List of deficiencies.xlsx

XLSX spreadsheet 13 KB Posted

Attached to
Z1DA--INTERSTITIAL DOOR DEFICIENCIES REPAIRS Federal contract opportunity
Solicitation number
36C26225Q0932
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 22

About this file

The file is a list of deficiencies spreadsheet detailing fire door and access issues across multiple floors of the VAMC San Diego Interstitial Spaces facility. The document comprehensively catalogs 68 specific door-related deficiencies ranging from door closure problems, improper gaps, missing fire-rated labels, broken latches, and unauthorized modifications across floors 1-7. Common issues include door gaps exceeding 1/8 inch, doors with undercuts greater than 3/4 inch, non-functional door closers, disabled fire door mechanisms, and doors lacking proper fire-rated labels.

The related federal contract opportunity (Solicitation Number: 36C26225Q0932) is for "Z1DA--INTERSTITIAL DOOR DEFICIENCIES REPAIRS" issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 22. The solicitation appears directly tied to addressing the documented door deficiencies, with the spreadsheet serving as a detailed inventory of repair requirements across the facility's interstitial spaces. The deficiencies span critical fire safety and operational concerns that will likely require comprehensive door repairs, replacements, and compliance upgrades to meet fire safety standards.

View the file

Other files for this federal contract opportunity

Other files attached to Z1DA--INTERSTITIAL DOOR DEFICIENCIES REPAIRS, newest first.
File Type Posted
36C26225Q0932 0001.docx DOCX document
FMS Vendor File Update Request Form.pdf PDF
W-9 Form.pdf PDF
VA10091.pdf PDF
36C26225Q0932_1.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

ProjectIdLayerLayer HierarchyStatusBICRoomDescription
VAMC San Diego Interstitial Spaces32211-B11-BOpenM&OIS Basement bld 11Broken door on electrical panel.
VAMC San Diego Interstitial Spaces285Floor 1Floor 1OpenM&OIS 1st floor fire wall above EDDoor undercut greater than 3/4 inch.
VAMC San Diego Interstitial Spaces286Floor 1Floor 1OpenM&OIS 1st floor fire wall above EDUndercut greater than 3/4 inch.
VAMC San Diego Interstitial Spaces290Floor 1Floor 1OpenM&OIS 1st floor fire wall above EDFire doors missing required closure. Left open.
VAMC San Diego Interstitial Spaces296Floor 1Floor 1OpenM&OIS 1st floor A1008 transformer roomDoor closure broke. Door not closing.
VAMC San Diego Interstitial Spaces297Floor 1Floor 1OpenM&OIS 1st floor A1008 transformer roomDoor gap greater than 1/8 inch.
VAMC San Diego Interstitial Spaces301Floor 1Floor 1OpenM&OIS 1st floor A1008 transformer roomDoor and frame missing required 2-hour rated labels
VAMC San Diego Interstitial Spaces310Floor 1Floor 1OpenM&OIS 1st floor fire wall doors above EDThe access doors for the fire wall do not have the required fire rated label
VAMC San Diego Interstitial Spaces311Floor 1Floor 1OpenM&OIS 1st floor fire wall doors above EDSeveral fire doors for this wall do not have the required door closure
VAMC San Diego Interstitial Spaces312Floor 1Floor 1OpenM&O1st floor A1011aDoor closer missing on fire door.
VAMC San Diego Interstitial Spaces314Floor 1Floor 1OpenM&O1st floor A1011aBroken door closer.
VAMC San Diego Interstitial Spaces193Floor 2Floor 2OpenM&OIS 2nd floor fire doorGap at top on door.
VAMC San Diego Interstitial Spaces212Floor 2Floor 2OpenM&OIS 2nd floor A2021Door will not close and latch.
VAMC San Diego Interstitial Spaces217Floor 2Floor 2OpenM&OIS 2nd floor fire doorDoor gap greater than 1/8 inch.
VAMC San Diego Interstitial Spaces229Floor 3Floor 3OpenM&OIS 3rd Floor fire doorDoor gap greater than 1/8 inch.
VAMC San Diego Interstitial Spaces233Floor 3Floor 3OpenM&OIS 3rd Floor fire door AC 21 room A3003Gap greater than1/8 inch at top.
VAMC San Diego Interstitial Spaces234Floor 3Floor 3OpenM&OIS 3rd Floor fire doorWall fire door disabled. No closure swing or latching.
VAMC San Diego Interstitial Spaces241Floor 3Floor 3OpenM&OIS 3rd Floor fire doorTop gap greater than 1/8 inch. Missing door frame.
VAMC San Diego Interstitial Spaces247Floor 3Floor 3OpenM&OIS 3rd Floor A3006Door is damaged and undercut greater than 3/4 inch.
VAMC San Diego Interstitial Spaces254Floor 3Floor 3OpenM&OIS 3rd Floor fire doorDoor gap greater than 1/8 inch.
VAMC San Diego Interstitial Spaces258Floor 3Floor 3OpenM&OIS 3rd Floor A3012 AC 19 roomDoor gap greater than 1/8 inch.
VAMC San Diego Interstitial Spaces261Floor 3Floor 3OpenM&OIS 3rd Floor fire doorDoor gap greater than 1/8 inch.
VAMC San Diego Interstitial Spaces275Floor 3Floor 3OpenM&OIS 3rd Floor A3018Door latch is broken. Risk of door jamming.
VAMC San Diego Interstitial Spaces280Floor 3Floor 3OpenM&OIS 3rd Floor at stair 9Door latching is disabled and not working.
VAMC San Diego Interstitial Spaces117Floor 4Floor 4OpenM&OIS 4th floorTop gap is greater than 1/8 inch.
VAMC San Diego Interstitial Spaces120Floor 4Floor 4OpenM&OIS 4th floorGap at top greater than 1/8 inch.
VAMC San Diego Interstitial Spaces122Floor 4Floor 4OpenM&OIS 4th floor AC 25 roomDoor top gap greater than 1/8 inch,
VAMC San Diego Interstitial Spaces127Floor 4Floor 4OpenM&OIS 4th floor at AC 24 room A4005Door latching and closing mechanism is not functional.
VAMC San Diego Interstitial Spaces130Floor 4Floor 4OpenM&OIS 4th floorFire door not latching when tested.
VAMC San Diego Interstitial Spaces138Floor 4Floor 4OpenM&OIS 4th floor fire doorDoor gap greater than 1/8 inch
VAMC San Diego Interstitial Spaces141Floor 4Floor 4OpenM&OIS 4th floor fire doorFire door label is not visible
VAMC San Diego Interstitial Spaces142Floor 4Floor 4OpenM&OIS 4th floor fire doorUndercut greater than 3/4 inch.
VAMC San Diego Interstitial Spaces145Floor 4Floor 4OpenM&OIS 4th floor fire doorGap at top is greater than 1/8 inch.
VAMC San Diego Interstitial Spaces159Floor 4Floor 4OpenM&OIS 4th floor fire doorDoor gap greater than 1/8 inch.
VAMC San Diego Interstitial Spaces161Floor 4Floor 4OpenM&OIS 4th floor fire wallFire door not closing and latching.
VAMC San Diego Interstitial Spaces174Floor 4Floor 4OpenM&OIS 4th floor fire doorDoor has been modified and cut. Need to be replaced with shorter door
VAMC San Diego Interstitial Spaces183Floor 4Floor 4OpenM&OIS 4th floor fire doorTop gap is greater than 1/8 inch.
VAMC San Diego Interstitial Spaces66Floor 5Floor 5OpenM&OTop of fire door gap is greater than 1/8 inch. No seal.
VAMC San Diego Interstitial Spaces75Floor 5Floor 5OpenM&OIS 5th floor AC 28 roomCenter gap greater than 1/8 inch.
VAMC San Diego Interstitial Spaces98Floor 5Floor 5OpenM&OIS 5th floor AC 27 roomFire door broke and not closing and latching.
VAMC San Diego Interstitial Spaces2Floor 6Floor 6OpenM&OIS 6. Fire wallDoor undercut is greater than 3/4 inch.
VAMC San Diego Interstitial Spaces9Floor 6Floor 6OpenM&OIS 6. Fire wallSmoke tight seal missing on fire door.
VAMC San Diego Interstitial Spaces13Floor 6Floor 6OpenM&OIS 6 fire wall doorDoor gap greater than 1/8 inch.
VAMC San Diego Interstitial Spaces16Floor 6Floor 6OpenM&OIS 6 fire wall doorDoor closer and latch is non functional.
VAMC San Diego Interstitial Spaces24Floor 6Floor 6OpenM&OIS 6 fire wall doorChase door spring missing. Not self closing and latch is broke.
VAMC San Diego Interstitial Spaces25Floor 6Floor 6OpenM&OIS 6 fire wall doorUndercut greater than 3/4 inch.
VAMC San Diego Interstitial Spaces38Floor 6Floor 6OpenM&OIS 6 fire wall doorDoor undercut is greater than 3/4 inch.
VAMC San Diego Interstitial Spaces43Floor 6Floor 6OpenM&OIS 6 fire wall doorFire door modified and unauthorized cut. Needs to be replaced.
VAMC San Diego Interstitial Spaces45Floor 6Floor 6OpenM&OA6006.1Fire door modified and unauthorized cut. Needs to be replaced.
VAMC San Diego Interstitial Spaces51Floor 6Floor 6OpenM&OIS 6 fire wall doorFire door undercut is greater than 3/4 inch.
VAMC San Diego Interstitial Spaces52Floor 6Floor 6OpenM&OIS 6. Fire wallDoor undercut greater than 3/4 inch.
VAMC San Diego Interstitial Spaces57Floor 6Floor 6OpenM&OIS 6 fire wall doorUndercut greater than 3/4 inch.
VAMC San Diego Interstitial Spaces59Floor 6Floor 6OpenM&OIS 6 fire wall doorFire door is not operational.
VAMC San Diego Interstitial Spaces63Floor 6Floor 6OpenM&OIS 6 fire wall doorDoor not closing and latching.
VAMC San Diego Interstitial Spaces221Floor 7Floor 7OpenM&OFloor 7 mechanical elevator control room.The fire door undercut is greater than 3/4 inches.