About this file

This is a Life Safety Plans document prepared for the Greater Dayton Regional Transit Authority (RTA) in Montgomery County, Ohio, detailing fire safety and egress requirements for a paratransit bus garage facility located at 701 Longworth Street, Dayton, Ohio. The plans illustrate comprehensive life safety provisions for a 66,990 square-foot bus garage complex that includes multiple functional areas: a main bus garage (Building 1), a bus wash facility with fuel-dispensing area (Building 2), and supporting spaces such as electric rooms, IT facilities, restrooms, and janitorial areas. The document specifies occupancy classifications, exit configurations, egress pathways, fire barrier ratings, and portable fire extinguisher locations and signage requirements throughout both facilities. The bus garage is designed with a maximum occupant load of ten drivers during operating hours, while the bus wash and fuel-dispensing facility accommodates a maximum of three drivers simultaneously. Life safety signage is detailed at specific heights: fire extinguisher signs in the bus garage are mounted 12 feet above finish floor on columns and walls, while bus wash fire extinguisher signs are positioned 5 feet above finish floor on metal wall panels. The plans indicate construction document issuances dated February 14, 2025, with revisions through September 18, 2025, and reference coordinated drawing sheets covering code information, material identification, partition types, and energy compliance documentation. All specifications comply with Ohio Building Code requirements and include detailed egress element calculations, exit capacity ratings, and fire-rated construction specifications including 1-hour and 2-hour rated fire barriers and ceiling membranes per UL standards.

The document does not contain specific information regarding pricing terms, contract set-asides, incumbents, funding sources, or bid submission deadlines, as this is a technical architectural drawing set rather than a procurement specification document. The plans serve as supporting documentation for the related RTA Sprinkler System Periodic Testing, Inspections & Maintenance solicitation, providing facility layout and fire safety infrastructure details necessary for contractors to understand the scope of sprinkler system maintenance and testing required across the paratransit bus garage complex.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

F A

C P

RAP

J

D

C

A

4 5 6 7x1 2 6.7

BUS GARAGE

BG1

ELECTRIC

BG2

I.T.

BG3

RESTROOM

BG4

JANITOR

BG5

66,990 SF S-1

2101 / 200

STORAGE

EXIT

1" 0.2"

34"

EXIT

1" 0.2"

34"

EXIT

1" 0.2"

34"

29'-9" CPT

203'-0" EATD

60 MIN

RATED DOOR

60 60 60 60

1.5 3.5 4.5 5.5 6.3

0 0.3 0.6

0.9

A.5 A.6

B.4

B.6

B.7

C.3

C.6

606060

60 60 60 60

SIGN-7 SIGN-7 SIGN-7

SIGN-7 SIGN-7 SIGN-7

SIGN-7 SIGN-7 SIGN-7

B

B.9

C.1

I.T.

BG6

SIGN-7

SIGN-7

SIGN-7

*OCCUPANT LOAD PER

OBC SECTION 1004.5

EXCEPTION. OWNER'S

BUS SCHEDULE NOTES

THAT MAXIMUM

10 DRIVERS WILL PICK

UP AND/OR DROP OFF

BUSES AT SAME TIME

DURING OPERATING

HOURS

EXIT ENCLOSURE OR HOIZONTAL EXIT

EGRESS PATH, PRIMARY

EGRESS PATH, SECONDARY

EXIT

20" 0.2"

32"

200SF B

21001 / 100

BUSINESS

EGRESS ELEMENT

EXIT CAPACITY

(REQUIRED)

EGRESS WIDTH

(REQUIRED)

EGRESS WIDTH

(PROVIDED)

EXIT CAPACITY

(PROVIDED)

REQUIRED ELEMENT

WIDTH FACTOR

SPACE AREA

FUNCTION OF SPACE

USE AND OCCUPANCY

CLASSIFICATION

NUMBER OF REQUIRED EXITS

NUMBER OF OCCUPANTS

REQUIRED S.F. PER

OCCUPANT

0' - 0" CPT

COMMON PATH OF EGRESS

TRAVEL DISTANCE

EXIT SIGN - SEE ELECTRICAL DRAWINGS

CLASS "2A:20B:C" PORTABLE FIRE

EXTINGUISHER, LOCATED IN CABINET

START POINT

NEW 1-HOUR RATED FIRE BARRIER, UL U465

0' - 0" EATD EXIT ACCESS TRAVEL DISTANCE

NEW 1-HOUR RATED CEILING MEMBRANE,

UL I501

CLASS "4A:60B:C" PORTABLE FIRE

EXTINGUISHER, SURFACE-MOUNTED ON BRACKET

NEW 2-HOUR RATED FIRE BARRIER, UL U937

FLEET

VEHICLE

MOTOR

FUEL-DISPENSING

FACILITY

FDF1

FUELING LANE 1

FUELING LANE 2

EXIT

0.6" 0.2"

34"

2,200 SF B

131 / 150

BUSINESS AREAS

75'-2" CPT

W.A

W.B

W.C

W.1 W.2 W.3 W.4

SIGN-8

SIGN-8

W2.2 W2.4 W2.5

WA.3

I.T.

BW4

ELECTRIC

BW5

EQUIPMENT

BW2

BUS WASH

BW1

GENERATOR YARD

*OCCUPANT LOAD PER OBC SECTION

1004.5 EXCEPTION. MAXIMUM 3

DRIVERS WILL USE FACILITY AT SAME

TIME

BUS GARAGE FIRE EXTINGUISHER

SIGNAGE , SIGN-7

SIGNS ABOVE COLUMN-MOUNTED

FIRE EXTINGUISHERS TO BE ATTACHED TO

COLUMN FLANGES, 12'-0" ABOVE FINISH

FLOOR, MEASURED TO THE BOTTOM OF THE

SIGN. INSTALLATION HEIGHT MAINTAINS

VISIBILITY ABOVE BUSES

SIGNS ABOVE PERIMETER WALL-MOUNTED

FIRE EXTINGUISHERS TO BE CENTERED ON

WALL PANELING, 12'-0" ABOVE FINISH

FLOOR, MEASURED TO THE BOTTOM OF THE

SIGN. INSTALLATION HEIGHT MAINTAINS

VISIBILITY ABOVE BUSES

BUS WASH FIRE EXTINGUISHER SIGNAGE, SIGN-8

SIGNS CENTERED ON METAL WALL PANELS

ABOVE FIRE EXTINGUISHERS, 5'-0" ABOVE FINISH

FLOOR, MEASURED TO THE BOTTOM OF THE

SIGN

S T

AT E OF OH

IO

R E

G

IS

T

ERED A RCH

I T E

C T

B.J.

GREENE

1115372

BRYAN J. GREENE

LICENSE #1115372

EXPIRATION DATE 12/31/2025

ISSUANCES

t h i n k c h a m p l i n . c o m

Drawn By

Checked By

Project No.

Client No.

10 S Patterson Blvd Dayton, OH 45402

T 937.224.4474

1400 W Dorothy Lane, Dayton, OH 45409 T: 937.224.0861

2500 Newmark Drive, Miamisburg, OH 45342 T: 937.259.5000

537 East Pete Rose Way, Suite 400, Cincinnati, OH 45202 T: 513.542.3300

/3

/2

:1

:0

P

M

LS001

GDRTA

PARATRANSIT

BUS GARAGE

Checker

Author

LIFE SAFETY PLANS

701 Longworth Street, Dayton, OH 45402

1/16" = 1'-0"LS001

1 BUS GARAGE LIFE SAFETY PLAN LIFE SAFETY LEGEND

3/32" = 1'-0"LS001

2 BUS WASH AND FUEL-DISPENSING FACILITY LIFE SAFETY PLAN SIGNAGE LEGEND

No. Description Date

1 CONSTRUCTION SET 02/14/25

2 REV 1 - PERM COMMENTS 04/11/25

3 BID SET 04/28/25

4 CONFORMED SET 09/18/25

dhenners Callout

PLEASE NOTE THAT THE FIRE EXTINGUISHERS AT THE BUS WASH WILL NOW BE:

3-A:40-B:C

Sheets
G000 - COVER SHEET
G001 - CODE INFORMATION, GENERAL NOTES, ABBREVIATIONS AND SYMBOLS
G002 - MATERIAL I.D. CODES
G003 - PARTITION TYPES
G004 - COMCHECK
LS001 - LIFE SAFETY PLANS