M0026323Q0018
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
SECTION C - DESCRIPTIONS AND SPECIFICATIONS
The following have been added by full text:
QUESTIONS AND ANSWERS
M0026323Q0018 Amendment 0001
| Who will remove old units? |
| Per paragraph 17.1.2 of the Performance Work Statement of the solicitation, “The successful will be responsible for the disposal and removal of old machines. |
Will the government provide the contractor with a secure location to offload the new units and store them during the installation process?
No. Per paragraph 17.1.2 of the Performance Work Statement, “Upon removal, the old machines will become the successful contractor’s property and responsibility. The successful contractor will not be allowed to store any of the removed washers and dryers on base past the submitted phase in/out period.”
Phase In/Out time period shall not span more than 60-90 days after the start of the contract
| Please provide the electrical requirements for the 60 washers and 60 dryers |
| Per paragraph 4.2.1 |
Washer specifications. Contractor shall provide washers in accordance with the following specifications:
1. Industrial front load, single stack clothes washer.
1. ii. Washers shall have leveling capability for proper installation;
1. iii. The contractor shall follow all manufacturer installation and maintenance instructions.
1. If washers are equipped with coin buttons or switches, the coin slot shall be disabled; blocked or plugged.
| Cylinder Diameter |
| 24-27 in |
| Cylinder Volume |
| 4-7 cu. Ft |
| Door Opening Size |
| 14-17 in |
| Door Bottom to Floor |
| 14-15 in |
| Water Inlet Connection |
| 2x0.75 in |
| Drain height to floor |
| 4-5 in |
| Motor Power Consumption |
| 1-2 HP/0.75-1.5 kW |
| Voltage/Circuit Breaker |
| Hardmount; B: 15-12 – 20-15, X: 15-7 – 15-4 |
Per paragraph 4.2.2
Dryer specification. Contractor shall provide dryers in accordance with the following specifications:
1. Industrial front load, single stack clothes dryer.
1. Dryers shall have leveling capability for proper installation
1. The contractor shall furnish clamps with metal flexible duct venting -5 feet or longer; vent connectors for each dryer
1. The contractor shall follow the manufacturer's instructions for installation and maintenance for each machine
1. v. If dryers are equipped with coin buttons or switches, the coin slot shall be disabled; blocked or plugged
| Cylinder Diameter |
| 26-30 in |
| Cylinder Volume |
| 9-13 cu. Ft |
| Door Opening Size |
| 22-24 in |
| Heat Input Power |
| 21-24 kW |
| Motor HP |
| Fan/Cylinder: 0.5/0.5 |
| Electrical Specs |
| Hardmount; D: 104-118 amps |