LS Drawings Bldg 111 Bldg 144.pdf

PDF 15 MB Posted

Attached to
Z1DA-- Fire Barrier Maintenance, Inspection and Repaie Services B 4 OY
Solicitation number
36C25224Q0512
Issued by

About this file

This document appears to be a set of drawings related to a federal contract opportunity for fire barrier maintenance, inspection, and repair services at the Clement J. Zablocki Medical Center in Milwaukee, WI.

The key details of the federal contract opportunity are: The contractor shall provide all labor, materials, tools, management, travel, and equipment necessary to inspect and repair the rated wall assemblies located within Buildings 111 and 144 of the medical center, with an approximate combined square footage of 922,455. The work is to begin within 90 days of contract award. The solicitation is being issued by the Department of Veterans Affairs, Veterans Health Administration, Veterans Integrated Service Network 12. This is a solicitation for the required services, with no incumbent contractor identified.

View the file

Other files

File Type Posted
36C25224Q0512 R COMPLETE.docx DOCX document
SOC08 111-7 SOC.pdf PDF
FMD-002.pdf PDF
SOC05 111-4 SOC.pdf PDF
SOC07 111-6 SOC.pdf PDF
SOC11 111-10 SOC.pdf PDF
SOC02 144-1-SOC.pdf PDF
SOC10 111-9 SOC.pdf PDF
SOC12 111-11-SOC.pdf PDF
SOC14 111-13-SOC.pdf PDF
SOC09 111-8 SOC.pdf PDF
SOC01 144-B-SOC RE.pdf PDF
SOC04 111-3 SOC.pdf PDF
SOC03 111-2 SOC.pdf PDF
00S-214.pdf PDF
SOC02 144-PENTHOUSE-SOC.pdf PDF
FMD-058 .pdf PDF
SOC02 111-1 SOC.pdf PDF
SOC06 111-5 SOC.pdf PDF
SOC13 111-12-SOC.pdf PDF
SOC01 144-B-SOC.pdf PDF
SOC01 111-B SOC.pdf PDF
SOC02 144-1-SOC NW.pdf PDF
Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ALL PENETRATIONS ARE SEALED WITH LISTED FIRESTOP MATERIALS FOR

PROTECTING 2-HOUR WALL ASSEMBLIES. PENETRATIONS ARE TO BE FILLED

ON BOTH SIDES OF THE WALL.

ALL DUCT PENETRATIONS ARE PROTECTED BY FIRE DAMPERS.

WALL EXTENDS FROM FLOOR TO DECK ABOVE.

DOORS:

PENETRATIONS:

DUCTS:

WALL CONSTRUCTION:

2-HOUR FIRE BARRIER

THIS APPLIES TO OCCUPANCY SEPARATION WALLS, HORIZONTAL EXITS, AND

STAIRWELLS OF 4 OR MORE STORIES.

1-HOUR FIRE BARRIER

THIS APPLIES TO 1-HOUR RATED ENCLOSURES, HAZARDOUS ROOMS AND

STAIRWELLS 3 STORIES OR LESS.

DOORS REQUIRE THE FOLLOWING:

1. LABELED FRAMES (NFPA 80 4.2.1, NFPA 101 8.3.3.2.2)

2. LABELED 3/4 OR 1-HOUR DOOR (NFPA 101 TABLE 8.3.3.2.2)*

3. VISION PANEL - MAXIMUM SIZE TESTED (NFPA 80 4.4.5 & NFPA 101 TABLE

8.3.3.2.2)

4. POSITIVE LATCHING (NFPA 80 4.3.7)

5. SELF CLOSING OR AUTOMATIC CLOSING (NFPA 80 4.3.7)

6. COORDINATING DEVICES REQUIRED ON DOORS WITH ASTRAGALS THAT

PREVENT LATCHING (NFPA 80 6.4.1.2.1)

7. MAXIMUM 1/8" GAP BETWEEN DOORS (NFPA 80 6.3.1.7)

8. MAXIMUM 3/4" UNDERCUT (NFPA 80 4.8.4.1)

9. MAXIMUM 16" NON-LABELED PROTECTIVE PLATE (NFPA 80 6.4.5.3)

10. STAIRWELL DOORS SWING IN PRIMARY DIRECTION OF TRAVEL (NFPA 101

7.2.1.4.2)

11. SWING IN ANY DIRECTION FOR HAZARDOUS ROOMS (NFPA 101 18/19.3.2.1

& 7.2.1.2)

12. FIRE DOOR ASSEMBLIES SHALL BE INSPECTED AND TESTED ANNUALLY

(NFPA 80 5.2.4.1)

ALL PENETRATIONS ARE SEALED WITH LISTED FIRESTOP MATERIALS FOR

PROTECTING 1-HOUR WALL ASSEMBLIES. PENETRATIONS ARE TO BE FILLED

ON BOTH SIDES OF THE WALL.

STEEL DUCT PENETRATIONS NOT REQUIRED TO BE PROTECTED BY FIRE

DAMPERS.

* 1-HOUR DOORS ARE REQUIRED IN STAIRWELLS THAT ARE 3 STORIES OR LESS.

DOORS:

PENETRATIONS:

DUCTS:

WALL CONSTRUCTION: WALL EXTENDS FROM FLOOR TO DECK ABOVE.

THIS APPLIES TO OCCUPANCY SEPARATION WALLS, HORIZONTAL EXITS, AND STAIRWELLS

OF 4 OR MORE STORIES. THIS COMBINATION WALL IS WHERE A PORTION OF THE 2-HOUR

RATED WALL IS ALSO PART OF THE SMOKE WALL.

DOORS REQUIRE THE FOLLOWING:

1. LABELED FRAMES (NFPA 80 4.2.1; NFPA 101 8.3.3.2.2)

2. LABELED 1 1/2 HOUR DOOR (NFPA 101 TABLE 8.3.3.2.2)

3. VISION PANEL - MAXIMUM SIZE TESTED (NFPA 80 4.4.5 & NFPA 101 TABLE

8.3.3.2.2)

4. POSITIVE LATCHING (NFPA 80 4.3.7)

5. SELF CLOSING OR AUTOMATIC CLOSING (NFPA 80 4.3.7)

6. COORDINATING DEVICES REQUIRED ON DOORS WITH ASTRAGALS THAT

PREVENT LATCHING (NFPA 80 6.4.1.2.1)

7. MAXIMUM 1/8" GAP (NFPA 80 6.3.1.7)

8. MAXIMUM 3/4" UNDERCUT (NFPA 80 4.8.4.1)

9. MAXIMUM 16" NON-LABELED PROTECTIVE PLATE (NFPA 80 6.4.5.3)

10. SWING IN DIRECTION OF TRAVEL EGRESS (NFPA 101 7.2.4.3.8)

11. FIRE DOOR ASSEMBLIES SHALL BE INSPECTED AND TESTED ANNUALLY.

(NFPA 80 5.2.4.1)

ALL PENETRATIONS ARE SEALED WITH LISTED FIRESTOP MATERIALS

FOR PROTECTING 2-HOUR WALL ASSEMBLIES. PENETRATIONS ARE

TO BE FILLED ON BOTH SIDES OF THE WALL.

ALL DUCT PENETRATIONS ARE PROTECTED BY COMBINATION FIRE AND

SMOKE DAMPERS. SMOKE DAMPERS ARE NOT REQUIRED WHERE ADJACENT

SMOKE COMPARTMENTS ARE PROTECTED BY QUICK RESPONSE SPRINKLERS

THROUGHOUT EACH COMPARTMENT.

WALL EXTENDS FROM FLOOR TO DECK ABOVE.

2-HOUR FIRE/SMOKE BARRIER

DOORS:

PENETRATIONS:

DUCTS:

WALL CONSTRUCTION:

SMOKE ZONE BARRIER

SUBSTANTIAL WALLS AND DOORS TO DIVIDE EACH FLOOR INTO COMPARTMENTS FOR

DEFEND IN PLACE EMERGENCY OPERATIONS. IF THE SMOKE ZONE BARRIER WALL IS OF

MASONRY, GYPSUM BOARD, OR METAL LATH AND PLASTER CONSTRUCTION, AND THE

BARRIER WAS CONSTRUCTED POST 1948, THE SMOKE ZONE BARRIER WALLS ARE

REQUIRED TO BE OF 1-HOUR FIRE-RESISTANCE RATING. (NFPA 101, 18.3.7.6) SMOKE ZONE

BARRIER WALLS OF WOOD LATH AND PLASTER CONSTRUCTION ARE PERMITTED TO BE OF

A 12 HOUR FIRE-RESISTANCE RATING (NFPA 101, 19.3.7.3)

DOORS REQUIRE THE FOLLOWING:

1. NON-LABELED FRAME (18.3.7.6)

2. 20-MINUTE OR SOLID WOOD CORE, 13

4" THICK (NFPA 101 18.3.7.6)

3. VISION PANEL - MAXIMUM SIZE TESTED (NFPA 80 4.4.5 & NFPA 101 TABLE

8.3.3.2.2)

4. POSITIVE LATCHING NOT REQUIRED (NFPA 101 18.3.7.8)

5. SELF CLOSING OR AUTOMATIC CLOSING (NFPA 101 18.3.7.8)

6. MAXIMUM 1/8" GAP BETWEEN DOORS (NFPA 80 6.3.1.7)

7. MAXIMUM 3/4" UNDERCUT (NFPA 80 4.8.4.1)

8. UNLIMITED IN HEIGHT PROTECTIVE PLATES PERMITTED (NFPA 101

18/19.3.7.6)

9. SWING IN DIRECTION OPPOSITE OF EACH IF NEW (NFPA 101 18.3.7.6)

10. SWING IN ANY DIRECTION IF EXISTING (NFPA 101 19.3.7.6)

11. SMOKE DOOR ASSEMBLIES SHALL BE INSPECTED AND TESTED

ANNUALLY (NFPA 80 5.2.4.1)

ALL PENETRATIONS ARE SEALED WITH LISTED FIRESTOP MATERIALS FOR

PROTECTING 1-HOUR WALL ASSEMBLIES. PENETRATIONS ARE TO BE FILLED

ON BOTH SIDES OF THE WALL.

ALL DUCT PENETRATION ARE PROTECTED BY SMOKE DAMPERS. SMOKE

DAMPERS ARE NOT REQUIRED WHERE ADJACENT SMOKE COMPARTMENTS

ARE PROTECTED BY QUICK RESPONSE SPRINKLERS THROUGHOUT EACH

COMPARTMENT - UNLESS THE STATE BUILDING CODES REQUIRE DAMPERS.

DOORS:

PENETRATIONS:

DUCTS:

WALL CONSTRUCTION: WALL EXTENDS FROM FLOOR TO DECK ABOVE.

SMOKE RESISTIVE HAZARDOUS ROOM ENCLOSURE

DOORS: DOORS REQUIRE THE FOLLOWING:

1. NON-LABELED FRAME (NFPA 101 19.3.6.3.15)

2. 20-MINUTE OR SOLID WOOD CORE DOOR (NFPA 101 19.3.6.3.1)

3. GLASS DOORS PERMITTED IF SPRINKLERED (NFPA 101

18.3.6.3.1, 19.3.6.3.17, & TABLE 8.3.4.2)

4. POSITIVE LATCHING EXCEPT TOILET ROOMS, SHOWER ROOMS AND SINK

CLOSETS (NFPA 101 18/19.3.6.3.5, 18/19.3.6.3.6

5. SELF-CLOSING NOT REQUIRED (NFPA 101 18/19.3.6.3.11)

6. LIMIT THE TRANSFER OF SMOKE (NFPA 101 18/19.3.6.3.1)

7. MAXIMUM 1" UNDERCUT (NFPA 101 18.3.6.3.1 AND 19.3.6.3.4)

8. UNLIMITED IN HEIGHT PROTECTIVE PLATES PERMITTED (NFPA 101

18/19.3.6.3.12)

9. TRANSFER GRILLS NOT PERMITTED EXCEPT TOILETS,

SHOWER AND SINK CLOSETS (NFPA 101 18/19.3.6.4.2)

10. SWING IN ANY DIRECTION (NFPA 101 7.2.1.4.2)

11. DOORSTOPS NOT PERMITTED (NFPA 101 18/19.3.6.3.10)

THIS APPLIES TO EXISTING SMOKE BARRIER WALLS.

ALL DUCT PENETRATIONS ARE PROTECTED BY SMOKE

DAMPERS. SMOKE DAMPERS ARE NOT REQUIRED WHERE

ADJACENT SMOKE COMPARTMENTS ARE PROTECTED BY QUICK

RESPONSE SPRINKLERS THROUGHOUT EACH COMPARTMENT.

ALL PENETRATIONS ARE SEALED WITH LISTED FIRESTOP MATERIALS FOR

PROTECTING 1 HOUR ASSEMBLIES.

DOORS REQUIRE THE FOLLOWING:

1. NON-LABELED FRAME (NFPA 101 8.5 & 19.3.7.3).

2. CONSTRUCTION THAT RESISTS FIRE FOR 20 MINUTES (NFPA 101 19.3.7.6)

3. VISION PANEL - MAXIMUM SIZE TESTED (NFPA 101 19.3.7.6.2)

4. SELF CLOSING OR AUTOMATIC CLOSING (NFPA 101 19.3.7.8)

6. POSITIVE LATCHING NOT REQUIRED (NFPA 101 19.3.7.8)

7. MINIMUM CLEARANCE NECESSARY FOR PROPER OPERATION (NFPA 101

8.5.4.1)

8. MAXIMUM 3/4" UNDERCUT (NFPA 101 8.5.4.1)

9. UNLIMITED IN HEIGHT PROTECTIVE PLATE (NFPA 101 19.3.7.6.1)

10. SWING IN ANY DIRECTION OF TRAVEL (NFPA 101 19.3.7.8)

11. SMOKE DOOR ASSEMBLIES SHALL BE INSPECTED ANNUALLY (NFPA 80

5.2.4.1)

NOTE: ALL CODE REFERENCES ARE PER THE 2021 EDITION OF NFPA 101 LIFE SAFETY CODE AND THE OTHER APPLICABLE CODES.

FEDERAL FACILITIES FOLLOW 2021 LIFE SAFETY CODE.

HEALTH CARE OCCUPANCY NON-RATED CORRIDOR

CORRIDOR WALLS SHALL BE CONTINUOUS FROM THE FLOOR TO THE UNDERSIDE OR ROOF

DECK ABOVE AND SHALL HAVE A FIRE RESISTANCE RATING OF NOT LESS THAN 1/2 HOUR,

EXCEPT IF SMOKE COMPARTMENT IS SPRINKLERED, THE WALL SHALL BE PERMITTED TO

TERMINATE AT THE CEILING.

30 MINUTE SMOKE BARRIER

WALL CONSTRUCTION:

DUCTS:

PENETRATIONS:

DOORS:

WALL EXTENDS FROM FLOOR TO DECK ABOVE.

DOORS REQUIRE THE FOLLOWING:

1. LABELED FRAMES (NFPA 80 4.2.1; NFPA 101 8.3.3.2.2)

2. LABELED 1 1/2 HOUR DOOR (NFPA 101 TABLE 8.3.3.2.2)

3. VISION PANEL - MAXIMUM SIZE TESTED (NFPA 80 4.4.5 & NFPA 101 TABLE

8.3.3.2.2)

4. POSITIVE LATCHING (NFPA 80 4.3.7)

5. SELF CLOSING OR AUTOMATIC CLOSING (NFPA 80 4.3.7)

6. COORDINATING DEVICES REQUIRED ON DOORS WITH ASTRAGALS THAT

PREVENT LATCHING (NFPA 80 6.4.1.2.1)

7. MAXIMUM 1/8" GAP BETWEEN DOORS (NFPA 80 6.3.1.7)

8. MAXIMUM 3/4" UNDERCUT (NFPA 80 4.8.4.1)

9. MAXIMUM 16" NON-LABELED PROTECTIVE PLATE (NFPA 80 6.4.5.3)

10. SWING IN PRIMARY DIRECTION OF TRAVEL (NFPA 101 7.2.4.3.8)

11. FIRE DOOR ASSEMBLIES SHALL BE INSPECTED AND TESTED ANNUALLY.

(NFPA 80 5.2.4.1)

DOORS REQUIRE THE FOLLOWING:

1. NON-LABELED FRAME (NFPA 101 18.3.6.3.1 & 19.3.6.3.15)

2. CONSTRUCTION THAT RESISTS FIRE FOR 20 MINUTES OR SOLID WOOD

CORE (NFPA 101 18/19.3.6.3.1)

3. VISION PANEL - MAXIMUM SIZE TESTED (NFPA 101 18/19.3.2.1; 8.4)

4. POSITIVE LATCHING NOT REQUIRED (NFPA 101 18/19.3.6.3.5 & CMS)

5. SELF CLOSING OR AUTOMATIC CLOSING (NFPA 10118.3.6.3.11 & 19.3.2.1.3)

6. MAXIMUM 1/8" GAP PER MANUFACTURES RECOMMENDATION ((NEW) NFPA

101 18.3.6.3.1 /(EXISTING) 19.3.2.1.2 &8.4.3.4)

7. MAXIMUM 3/4" UNDERCUT (NFPA 101 18.3.2.1; 19.3.2.1.2)

8. UNLIMITED HEIGHT IN NEW & EXISTING MAXIMUM 48" PROTECTIVE PLATE

IN RATED ROOMS (NFPA 101 19.3.2.1.4)

9. SWING IN ANY DIRECTION (NFPA 101 7.2.1.4.2)

DOORS:

DUCTS:

EXISTING HAZARDOUS ROOMS:

NO REQUIREMENTS FOR PENETRATIONS ABOVE THE CEILING IF

SPRINKLERED. IF THE SPACE IS NON-SPRINKLERED, THEN THE WALL NEEDS

TO GO TO THE DECK ABOVE.

STEEL DUCT PENETRATIONS ARE NOT REQUIRED TO BE PROTECTED BY FIRE

DAMPERS OR SMOKE DAMPERS.

WALLS ONLY NEED TO GO UP TO THE DROP CEILING IF SPRINKLERED OR UP

TO THE DECK ABOVE IF THERE IS NO CEILING IN THE SPRINKLERED ROOM.

HAZARDOUS ROOMS:WALL CONSTRUCTION:

NON-RATED SMOKE PARTITION

WALL CONSTRUCTION:

DUCTS:

PENETRATIONS:

DOORS:

WALL EXTENDS FROM FLOOR TO CEILING OR DECK ABOVE.

NO MINIMUM REQUIREMENTS.

NO MINIMUM REQUIREMENTS FOR WALL PENETRATIONS ABOVE A

SUSPENDED CEILING. PENETRATIONS BELOW A SUSPENDED CEILING OR

DECK SEALED WITH NON-FIRE-RATED MATERIALS TO BE SMOKE RESISTIVE.

NON-FIRE-RATED DOORS AND FRAMES SELF CLOSING OR AUTOMATIC

CLOSING.

FORMER DECOMMISSIONED SMOKE BARRIER RETAINED AS FIRE ALARM/SPRINKLER ZONE.

BUILDING OCCUPANTS PERMITTED TO DEFEND IN PLACE UNTIL DIRECTED BY THE FIRE

DEPARTMENT PER SECTION 16.7.4.3 OF NFPA 99 AND PRIVATE MODE AUDIBLE

REQUIREMENTS OF SECTION 18.4.5 OF NFPA 72.

(COLOR #230)

(COLOR #5)

(COLOR #3)(COLOR #4)

(COLOR #1)(COLOR #5)

(COLOR #30)

(COLOR #30)

SUITE DESIGNATION

AREA OPEN TO CORRIDOR - WITH SMOKE DETECTION

EXIT STAIR OR PASSAGEWAY

SMOKE RESISTIVE HAZARDOUS AREA

1 HOUR FIRE BARRIER ENCLOSURE

FIRE ALARM/SPRINKLER ZONES

AREA OPEN TO CORRIDOR WITH 24/7 SUPERVISION

- NO SMOKE DETECTION REQUIRED

(Color #2)

(Color #40)

(Color #230)

(Color #4)

(Color #3)

(Color #2)

SYMBOLS LIST

FIRE EXTINGUISHER

EXIT SIGN

F

FAAP

FACP

SPRINKLER SYSTEM RISER

EMERGENCY LIGHT

FIRE ALARM PULL STATION

FIRE ALARM ANNUNCIATOR PANEL

FIRE ALARM CONTROL PANEL

* 2-HOUR DOORS ARE REQUIRED IN STAIRWELLS THAT ARE 4 STORIES OR MORE.

DESCRIPTION PAGE

WALL TYPES

CONSULTANTS KC, LLC

1330 BURLINGTON STREET, SUITE 200

NORTH KANSAS CITY, MO 64116

(816)931-3377

FP&C

PENETRATIONS

FIRE/SMOKE BARRIER PEN-X

AutoCAD SHX Text

DESCRIPTION PAGE

AutoCAD SHX Text Sht. 1 Of 1

AutoCAD SHX Text Date

AutoCAD SHX Text Revisions

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text AutoCAD File Name

AutoCAD SHX Text Building No.

AutoCAD SHX Text Client Project No.

AutoCAD SHX Text Project Title

AutoCAD SHX Text Drawn By

AutoCAD SHX Text Location

AutoCAD SHX Text Designed By

AutoCAD SHX Text

DJB

AutoCAD SHX Text

BWC

AutoCAD SHX Text Checked By

AutoCAD SHX Text Scale:

AutoCAD SHX Text Date

AutoCAD SHX Text

DJB

AutoCAD SHX Text Drawing No.

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text

MILWAUKEE, WISCONSIN

AutoCAD SHX Text

CLEMENT J. ZABLOCKI VAMC

AutoCAD SHX Text

CLEMENT J. ZABLOCKI

AutoCAD SHX Text

VAMC

AutoCAD SHX Text Milwaukee, WI 53295

AutoCAD SHX Text 5000 W. National Ave.

AutoCAD SHX Text 06/12/23

AutoCAD SHX Text

X1 DESCRIPTIONPAGE

AutoCAD SHX Text 23104.00

AutoCAD SHX Text FP&C Project No.

AutoCAD SHX Text Client Review Set

AutoCAD SHX Text 07/15/2023

AutoCAD SHX Text Final Submittal

AutoCAD SHX Text 08/15/2023

1. THE ORIGINAL BUILDING WAS DESIGNED TO THE 1965 EDITION OF NFPA 101, LIFE SAFETY CODE.

2. THE 1960 PUBLIC BUILDING AMENDMENT ACT (PL100-678) REQUIRES ALL FEDERAL AGENCIES TO FOLLOW THE LATEST

EDITIONS OF NATIONALLY RECOGNIZED FIRE AND LIFE SAFETY CODES. THE VA HAS ADOPTED THE NATIONAL FIRE CODES PUBLISHED BY THE NATIONAL FIRE PROTECTION ASSOCIATION. LIFE SAFETY REQUIREMENTS ARE

SPECIFICALLY ADDRESSED IN THE 2018 EDITION OF NFPA 101, LIFE SAFETY CODE.

3. ALL NEW CONSTRUCTION OR BUILDING RENOVATIONS ARE REQUIRED TO COMPLY WITH THE LATEST EDITION OF NFPA 101 OR IT’S REFERENCED STANDARDS. EXISTING BUILDING CONDITIONS ARE REQUIRED TO COMPLY WITH THE APPLICABLE CODES OR STANDARDS AT THE TIME OF BUILDING DESIGN AND THE APPLICABLE PROVISIONS FOR

EXISTING BUILDINGS IN CURRENT EDITIONS OF APPLICABLE CODES AND STANDARDS.

4. OTHER NFPA CODES AND STANDARDS:

4.1. NFPA 10 - PORTABLE FIRE EXTINGUISHERS, 2022 EDITION

4.2. NFPA 13 - SPRINKLER SYSTEMS, 2022 EDITION

4.3. NFPA 14 - STANDPIPE SYSTEMS, 2019 EDITION

4.4. NFPA 20 - FIRE PUMPS, 2022 EDITION

4.5. NFPA 25 - WATER-BASED FIRE PROTECTION SYSTEMS 2023 EDITION

4.6. NFPA 70 - NATIONAL ELECTRIC CODE, 2023 EDITION

4.7. NFPA 72 - NATIONAL FIRE ALARM CODE, 2022 EDITION

4.8. NFPA 75 - ELECTRONIC COMPUTER EQUIPMENT, 2020 EDITION

4.9. NFPA 80 - FIRE DOORS, 2022 EDITION

4.10. NFPA 90A&B - HEATING AND AIR CONDITIONING SYSTEMS, 2021 EDITION

4.11. NFPA 96 - COMMERCIAL COOKING EQUIPMENT, 2021 EDITION

4.12. NFPA 99 - HEALTH CARE FACILITIES CODE, 2021 EDITION

4.13. NFPA 105 - SMOKE DOORS, 2022 EDITION

4.14. NFPA 110 - EMERGENCY POWER SYSTEMS, 2022 EDITION

4.15. NFPA 241 - CONSTRUCTION AND DEMOLITION, 2022 EDITION

APPLICABLE CODES AND STANDARDS

1. SUITES ARE UTILIZED TO ILLUSTRATE AREAS WITH THE SAME FUNCTION, USE OF HALLWAYS OR AISLES AND TO DEFINE THE END OF PUBLIC EXIT CORRIDORS. NO EXIT SIGNS OUTSIDE OF THE SUITE MAY DIRECT OCCUPANTS INTO A SUITE

TO REACH AN EXIT.

2. HEALTH CARE OCCUPANCY SUITES ARE REGULATED BY FUNCTION AND SIZE.

3. HEALTH CARE OCCUPANCY PATIENT SLEEPING SUITES:

3.1. SINGLE EXIT SUITE - 1,000 SQ. FT. (NFPA 101 -19.2.5.7.2.2.B)

3.2. MULTI EXIT SUITE - 5,000 SQ. FT. (NFPA 101 - 19.2.5.7.2.3.A)

3.3. MULTI EXIT SUITE WITH STANDARD RESPONSE SPRINKLERS AND COMPLETE SMOKE DETECTION, OR WITH QUICK

RESPONSE SPRINKLERS - 7,500 SQ. FT. (NFPA 101 - 19.2.5.7.2.3.B)

3.4. MULTI EXIT SUITE WITH DIRECT VISUAL SUPERVISION, QUICK RESPONSE SPRINKLERS AND COMPLETE SMOKE

DETECTION - 10,000 SQ. FT. (NFPA 101 - 19.2.5.7.2.3.C)

4. PATIENT CARE NON - SLEEPING SUITES:

4.1. SINGLE EXIT SUITE - 2,500 SQ. FT. (NFPA 101-19.2.5.7.3.1.B)

4.2. MULTI EXIT SUITE - 10,000 SQ. FT. (NFPA 101 -19.2.5.7.3.2)

4.3. MULTI EXIT SUITE WITH STANDARD RESPONSE SPRINKLERS AND COMPLETE SMOKE DETECTION, OR WITH QUICK

RESPONSE SPRINKLERS -12,500 SQ. FT. (NFPA 101 - 19.2.5.7.3.2.A)

4.4. MULTI EXIT SUITE WITH QUICK RESPONSE SPRINKLERS AND COMPLETE SMOKE DETECTION - 15,000 SQ. FT. (NFPA

101 - 19.2.5.7.3.2.B)

5. HEALTH CARE OCCUPANCY NON - PATIENT - CARE SUITES FOLLOW THE TRAVEL DISTANCE REQUIREMENTS AS LISTED

IN TABLE A.7.6 OF NFPA 101.

6. SUITES IN OTHER OCCUPANCIES ARE NOT REGULATED IN SIZE BUT STILL FOLLOW THE TRAVEL DISTANCE

REQUIREMENTS AS LISTED IN TABLE A.7.6 OF NFPA 101.

SUITES

1. EXITS (STAIRWAYS, HORIZONTAL EXITS AND DIRECT EXTERIOR EXIT DOORS), OTHER THAN EXTERIOR EXIT DOORS THAT ARE OBVIOUSLY AND CLEARLY IDENTIFIABLE AS EXITS. (GLASS DOORS, VISION PANELS OR ADJACENT WINDOWS) SHALL

BE MARKED WITH EXIT SIGNAGE. (NFPA 101 - 7.10.1.2.1)

2. DIRECTIONAL SIGNS REQUIRED WHERE DIRECTION OF TRAVEL IS NOT APPARENT IN AN EXIT ACCESS CORRIDOR. (NFPA 101 - 7.10.2.1)

3. DIRECTIONAL SIGNAGE (EXIT PLACARDS) REQUIRED WITHIN HORIZONTAL COMPONENTS OF EXIT STAIR ENCLOSURES

WHERE EGRESS PATH IS NOT OBVIOUS (NFPA 101 - 7.10.2.2 AND 7.10.1.2.2)

4. MAXIMUM VIEWING DISTANCE TO AN EXIT SIGN IN AN EXIT ACCESS CORRIDOR IS 100 FT. (NFPA 101 - 7.10.1.5.2)

5. EXIT SIGNS SHALL BE INSPECTED MONTHLY. (NFPA 101 - 7.10.9)

6. DIRECTIONAL SIGNAGE (EXIT PLACARDS OR EXIT SIGNS) WITH OR WITHOUT DIRECTIONAL ARROWS SHOULD BE

PROVIDED IN SUITES USED BY THE GENERAL PUBLIC (LESS THAN 50 TOTAL OCCUPANTS) TO DIRECT THE GENERAL

PUBLIC BACK TO THE WAITING AREA. (NFPA 101 - 7.10.2.1)

7. ROOMS OR SUITES OF ROOMS USED FOR 50 OCCUPANTS OR MORE SHALL BE PROVIDED WITH EXIT SIGNAGE. (NFPA 101

- 13.2.10.1 AND 3.3.198.2)

EXIT SIGN REQUIREMENTS

THE VA HAS ELECTIVE ACCREDITATION WITH THE JOINT COMMISSION (TJC) FOR HEALTH CARE FACILITIES. SEE THE MEMORANDUM OF UNDERSTANDING (EFFECTIVE SEPTEMBER 4, 2017) BETWEEN THE VA AND TJC FOR IMPLEMENTATION OF

TJC ENVIRONMENT OF CARE (EC) AND LIFE SAFETY (LS) STANDARDS.

THE VA HAS ELECTIVE ACCREDITATION WITH THE LONG-TERM CARE INSTITUTE, INC. (LTCI) FOR COMMUNITY LIVING CENTERS (CLC). SEE THE CLARIFICATION MEMORANDUM BETWEEN THE VA AND THE LTCI FOR IMPLEMENTATION OF LIFE SAFETY

REQUIREMENTS.

THE FOLLOWING NATIONWIDE VA EQUIVALENCIES HAVE BEEN REVIEWED AND APPROVED BY THE JOINT COMMISSION AND

APPLY TO ALL BUILDINGS:

1. OVERSIZED PROTECTIVE PLATES PERMITTED ON FIRE RATED DOORS

2. BUSINESS OCCUPANCY DEAD END CORRIDORS PERMITTED TO EXCEED 50 FEET

3. SELF-CLOSING DOOR REQUIREMENT FOR CORRIDOR DOORS IN A DORMITORY OCCUPANCY

EQUIVALENCIES

1. THE COMBINATION STANDPIPE AND FIRE SPRINKLER SYSTEM WAS DESIGNED TO NFPA 13 AND NFPA 14.

2. QUICK RESPONSE TYPE SPRINKLERS ARE INSTALLED THROUGHOUT MOST OF THE BUILDING. STANDARD RESPONSE TYPE SPRINKLERS ARE INSTALLED IN THE ELEVATOR MACHINE ROOMS (NFPA 13 - 3.3.4.16).

3. SPRINKLERS WERE INSTALLED IN LIGHT HAZARD AREAS INCLUDING; CORRIDORS, OFFICES, PATIENT CARE AND PATIENT SLEEPING ROOMS AT LIGHT HAZARD 0.10 GPM/1500 SQ. FT. DENSITY. MAXIMUM PROTECTION AREA OF 225 SQ. FT. (NFPA 13 - TABLE

19.2.3.1.1).

4. SPRINKLERS WERE INSTALLED IN ORDINARY HAZARD GROUP I AREAS INCLUDING; LABORATORIES (WITHOUT FLAMMABLE LIQUIDS), MECHANICAL EQUIPMENT ROOMS, ELECTRICAL SWITCH GEAR ROOMS, REPAIR SHOPS AND STORAGE ROOMS UNDER 250

SQ. FT. AT A 0.15 GPM/1500 SQ. FT. DENSITY. MAXIMUM PROTECTION AREA OF 150 SQ. FT. (NFPA 13 - TABLE 19.2.3.1.1).

5. SPRINKLERS WERE INSTALLED IN ORDINARY HAZARD GROUP II AREAS INCLUDING GENERAL STORAGE ROOMS OVER 250 SQ. FT. AND LABORATORIES (WITH THE USE OF FLAMMABLE LIQUIDS) AT A 0.20 GPM/1500 SQ. FT. DENSITY.

6. MAXIMUM DISTANCE FROM SPRINKLERS TO WALLS FOR STANDARD SPRAY SPRINKLERS SHALL NOT EXCEED 7'-6" (NFPA 13 - 10.2.5.2.1). MAXIMUM DISTANCE FROM SPRINKLERS TO WALLS FOR STANDARD SPRAY SPRINKLERS IN SMALL ROOMS (800 SQ. FT.

MAXIMUM) SHALL NOT EXCEED 9' FROM ANY SINGLE WALL (NFPA 13 -10.2.5.2.3).

7. SPRINKLERS SHALL BE INSTALLED UNDER FIXED OBSTRUCTIONS (I.E. DUCTWORK) OVER 4' WIDE (NFPA 13-12.1.10.3.2). THE WIDTH OF DUCT INSULATION NOT A FACTOR FOR SPRINKLERS INSTALLED PRIOR TO THE CURRENT EDITION ON NFPA 13.

SPRINKLERS NOT REQUIRED UNDER NON COMBUSTIBLE OBSTRUCTIONS OVER 4' WIDE WHERE THE BOTTOM OF THE OBSTRUCTION IS A MAXIMUM 24" ABOVE THE FLOOR (NFPA 13 - 9.5.5.3.1).

8. SPRINKLERS SHALL BE INSTALLED A MAXIMUM 12" BELOW A CEILING OR FLOOR/ROOF DECK (NFPA 13 - 10.2.6.1.1.1) OR A MAXIMUM 22" BELOW A FLOOR/ROOF DECK WITH STRUCTURAL MEMBER OBSTRUCTIONS (NFPA 13-10.2.6.1.2).

9. SHELVING ON A WALL OR SHELVING AGAINST A WALL INCLUDING STORAGE THEREON SHALL BE PERMITTED TO EXTEND WITHIN THE 18" SPRINKLERS CLEARANCE BELOW CEILING SPRINKLER DEFLECTORS (NFPA - 13 9.5.5.2).

10. WHERE THE 18" CLEARANCE BETWEEN SPRINKLERS AND SHELVING STORAGE CANNOT BE MAINTAINED, SPRINKLERS SHALL BE INSTALLED IN EVERY AISLE PER NFPA 13 - 9.5.5.2.

11. CEILING MOUNTED OBSTRUCTIONS (I.E. PATIENT LIFT TRACKS) WITHIN THE 8" SPRINKLER DISCHARGE CLEARANCE ARE PERMITTED PER NFPA 13 - TABLE 10.2.7.1.2 AND FIGURE 10.2.7.1.2(a).

12. FLOOR MOUNTED OBSTRUCTIONS (I.E. ROOM DIVIDERS OR SHELVING) WITHIN THE 18" SPRINKLER DISCHARGE CLEARANCE ARE PERMITTED PER NFPA 13 - TABLE 10.2.7.2.2 AND FIGURE 10.2.7.2.2.

FIRE SPRINKLER SYSTEM

1. THE FIRE ALARM SYSTEM WAS DESIGNED TO 2019 EDITION OF NFPA 72, NATIONAL FIRE ALARM CODE.

2. PRIVATE MODE BUILDING OCCUPANT NOTIFICATION IS INSTALLED PER SECTIONS 19.3.4.3.1 AND 9.6.3.6.3 OF NFPA 101-2018 EDITION.

3. PRIVATE MODE AUDIBLE DEVICES (SPEAKERS) ARE INSTALLED IN CORRIDORS AND LARGER ROOMS OR SUITES PER SECTION 18.4.4.1 OF NFPA 72 - 2019 EDITION.

4. PRIVATE MODE VISIBLE DEVICES (STROBES) ARE INSTALLED AT REDUCED QUANTITY AND SPACING PER SECTION 18.6 OF THE NFPA 72 - 2019 EDITION.

5. STROBE CIRCUITS ARE REQUIRED TO BE SYNCHRONIZED IN ACCORDANCE WITH SECTION 18.5.4.3.2(3) OF NFPA 72 - 2019 EDITION.

6. TYPICAL SMOKE DETECTORS HAVE A 21 FT. RADIUS OF COVERAGE AREA (NFPA 72 -17.7.3.2.3.1) SMOKE DETECTORS THAT ARE CONNECTED TO THE BUILDING FIRE ALARM SYSTEM AND LOCATED ON BOTH SIDES OF SMOKE/FIRE DOORS MAY BE SPACED AT

MAXIMUM 21' RADIUS FOR DOOR RELEASE SERVICE (NFPA 72 - 17.7.5.6.1)

7. SMOKE DETECTORS NOT CONNECTED TO THE BUILDING FIRE ALARM SYSTEM AND USED EXCLUSIVELY FOR SMOKE/FIRE DOOR RELEASE SHALL BE LOCATED AND SPACED PER NFPA 2- 17.7.5.6.

8. CEILINGS WITH BEAM DEPTHS OF LESS THAN 10% OF CEILING HEIGHT SHALL BE CONSIDERED A SMOOTH CEILING FOR SMOKE DETECTOR COVERAGE. CEILINGS WITH BEAM DEPTHS GREATER THAN 10% OF CEILING HEIGHT SHALL HAVE REDUCED SMOKE

DETECTOR SPACING COVERAGE (NFPA 72 -17.7.3.2.4.2).

9. SMOKE DETECTORS SHALL BE LOCATED ON THE CEILINGS THE BOTTOM OF BEAMS OR MAXIMUM 12" DOWN FROM THE CEILING TO TOP OF THE DETECTOR (NFPA 72-17.7.3.2.1).

10. SMOKE DETECTORS SHALL NOT BE LOCATED DIRECTLY IN THE AIR STREAM OF SUPPLY AIR REGISTERS (NFPA 72- 17.7.6.3.2).

FIRE ALARM SYSTEM

OCCUPANCY TABLE

BUILDING FLOOR HEALTH CARE

AMBULATORY

HEALTH CARE

BUSINESS INDUSTRIAL DORMITORY TOTAL

111 13 4,380 4,380

111 12 9,650 9,650

111 11 8,982 8,982

111 10 50,943 50,943

111 9 51,630 51,630

111 8 53,222 53,222

111 7 53,222 53,222

111 6 57,880 57,880

111 5 61,140 61,140

111 4 61,140 61,140

111 3 61,140 61,140

111 2 105,503 105,503

111 1 141,528 141,528

111 BASEMENT 137,574 137,574

144 PENTHOUSE 7,013 7,013

144 1 26,417 26,417

144 BASEMENT 31,091 31,091

TOTALS 509,163 194,750 188,517 30,025 0 922,455

DESCRIPTION PAGE

CODE SUMMARY

CONSULTANTS KC, LLC

1330 BURLINGTON STREET, SUITE 200

NORTH KANSAS CITY, MO 64116

(816)931-3377

FP&C

FIRE/LIFE SAFETY LS-X2

AutoCAD SHX Text

DESCRIPTION PAGE

AutoCAD SHX Text Sht. 1 Of 1

AutoCAD SHX Text Date

AutoCAD SHX Text Revisions

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text AutoCAD File Name

AutoCAD SHX Text Building No.

AutoCAD SHX Text Client Project No.

AutoCAD SHX Text Project Title

AutoCAD SHX Text Drawn By

AutoCAD SHX Text Location

AutoCAD SHX Text Designed By

AutoCAD SHX Text

JMZ

AutoCAD SHX Text

BWC

AutoCAD SHX Text Checked By

AutoCAD SHX Text Scale:

AutoCAD SHX Text Date

AutoCAD SHX Text

DJB

AutoCAD SHX Text Drawing No.

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text

MILWAUKEE, WISCONSIN

AutoCAD SHX Text 23104.00

AutoCAD SHX Text

CLEMENT J. ZABLOCKI VAMC

AutoCAD SHX Text

CLEMENT J. ZABLOCKI

AutoCAD SHX Text

VAMC

AutoCAD SHX Text Milwaukee, WI 53295

AutoCAD SHX Text 5000 W. National Ave.

AutoCAD SHX Text 06/12/23

AutoCAD SHX Text

X2 CODE SUMMARY

AutoCAD SHX Text FP&C Project No.

AutoCAD SHX Text Client Review Set

AutoCAD SHX Text 07/15/2023

AutoCAD SHX Text Final Submittal

AutoCAD SHX Text 08/15/2023