Questions and Answers:
1. Question:
If available, please provide single line diagrams and record drawings for the Medium and low voltage Electrical distribution system components which requiring Arc Flash analysis described by the Scope of Work.
Answer: Daigram has been added as an item to the FBO.GOV package
2. Question:
Please clarify if Distribution panels, MCC's etc. less than 240V shall be included in study or to what extent they are to be labeled, see C.1.3.
Answer: If labeling is not required by NEC 70E, minimal PPE Category label shall be placed on the electrical distribution panel..
3. Question:
Refer to C.1.5; is an equipment study comparing the calculated SCR to existing equipment short circuit interrupting ratings required and if so how far do we carry that verification into the distribution system?
Answer: Building point of entry
4. Question:
Items C2.2 and C.4.1; imply that an overcurrent protective device coordination study is required. Please confirm that a coordination study is part of this contract and if so how far do we carry that verification into the distribution system?
Answer: Overcurrent protective device coordination study is not required. Short circuit and arc flash calculations will be required.
5. Question:
Please confirm the duration to complete the entire job shall be 30 days.
Answer: Start within 15 days of award. Job shall be completed within 30 days of start.
6. Question:
Does the study include the CDC, WWTP, WTP and PX mech. at the Coleville facility?
Answer: WWTP and the WTP only