL / KEY NOTE
DEMILITION NOTE
WALL / PARTITION TYPE
ROOM NAME
ROOM NUMBER
CENTER LINE
STRUCTURAL GRID COMPONENT
EXISTING POWER/ DATA FLOOR BOX
W/ COVER
REVISION NUMBER
REVISION CLOUD
NEW DOOR ASSEMBLYX-
XX
X
EXISTING DOOR ASSEMBLY WITHIN
THE AREA OF WORK TO REMAINX-XXX
EXISTING DOOR ASSEMBLY
TO BE REMOVED
NOT IN THE SCOPE OF WORK
DOOR NUMBER
NEW WALL AS PER WALL TYPE
NEW STC-50 WALL
EXISTING WALL TO REMAIN
WALL TO BE REMOVED
FLOOR FINISH TRANSITION
FINISH ELEVATION
EXISTING DOOR ASSEMBLY OUTSIDE
THE AREA OF WORK TO REMAIN
EXISTING PENDANT LIGHT FIXTURE TO
REMAIN AS IS. PROTECT DURING
CONSTRUCTION
EXISTING SPRINKLER HEAD TO
REMAIN UNALTERED
EXISTING HISTORIC VAULTED, PLASTER
CEILING TO REMAIN UNALTERED.
PROTECT DURING CONSTRUCTION
EXISTING FCU AND ASSOCIATED
PIPING CABINET TO REMAIN AS IS.
PROTECT DURING CONSTRUCTION
PRIOR TO REFINISHING
(E)
(E) POWER/ DATA FLOOR BOX W/ COVER
AND FLOOR PANEL TO BE RELOCATED
RELOCATED POWER/ DATA FLOOR BOX
W/ COVER AND FLOOR PANEL
NEW POWER/ DATA FLOOR BOX
W/ COVER
(E)
2457A
20'-61 4"
E
'-1
'-4
VI
F
ELEV 0'- (± 6")
ELEV 0'- (± 6")
VI
F
VIF
2453 E
OFFICE
OFFICE
ELECTRICAL
CLOSET
201CL
202CL
203CL
204CL
(E) (E)
(E) (E)
(E)
(E)
(E)
(E)
(E)(E)
(E)
(E) (E)
(E)
(E)(E)(E)
2453 E
OFFICE
OFFICE
ELECTRICAL
CLOSET
201CL
202CL
203CL
204CL
EXISTING WALLS TO REMAIN
EXISTING DOORS TO BE REMOVED
EXISTING IRVINE-TATE CONCORE / ALL STEEL 24"x 24" FLOOR PANEL SYSTEM TO REMAIN
EXISTING IRVINE-TATE CONCORE / ALL STEEL 24"x 24" FLOOR PANEL TO BE REMOVED TO
ALLOW FOR WALL CONSTRUCTION. PANELS TO REMAIN ON SITE UNTIL CONSTRUCTION IS
COMPLETED. REINSTALL AFTER COMPLETION
PORTION OF WALL TO BE REMOVED
ERECT ZIP WALLS OR EQUIVALENT FROM TATE FLOOR SYSTEM TO HISTORIC CEILING TO ENCLOSE
PROJECT AREA INCLUDING CORRIDOR.
ORIGINAL HISTORIC CROWN MOLDING AND CEILING RIB MOLDINGS TO REMAIN. THE NEW PARTITIONS
SHOULD BE BUILD AS PER WALL SECTIONS TO AVOID DAMAGING THE HISTORIC ELEMENTS.
EXISTING DOOR ASSEMBLY TO REMAIN. PROTECT DURING CONSTRUCTION
EXISTING FCU TO REMAIN. COVER DURING CONSTRUCTION TO PREVENT DUST FROM ENTERING THE
VENTS
EXISTING MILLWORK TO REMAIN UNALTERED. PROTECT DURING CONSTRUCTION FRAME NEW PARTITION
AROUND MILLWORK AS INDICATED IN SECTIONS & FRAMING PLAN. DO NOT ALTER MILLWORK.
EXISTING LIGHT FIXTURES AND FIRE SUPPRESSION SYSTEM TO REMAIN UNALTERED. PROTECT DURING
CONSTRUCTION
EXISTING ORIGINAL WALL & BASEBOARD TO REMAIN UNALTERED. PREPARE TO BE REFINISHED. PROTECT
DURING CONSTRUCTION
EXISTING FLOOR BOXES TO REMAIN UNALTERED. PROTECT DURING CONSTRUCTION
EXISTING NON-ORIGINAL PARTITION W/ BASEBOARD AND CLERESTORY WINDOWS TO REMAIN. PREPARE
TO BE REFINISHED
EXISTING NON-ORIGINAL PARTITION W/ BASEBOARD TO REMAIN. ALTER BASEBOARD AS NEEDED TO
INSTALL NEW PARTITION
EXISTING PANELED PARTITION TO REMAIN. PROTECT DURING CONSTRUCTION
1 EXISTING PARTITION W/ BASEBOARD AND CLERESTORY WINDOWS TO BE DEMOLISHED AND DISPOSED.
EXISTING 2-PANEL DOOR W/ FLAT CASING TO BE REMOVED. DISPOSE OF CASING AND RETURN HARDWARE
TO COR.
NOTE: IF DOOR ASSEMBLY (DOOR LEAF + FRAME) IS IN GOOD CONDITION AND IT IS APPROVED BY TREASURY'S COR, KEEP THE ASSEMBLY ON SITE DOOR TO BE REUSED AT NEW OFFICE LOCATION.
EXISTING MILLWORK AND CROWN MOLDING AFFECTED BY THE REMOVAL OF THE PARTITION TO BE
RESTORED
REMOVE FLOOR SYSTEM PANELS AS DEPICTED TO ALLOW FOR THE DEMOLITION OF THE EXISTING WALL AND FOR THE CONSTRUCTION OF THE NEW WALLS. KEEP THE PANELS ON SITE AND REINSTALL AT THE
COMPLETION OF THE WALL CONSTRUCTION
REMOVE AND DISPOSE OF CARPET. PREPARE FLOOR PANELS TO RECEIVE NEW CARPET BY REMOVING
GLUE AND DEBRIS
REMOVE FLOOR SYSTEM PANELS WITH POWER AND DATA BOXES AS DEPICTED. KEEP THE PANELS ON
SITE AND REINSTALL AT NEW LOCATION
REMOVE OR PROTECT WINDOW BLINDS FOR THE ENTIRE DURATION OF THE WORK. IF REMOVED THEY NEED
TO BE STORED ON SITE AND REINSTALLED AT THE CONCLUSION OF THE JOB
EXISTING FLOOR BOX TO REMAIN UNALTERED. PROTECT DURING CONSTRUCTION(E)
XXX-A
FOOTPRINT OF NEW WALL
EXISTING FCU AND ASSOCIATED PIPING CABINET TO REMAIN AS IS. PROTECT DURING
CONSTRUCTION PRIOR TO REFINISHING
CAUTION: IF THIS DRAWING IS A REDUCTION THIS GRAPHIC SCALE MUST BE USEDCAUTION: IF THIS DRAWING IS A REDUCTION THIS GRAPHIC SCALE MUST BE USED
AD101
EXISTING, DEMOLITION AND PROTECTION
OF
R
EV
IS
IO
N N
O
TE
S
GR
AP
HI
C
SC
AL
E
MARK DATE DESCRIPTION
AGF
CE
RT
IFI
CA
TIO
NS
SHEET SIZE:
SHEET
DISCIPLINE SHEET TYPE SEQUENCE
DRAWING NO.
DRAWING TITLE
FILE NAME
CHECKED BY
DRAWN BY DATE DRAFTED:
PROJECT NO.
GSA PM
SUB. DATE
SUBMISSION
DESCRIPTION
PROJECT
TITLE
BUILDING NOs.
OTHER
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
DR
AW
IN
G
PR
OJ
EC
T
BU
ILD
IN
G
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
CO
NT
RA
CT
OR
S
FLOOR NO.
FACILITY CODE
PROJECT
A/E TASK NO.
CONS. WORK
24 x 36
DC-
1 2 3 4 5
A
B
C
D
WASHINGTON, DC
MERIDIEN GROUP / CITADEL DCA
LSP
MERIDIEN GROUP, LLC
208 SOUTH KING ST. SUITE 303
LEESBURG, VA 20175
(703) 777-8285 www.meridiengroupllc.com
BARBARA CHOATE
04/14/2026
2ND FLOOR
MT2453_26_004
28 APRIL 2026
100% SUBMISSION FOR REVIEW
FEDERAL OFFICE BUILDING
N
KE
Y
PL
AN
1 2 3 4 5
CAUTION: IF THIS DRAWING IS A REDUCTION THIS GRAPHIC SCALE MUST BE USED
RENOVATION OF SECOND FLOOR SUITE
MT 2453 OFFICE RENOVATION
NO
RT
H
PROJECT LOCATION
NORTH COURTYARD
EXISTING & DEMOLITIOM FLOOR PLANA-1
1/4" = 1'-0"
1. CONTRACTOR TO VERIFY EXISTING CONDITIONS BEFORE STARTING. NO FORENSIC DEMOLITION WAS
CONDUCTED AT THE TIME OF THE SURVEY. DISCREPANCIES MIGHT BE ENCOUNTERED BETWEEN
ACTUAL CONDITIONS AND DRAWINGS. INFORM COR PRIOR TO PROCEEDING w/ WORK
2. IN CASE OF CONFLICTS BETWEEN PLANS, KEY NOTES, SECTIONS, DETAILS AND SPECIFICATIONS, THE
MOST STRINGENT REQUIREMENT APPLIES
3. ALL DIMENSIONS ARE GIVEN FROM FINISH WALL OR PARTITION TO FINISH WALL OR PARTITION
4. ALL WORK PROVIDED UNDER THIS CONTRACT SHALL BE NEW UNLESS SPECIFICALLY MARKED
"EXISTING," "EXTG", OR "(E)"
5. BEST PRACTICES, METHODS AND MATERIALS, MUST BE FOLLOWED AT ALL TIMES. ANY ITEM NOT
SPECIFICALLY LISTED OR SHOWN ON THE CONTRACT DOCUMENTS BUT NECESSARY FOR THE
COMPLETION OF THE PROJECT, SHALL BE CONSIDERED PART OF THE CONTRACT'S SCOPE OF WORK
6. THE CONTRACTOR SHALL CLEAN UP ALL ACTIVE WORK AREAS AFTER EACH DAY’S WORK. THE CONTRACTOR IS RESPONSIBLE FOR THE REMOVAL AND PROPER DISPOSAL OF ALL WORK RELATED
TRASH AND DEBRIS
7. PROTECT ALL GOVERNMENT PROPERTY ENCOUNTERED AT THE JOB SITE AGAINST DAMAGE. ALL DAMAGES CAUSED BY THE CONTRACTOR SHALL BE REPAIRED OR REPLACED TO MATCH EXISTING AND
TO THE SATISFACTION AND APPROVAL OF THE COR
8. AREA OF WORK MUST BE ISOLATED FROM THE REST OF ADJACENT AREAS. PROTECT ALL SURFACES, EQUIPMENT& FURNITURE PRIOR TO START OF WORK.
9. REMOVE ALL HVAC COVERS AS NEEDED. SEAL EXPOSED DUCTS AND VENTS TO PREVENT INTRODU- CING DUST INTO THE SYSTEM. (REMOVED COVERS MUST BE REINSTALLED AT END OF THE JOB)
10. PROTECT ALL HISTORIC FABRIC DURING DEMOLITION AND CONSTRUCTION.
11. DO NOT REMOVE HISTORIC FABRIC UNLESS SPECIFICALLY NOTED ON DOCUMENTS. ANY HISTORIC
FABRIC REMOVED MUST BE RETURNED TO COR. DO NOT DISPOSE.
EXISTING AND DEMOLITION FLOOR PANEL SYSTEMA-3
1/4" = 1'-0"
GENERAL NOTES SYMBOLS LEGENDDEMOLITION & PROTECTION NOTES
1/4" =1'-0" 6"
12"36" 1' 2' 3' 4'
30"
5' 6' 7' 8'
18"
24"
KEY NOTES
NOT IN THE SCOPE OF WORK
1 3
4 5
(E) EXISTING FLOOR BOX AND FLOOR PANEL TO BE RELOCATED
6 6
DUE TO THE PRESENCE OF CARPET, THE FLOOR PANEL SYSTEM HAS NOT BEEN SURVEYED. THESE DRAWINGS REPRESENT ONLY AN APPROXIMATION OF THE EXISTING CONDITIONS, THUS ADJUSTMENTS WILL BE NECESSARY. THE ARCHITECT WILL SURVEY THE FLOOR ONCE CARPET HAS BEEN REMOVE
2453 E
OFFICE
OFFICE
ELECTRICAL
CLOSET
201CL
202CL
203CL
204CL
VAULT
VAULT
VAULT
VAULT
VAULT
VAULT
VAULT
VAULT
VAULT
VAULT
CAUTION: IF THIS DRAWING IS A REDUCTION THIS GRAPHIC SCALE MUST BE USEDCAUTION: IF THIS DRAWING IS A REDUCTION THIS GRAPHIC SCALE MUST BE USED
AD102
04 OF
R
EV
IS
IO
N N
O
TE
S
GR
AP
HI
C
SC
AL
E
MARK DATE DESCRIPTION
AGF
CE
RT
IFI
CA
TIO
NS
SHEET SIZE:
SHEET
DISCIPLINE SHEET TYPE SEQUENCE
DRAWING NO.
DRAWING TITLE
FILE NAME
CHECKED BY
DRAWN BY DATE DRAFTED:
PROJECT NO.
GSA PM
SUB. DATE
SUBMISSION
DESCRIPTION
PROJECT
TITLE
BUILDING NOs.
OTHER
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
DR
AW
IN
G
PR
OJ
EC
T
BU
ILD
IN
G
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
CO
NT
RA
CT
OR
S
FLOOR NO.
FACILITY CODE
PROJECT
A/E TASK NO.
CONS. WORK
24 x 36
DC-
1 2 3 4 5
A
B
C
D
WASHINGTON, DC
MERIDIEN GROUP / CITADEL DCA
LSP
MERIDIEN GROUP, LLC
208 SOUTH KING ST. SUITE 303
LEESBURG, VA 20175
(703) 777-8285 www.meridiengroupllc.com
BARBARA CHOATE
04/14/2026
2ND FLOOR
MT2453_26_004
28 APRIL 2026
100% SUBMISSION FOR REVIEW
FEDERAL OFFICE BUILDING
N
KE
Y
PL
AN
1 2 3 4 5
CAUTION: IF THIS DRAWING IS A REDUCTION THIS GRAPHIC SCALE MUST BE USED
RENOVATION OF SECOND FLOOR SUITE
MT 2453 OFFICE RENOVATION
NO
RT
H
PROJECT LOCATION
NORTH COURTYARD
A-1
1. CONTRACTOR TO VERIFY EXISTING CONDITIONS BEFORE STARTING. NO FORENSIC DEMOLITION WAS
CONDUCTED AT THE TIME OF THE SURVEY. DISCREPANCIES MIGHT BE ENCOUNTERED BETWEEN
ACTUAL CONDITIONS AND DRAWINGS. INFORM COR PRIOR TO PROCEEDING w/ WORK
2. IN CASE OF CONFLICTS BETWEEN PLANS, KEY NOTES, SECTIONS, DETAILS AND SPECIFICATIONS, THE
MOST STRINGENT REQUIREMENT APPLIES
3. ALL DIMENSIONS ARE GIVEN FROM FINISH WALL OR PARTITION TO FINISH WALL OR PARTITION
4. ALL WORK PROVIDED UNDER THIS CONTRACT SHALL BE NEW UNLESS SPECIFICALLY MARKED
"EXISTING," "EXTG", OR "(E)"
5. BEST PRACTICES, METHODS AND MATERIALS, MUST BE FOLLOWED AT ALL TIMES. ANY ITEM NOT
SPECIFICALLY LISTED OR SHOWN ON THE CONTRACT DOCUMENTS BUT NECESSARY FOR THE
COMPLETION OF THE PROJECT, SHALL BE CONSIDERED PART OF THE CONTRACT'S SCOPE OF WORK
6. THE CONTRACTOR SHALL CLEAN UP ALL ACTIVE WORK AREAS AFTER EACH DAY’S WORK. THE CONTRACTOR IS RESPONSIBLE FOR THE REMOVAL AND PROPER DISPOSAL OF ALL WORK RELATED
TRASH AND DEBRIS
7. PROTECT ALL GOVERNMENT PROPERTY ENCOUNTERED AT THE JOB SITE AGAINST DAMAGE. ALL DAMAGES CAUSED BY THE CONTRACTOR SHALL BE REPAIRED OR REPLACED TO MATCH EXISTING AND
TO THE SATISFACTION AND APPROVAL OF THE COR
8. AREA OF WORK MUST BE ISOLATED FROM THE REST OF ADJACENT AREAS. PROTECT ALL SURFACES, EQUIPMENT& FURNITURE PRIOR TO START OF WORK.
9. REMOVE ALL HVAC COVERS AS NEEDED. SEAL EXPOSED DUCTS AND VENTS TO PREVENT INTRODU- CING DUST INTO THE SYSTEM. (REMOVED COVERS MUST BE REINSTALLED AT END OF THE JOB)
10. PROTECT ALL HISTORIC FABRIC DURING DEMOLITION AND CONSTRUCTION.
11. DO NOT REMOVE HISTORIC FABRIC UNLESS SPECIFICALLY NOTED ON DOCUMENTS. ANY HISTORIC
FABRIC REMOVED MUST BE RETURNED TO COR. DO NOT DISPOSE.
GENERAL NOTES SYMBOLS LEGENDDEMOLITION NOTES
1/4" =1'-0" 6"
12"36" 1' 2' 3' 4'
30"
5' 6' 7' 8'
18"
24"
EXISTING WALLS TO REMAIN
EXISTING DOORS TO BE REMOVED
PORTION OF WALL TO BE REMOVED
FOOTPRINT OF NEW WALL
EXISTING HISTORIC VAULTED, PLASTER CEILING TO REMAIN UNALTERED.
PROTECT DURING CONSTRUCTION
EXISTING PENDANT LIGHT FIXTURE TO REMAIN AS IS. PROTECT DURING CONSTRUCTION
EXISTING SPRINKLER HEAD TO REMAIN UNALTERED
NOT IN THE SCOPE OF WORK
EXISTING, DEMOLITION AND PROTECTION RCP
HISTORIC PLASTER CEILING TO REMAIN UNALTERED. NEW WALLS SHOULD BE BUILD AS PER WALL
SECTION TO AVOID DAMAGING THE HISTORIC FABRIC.
HISTORIC CROWN MOLDING TO REMAIN. NEW WALLS SHOULD BE BUILD AS PER WALL SECTION TO
AVOID DAMAGING THE HISTORIC ELEMENTS.
HISTORIC VAULT RIBS TO REMAIN UNALTERED. NEW WALLS SHOULD BE BUILD AS PER WALL SECTION
TO AVOID DAMAGING THE HISTORIC FABRIC.
EXISTING LIGHTING TO REMAIN. PROTECT DURING CONSTRUCTION
EXISTING SPRINKLER HEADS TO REMAIN. PROTECT DURING CONSTRUCTION
KEY / PROTECTION NOTES
TYPICAL EXISTING LIGHT FIXTURE
HISTORIC VAULT RIB TO
REMAIN UNALTERED. TYPICAL
HISTORIC ORIGINAL CROWN MOLDING
TO REMAIN UNALTERED. TYPICAL
HISTORIC VAULTED PLASTER CEILING
TO REMAIN UNALTERED. TYPICAL
VAULT 4 VAULT 5
PLASTER DAMAGE
VAULT 5
HISTORIC VAULTED PLASTER CEILING
TO REMAIN UNALTERED. TYPICAL
HISTORIC VAULT RIB TO
REMAIN UNALTERED. TYPICAL
CAST IRON WINDOW
FRAME AND CASING. TYPICAL
HISTORIC ORIGINAL CROWN MOLDING
TO REMAIN UNALTERED. TYPICAL
WALL WITH CLERESTORY
WINDOWS TO BE DEMOLISHED
EXTERIOR MASONRY TO REMAIN UNALTERED.
PREP AND REFINISH TYPICAL
1 AS WALL / PARTITION IS REMOVED, ENSURE THAT PLASTER CEILING IS TREATED WITH OUTMOST CARE, AND NO DAMAGE IS INFLICTED TO CEILING, DECORATIVE VAULT RIBS, OR CROWN MOLDING IN THE PROCESS. IF ANY PORTION OF A DECORATIVE ELEMENT IS BROKEN, DO NOT DISPOSE, PORTION MUST
REMAIN ON SITE UNTIL ARCHITECT INSPECTS DAMAGE.
PLASTER DAMAGE TO BE REPAIRED AS INDICATED ON A-102
EXISTING CROWN MOLDING AFFECTED BY THE REMOVAL OF THE PARTITION TO BE RESTORED AS
INDICATED ON A-102
EXISTING SPRINKLER HEAD. TYPICAL 5
455 4
EXISTING AND DEMOLITION REFLECTED CEILING PLAN (RCP)
1/4" = 1'-0"
OPEN 0FFICE
EXISTING CEILING STRUCTURE
0FFICE
4' -2
" V .I.
F.
2453E
OPEN 0FFICE
2453-A2449-A
VAULT
CL
VAULT
CL
VAULT
CL
VAULT
CL
VAULT
CL
VAULT
CL
VAULT
CL
VAULT
CL
2453-E
EQEQEQ
GENERAL NOTES
06"12"18" 1' 2' 3' 4'
3"9"15"
CAUTION: IF THIS DRAWING IS A REDUCTION THIS GRAPHIC SCALE MUST BE USED
AD201
EXISTING AND DEOLITION
OF
R
EV
IS
IO
N N
O
TE
S
GR
AP
HI
C
SC
AL
E
MARK DATE DESCRIPTION
AGF
CE
RT
IFI
CA
TIO
NS
SHEET SIZE:
SHEET
DISCIPLINE SHEET TYPE SEQUENCE
DRAWING NO.
DRAWING TITLE
FILE NAME
CHECKED BY
DRAWN BY DATE DRAFTED:
PROJECT NO.
GSA PM
SUB. DATE
SUBMISSION
DESCRIPTION
PROJECT
TITLE
BUILDING NOs.
OTHER
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
DR
AW
IN
G
PR
OJ
EC
T
BU
ILD
IN
G
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
CO
NT
RA
CT
OR
S
FLOOR NO.
FACILITY CODE
PROJECT
A/E TASK NO.
CONS. WORK
24 x 36
DC-
1 2 3 4 5
A
B
C
D
WASHINGTON, DC
MERIDIEN GROUP / CITADEL DCA
LSP
MERIDIEN GROUP, LLC
208 SOUTH KING ST. SUITE 303
LEESBURG, VA 20175
(703) 777-8285 www.meridiengroupllc.com
BARBARA CHOATE
04/14/2026
2ND FLOOR
MT2453_26_004
28 APRIL 2026
100% SUBMISSION FOR REVIEW
FEDERAL OFFICE BUILDING
N
KE
Y
PL
AN
1 2 3 4 5
CAUTION: IF THIS DRAWING IS A REDUCTION THIS GRAPHIC SCALE MUST BE USED
RENOVATION OF SECOND FLOOR SUITE
MT 2453 OFFICE RENOVATION
NO
RT
H
PROJECT LOCATION
NORTH COURTYARD
1. CONTRACTOR TO VERIFY EXISTING CONDITIONS BEFORE STARTING. NO FORENSIC DEMOLITION WAS
CONDUCTED AT THE TIME OF THE SURVEY. DISCREPANCIES MIGHT BE ENCOUNTERED BETWEEN
ACTUAL CONDITIONS AND DRAWINGS. INFORM COR PRIOR TO PROCEEDING w/ WORK
2. IN CASE OF CONFLICTS BETWEEN PLANS, KEY NOTES, SECTIONS, DETAILS AND SPECIFICATIONS, THE MOST
STRINGENT REQUIREMENT APPLIES
3. ALL DIMENSIONS ARE GIVEN FROM FINISH WALL OR PARTITION TO FINISH WALL OR PARTITION
4. ALL WORK PROVIDED UNDER THIS CONTRACT SHALL BE NEW UNLESS SPECIFICALLY MARKED "EXISTING,"
"EXTG", OR "(E)"
5. BEST PRACTICES, METHODS AND MATERIALS, MUST BE FOLLOWED AT ALL TIMES. ANY ITEM NOT SPECIFICALLY LISTED OR SHOWN ON THE CONTRACT DOCUMENTS BUT NECESSARY FOR THE COMPLETION OF THE
PROJECT, SHALL BE CONSIDERED PART OF THE CONTRACT'S SCOPE OF WORK
6. THE G.C. SHALL CLEAN UP ALL ACTIVE WORK AREAS AFTER EACH DAY’S WORK. THE G.C. IS RESPONSIBLE
FOR THE REMOVAL AND PROPER DISPOSAL OF ALL WORK RELATED TRASH AND DEBRIS
7. PROTECT ALL GOVERNMENT PROPERTY ENCOUNTERED AT THE JOB SITE AGAINST DAMAGE. ALL DAMAGES CAUSED BY THE CONTRACTOR SHALL BE REPAIRED OR REPLACED TO MATCH EXISTING AND TO THE
SATISFACTION AND APPROVAL OF THE COR
8. AREA OF WORK MUST BE ISOLATED FROM THE REST OF ADJACENT AREAS. PROTECT ALL SURFACES, EQUIP-
MENT& FURNITURE PRIOR TO START OF WORK.
9. REMOVE ALL HVAC COVERS AS NEEDED. SEAL EXPOSED DUCTS AND VENTS TO PREVENT INTRODUCING DUST
DUST INTO THE SYSTEM. (REMOVED COVERS MUST BE REINSTALLED AT END OF THE JOB)
10. PROTECT ALL HISTORIC FABRIC DURING DEMOLITION AND CONSTRUCTION.
11. DO NOT REMOVE HISTORIC FABRIC UNLESS SPECIFICALLY NOTED ON DOCUMENTS. ANY HISTORIC FABRIC
REMOVED MUST BE RETURNED TO COR. DO NOT DISPOSE.
EXISTING ORIGINAL MASONRY WALL AND BASEBOARD TO REMAIN UNALTERED. PROTECT DURING
CONSTRUCTION PRIOR TO ITS PREP FOR REFINISHING
EXISTING LIGHT FIXTURES AND FIRE SUPPRESSION SYSTEM TO REMAIN UNALTERED. PROTECT DURING
CONSTRUCTION PRIOR TO ITS PREP FOR REFINISHING
EXISTING NOT ORIGINAL WALL AND BASEBOARD TO REMAIN UNALTERED. PROTECT DURING
CONSTRUCTION PRIOR TO ITS PREP FOR REFINISHING
EXISTING ORIGINAL BUILT-IN BOOK CASE TO REMAIN UNALTERED. PROTECT DURING CONSTRUCTION
PRIOR TO ITS PREP FOR REFINISHING
EXISTING NON-ORIGINAL PARTITION W/ BASEBOARD AND CLERESTORY WINDOWS TO REMAIN
UNALTERED. PROTECT DURING CONSTRUCTION PRIOR TO ITS PREP FOR REFINISHING
EXISTING DOOR ASSEMBLY TO REMAIN. DO NOT ALTER AND PROTECT DURING CONSTRUCTION PRIOR
TO ITS PREP FOR REFINISHING
ORIGINAL HISTORIC VAULTED PLASTER CEILING, CROWN MOLDING AND CEILING RIB MOLDING TO REMAIN UNALTERED. NEW PARTITIONS SHOULD BE BUILD AS PER WALL SECTIONS TO AVOID DAMAGING THE HISTORIC ELEMENTS. HISTORIC PLASTER MOLDINGS MUST NOT BE CUT OR ALTERED IN ANY
MANNER
LEGEND
1/2" = 1' - 0"
1 ERECT ZIP WALLS OR EQUIVALENT FROM TATE FLOOR SYSTEM TO HISTORIC CEILING TO ENCLOSE PROJECT
AREA
EXISTING NON-ORIGINAL PARTITION W/ BASEBOARD AND CLERESTORY WINDOWS TO BE REMOVED
EXISTING 2-PANEL DOOR W/ FLAT CASING TO BE REMOVED. DISPOSE OF CASING AND RETURN HARDWARE
TO COR.
NOTE: IF DOOR ASSEMBLY (DOOR LEAF + FRAME) IS IN GOOD CONDITION AND IT IS APPROVED BY TREASURY'S COR, KEEP THE ASSEMBLY ON SITE DOOR TO BE REUSED AT NEW OFFICE LOCATION.
EXISTING MILLWORK AND CROWN MOLDING AFFECTED BY THE REMOVAL OF THE PARTITION TO BE RESTORED
DEMOLISH EXISTING CARPET FROM PROJECT AREA. REMOVE GLUE AND CLEAN FLOOR SYSTEM PANELS AS NEEDED. STORE PANELS AND CARPET ON SITE AND REINSTALL ALTERED AT THE COMPLETION OF THE JOB.
EXISTING DOOR ASSEMBLY TO REMAIN. DO NOT ALTER AND PROTECT DURING CONSTRUCTION
EXISTING FCU TO REMAIN. COVER DURING CONSTRUCTION TO PREVENT DUST FROM ENTERING THE VENTS
EXISTING FCU MILLWORK TO REMAIN UNALTERED. DO NOT ALTER AND PROTECT DURING CONSTRUCTION
PRIOR TO ITS PREP FOR REFINISHING
EXISTING FLOOR SYSTEM AND ELECTRICAL BOXES TO REMAIN UNALTERED. PROTECT FLOOR BOXES DURING
CONSTRUCTION
DEMOLITION & PROTECTION NOTES
NO
RT
H
C-1 1/2" = 1'-0"
EXISTING & DEMOLITION : SECTION 2 - 2A-1
1/2" = 1'-0"
EXISTING & DEMOLITION : SECTION 1 - 1
1 1
6 6
11 11
11 11 11 11
10 12
TYP
16 16
EXISTING CEILING STRUCTURE
0FFICE
4' -2
" V .I.
F.
2453E
OPEN 0FFICE
CL
CL
CL
CL
VAULT
VAULT
VAULT
VAULT
VAULT
VAULT
VAULT
VAULT
CLCL CL CL
2453-E
06"12"18" 1' 2' 3' 4'
3"9"15"
CAUTION: IF THIS DRAWING IS A REDUCTION THIS GRAPHIC SCALE MUST BE USED
AD202
EXISTING AND DEOLITION
OF
R
EV
IS
IO
N N
O
TE
S
GR
AP
HI
C
SC
AL
E
MARK DATE DESCRIPTION
AGF
CE
RT
IFI
CA
TIO
NS
SHEET SIZE:
SHEET
DISCIPLINE SHEET TYPE SEQUENCE
DRAWING NO.
DRAWING TITLE
FILE NAME
CHECKED BY
DRAWN BY DATE DRAFTED:
PROJECT NO.
GSA PM
SUB. DATE
SUBMISSION
DESCRIPTION
PROJECT
TITLE
BUILDING NOs.
OTHER
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
DR
AW
IN
G
PR
OJ
EC
T
BU
ILD
IN
G
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
CO
NT
RA
CT
OR
S
FLOOR NO.
FACILITY CODE
PROJECT
A/E TASK NO.
CONS. WORK
24 x 36
DC-
1 2 3 4 5
A
B
C
D
WASHINGTON, DC
MERIDIEN GROUP / CITADEL DCA
LSP
MERIDIEN GROUP, LLC
208 SOUTH KING ST. SUITE 303
LEESBURG, VA 20175
(703) 777-8285 www.meridiengroupllc.com
BARBARA CHOATE
04/14/2026
2ND FLOOR
MT2453_26_004
28 APRIL 2026
100% SUBMISSION FOR REVIEW
FEDERAL OFFICE BUILDING
N
KE
Y
PL
AN
1 2 3 4 5
CAUTION: IF THIS DRAWING IS A REDUCTION THIS GRAPHIC SCALE MUST BE USED
RENOVATION OF SECOND FLOOR SUITE
MT 2453 OFFICE RENOVATION
NO
RT
H
PROJECT LOCATION
NORTH COURTYARD
1/2" = 1' - 0"
GENERAL NOTES
1. CONTRACTOR TO VERIFY EXISTING CONDITIONS BEFORE STARTING. NO FORENSIC DEMOLITION WAS
CONDUCTED AT THE TIME OF THE SURVEY. DISCREPANCIES MIGHT BE ENCOUNTERED BETWEEN
ACTUAL CONDITIONS AND DRAWINGS. INFORM COR PRIOR TO PROCEEDING w/ WORK
2. IN CASE OF CONFLICTS BETWEEN PLANS, KEY NOTES, SECTIONS, DETAILS AND SPECIFICATIONS, THE MOST
STRINGENT REQUIREMENT APPLIES
3. ALL DIMENSIONS ARE GIVEN FROM FINISH WALL OR PARTITION TO FINISH WALL OR PARTITION
4. ALL WORK PROVIDED UNDER THIS CONTRACT SHALL BE NEW UNLESS SPECIFICALLY MARKED "EXISTING,"
"EXTG", OR "(E)"
5. BEST PRACTICES, METHODS AND MATERIALS, MUST BE FOLLOWED AT ALL TIMES. ANY ITEM NOT SPECIFICALLY LISTED OR SHOWN ON THE CONTRACT DOCUMENTS BUT NECESSARY FOR THE COMPLETION OF THE
PROJECT, SHALL BE CONSIDERED PART OF THE CONTRACT'S SCOPE OF WORK
6. THE G.C. SHALL CLEAN UP ALL ACTIVE WORK AREAS AFTER EACH DAY’S WORK. THE G.C. IS RESPONSIBLE
FOR THE REMOVAL AND PROPER DISPOSAL OF ALL WORK RELATED TRASH AND DEBRIS
7. PROTECT ALL GOVERNMENT PROPERTY ENCOUNTERED AT THE JOB SITE AGAINST DAMAGE. ALL DAMAGES CAUSED BY THE CONTRACTOR SHALL BE REPAIRED OR REPLACED TO MATCH EXISTING AND TO THE
SATISFACTION AND APPROVAL OF THE COR
8. AREA OF WORK MUST BE ISOLATED FROM THE REST OF ADJACENT AREAS. PROTECT ALL SURFACES, EQUIP-
MENT& FURNITURE PRIOR TO START OF WORK.
9. REMOVE ALL HVAC COVERS AS NEEDED. SEAL EXPOSED DUCTS AND VENTS TO PREVENT INTRODUCING DUST
DUST INTO THE SYSTEM. (REMOVED COVERS MUST BE REINSTALLED AT END OF THE JOB)
10. PROTECT ALL HISTORIC FABRIC DURING DEMOLITION AND CONSTRUCTION.
11. DO NOT REMOVE HISTORIC FABRIC UNLESS SPECIFICALLY NOTED ON DOCUMENTS. ANY HISTORIC FABRIC
REMOVED MUST BE RETURNED TO COR. DO NOT DISPOSE.
LEGEND
DEMOLITION & PROTECTION NOTES
NO
RT
H
C-1 1/2" = 1'-0"
EXISTING & DEMOLITION : SECTION 4 - 4A-1
1/2" = 1'-0"
EXISTING & DEMOLITION : SECTION 3 - 3
3 3
EXISTING ORIGINAL MASONRY WALL AND BASEBOARD TO REMAIN UNALTERED. PROTECT DURING
CONSTRUCTION PRIOR TO ITS PREP FOR REFINISHING
EXISTING LIGHT FIXTURES AND FIRE SUPPRESSION SYSTEM TO REMAIN UNALTERED. PROTECT DURING
CONSTRUCTION PRIOR TO ITS PREP FOR REFINISHING
EXISTING NOT ORIGINAL WALL AND BASEBOARD TO REMAIN UNALTERED. PROTECT DURING
CONSTRUCTION PRIOR TO ITS PREP FOR REFINISHING
EXISTING NON-ORIGINAL PANELED PARTITION W/ BASEBOARD TO REMAIN UNALTERED. PROTECT DURING
CONSTRUCTION PRIOR TO ITS PREP FOR REFINISHING
EXISTING NON-ORIGINAL PARTITION W/ BASEBOARD AND CLERESTORY WINDOWS TO REMAIN
UNALTERED. PROTECT DURING CONSTRUCTION PRIOR TO ITS PREP FOR REFINISHING
EXISTING DOOR ASSEMBLY TO REMAIN. DO NOT ALTER AND PROTECT DURING CONSTRUCTION PRIOR
TO ITS PREP FOR REFINISHING
ORIGINAL HISTORIC VAULTED PLASTER CEILING, CROWN MOLDING AND CEILING RIB MOLDING TO REMAIN UNALTERED. NEW PARTITIONS SHOULD BE BUILD AS PER WALL SECTIONS TO AVOID DAMAGING
THE HISTORIC ELEMENTS. HISTORIC PLASTER MOLDINGS MUST NOT BE CUT OR ALTERED
EXISTING ORIGINAL BUILT-IN BOOK CASE TO REMAIN UNALTERED. PROTECT DURING CONSTRUCTION
PRIOR TO REFINISHING
1 ERECT ZIP WALLS OR EQUIVALENT FROM TATE FLOOR SYSTEM TO HISTORIC CEILING TO ENCLOSE PROJECT
AREA (NOT DEPICTED ON THIS DRAWING)
EXISTING NON-ORIGINAL PARTITION W/ BASEBOARD AND CLERESTORY WINDOWS TO BE REMOVED
EXISTING 2-PANEL DOOR W/ FLAT CASING TO BE REMOVED. DISPOSE OF CASING AND RETURN HARDWARE
TO COR.
NOTE: IF DOOR ASSEMBLY (DOOR LEAF + FRAME) IS IN GOOD CONDITION AND IT IS APPROVED BY TREASURY'S COR, KEEP THE ASSEMBLY ON SITE DOOR TO BE REUSED AT NEW OFFICE LOCATION.
EXISTING MILLWORK AND CROWN MOLDING AFFECTED BY THE REMOVAL OF THE PARTITION TO BE RESTORED
DEMOLISH EXISTING CARPET FROM PROJECT AREA. REMOVE GLUE AND CLEAN FLOOR SYSTEM PANELS AS NEEDED. STORE PANELS AND CARPET ON SITE AND REINSTALL ALTERED AT THE COMPLETION OF THE JOB.
EXISTING WINDOW WITH ORIGINAL CAST IRON SURROUND TO REMAIN UNALTERED. PROTECT DURING
CONSTRUCTION PRIOR TO ITS PREP FOR REFINISHING THE SURROUND AND SILL
EXISTING FCU TO REMAIN. COVER DURING CONSTRUCTION TO PREVENT DUST FROM ENTERING THE VENTS
EXISTING FCU MILLWORK TO REMAIN UNALTERED. DO NOT ALTER AND PROTECT DURING CONSTRUCTION
PRIOR TO ITS PREP FOR REFINISHING
EXISTING FLOOR SYSTEM AND ELECTRICAL BOXES TO REMAIN UNALTERED. PROTECT FLOOR BOXES DURING
CONSTRUCTION
11 11 11 11
10 10
7 87 8 8 8 8 87 8 7 8
6 6 6 6
TYP
2457A
-E
3'-2" R.O.
ELECTRICAL
CLOSET
2453E
OFFICE
OFFICE
ELEV 0'- (± 6")
ELEV 0'- (± 6" VIF)
11" 7'-4"
3'-0"
5' -1
0"
1' -9
6'-6"
201CL
202CL
203CL
204CL
19'-01 4"
V.I.F.
S
2457A
-E
ELECTRICAL
CLOSET
201CL
202CL
203CL
204CL
2453 E
OFFICE
OFFICE
CAUTION: IF THIS DRAWING IS A REDUCTION THIS GRAPHIC SCALE MUST BE USEDCAUTION: IF THIS DRAWING IS A REDUCTION THIS GRAPHIC SCALE MUST BE USED
A-101
NEW WORK
OF
R
EV
IS
IO
N N
O
TE
S
GR
AP
HI
C
SC
AL
E
MARK DATE DESCRIPTION
AGF
CE
RT
IFI
CA
TIO
NS
SHEET SIZE:
SHEET
DISCIPLINE SHEET TYPE SEQUENCE
DRAWING NO.
DRAWING TITLE
FILE NAME
CHECKED BY
DRAWN BY DATE DRAFTED:
PROJECT NO.
GSA PM
SUB. DATE
SUBMISSION
DESCRIPTION
PROJECT
TITLE
BUILDING NOs.
OTHER
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
DR
AW
IN
G
PR
OJ
EC
T
BU
ILD
IN
G
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
CO
NT
RA
CT
OR
S
FLOOR NO.
FACILITY CODE
PROJECT
A/E TASK NO.
CONS. WORK
24 x 36
DC-
1 2 3 4 5
A
B
C
D
WASHINGTON, DC
MERIDIEN GROUP / CITADEL DCA
LSP
MERIDIEN GROUP, LLC
208 SOUTH KING ST. SUITE 303
LEESBURG, VA 20175
(703) 777-8285 www.meridiengroupllc.com
BARBARA CHOATE
100% SUBMISSION FOR REVIEW
KE
Y
PL
AN
1 2 3 4 5
CAUTION: IF THIS DRAWING IS A REDUCTION THIS GRAPHIC SCALE MUST BE USED
04/14/2026
2ND FLOOR
MT2453_26_004
28 APRIL 2026
FEDERAL OFFICE BUILDING
RENOVATION OF SECOND FLOOR SUITE
MT 2453 OFFICE RENOVATION
N
NO
RT
H
PROJECT LOCATION
NORTH COURTYARD
NEW WALL AS PER WALL TYPE
EXISTING WALL TO REMAIN
NEW DOOR ASSEMBLYX-
XX
X
EXISTING DOOR ASSEMBLY WITHIN THE AREA
OF WORK TO REMAIN
X-XXX
DOOR NUMBER
EXISTING DOOR ASSEMBLY OUTSIDE THE AREA
OF WORK TO REMAIN
A-1 1/4" = 1'-0"
1. CONTRACTOR TO VERIFY EXISTING CONDITIONS BEFORE STARTING. NO FORENSIC DEMOLITION WAS
CONDUCTED AT THE TIME OF THE SURVEY. DISCREPANCIES MIGHT BE ENCOUNTERED BETWEEN
ACTUAL CONDITIONS AND DRAWINGS. INFORM COR PRIOR TO PROCEEDING w/ WORK
2. IN CASE OF CONFLICTS BETWEEN PLANS, KEY NOTES, SECTIONS, DETAILS AND SPECIFICATIONS, THE
MOST STRINGENT REQUIREMENT APPLIES
3. ALL DIMENSIONS ARE GIVEN FROM FINISH WALL OR PARTITION TO FINISH WALL OR PARTITION
4. ALL WORK PROVIDED UNDER THIS CONTRACT SHALL BE NEW UNLESS SPECIFICALLY MARKED
"EXISTING," "EXTG", OR "(E)"
5. BEST PRACTICES, METHODS AND MATERIALS, MUST BE FOLLOWED AT ALL TIMES. ANY ITEM NOT
SPECIFICALLY LISTED OR SHOWN ON THE CONTRACT DOCUMENTS BUT NECESSARY FOR THE
COMPLETION OF THE PROJECT, SHALL BE CONSIDERED PART OF THE CONTRACT'S SCOPE OF WORK
6. THE CONTRACTOR SHALL CLEAN UP ALL ACTIVE WORK AREAS AFTER EACH DAY’S WORK. THE CONTRACTOR IS RESPONSIBLE FOR THE REMOVAL AND PROPER DISPOSAL OF ALL WORK RELATED
TRASH AND DEBRIS
7. PROTECT ALL GOVERNMENT PROPERTY ENCOUNTERED AT THE JOB SITE AGAINST DAMAGE. ALL DAMAGES CAUSED BY THE CONTRACTOR SHALL BE REPAIRED OR REPLACED TO MATCH EXISTING AND
TO THE SATISFACTION AND APPROVAL OF THE COR
8. AREA OF WORK MUST BE ISOLATED FROM THE REST OF ADJACENT AREAS. PROTECT ALL SURFACES, EQUIPMENT& FURNITURE PRIOR TO START OF WORK.
9. REMOVE ALL HVAC COVERS AS NEEDED. SEAL EXPOSED DUCTS AND VENTS TO PREVENT INTRODU- CING DUST INTO THE SYSTEM. (REMOVED COVERS MUST BE REINSTALLED AT END OF THE JOB)
10. PROTECT ALL HISTORIC FABRIC DURING DEMOLITION AND CONSTRUCTION.
11. DO NOT REMOVE HISTORIC FABRIC UNLESS SPECIFICALLY NOTED ON DOCUMENTS. ANY HISTORIC
FABRIC REMOVED MUST BE RETURNED TO COR. DO NOT DISPOSE.
A-3 1/4" = 1'-0"
GENERAL NOTES SYMBOLS LEGEND
EXISTING FCU AND ASSOCIATED PIPING CABINET TO REMAIN AS IS. PROTECT DURING
CONSTRUCTION PRIOR TO REFINISHING
NOT IN THE SCOPE OF WORK
KEY NOTES
NEW 4 7/8" PARTITION ( 3 5/8" 16 GA STEEL STUDS, 5/8" GWB EACH SIDE, & 3 1/2" BATT INSULATION) TO EXTEND FROM TOP OF TATE RAISED FLOOR TO HISTORIC PLASTER CEILING. SECTION UNDER THE FLOOR SYSTEM TO RECEIVE (2) LAYERS OF GWB EACH SIDE. SEE ROOM SECTIONS AND WALL TYPE. FINISHES AS
PER FINISHES SCHEDULE.
EXISTING MILLWORK TO REMAIN UNALTERED. PROTECT DURING CONSTRUCTION. FRAME NEW PARTITION AROUND MILLWORK AS PER SECTION AND FRAMING PLAN. DO NOT ALTER MILLWORK. REFINISH IN KIND
AS PER FINISHES SCHEDULE
REMOVE PORTION OF EXISTING NOT ORIGINAL BASEBOARD AS NEEDED TO INSTALL NEW PARTITION
WHERE THE NEW PARTITION IS ATTACHED TO EXISTING EXTERIOR MASONRY & PLASTER WALL INSTALL A
MOISTURE BARRIER THE WIDTH OF THE STUDS FULL HEIGHT
NEW DOOR ASSEMBLY CONSISTING OF A 2-PANEL DOOR LEAF & FLAT CASING PAINTED TO MATCH EXACTLY EXISTING DOOR ASSEMBLY 2453-E ( HEIGHT, PROFILE AND WIDTH OF CASING) HARDWARE WILL
DIFFER TO COMPLY WITH ADA. SEE DOOR AND HARDWARE SCHEDULE
NOTE: IF EXISTING DOOR 2453 E IS USABLE AND IT IS APPROVED BY TREASURY'S COR, REINSTALL EXISTING ASSEMBLY, LEAF AND FRAME, BUT INSTALL NEW HARDWARE AS PER SCHEDULE AND CASING
INSTALL NEW CARPET ON CLEAN FLOOR SYSTEM PANELS AS PER FINISHES SCHEDULE. FOLLOW THE
MANUFACTURER SPECIFICATIONS FOR INSTALLATION
EXISTING ORIGINAL MASONRY WALL AND BASEBOARD TO REMAIN UNALTERED. PROTECT DURING
CONSTRUCTION
EXISTING WINDOW WITH ORIGINAL CAST IRON SURROUND TO REMAIN UNALTERED. PROTECT DURING CONSTRUCTION. REFINISH CAST IRON SURROUND, JAMBS AND SILL AS PER FINISHES SCHEDULE (IN KIND)
HISTORIC CROWN MOLDING AND CEILING RIB MOLDING TO REMAIN. NEW PARTITIONS SHOULD BE BUILD AS PER WALL SECTIONS TO AVOID DAMAGING THE HISTORIC ELEMENTS. HISTORIC PLASTER MOLDINGS
MUST NOT BE CUT OR ALTERED IN ANY MANNER
EXISTING FCU TO REMAIN. COVER DURING CONSTRUCTION TO PREVENT DUST FROM ENTERING THE VENTS.
REFINISH MILLWORK WITHIN ROOM 2453-D AS PER FINISHES SCHEDULE (IN KIND)
NEW PARTITION TO RECEIVE 34" THICK STRAIGHT BASEBOARD (PAINTED) TO MATCH THE HEIGHT OF THE
FIRST STEP OF THE EXISTING, ORIGINAL BASEBOARD ON BOTH SIDES
PATCH AND PREP ENTIRE SPACE FOR NEW PAINT, ALL ELEMENTS THAT ARE CURRENTLY PAINTED INCLUDED (WALLS, CEILING, CROWN MOLDING, BASEBOARD, FCU CABINETS, WINDOWS, DOORS AND NICHE) REFINISH
ALL COMPONENTS AS PER FINISHES SCHEDULE
FOR PLASTER REPAIRS, FOLLOW RESTORATION GUIDELINES INCLUDED UNDER THE HEADING "PLASTER REPAIRS AND RESTORATION METHODS AND MATERIALS" ON A-102. DO NOT USE JOINT OR SPACKLING
COMPOUND.
DO NOT USE WOOD FILLERS NOT LABELED FOR THAT PURPOSE TO REPAIR HISTORIC AND NON-HISTORIC
ELEMENTS
NEW SYSTEMS FURNITURE BY TREASURY
INSTALL A FIRE ALARM DEVICE COMBINATION SPEAKER AND ADA STROBE DEVICE. WALL MOUNTED
CD= CANDELA RATING
1/4" =1'-0" 6"
12"36" 1' 2' 3' 4'
30"
5' 6' 7' 8'
18"
24"
14 NEW SYSTEMS FURNITURE BY TREASURY
NEW WORK | FLOOR PLAN NEW WORK | FLOOR PLAN WITH NEW FURNITURE
XXcd
COMBINATION SPEAKER AND ADA
STROBE DEVICE. WALL MOUNTED
CD= CANDELA RATING
201CL
202CL
203CL
204CL
VAULT
VAULT
VAULT
VAULT
VAULT
VAULT
VAULT
VAULT
VAULT
VAULT
ELECTRICAL
CLOSET
2453 E
OFFICE
OFFICE
EXISTING HISTORIC VAULTED, PLASTER CEILING TO REMAIN UNALTERED.
PROTECT DURING CONSTRUCTION
EXISTING PENDANT LIGHT FIXTURE TO REMAIN AS IS. PROTECT DURING CONSTRUCTION
EXISTING SPRINKLER HEAD TO REMAIN UNALTERED
NOT IN THE SCOPE OF WORK
CAUTION: IF THIS DRAWING IS A REDUCTION THIS GRAPHIC SCALE MUST BE USEDCAUTION: IF THIS DRAWING IS A REDUCTION THIS GRAPHIC SCALE MUST BE USED
A-102
NEW WORK RCP
OF
R
EV
IS
IO
N N
O
TE
S
GR
AP
HI
C
SC
AL
E
MARK DATE DESCRIPTION
AGF
CE
RT
IFI
CA
TIO
NS
SHEET SIZE:
SHEET
DISCIPLINE SHEET TYPE SEQUENCE
DRAWING NO.
DRAWING TITLE
FILE NAME
CHECKED BY
DRAWN BY DATE DRAFTED:
PROJECT NO.
GSA PM
SUB. DATE
SUBMISSION
DESCRIPTION
PROJECT
TITLE
BUILDING NOs.
OTHER
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
DR
AW
IN
G
PR
OJ
EC
T
BU
ILD
IN
G
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
CO
NT
RA
CT
OR
S
FLOOR NO.
FACILITY CODE
PROJECT
A/E TASK NO.
CONS. WORK
24 x 36
DC-
1 2 3 4 5
A
B
C
D
WASHINGTON, DC
MERIDIEN GROUP / CITADEL DCA
LSP
MERIDIEN GROUP, LLC
208 SOUTH KING ST. SUITE 303
LEESBURG, VA 20175
(703) 777-8285 www.meridiengroupllc.com
BARBARA CHOATE
100% SUBMISSION FOR REVIEW
KE
Y
PL
AN
1 2 3 4 5
CAUTION: IF THIS DRAWING IS A REDUCTION THIS GRAPHIC SCALE MUST BE USED
04/14/2026
2ND FLOOR
MT2453_26_004
28 APRIL 2026
FEDERAL OFFICE BUILDING
RENOVATION OF SECOND FLOOR SUITE
MT 2453 OFFICE RENOVATION
N
NO
RT
H
PROJECT LOCATION
NORTH COURTYARD
NEW WALL AS PER WALL TYPE
EXISTING WALL TO REMAIN
NEW WORK | REFLECTED CEILING PLANA-1
1/4" = 1'-0"
1. CONTRACTOR TO VERIFY EXISTING CONDITIONS BEFORE STARTING. NO FORENSIC DEMOLITION WAS
CONDUCTED AT THE TIME OF THE SURVEY. DISCREPANCIES MIGHT BE ENCOUNTERED BETWEEN
ACTUAL CONDITIONS AND DRAWINGS. INFORM COR PRIOR TO PROCEEDING w/ WORK
2. IN CASE OF CONFLICTS BETWEEN PLANS, KEY NOTES, SECTIONS, DETAILS AND SPECIFICATIONS, THE
MOST STRINGENT REQUIREMENT APPLIES
3. ALL DIMENSIONS ARE GIVEN FROM FINISH WALL OR PARTITION TO FINISH WALL OR PARTITION
4. ALL WORK PROVIDED UNDER THIS CONTRACT SHALL BE NEW UNLESS SPECIFICALLY MARKED
"EXISTING," "EXTG", OR "(E)"
5. BEST PRACTICES, METHODS AND MATERIALS, MUST BE FOLLOWED AT ALL TIMES. ANY ITEM NOT
SP…