Summary: Bid Set for Lewis County Rainier North Building Tenant Improvement
This is a comprehensive architectural and engineering bid set for the Lewis County Facilities Department's tenant improvement project at the Rainier North Building, located at 185 NW Chehalis Avenue, Chehalis, Washington 98532. The project involves the interior renovation of approximately 4,740 square feet to establish the County's Information Technology Department offices, including new construction of offices, meeting rooms, help desk and reception areas, break room, storage, restrooms, server room, and electrical room. The design is coordinated among KMB Architects (prime architect), Hargis (electrical), Hultz BHU (mechanical), and WSP (structural). The bid set includes detailed architectural drawings covering floor plans, reflected ceiling plans, interior elevations, wall sections, door and window details, casework details, and finish schedules; structural drawings with floor and roof plans and details; mechanical drawings with HVAC floor plan, equipment schedules, and VRF system schematic; and electrical drawings with lighting plans, power plans, and control systems. The project is designed to comply with the 2021 International Building Code, 2021 International Mechanical Code, 2023 National Electrical Code, Washington State Energy Code, and local City of Chehalis amendments. Key design parameters include wind speed of 110 mph (Vult), seismic design category D, 25 psf snow load, and construction type III-B for business occupancy.
The bid set specifies major scope items including interior metal stud framing with 5/8-inch Type X gypsum board, hollow metal doors and frames with hardware, acoustic ceiling tiles and gypsum board ceilings at 9-foot height, resilient flooring and carpet finishes with rubber base, ceramic tile in restrooms, solid surface countertops with casework, and paint finishes. Mechanical work includes installation of a Variable Refrigerant Flow (VRF) system with outdoor unit HP-CU-200 (192 MBH cooling, 215 MBH heating), multiple ceiling cassette indoor units ranging from 8 to 24 MBH, a Dedicated Outside Air System (DOAS) unit rated at 750 CFM, two rooftop cooling units for the server room, electric duct heater, ductwork with appropriate insulation, grilles, and controls. Electrical work encompasses new lighting with recessed troffers and pendant fixtures, occupancy and photosensor controls, power distribution, data and communications rough-in, fire alarm rough-in, and emergency lighting. All equipment weights, electrical requirements, and performance specifications are detailed in the mechanical and electrical schedules. The file contains no explicit pricing information, set-aside designations, incumbent contractor data, or funding source details; these elements would be found in separate bid documents or the formal solicitation notice.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| IT_building_Tenant_improvement.pdf | ||
| Insurance_(2).docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A-251
DOOR NUMBER DESIGNATION -
SEE DOOR SCHEDULE
ROOM NAME & NUMBER
BUILDING SECTION DESIGNATION
SHEET NUMBER WHERE SECTION APPEARS
WALL SECTION DESIGNATION
SHEET NUMBER WHERE SECTION APPEARS
SHEET NUMBER WHERE DETAIL APPEARS
DETAIL NUMBER
TYPE DESIGNATION:
W = WINDOW,
L = LOUVER
R = RELITE
CEILING HEIGHT
CEILING DESIGNATION
INTERIOR ELEVATION NUMBER(S) DESIGNATION
DIRECTION IN ROOM (FILLED ARROW)
SHEET NUMBER WHERE ELEVATION(S) APPEARS
4 2
EXTERIOR ELEVATION DESIGNATION
SHEET NUMBER WHERE ELEVATION APPEARS
Room name
1 REVISION DESIGNATION
XX
202A
LEWIS COUNTY FACILITIES DEPARTMENT
PROJECT LOCATION
AUTHORITY HAVING JURISDICTION
351 NW NORTH STREET
CHEHALIS, WA 98532
DOUG CAREY
CONTACT EMAIL: DOUG.CAREY@LEWISCOUNTY
WA.GOV
PHONE #: (360) 740-1337
COUNTY SITE PARKING
CHEHALIS, WA 98532
DOUG CAREY
CONTACT EMAIL: DOUG.CAREY@LEWISCOUNTY
WA.GOV
PHONE #: (360) 740-1337
CITY OF CHEHALIS BUILDING & PLANNING
DEPARTMENT
1321 S MARKET BLVD
CHEHALIS, WA 98532
CONTACT PERSON: CHELBI BROWNE
CONTACT EMAIL: CBROWNE@CI.CHEHALIS.WA.US
PHONE# (360) 748-0271
ARCHITECT
KMB ARCHITECTS
906 COLUMBIA STREET SW, SUITE 400
OLYMPIA, WASHINGTON 98501
JAMES HILL, RA- PRINCIPAL
360.352.8883
ELECTRICAL
HARGIS
1201 THIRD AVENUE, STE 600
SEATTLE, WA 98101
CONTACT: ERIK STEARNS
EMAIL: ERIK.STEARNS@HARGIS.BIZ
PHONE #: (206) 448-3376
MECHANICAL
HULTZ BHU
1111 FAWCETT AVENUE, SUITE 100
TACOMA, WA 98402
CONTACT: RICHARD HULTZ
EMAIL: RICKH@HULTZBHU.COM
PHONE #: (253) 383-3257
STRUCTURAL
WSP
1001 4TH AVENUE, SUITE 3100
SEATTLE, WA 98154
CONTACT: JASON TORNQUIST
EMAIL: JASON.TORNQUIST@WSP.COM
PHONE #: (206) 409-6534
LOCATION OF PROJECT
1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SAFETY IN THE AREA OF WORK IN
ACCORDANCE WITH ALL SAFETY CODES AND REQUIREMENTS.
2. KEEP ALL AREAS UNDER CONSTRUCTION CLEAN OF DEBRIS CAUSED BY THIS
SCOPE OF WORK. STORE CONSTRUCTION MATERIALS AND EQUIPMENT IN
DESIGNATED AREAS.
3. THE CONTRACTOR IS RESPONSIBLE FOR CHECKING THE SITE CONDITIONS AND
THE PLANS AND TO NOTIFY THE OWNER'S REP / ARCHITECT OF ANY ERRORS OR
OMISSIONS PRIOR TO THE START OF CONSTRUCTION.
4. DO NOT SCALE DRAWINGS. NOTIFY ARCHITECT FOR CLARIFICATION WHERE
NECESSARY.
5. CONTRACTOR SHALL OBTAIN ALL PERMITS REQUIRED BY LOCAL AND STATE
GOVERNING AUTHORITIES.
6. ALL WORK SHALL MEET THE STANDARDS AND SPECIFICATIONS OF THE LOCAL AND
STATE GOVERNING AUTHORITIES. REFERENCE CODES, STANDARDS AND
AMENDMENTS SHALL BE THE EDITION MOST RECENTLY ADOPTED OR IN USE IN THE
JURISDICTION.
7. CONTRACTOR SHALL VERIFY ALL DIMENSIONS IN FIELD AND SHALL COORDINATE
INSTALLATION OF ALL MATERIAL AND/OR EQUIPMENT WHOSE DIMENSIONS ARE
FIXED.
8. CONTRACTOR SHALL COORDINATE THE WORK OF ALL TRADES REQUIRED TO
PERFORM THE WORK. WHERE INSTALLATION AND/OR CONNECTION OF EQUIPMENT
IS NOT SPECIFIED AND WHERE SUCH CONNECTION AND/OR INSTALLATION IS
REQUIRED FOR A COMPLETE AND OPERABLE FACILITY, THE CONTRACTOR SHALL
BE HELD RESPONSIBLE FOR SUCH INSTALLATION AND/OR CONNECTION.
9. CONTRACTOR SHALL BEAR ALL EXPENSE OF REPAIR OR REPLACEMENT OF
UTILITIES OR OTHER PROPERTY DAMAGED BY OPERATIONS IN CONJUNCTION WITH
THE EXECUTION OF THIS WORK.
10. NO PORTION OF THE WORK REQUIRING A SHOP DRAWING OR SAMPLE SUBMISSION
SHALL BE COMMENCED UNTIL THE SUBMISSION HAS BEEN APPROVED BY THE
ARCHITECT. ALL SUCH PORTIONS OF THE WORK SHALL BE IN ACCORDANCE WITH
APPROVED SHOP DRAWINGS AND SAMPLE.
11. ALL SUBCONTRACTORS ARE RESPONSIBLE FOR REVIEWING ENTIRE SET OF
DRAWINGS AND BRINGING ANY DISCREPANCIES TO CONTRACTOR'S AND
ARCHITECT'S NOTICE DURING BIDDING.
GENERAL SEALANT NOTES
1. SEALANT OR CAULK SHALL BE USED AT JOINTS BETWEEN DIFFERENT WALL
MATERIALS (CMU TO GYPSUM BOARD, WOOD OR CASEWORK TO MASONRY,
GWB TO P-LAM, ETC).
2. SEALANT SHALL BE USED AS FILETS AT WALL INTERSECTIONS BETWEEN
WALLS, COUNTERTOPS AND BACK SPLASHES. PAINT EXPOSED ENDS OF
WOOD/PARTICLE BOARD COUNTER TOPS AND TRIM AND FULLY BED
EXPOSED EDGES AND ENDS OF COUNTERTOPS AND BACKSPLASHES
WHERE THEY MEET WALLS.
3. USE SEALANT AROUND WALL, FLOOR AND HARD CEILING PIPE
PENETRATIONS. WHERE ESCUTCHEONS ARE SPECIFIED OR PROVIDED, SET
THE ESCUTCHEON IN A BEAD OF SEALANT.
4. USE CAULK OR SEALANT AT WALL MATERIAL GAPS OF 1/16TH INCH OR
MORE UNLESS THE GAP IS SHOWN AS AN ARCHITECTURAL REVEAL.
THIS PROJECT FOR THE LEWIS COUNTY COMMUNITY DEVELOPMENT
CENTER RENOVATION PROJECT AND DOWNTOWN COUNTY CORE
IMPROVEMENTS INVOLVES THE TENANT IMPROVEMENT OF THE RAINIER
NORTH BUILDING.
THE WORK INVOLVES THE INTERIOR RENOVATION OF APPROXIMATELY
4,740 SF TO SERVE AS THE COUNTY'S IT DEPARTMENT OFFICES.
906 Columbia Street SW, Suite 400
Olympia, Washington 98501
360.352.8883 architects
KMB Project #
SHEET NO.
REVISIONS:
DATE:
ORIGINAL SHEET SIZE = 24 x 36
HALF SIZE REDUCTIONS = 11 x 17
P
LO
T D
A T
E
ARCHITECT
STATE OF WASHINGTON
REGISTERED
/3
/2
:4
8:
P M
7-31-2026
BID SET
GI001
COVER SHEET
LE
W
IS
C
O U
N
TY
R A
IN
IE
R N
O R
TH
B
U
IL
D
IN
G T
I
LE
W
IS
C O
U N
TY
F
A C
IL
IT
IE
S
D
EP
A R
TM
EN
T
N W
N O
R
TH
S
TR
EE
T, C H
EH
A
LI
S
, W A
Fa ci lit ie s D ep ar tm en t
J2037C
LEWIS COUNTY RAINIER NORTH BUILDING TI
LEWIS COUNTY FACILITIES DEPARTMENT
351 NW NORTH STREET, CHEHALIS, WA 98532
J2037C
SCALE: N. T. S.
AREA MAP
SCALE: 1" = 400'-0"
VICINITY MAP
SHEET INDEXDESIGN TEAM - SHEET
DRAWING SYMBOLS
PROJECT INFORMATION
LOCATION OF PROJECT
PROJECT DESCRIPTION GENERAL NOTES
GENERAL
GI001 COVER SHEET
GI201 GENERAL CODE INFORMATION
ARCHITECTURAL
A-122 ENLARGED FLOOR PLAN - NORTH BUILDING
A-153 ENLARGED REFLECTIVE CEILING PLAN - NORTH BUILDING
A-251 ENLARGED PLANS & INTERIOR ELEVAITONS
A-311 WALL SECTIONS
A-502 INTERIOR WALL TYPES
A-541 DOOR AND WINDOW DETAILS
A-561 CEILING DETAILS
A-583 CASEWORK DETAILS
A-585 INTERIOR DETAILS
A-601 DOOR SCHEDULE
A-621 FINISH PLAN & SCHEDULE
STRUCTURE
S0.1 STRUCTURAL GENERAL NOTES
S1.0 STRUCTURAL FLOOR PLAN
S1.1 STRUCTURAL ROOF PLAN
S2.0 DETAILS
MECHANICAL
M-001 MECHANICAL LEGEND AND NOTES
M-002 MECHANICAL SCHEDULES
M-003 MECHANICAL SCHEDULES
M-401 FLOOR PLAN BLDG 2 - ZONING
M-402 HVAC DETAILS
M-403 HVAC DETAILS
M-404 HVAC DETAILS
M-405 VRF SYSTEM SCHEMATIC
ELECTRICAL
E0.01 ELECTRICAL LEGEND AND DRAWING INDEX
E0.02 ELECTRICAL NOTES AND ABBREVIATIONS
E0.03 ELECTRICAL SCHEDULES
E2.01 LEVEL 1 LIGHTING PLAN
E2.01A LEVEL 1 LIGHTING ZONE CONTROL PLAN
E3.01 LEVEL 1 POWER PLAN
E4.01 LEVEL 1 MECHANICAL POWER PLAN
E4.02 ROOF MECHANICAL POWER PLAN
E8.01 ELECTRICAL DETAILS
E8.02 ELECTRICAL DETAILS
E9.01 ELECTRICAL ONE-LINE DIAGRAM
E10.01 PANEL SCHEDULES
DRAWING ABBREVIATIONS
& AND
∠ ANGLE
@ AT
Ø DIAMETER
' FOOT (FEET)
" INCH
d PENNY (NAILS)
# POUNDS
⅊ PLATE or PROPERTY LINE
AB ANCHOR BOLT
ABV ABOVE
ACT ACOUSTIC CEILING TILE
AC ARCHITECTURAL CONCRETE
A/C ASPHALTIC CONCRETE
ACM ALUMINUM COMPOSITE METAL (PANELS)
AD AREA DRAIN
ADD ADDENDUM
ADJ ADJUSTABLE
AF ACCESS FLOOR
AFF ABOVE FINISH FLOOR
AFP ACOUSTICAL FIBERGLASS PANEL
AFG ABOVE FINISH GRADE
AGG AGGREGATE
AHU AIR HANDLING UNIT
ALT ALTERNATE
AMT AMOUNT
APPROX APPROXIMATE
ARCH ARCHITECT(URAL)
ASSY ASSEMBLY
AUTO AUTOMATIC
HM HOLLOW METAL
HNDRL HANDRAIL
HORIZ HORIZONTAL
HR HOUR
HSTL HOLLOW STEEL
HT HEIGHT
HTG HEATING
HTR HEATER
HV HOSE VALVE
HVAC HEATING, VENTILATING & AIR CONDITIONING
ID INSIDE DIAMETER / DIMENSION
IN INCH
INCL INCLUDED
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
INV INVERT
JB JUNCTION BOX
JST JOIST
JT JOINT
L LENGTH
LAM LAMINATE
LAV LAVATORY
LB POUND OR LAG BOLT
LF LINEAR FOOT OR FEET
LH LEFT HAND
LIN LINOLEUM
LIN LINOLEUM
LL LIVE LOAD
LT LIGHT
SS STAINLESS STEEL
ST STREET
STN STAIN(ED)
STAG STAGGERED
STD STANDARD
STL STEEL
STOR STORAGE
STRUCT STRUCTURAL
SURF SURFACE
SUSP SUSPENDED
SWS SEE WALL SECTIONS
SYM SYMMETRICAL
SYS SYSTEM
T TILE
THR THREAD
TEMP TEMPORARY
TEMP GL TEMPERED GLASS
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
THK THICK
THRSH THRESHOLD
THRU THROUGH
T/M TO MATCH
T/M TO MATCH
TO TOP OF
TOC TOP OF CONCRETE OR CURB
TOS TOP OF STEEL
TOT TOTAL
TYP TYPICAL
UNFIN UNFINISHED
BC BOTTOM OF CURB
BD BOARD
BFF BELOW FINISH FLOOR
BLDG BUILDING
BLK BLOCK
BLKG BLOCKING
BM BEAM OR BENCH MARK
BO BOTTOM OF
BOD BOTTOM OF DEK
BOR BOTTOM OF REVEAL
BOT BOTTOM
BRG BEARING
BR BRICK
BV BRICK VANEER
CAB CABINETRY
CB CATCH BASIN
CEM CEMENT
CG CORNER GUARD
CIP CAST IN PLACE
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONT CONTINUOUS
CORR CORRIDOR
COV PL COVER PLATE
CPT CARPET
CT CERAMIC TILE
CTR CENTER
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIFF DIFFUSER
DIM DIMENSION
DN DOWN
DR DOOR
DRN DRAIN
DS DOWNSPOUT
DT DOUBLE TREE
DWG DRAWING
E EAST
(E) EXISTING
EB EXPANSION BOLT
EJ EXPANSION JOINT
ELEC ELECTRICAL
ELEV ELEVATION
EMER EMERGENCY
ENCL ENCLOSURE
ENGR ENGINEER
EP EPOXY PAINT
ENAM ENAMEL
EQ EQUAL
EQUIP EQUIPMENT
EXH EXHAUST
EXT EXTERIOR
FA FIRE ALARM
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISH FLOOR
FIN FINISH
FLR FLOOR
FLUOR FLUORESCENT
FO FACE OF
FOF FACE OF FINISH
FOH FRONT OF HOUSE
FOC FACE OF CONCRETE
FOM FACE OF MASONARY
FOS FACE OF STUDS
FPRF FIREPROOFING
FR FIRE RESITIVE
FT FEET or FOOT
FTG FOOTING
FV FEILD VERIFY
GA GAUGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GL GLASS
GLB GLULAM BEAM
GRD GRADE
GND GROUND
GWB GYPSUM WALL BOARD
HB HOSE BIB
HDR HEADER
HDW HARDWARE
HDWD HARDWOOD
LVR LOUVER
LYRS LAYERS
M METRIC/METER
MACH MACHINE
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MB MARKER BOARD
MECH MECHANICAL
MEMB MEMBRANE
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MI MIRROR
MISC MISCELLANEOUS
MO MASONRY OPENING
MRG MOISTURE RESISTANT GYPSUM BOARD
MTD MOUNTED
MTL METAL
N NORTH
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NS NON-SHRINK
NTS NOT TO SCALE
OA OUTSIDE AIR
OC ON CENTER
OD OUTSIDE DIAMETER / DIMENSION
OFCI OWNER FURNISHED, CONTRACTOR INSTALLED
OFOI OWNER FURNISHED, OWNER INSTALLED
OPNG OPENING
OPP OPPOSITE
OPT OPTIONAL
ORIG ORIGINAL
OVHD OVERHEAD
OV OVERFLOW DRAIN
PAV PAVERS
PC PRECAST CONCRETE
PCF POUNDS PER CUBIC FOOT
PERF PERFORATED
P/L PROPERTY LINE
PL PLATE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLUMB PLUMBING
PLF POUNDS PER LINEAL FOOT
PLYWD PLYWOOD
PNL PANEL
PRELIM PRELIMINARY
PSI POUNDS PER SQUARE INCH
P PAINT
PT PRESSURE TREATED
PTD PAINTED
QT QUARRY TILE
QTR QUARTER
R RISER
R- THERMAL RESISTANCE
RA RETURN AIR
RAD RADIUS
RB RUBBER BASE
RD ROOF DRAIN
REC RECESSED
RE: REFERENCE
REF REFRIGERATOR
REINF REINFORCE(D)(MENT)(ING)
REQD REQUIRED
REV REVISION
RF RESILIENT FLOORING
RFL REFLECTED
RM ROOM
RND ROUND
RO ROUGH OPENING
RQMT REQUIREMENT(S)
RV ROOF VENT
R/W RIGHT OF WAY
RWF RESILIENT WOOD FLOOR
S SOUTH
SC SOLID CORE
SCHED SCHEDULE
SECT SECTION
SF SQUARE FOOT
SHTHG SHEATHING
SHT SHEET
SIM SIMILAR
SJ SEISMIC JOINT
SLR SEALER
SOG SLAB ON GRADE
SPEC SPECIFICATION
SQ SQUARE
UON UNLESS OTHERWISE NOTED
V VOLTAGE
V VALVE
VB VAPOR BARRIER
VENT VENTILATION
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
VNR VENEER
VTR VENT TO ROOF
W WEST
W/ WITH
WD WOOD
WDN WINDOW
WLD WELD(ED)
WOM WALK OFF MAT
W/O WITHOUT
WP WATERPROOFING
WSCT WAINSCOT
WT WEIGHT
WTR WATER
XFRMR TRANSFORMER
YD YARD
PROPERTY INFORMATION
PROJECT NAME: LEWIS COUNTY RAINIER NORTH BUILDING TI
PARCEL NUMBER: 003752000000
SITE ADDRESS: 185 NW CHEHALIS AVE
CHEHALIS, WASHINGTON 98532
AUTHORITIES HAVING JURISDICTION
CITY OF CHEHALIS
DEPARTMENT OF BUILDING AND PLANNING
351 NW NORTH STREET
CHEHALIS, WA 98532
CODE ANALYSIS
GOVERNING CODES:
INTERNATIONAL & NATIONAL CODES:
2021 INTERNATIONAL BUILDING CODE (IBC)
2021 INTERNATIONAL MECHANICAL CODE (IMC)
2021 INTERNATIONAL FIRE CODE
2021 UNIFORM PLUMBING CODE (UPC)
2023 NATIONAL ELECTRICAL CODE
2017 ACCESSABLE AND USABLE BUILDINGS (A117.1)
WASHINGTON STATE CODES:
2021 WASHINGTON STATE ENERGY CODE CHAPTER 51-11 WAC
WASHINGTON STATE CODES AMENDMENTS:
WA STATE AMENDMENTS TO THE 2021 IBC CHAPTER 51-50 WAC
WA STATE AMENDMENTS TO THE 2021 IMC CHAPTER 51-52 WAC
WA STATE AMENDMENTS TO THE 2021 IFC CHAPTER 51-54 WAC
WA STATE AMENDMENTS TO THE 2021 UPC CHAPTER 51-56 AND 51-57 WAC
ALL AMENDMENTS, SUPPLEMENTS, MODIFICATIONS, EXCLUSIONS, EXCEPTIONS, AND
ADDITIONS TO THE CODES LISTED ABOVE AS ADOPTED BY THE WASHINGTON STATE
BUILDING CODE COUNCIL RCW 19.27 AND WAC TITLE 51.
LOCAL AMENDMENTS TO THE ABOVE LISTED CODES AND LOCAL ORDINANCE AS ADOPTED BY
THE AUTHORITY HAVING JURISDICTION: CITY OF CHEHALIS
CITY OF CHEHALIS DESIGN REQUIREMENTS
1. DESIGN WIND SPEED: 5 mph basic (Vasd) + 110 mph (Vult).
2. WIND EXPOSURE: B”
3. SEISMIC DESIGN CATEGORY: 1
4. GROUND AND ROOF SNOW LOAD: 25 psf
BUILDING CONSTRUCTION DATA:
USE AND OCCUPANCY CLASSIFICATION: BUSINESS GROUP B
CONSTRUCTION TYPE: TYPE III-B
BUILDING AREA:
NUMBER OF STORIES ALLOWED (CHAPTER 5 & TABLE 504.4):
FOR B OCCUPANCY IN CONSSTRUCTION Type III-B = 3 ; ACTUAL = 1 (EXISTING)
BUILDING HEIGHT (CHAPTER 5, TABLE 504.3):
FOR B OCCUPANCY IN CONSTRUCTIONTYPE III-B = 55 FT; ACTUAL = 19 FT (EXISTING)
ACTUAL AREA: 4,742 SF (NOT INCLUDING EXTERIOR WALL THICKNESS)
5,029 SF (INCLUDING EXTERIOR WALL THICKNESS)
ALLOWABLE AREA: FOR B OCCUPANCY IN CONSTRUCTION TYPE III-B : 19,000 SF
TOTAL GROSS BUILDING AREA = 5,029 SF
HELP DESK
719 SF
MEETING
ROOM
DIRECTOR
OFFICE
OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE
BREAK
ROOM
267 SF
91 SF 86 SF 86 SF 100 SF 84 SF 90 SF 84 SF 127 SF
159 SF
116 SF
297 SF
150 1150 1150 1150 1150 1150 1150 1150 1
150 1
150 2
150 5
15 11
15 18
14 13
13 OCCUPANTS
WIDTH REQUIRED = 1.95"
WIDTH PROVIDED = 32"
14 OCCUPANTS
WIDTH REQUIRED = 2.1"
WIDTH PROVIDED = 64"
19 OCCUPANTS
WIDTH REQUIRED = 2.85"
WIDTH PROVIDED = 32"
MTD: 108'-3"
FEC
FEC
OFFICE
150 SF
150 1
DENOTES MAXIMUM TRAVEL DISTANCE
EXIT
XX
XX XX
SQUARE FOOTAGE
OCCUPANT FACTOR / OCCUPANT LOAD
1 - HOUR FIRE WALL (EXISTING)
UL U906 (2-hr Rated)
MTD: 108'-3"
1 - HOUR FIRE RATED STEEL COLUMN
(EXISTING) UL 263, NFPA 251, ASTM E-119-106
(1-hr Rated)- APPLY INTUMESCENT PAINT PER
MANUF. RECOMMENDATIONS
ILLUMINATED EXIT SIGNAGE
FEC
FIRE EXTINGUISHER INSIDE
SURFACE MOUNT WALL CABINET
906 Columbia Street SW, Suite 400
Olympia, Washington 98501
360.352.8883 architects
KMB Project #
SHEET NO.
REVISIONS:
DATE:
ORIGINAL SHEET SIZE = 24 x 36
HALF SIZE REDUCTIONS = 11 x 17
P
LO
T D
A T
E
ARCHITECT
STATE OF WASHINGTON
REGISTERED
JAMES HILL
10347
/3
/2
:4
8:
P M
7-31-2026
BID SET
GI201
GENERAL CODE
INFORMATION
LE
W
IS
C
O U
N
TY
R A
IN
IE
R N
O R
TH
B
U
IL
D
IN
G T
I
LE
W
IS
C O
U N
TY
F
A C
IL
IT
IE
S
D
EP
A R
TM
EN
T
N W
N O
R
TH
S
TR
EE
T, C H
EH
A
LI
S
, W A
Fa ci lit ie s D ep ar tm en t
J2037C
3/32" = 1'-0"1
LEVEL ONE- CODE & EXITING PLAN
CODE FLOOR PLAN LEGEND
1 2 4 5 6
A
C
B
LD
G
25'-7 3/4" VIF 18'-7 1/4" VIF 18'-7 1/4" VIF 18'-7 1/4" VIF 18'-11 1/2" VIF
A1c
A1c
A1cA1c
A1c
A1cA3cA1c
A3d
A1b
A1b
A1d
A1b
A1b
A1d
A3d
A1b
A1b A3d
A1
A1d
A1
A1d
4A
5A
6A
7A
8A
8A
0A
9A
2A
111A
2B
4A
5A
6A
7A
123A
102A
1A
HELP DESK
STORAGE
ELECTRIC
RESTROOM
CUSTODIAN
RESTROOM
SERVER
OFFICE
OFFICE
OFFICE
OFFICE
HALLWAY
OFFICE
OFFICE
OFFICE
OFFICE
HALLWAY
HALLWAY
BREAK
ROOM
OFFICE
DIRECTOR
MEETING
ROOM
A3
A1d
'-0
'-6
A
LI
G N
'-0
4'
-4
A
LI
G N
2'-0"
2' -6
'-1
A
LI
G N
4'-8 1/2" 3" 7'-6 1/2" 3'-3" 2'-3"
7B
5' -7
2'
-9
7' -3
6'-0" 9"
A-585
A-251
A-251
W2
W2
A1
A1d
A3a
2' -0
2'
-0
2' -0
3'
-0
A3a 1
A-585
A-585
A9
A9
FEC
FEC
MONITOR BY OTHERS,
OFOI REFER TO ELEC. FOR
POWER/DATA LOCATIONS.
PROVIDE BACKING IN
WALL. 5'-0" HIGH TO
CENTERLINE OF MONITOR
MONITOR BY OTHERS, OFOI REFER TO
ELEC. FOR POWER/DATA LOCATIONS.
PROVIDE BACKING IN WALL. 4'-0" HIGH
TO CENTERLINE OF MONITOR
5' -3
A-585
A-585
A3
A1c
A1b
A1
CENTER WALL ON
EXISTING COLUMN
CENTER WALL ON
EXISTING COLUMN
CENTER WALL ON
EXISTING COLUMN
A-311
A1b
'-0
MONITOR BY OTHERS,
OFOI REFER TO ELEC. FOR
POWER/DATA LOCATIONS.
PROVIDE BACKING IN
WALL. 5'-0" HIGH TO
CENTERLINE OF MONITOR
EQ EQ
HALLWAY
OFFICE
103A
124A
A1b A1b
2' -0
2'
-0
2' -0
2'
-0
W2
W2
906 Columbia Street SW, Suite 400
Olympia, Washington 98501
360.352.8883 architects
KMB Project #
SHEET NO.
REVISIONS:
DATE:
ORIGINAL SHEET SIZE = 24 x 36
HALF SIZE REDUCTIONS = 11 x 17
P
LO
T D
A T
E
ARCHITECT
STATE OF WASHINGTON
REGISTERED
JAMES HILL
10347
/3
/2
:4
8:
P M
7-31-2026
BID SET
A-122
ENLARGED FLOOR PLAN -
NORTH BUILDING
LE
W
IS
C
O U
N
TY
R A
IN
IE
R N
O R
TH
B
U
IL
D
IN
G T
I
LE
W
IS
C O
U N
TY
F
A C
IL
IT
IE
S
D
EP
A R
TM
EN
T
N W
N O
R
TH
S
TR
EE
T, C H
EH
A
LI
S
, W A
Fa ci lit ie s D ep ar tm en t
J2037C
3/16" = 1'-0"1
ENLARGED FLOOR PLAN BLDG 2
1. ALL DIMENSIONS TO FACE OF CMU, FACE OF STUD OR GRIDLINES, U.N.O.
2. DOOR FRAMES TO BE 3" OFF ADJACENT PERPENDICULAR WALL, U.N.O.
FLOOR PLAN GENERAL NOTES
C
B
LD
G
8' - 0"
8' - 0"
8' - 0"
9' - 0"
9' - 0"
9' - 0"
9' - 0"
9' - 0"
9' - 0"
9' - 0"
9' - 0"
9' - 0"
9' - 0"
9' - 0"
9' - 0"
MEETING
ROOM
DIRECTOR
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
SERVER
ELECTRIC
STORAGE
RESTROOM
CUSTODIAN
115 RESTROOM
BREAK
ROOM
HELP DESK
HALLWAY
HALLWAY
HALLWAY
OTS
OTS
OTS
OTS
25'-7 3/4" 18'-7 1/4" 18'-7 1/4" 18'-7 1/4" 18'-11 1/2"
'-1
P M
VG
P M
VG
P M
VG
P M
VG
P M
VG
P M
VG
P M
VG
M
M
M P P
P
VG
VG
M
MP
P
M
M P
M
P
P
P P
VG
VG
HP-CU-200
HP-BC-200
HP-SBC-201
HP-112-1
HP-112-2
DH-200
DOAS-200
VG
P M
A-561
A-561
1' -0
1' -0
A-561
OTS
OTS
P
VG
VG
A-311
OFFICE
HALLWAY
9' - 0"
9' - 0"
9' - 0"
VG
VG
M
P
P
M
P
M
P
MECHANICAL SUPPLY AIR GRILLE - REFER TO
MECH. FOR SIZE AND TYPE
MECHANICAL RETURN AIR GRILLE - REFER TO
MECH. FOR SIZE AND TYPE
EXHAUST GRILLE - REFER TO MECH. FOR SIZE
AND TYPE
RECESSED CEILING TROFFER -
REFER TO ELECT.
RECESSED CEILING TROFFER -
REFER TO ELECT.
RECESSED CEILING TROFFER
W/ BATTERY BACK-UP POWER -
REFER TO ELECT.
PENDANT LIGHTING -
REFER TO ELECT.
RECESSED CAN LIGHT -
REFER TO ELECT.
CEILING ACCESS PANEL
CEILING MOUNTED ILLUMINATED
EXIT SIGN
VRF HEAT PUMP
VG
VENTILATION GRILLE
PENDANT LIGHTING
W/ BATTERY BACK-UP POWER -
REFER TO ELECT.
TRANSFER GRILLE
PHOTOSENSORP
OCCUPANCY SENSORM
CEILING TYPES: XX TYPE
X' - X" HEIGHT
ACT-1 -2x4 SUSPENDED ACOUSTICAL CEILING PANEL AND
CONCEALED GRID SYSTEM
GWB OVER STEEL STUD FRAMING
MOLD/ MOISTURE RESISTANT GYPSUM BOARD OVER STEEL
STUD FRAMING
(2) LAYERS GWB INSTALLED OVER CURRENT CEILING W/ (ACT-1)
2x4 SUSPENDED ACOUSTICAL CEILING PANEL AND CONCEALED
GRID SYSTEM
OPEN TO STRUCTURE
FULL HEIGHT WALL UP TO BOTTOM OF METAL DECKING AT ROOF ABOVE.
LOCATION OF EXTERIOR WALL ABOVE, BETWEEN LOWER AND UPPER ROOFS.
1. THESE GENERAL NOTES APPLY TO ALL REFLECTED CEILING PLANS.
2. CEILING HEIGHTS ARE FROM FINISH FLOOR UNO.
3. TYPICAL CEILING HEIGHT TO BE 9' - 0", UNO.
4. ALIGN SOFFITS WITH FACE OF ADJACENT WALL, UNO
5. NOT ALL LIGHTING, INCLUDING PENDANT AND WALL MOUNTED LIGHT FIXTURES,
SHOWN. SEE ELECTRICAL.
6. OTS = OPEN TO STRUCTURE. PAINT ALL EXPOSED CEILING/ROOF STRUCTURE, UNO.
7. U.N.O. - PAINT ALL GWB CEILINGS & SOFFITS PT-1 ( SEE FINISH SCHEDULE)
8. SEE DETAIL FOR TYP SUSPENDED GRID DETAIL..
9. INTERIOR WALLS ARE TYPICALLY 6" ABOVE CEILING HEIGHT SHOWN UNLESS NOTED
OTHERWISE ON ARCHITECTURAL OR STRUCTURAL DRAWINGS (i.e. SHEAR WALLS, SMOKE BARRIER WALLS, SOUND BARRIER WALLS, MECHANICAL ZONE WALLS).
10. COORDINATE LOCATION OF CEILING ACCESS DOORS WITH MECHANICAL &
ELECTRICAL CONTRACTORS.
11. PROVIDE ADDITIONAL EDGE BLOCKING, CROSS BRACING & SUSPENDED SUPPORT
WIRES OR ADDITIONAL FURRING FOR CEILING MOUNTED ITEMS (LIGHTING, ACCESS
PANELS, GRILLES, CAMERAS, ETC.)
FLAG NOTES TO REFLECTED CEILING PLAN:
OTS
906 Columbia Street SW, Suite 400
Olympia, Washington 98501
360.352.8883 architects
KMB Project #
SHEET NO.
REVISIONS:
DATE:
ORIGINAL SHEET SIZE = 24 x 36
HALF SIZE REDUCTIONS = 11 x 17
P
LO
T D
A T
E
ARCHITECT
STATE OF WASHINGTON
REGISTERED
JAMES HILL
10347
/3
/2
:4
8:
P M
7-31-2026
BID SET
A-153
ENLARGED REFLECTIVE
CEILING PLAN - NORTH
BUILDING
LE
W
IS
C
O U
N
TY
R A
IN
IE
R N
O R
TH
B
U
IL
D
IN
G T
I
LE
W
IS
C O
U N
TY
F
A C
IL
IT
IE
S
D
EP
A R
TM
EN
T
N W
N O
R
TH
S
TR
EE
T, C H
EH
A
LI
S
, W A
Fa ci lit ie s D ep ar tm en t
J2037C
3/16" = 1'-0"1
LEVEL 1 - ENLARGED REFLECTIVE CEILING PLAN - BLDG 2
REFLECTED CEILING PLAN LEGEND
REFLECTED CEILING PLAN NOTES
INTERIOR ELEVATION NOTES
- SEE A-501 FOR INTERIOR WALL TYPES
- SEE A-601 FOR DOOR TYPES
ABBREV DESCRIPTION
DW-1 UNDER COUNTER DISHWASHER
(34"H X 24"W X 27"D - OFCI
FEC-1 FIRE EXTINGUISHER IN CABINET
GB-1 GRAB BAR (SIDE WALL)
GB-2 GRAB BAR (BACK WALL)
GB-3 GRAB BAR (SIDE WALL, VERTICAL)
MR-2 MIRROR
MV-1 MICROWAVE
PR-1 POWER
PTD-1 PAPER TOWEL DISPENSER
PTD/GD-1 PAPER TOWEL DISPENSER & GARBAGE DISPOSAL
R-1 REFRIGERATOR (64"H X 28"W X 34"DEEP) - OFOI
RB-1 4" HIGH RUBBER BASE
S-1 SINK
S-4 2-COMPARTMENT SINK
SD-1 SOAP DISPENSER
SND-1 SANITARY NAPKIN DISPOSAL
SSF1 SOLID SURFACE COUNTERTOP
T-1 WALL MOUNTED TOILET
TSCD-1 TOILET SEAT COVER DISPENSER
TTD-1 TOILET TISSUE DISPENSER, NAPKIN DISPOSAL
ACCESSORIES ABBREVIATION LEGEND
**REFER TO A-701 ACCESSORIES & EQUIPMENT LEGEND FOR PRODUCT INFORMATION
2' -8
1'
-6
2' -1
0"
10'-3"
1"2'-6"2'-1"3'-0"2'-6"1"
2'-6" 3'-0"
SSF1
PLAM2
PLAM2
MV-1
DW-1
RB1
PT1
SD-1
PTD-1
A-583
A-583
A-583
A-583
A-251
DW-1 MV-1
R-1
S-4
A1b
A1b
RESTROOM
CUSTODIAN
RESTROOM
A-2512 4
A-251
A-251
10A3d
A1b A1b
A1d
A3d
A1b
TB1
TL2
PT1
4' -6
SD-1
S-1
TB1
TL2
PT1
SD-1
S-1
MR-2
T-1
4' -6
TB1
TL2
PT1
T-1
PTD/GD-1
SND-1
TTD-1
TSCD-1
4' -6
TB1
TL2
PT1
4' -6
TB1
TL2
PT1
SD-1
S-1
4' -6
TB1
TL2
PT1
SD-1
S-1
MR-2
T-1
GB-3
GB-2
TB1
TL2
PT1
T-1
PTD/GD-1
SND-1
TTD-1
TSCD-1
4' -6
GB-3
GB-1
TB1
TL2
PT1
4' -6
MOP SINK
RB1
PT1
2' -4
SIDE FRONT
ACCESSIBLE WATER CLOSET
FRONT
FREESTANDING LAVATORY
PTD
FEC
T.O. RIM
BOT. BAR
BARRIER-FREE DOORS AND HARDWARE
CL
M A
X
C O
N T
R O
LS
M A
X
1'
2'
3'
1'
2' - 6"
2'
3' - 4"
4' - 6"
2' -9
1' - 6" 1' - 6"
1' - 6" 2' - 1"
MAX 42"
M A
X
4' -0
1' -6
8"
4' -2
6' -8
3' -0
3' -7
" 5' -0
FIRE PULL
ELECTRICAL
OUTLET
ROOM SIGNAGE
5' -0
HEAT SHEILD TYP
(PRE-FORMED)
SOAP
DISPENSER
MIRROR
GRAB BAR
TOILET PAPER
DISPENSER
SANITARY NAPKIN
DISPOSAL @ WOMEN
MOUNT FLUSH VAVLE
TO OPEN SIDE
WHERE OCCURS
TOILET SEAT
COVER DISPENSER
FIRE ALARM
R E
F
LE
C T
IV
E
M A
X
906 Columbia Street SW, Suite 400
Olympia, Washington 98501
360.352.8883 architects
KMB Project #
SHEET NO.
REVISIONS:
DATE:
ORIGINAL SHEET SIZE = 24 x 36
HALF SIZE REDUCTIONS = 11 x 17
P
LO
T D
A T
E
ARCHITECT
STATE OF WASHINGTON
REGISTERED
JAMES HILL
10347
/3
/2
:4
8:
P M
7-31-2026
BID SET
A-251
ENLARGED PLANS &
INTERIOR ELEVAITONS
LE
W
IS
C
O U
N
TY
R A
IN
IE
R N
O R
TH
B
U
IL
D
IN
G T
I
LE
W
IS
C O
U N
TY
F
A C
IL
IT
IE
S
D
EP
A R
TM
EN
T
N W
N O
R
TH
S
TR
EE
T, C H
EH
A
LI
S
, W A
Fa ci lit ie s D ep ar tm en t
J2037C
1/4" = 1'-0"12
BREAK ROOM 113 - EAST ELEVATION
1/4" = 1'-0"11
ENLARGED FLOOR PLAN -
BREAK ROOM 113
1/4" = 1'-0"1
ENLARGED FLOOR PLAN - RESTROOM 114,
CUSTODIAN 115, RESTROOM 116
1/4" = 1'-0"2
RESTROOM 114 - NORTH
1/4" = 1'-0"3
RESTROOM 114 - EAST
1/4" = 1'-0"4
RESTROOM 114 - SOUTH
1/4" = 1'-0"5
RESTROOM 114 - WEST
1/4" = 1'-0"6
RESTROOM 116 - NORTH
1/4" = 1'-0"7
RESTROOM 116 - EAST
1/4" = 1'-0"8
RESTROOM 116 - SOUTH
1/4" = 1'-0"9
RESTROOM 116 - WEST
1/4" = 1'-0"10
CUSTODIAN 115 - EAST
TYPICAL MOUNTING HEIGHTS
BLDG 2 ROOF
20' - 10"
B.O. CANOPY 2
12' - 2"
LEV. 1 - BLDG 2
2' - 0 19/32"
EXISTING CONCRETE
SIDEWALK
EXISTING MASONRY WALL
EXISTING ROOF
HARD-LID CEILING
EXISTING PARAPET
OFFICE
HELP DESK
OPEN TO
HALLWAY 122
BEYOND
EXISTING WINDOW
EXISTING CANOPY
906 Columbia Street SW, Suite 400
Olympia, Washington 98501
360.352.8883 architects
KMB Project #
SHEET NO.
REVISIONS:
DATE:
ORIGINAL SHEET SIZE = 24 x 36
HALF SIZE REDUCTIONS = 11 x 17
P
LO
T D
A T
E
ARCHITECT
STATE OF WASHINGTON
REGISTERED
JAMES HILL
10347
/3
/2
:4
8:
P M
7-31-2026
BID SET
A-311
WALL SECTIONS
LE
W
IS
C
O U
N
TY
R A
IN
IE
R N
O R
TH
B
U
IL
D
IN
G T
I
LE
W
IS
C O
U N
TY
F
A C
IL
IT
IE
S
D
EP
A R
TM
EN
T
N W
N O
R
TH
S
TR
EE
T, C H
EH
A
LI
S
, W A
Fa ci lit ie s D ep ar tm en t
J2037C
1/2" = 1'-0"1
WALL SECTION AT EAST WALL
A1
TYPICAL WALL (3 1/2" STEEL STUD)
NON-FIRE RATED
3 1/2" STEEL STUDS
@ 16" O.C.
(1) LAYER 5/8" TYPE
'X' GWB
(1) LAYER 5/8"
TYPE 'X' GWB
R-13 SOUND BATT
INSULATION, NO
INSULATION AT HALF
WALL CONDITIONS
A2 TYPICAL WALL (8" STEEL STUD) & A2a (10"
STEEL STUD)
NON-FIRE RATED
8" STEEL STUDS @
16" O.C.
(1) LAYER 5/8" TYPE
'X' GWB
(1) LAYER 5/8"
TYPE 'X' GWB
R-21 SOUND BATT
INSULATION, NO
INSULATION AT HALF
WALL CONDITIONS
A3
TYPICAL WALL (6" STEEL STUD)
NON-FIRE RATED
6" STEEL STUDS @
16" O.C.
(1) LAYER 5/8" TYPE
'X' GWB
(1) LAYER 5/8"
TYPE 'X' GWB
R-21 SOUND BATT
INSULATION, NO
INSULATION AT HALF
WALL CONDITIONS
A4
TYPICAL CHASE WALL (3 1/2" STEEL STUD)
NON-FIRE RATED
3 1/2" STEEL STUDS
@ 16" O.C.
(1) LAYER 5/8" TYPE
'X' GWB
R-13 SOUND BATT
INSULATION, NO
INSULATION AT HALF
WALL CONDITIONS
A9
TYPICAL FURRING WALL (1 5/8" STEEL STUD)
NON-FIRE RATED
1 5/8" STEEL STUDS
@ 16" O.C.
(1) LAYER 5/8" TYPE
'X' GWB
AT RESTROOMS,
ADD TBB WHERE
TILE IS TO OCCUR
AT RESTROOMS,
ADD TBB WHERE
TILE IS TO OCCUR
AT RESTROOMS,
ADD TBB WHERE
TILE IS TO OCCUR
AT RESTROOMS,
ADD TBB WHERE
TILE IS TO OCCUR
1. A 1-HR DESIGNATION INDICATED GWB MUST BE 5/8" TYPE 'X' AND MEET
1-HR WALL REQUIREMENTS PER IBC, GA, UL OR SIMILAR.
2. REFER TO FINISH SCHEDULE FOR WALL FINISH.
3. NO BATT INSULATION AT HALF WALL CONDITIONS
4. PROVIDE BACKING IN WALLS FOR CASEWORK, MESSAGE BOARDS, TOILET
ACCESSORIES, OFOI FURNISHINGS AND ALL OTHER WALL SUPPORTED
ITEMS. REFER TO INTERIOR ELEVATIONS AND PLANS FOR LOCATIONS.
5. PROVIDE BACKING AT ELECTRICAL AND COMMUNICATIONS ROOMS AS
REQUIRED PER THE ELECTRICAL REQUIREMENTS.
6. TOP AND BOTTOM PLATES: ALIGN AND ANCHOR TO BUILDING
STRUCTURAL MEMBERS AT EACH END AND AT 24" O.C.
7. WHERE METAL STUD DEFLECTION TRACKS ARE USED, PROVIDE AT TOP
OF FULL WALL HEIGHT PARTITIONS TO ALLOW STRUCTURE TO DEFLECT
WITHOUT IMPOSING LOADS ON WALL.
8. AT CEILING AND SOFFIT FRAMING:
A. INSTILL FRAMING AT 16" O.C. AND CONNECT ENDS OF STUD TO
HORIZONTAL JOIST AND SECURELY ATTACH TO BUILDING STRUCTURE
OR WALL FRAMING.
B. PARTITION CORNERS: MINIMUM OF (3) STUDS.
9. AT AIR BARRIER WALLS PROVIDE:
A. SEALANT BETWEEN PLATES AND SUBSTRATE.
B. SEALANT BETWEEN WALL AND ADJACENT VERTICAL SURFACES.
C. SEAL AIR BARRIER MEMBRANE TO ADJACENT SURFACE, FULL
PERIMETER OF WALL.
D. SEALANT AROUND ALL OPENINGS AT ELECTRICAL DEVICES, DUCTS
AND PIPING, AND STRUCTURE PENETRATING WALL SURFACES.
11. AT STC RATED WALLS, PROVIDE:
A. SEALANT BETWEEN PLATES AND SUBSTRATE.
B. SEALANT BETWEEN STUDS AND ADJACENT VERTICAL SURFACES.
C. SEALANT AROUND ALL OPENINGS AT ELECTRICAL DEVICES, DUCTS
AND PIPING, AND STRUCTURE PENETRATING SURFACES.
TOP OF WALL CONDITION
NOTE: ALL WALLS AND GWB EXTEND TO STRUCTURE, UNLESS NOTED OTHERWISE.
REFER TO PARTITION HEIGHTS BELOW FOR WALLS THAT DO NOT EXTEND TO
STRUCTURE. REFER ALSO TO STRUCTURAL SHEETS FOR LOCATIONS OF SHEAR
WALL AND REQUIRED SHEATHING.
a. PARTIAL HEIGHT PARTITION
b. PARTITION - EXTEND GWB TO 6" ABOVE UPPERMOST CEILING ON BOTH SIDES
OF WALL AND BRACE STUDS TO STRUCTURE ABOVE AS REQUIRED
c. PARTITION - EXTEND TO 12" ABOVE UPPERMOST CEILING
d. PARTITION - EXTEND STUDS TO UNDERSIDE OF STRUCTURE ABOVE. EXTEND
GWB TO 6" ABOVE CEILING ON ONE SIDE AND TO STRUCTURE ON THE OTHER
BOT. OF STRUCTURE
FINISH FLOOR
CEILING
a b cTYP, UNO
1' -0
6" d
6"
906 Columbia Street SW, Suite 400
Olympia, Washington 98501
360.352.8883 architects
KMB Project #
SHEET NO.
REVISIONS:
DATE:
ORIGINAL SHEET SIZE = 24 x 36
HALF SIZE REDUCTIONS = 11 x 17
P
LO
T D
A T
E
ARCHITECT
STATE OF WASHINGTON
REGISTERED
JAMES HILL
10347
/3
/2
:4
8:
P M
7-31-2026
BID SET
A-502
INTERIOR WALL TYPES
LE
W
IS
C
O U
N
TY
R A
IN
IE
R N
O R
TH
B
U
IL
D
IN
G T
I
LE
W
IS
C O
U N
TY
F
A C
IL
IT
IE
S
D
EP
A R
TM
EN
T
N W
N O
R
TH
S
TR
EE
T, C H
EH
A
LI
S
, W A
Fa ci lit ie s D ep ar tm en t
J2037C
1 1/2" = 1'-0"1
INTERIOR WALL TYPES
WALL TYPE GENERAL NOTES
DOOR PER
SCHEDULE
/2
P E
R W
A L
L T
Y P
E S
/2
HOLLOW METAL FRAME
DOOR PER SCHEDULE
PER WALL TYPE
1/2"1/2"
MINERAL WOOL
BLANKET INSULATION
HOLLOW METAL FRAME
GLAZING
AND THROAT SIZE
COORD. W/ WALL TYPES
1/2" 1/2"
GWB, BOTH
SIDES TYP.
SILICONE
SEALANT
MINERAL WOOL
BLANKET
INSULATION
HOLLOW METAL
FRAME
PER WALL TYPE
HOLLOW METAL FRAME
1/2"1/2"
P E
R W
A L
L T
Y P
E S
/2
/2
HOLLOW METAL FRAME
906 Columbia Street SW, Suite 400
Olympia, Washington 98501
360.352.8883 architects
KMB Project #
SHEET NO.
REVISIONS:
DATE:
ORIGINAL SHEET SIZE = 24 x 36
HALF SIZE REDUCTIONS = 11 x 17
P
LO
T D
A T
E
ARCHITECT
STATE OF WASHINGTON
REGISTERED
JAMES HILL
10347
/3
/2
:4
8:
P M
7-31-2026
BID SET
A-541
DOOR AND WINDOW
DETAILS
LE
W
IS
C
O U
N
TY
R A
IN
IE
R N
O R
TH
B
U
IL
D
IN
G T
I
LE
W
IS
C O
U N
TY
F
A C
IL
IT
IE
S
D
EP
A R
TM
EN
T
N W
N O
R
TH
S
TR
EE
T, C H
EH
A
LI
S
, W A
Fa ci lit ie s D ep ar tm en t
J2037C
3" = 1'-0"2
DOOR JAMB
3" = 1'-0"1
DOOR HEAD
3" = 1'-0"3
RELITE HEAD (JAMB SIM.)
3" = 1'-0"4
CASED OPENING HEAD
3" = 1'-0"5
CASED OPENING JAMB
HORIZONTAL STEEL TRACK PER
STEEL STUD MANUF.
ACOUSTICAL SEALANT AT BOTH
SIDES - PROVIDE FIRE CAULKING
AT FIRE RATED WALLS
ACOUSTICAL SEALANT AROUND
ALL WALL PENETRATIONS AT
BOTH SIDES - PROVIDE FIRE
CAULKING AT FIRE RATED WALLS
REFER TO MECHANICAL,
ELECTRICAL AND PLUMBING
DRAWINGS FOR PIPE AND
DUCTWORK LOCATIONS
5/8" TYPE "X" GWB - REFER TO
INTERIOR ELEVATIONS FOR FINISH
- REFER TO WALL TYPES FOR
ALTERNATE SUBSTRATE TYPES
PER WALL TYPE
STEEL STUDS @ 16" O.C.
W/ BATT INSULATION PER
WALL TYPE
LINE OF STRUCTURE ABOVE (CLT ROOFING /
FLOOR JOISTS / BOTTOM CORD OF ROOF TRUSS)
REFER TO WALL TYPES FOR
ALTERNATE SUBSTRATE TYPES
PER WALL TYPE
STEEL STUDS @ 16" O.C.
W/ BATT INSULATION PER
WALL TYPE
5/8" TYPE "X" GWB - REFER TO
INTERIOR ELEVATIONS FOR FINISH
- REFER TO WALL TYPES FOR
ALTERNATE SUBSTRATE TYPES
LINE OF STRUCTURE ABOVE
(CLT ROOFING / FLOOR JOISTS / WOOD TRUSS BOTTON CORD)
STEEL BRACE FRAMING AT EACH
SIDE OF WALL @ 4'-0" O.C.
ALTERNATING
HORIZONTAL STEEL TRACK
PER STEEL STUD MANUF.
ACOUSTICAL CEILING PER
REFLECTED CEILING PLAN
REFER TO WALL TYPES FOR
ALTERNATE SUBSTRATE TYPES
PER WALL TYPE
STEEL STUDS @ 16" O.C. W/ BATT
INSULATION PER WALL TYPE
LINE OF STRUCTURE ABOVE
(CLT ROOFING / FLOOR JOISTS / WOOD TRUSS BOTTON CORD)
CEILING PER REFLECTED
CEILING PLAN
DOUBLE TOP PLATE
ACOUSTICAL CEILING PER
REFLECTED CEILING PLAN
5/8" TYPE "X" GWB - REFER TO
INTERIOR ELEVATIONS FOR FINISH
STEEL BRACE FRAMING AT
EACH SIDE OF WALL @ 4'-0"
O.C. ALTERNATING
8" MAX
3" M
A X
8" MAX
3" M
A X
45°
45°
ATTACHED GRID UNATTACHED GRID
NOTES:
1. INSTALL SYSTEM IN ACCORDANCE W/ THE LATEST EDITION OF THE INTERNATIONAL BUILDING CODE.
2. SUPPLY COMPRESSION STRUTS AT GRID INTERSECTION ADJACENT TO LATERAL BRACING POINTS.
3. SUPPLY ADDITIONAL 12GA WIRES FOR LIGHT FIXTURES AND MECHANICAL SERVICE INDEPENDENT OF GRID SUSPENSION SYSTEM.
4. ACCOUSTICAL MATERIALS SHALL COMPLY W/ INTERIOR FINISH REQUIREMENTS OF THE LATEST EDITIONS OF THE INTERNATIONAL
BUILDING CODE.
12 GA. VERT. HANGER WIRE
(MIN) @ 4'-0" O.C. BOTH WAYS
COMPRESSION STRUT 12'-0" O.C.
POSITIVELY ATTACHED TO GRID
AND STRUCTURE
LATERAL FORCE BRACING 4 EA 12
GA. WIRE SECURED TO MAIN RUNNER
WITHIN 2" OF CROSS TEE
INTERSECTION & SPLAYED 90° FROM
EA OTHER @ 12'-0" O,C, IN BOTH
DIRECTIONS W/ FIRST POINT WITHIN
6'-0" OF PERIMETER WALLS
MAIN RUNNERCROSS TEE
12GA (MIN) VERT PERIMETER
HANGING WIRE (TYP)
3 TURNS MIN (TYP)
MAIN RUNNER OR
CROSS TEE
ACOU. TILE
ATTACH GRID MEMBERS TO PERIMETER
WALL AT ANGLE & TWO ADJ WALLS ONLY
2" x 1" WALL ANGLE
3/4" AT UNATTACHED
GRID ENDS
PER WALL TYPE
STEEL STUDS @ 16" O.C.
W/ BATT INSULATION PER
WALL TYPE
5/8" TYPE "X" GWB
- REFER TO INTERIOR
ELEVATIONS FOR FINISH
ACOUSTICAL CEILING PER
REFLECTED CEILING PLAN
ACOUSTICAL CEILING PER
REFLECTED CEILING PLAN
HEIGHT PER RCP
EXISTING STRUCTURE
STEEL STUDS @ 16" O.C.
5/8" TYPE "X" GWB
- REFER TO FINISH SCHEDULE
ACOUSTICAL CEILING PER
REFLECTED CEILING PLAN
ALIGN
6"
ALIGN
HEIGHT PER RCP
EXISTING STRUCTURE
1'-0"
STEEL STUDS @ 16" O.C.
5/8" TYPE "X" GWB
- REFER TO FINISH SCHEDULE
ALIGN
HEIGHT PER RCP
EXISTING STRUCTURE
1'-0"
ACOUSTICAL CEILING PER
REFLECTED CEILING PLAN
ALIGN
6"
2X WOOD STUDS @ 16" O.C.
5/8" TYPE "X" GWB
- REFER TO FINISH SCHEDULE
906 Columbia Street SW, Suite 400
Olympia, Washington 98501
360.352.8883 architects
KMB Project #
SHEET NO.
REVISIONS:
DATE:
ORIGINAL SHEET SIZE = 24 x 36
HALF SIZE REDUCTIONS = 11 x 17
P
LO
T D
A T
E
ARCHITECT
STATE OF WASHINGTON
REGISTERED
JAMES HILL
10347
/3
/2
:4
8:
P M
7-31-2026
BID SET
A-561
CEILING DETAILS
LE
W
IS
C
O U
N
TY
R A
IN
IE
R N
O R
TH
B
U
IL
D
IN
G T
I
LE
W
IS
C O
U N
TY
F
A C
IL
IT
IE
S
D
EP
A R
TM
EN
T
N W
N O
R
TH
S
TR
EE
T, C H
EH
A
LI
S
, W A
Fa ci lit ie s D ep ar tm en t
J2037C
3" = 1'-0"1
WALL TYPE DETAIL @ FULL HEIGHT TO STRUCTURE
3" = 1'-0"2
WALL TYPE DEATIL @ BRACED WALL & ACT BOTH SIDES
3" = 1'-0"3
WALLTYPE DEATIL @ BRACED WALL @ GWB/ACT CEILING
1 1/2" = 1'-0"4
SUSPENDED CEILING SYSTEM - TYP.
3" = 1'-0"5
CEILING DETAIL @ ACOUSTICAL CEILING BOTH SIDES
1 1/2" = 1'-0"6
CEILING DETAIL @ SOFFIT
1 1/2" = 1'-0"7
CEILING DETAIL @ WINDOW
1 1/2" = 1'-0"8
CEILING DETAIL - GWB TO ACT TRANSITION @ PERIMETER
1/4" BACK
SECURE TO
WALL FRAMING
AND BACKING
CABINET (BOX) CONSTRUCTED FROM
3/4" SUBSTRATE, WHITE MELAMINE
FACED @ INTERIOR - TYPICAL
FRENCH
CLEAT
96MM WIRE PULL TYP, UNO
P-LAM FINISH PER INTERIOR
ELEVATIONS ON ALL EXPOSED
SIDES OF DOOR
3/4" WHITE MELAMINE ADJ.
SHELF, TYP.
BLUM 120° CONCEALED
HINGES, TYP.
SOLID 2x
BLOCKING
ADJ. SHELF
ADJ. SHELF
S E
E
IN
TE
R
IO
R
E
LE
V A
TI
O
N S
3"
2"
1'-3"
APPLY BASE PER
FINISH SCHEDULE
SCRIBE TO WALL SURFACE
SOILID SURFACE COUNTERTOP
AS SPECIFIED OVER PLYWOOD
BACKSPLASH WHERE OCCURS -
SEE INTERIOR ELEVATIONS
MARINE GRADE PLYWOOD
TOE BOX, TYPICAL
3"
96MM WIRE
PULL, TYP
3/4" WHITE MELAMINE
ADJ. SHELF, TYP.
ADJ. SHELF
4"
4"
REFER TO INTERIOR ELEVATION
R E
F E
R T
O
IN
T E
R
IO
R E
LE
V
A T
IO
N
4"
1/ 8"
6" 1/ 4"
1/
2"
3/4" IPB SCREW RAIL
(SECURED TO WALL VIA
THROUGH CABINET
MECH. FASTENERS)
SOLID 2x BLOCKING
NOTES:
• FULLY WELD BRACE ASSEMBLY,
GRIND WELDS SMOOTH
• PROVIDE BRACE SO NO COUNTER
SPAN IS GREATER THAN 3'-6"
TUBE STEEL BRACE, PAINT
TO MATCH WALL COLOR
HOLES FOR FASTENERS
@ SURFACE MOUNT
CONDITIONS, TYP.
BEVEL BOTTOM
EDGE
ANGLE FRONT EDGE
HOLES FOR FASTENERS @
CONCEALED CONDITIONS, TYP.
1' -9
5/
4" L
ESS THAN W
IDTH OF COUNTER
SCRIBE TO
WALL SURFACE
SOLID SURFACE COUNTERTOP
AS SPECIFIED
BACKSPLASH WHERE OCCURS -
SEE INTERIOR ELEVATIONS
MARINE GRADE PLYWOOD
TOE BOX, TYPICAL
S E
E
IN
TE
R
IO
R
E
LE
V A
TI
O
N S
1/
2"
DOOR LOCK, TYP
96MM WIRE PULL, TYP
FIN. FLOOR: INSTALL
BEFORE CASEWORK, TYP
4"
WHITE MELAMINE
INTERIOR, TYP.
6"
FIXED PANEL
ACTUAL SINK
ATTACHMENT TO
COUNTERTOP PER
MANUF/FABRICATOR
SEAMLESS, INTEGRAL SOLID
SURFACE SINK PER MECHANICAL
4"
MAINTAIN CLEAR TOE
KICK
REFER TO INTERIOR ELEVATION
1 1/2" x 1/8" SQ. TUBE STEEL
BRACE, PAINT. INSTALL BRACE
WHERE INDICATED AND @ 42"B
MAX. AT ALL UNSUPPORTED
COUNTERTOPS
ANGLE AND CAP AT TOP
AND BOTTOM AS SHOWN
3/8" DIA FASTENERS, TYP
1x WALL CLEAT
SOLID STEEL
STUD BLOCKING
FIN. FLOOR: INSTALL
BEFORE CASEWORK, TYP
BASE PER FINISH
SCHEDULE
4"
SCRIBE TO WALL SURFACE
SOILID SURFACE COUNTERTOP
AS SPECIFIED OVER PLYWOOD
BACKSPLASH WHERE OCCURS -
SEE INTERIOR ELEVATIONS
906 Columbia Street SW, Suite 400
Olympia, Washington 98501
360.352.8883 architects
KMB Project #
SHEET NO.
REVISIONS:
DATE:
ORIGINAL SHEET SIZE = 24 x 36
HALF SIZE REDUCTIONS = 11 x 17
P
LO
T D
A T
E
ARCHITECT
STATE OF WASHINGTON
REGISTERED
JAMES HILL
10347
/3
/2
:4
8:
P M
7-31-2026
BID SET
A-583
CASEWORK DETAILS
LE
W
IS
C
O U
N
TY
R A
IN
IE
R N
O R
TH
B
U
IL
D
IN
G T
I
LE
W
IS
C O
U N
TY
F
A C
IL
IT
IE
S
D
EP
A R
TM
EN
T
N W
N O
R
TH
S
TR
EE
T, C H
EH
A
LI
S
, W A
Fa ci lit ie s D ep ar tm en t
J2037C
1 1/2" = 1'-0"3
UPPER CABINET
1" = 1'-0"1
BASE CABINET W/ DOOR AND DRAWER
1 1/2" = 1'-0"5
TYPICAL COUNTERTOP BRACE
1" = 1'-0"2
BASE CABINET W/ SINK
1" = 1'-0"4
CASEWORK DETAIL @ COUNTERTOP
BACKING
WAINSCOT
BELOW
SEALANT
22 GA. BREAK METAL
OVER 3/8" MDF, MT2.
GRAB BAR
ASSEMBLY
GRAB BAR
ASSEMBLY
22 GA. BREAK METAL
OVER 3/8" MDF
NOTE: SPACER TO MATCH
THICKNESS OF WAINSCOT
BELOW
PLAN VIEW
ELEV.
CL
(3) STEEL STUD SUPPORT
BACKING AT GRAB BAR
CONNECTIONS
W A
LL
P
E R
P
LA
N
1/2"
RADIUS
REFER TO ROOM SIGN
X/A-XX FOR DETAIL
PROVIDE BRUSHED ALUMINUM (HORIZONTAL) PLATE ON
OPPOSITE SIDE OF GLAZING. 10" W X 8 3/4" H TO MATCH
SIGN FACE.
SECTION ELEVATION FRONT ELEVATION
NOTE: PICTOGRAM IN WHITE BACKGROUND
IN BLUE PER IBC 2015 (WAC 2015) 1101.2.6
(ICC A117.1 SECTION 703.6.3.1)
SIGN FACE.
HOLLOW METAL DOOR FRAME
SIDELITE GLAZING
MAXIMUM OCCUPANCY
XX PERSONS
1/
2"
1'-5"
O F
T E
X T
1" T
O T
O P
FONT SIZE: 1 INCH
FONT STYLE: ARIAL
REFER TO 1/G1201- CODE &
EXITING PLAN FOR
OCCUPANY LOADS
ROOM NAME
GRADE II BRAILLE
FONT SIZE: 3/4 INCH
FONT STYLE: ARIAL
10"
3"
O F
T E
X T
1" T
O T
O P
8"
9"
FONT SIZE: 3/4 INCH
FONT STYLE: ARIAL
GRADE II BRAILLE
SOLID COLOR ACRYLIC PLACARD
IN INTERNATIONAL BLUE, TYP.
EQ
PICTOGRAM O.C.
HORIZONTALLY EQ
NOTE: PICTOGRAM IN WHITE BACKGROUND
IN BLUE PER IBC 2015 (WAC 2015) 1101.2.6
(ICC A117.1 SECTION 703.6.3.1)
RESTROOM
1" 4"
1/ 4"
1" 3/
4" 2"
SIGN TO BE LOCATED AT ALL
RESTROOMS
7"
ACCESS FLOOR PER
MANUFACTURER
1/
2"
3/4"
RUBBER BASE
PARTIAL WALL,
REFER TO FLOOR PLAN FOR TYPE
1X2 WOOD TRIM
SOLID SURFACE ON 3/4" PLYWOOD
PER MANUFACTURER
(2) 3/4 T&G PLYWOOD
2X TREATED BLOCKING
@ 16" O.C.
EXISTING CONCRETE
FINISH AS INDICATED
IN FINISH PLAN
STAINLESS STL TRANSITION STRIP
SCHLUTER RENO RAMP 100B65 OR SIM.
(E) CONCRETE FLOOR SLAB
TILECONCRETE
TRANSITION STRIP ROPPE 67 OR SIM.
(E) CONCRETE FLOOR SLAB
CARPET /
LINOLEUMCONCRETE
906 Columbia Street SW, Suite 400
Olympia, Washington 98501
360.352.8883 architects
KMB Project #
SHEET NO.
REVISIONS:
DATE:
ORIGINAL SHEET SIZE = 24 x 36
HALF SIZE REDUCTIONS = 11 x 17
P
LO
T D
A T
E
ARCHITECT
STATE OF WASHINGTON
REGISTERED
JAMES HILL
10347
/3
/2
:4
8:
P M
7-31-2026
BID SET
A-585
INTERIOR DETAILS
LE
W
IS
C
O U
N
TY
R A
IN
IE
R N
O R
TH
B
U
IL
D
IN
G T
I
LE
W
IS
C O
U N
TY
F
A C
IL
IT
IE
S
D
EP
A R
TM
EN
T
N W
N O
R
TH
S
TR
EE
T, C H
EH
A
LI
S
, W A
Fa ci lit ie s D ep ar tm en t
J2037C
3" = 1'-0"8
GRAB BAR DETAIL
3" = 1'-0"6
ROOM SIGN @ SIDELITE
3" = 1'-0"5
MAXIMUM OCCUPANCY SIGNAGE
3" = 1'-0"4
ROOM SIGN
3" = 1'-0"7
UNISEX RESTROOM SIGN
1 1/2" = 1'-0"3
ACCESS FLOOR DETAIL
1" = 1'-0"1
HALF WALL SECTION
1 1/2" = 1'-0"2
FLOOR INFILL
3" = 1'-0"9
FLOOR TRANSITIONS
DOOR NOTES
ABBREVIATIONS
ALUM ALUMINUM
CC CLEAR COAT
FF FACTORY FINISH
FIN FINISH
H HEIGHT
HM HOLLOW METAL
MATL MATERIAL
MFG MANUFACTURER
N/A NOT APPLICAPLE
• PRE-FINISH = FINISHED BY MANUFACTURER TO MATCH KAWNEER BURGUNDY
• REFER TO INTERIOR FINISH SCHEDULE FOR PAINT SPECIFICS.
DOOR AND FRAME GENERAL NOTES
1. DOOR & FRAME SCHEDULE NOTES APPLY TO ALL DOOR & FRAME SCHEDULES.
2. DIMENSIONSOF ALL OPENINGS TO BE FIELD VERIFIED PRIOR TO FABRICATION.
3. PROVIDE 1/2" MAX SHIM SPACE AT HEAD, JAMB AND SILL AT OPENINGS.
4. FRAME MANUFACTURER SHALL COORDINATE LOCATIONS OF CONCEALED
CONDUIT & J-BOXES FOR SYSTEM HARDWARE PRIOR TO MANUFACTURING OF
FRAMES & COORDINATE WITH ASSOCIATED HARDWARE & DEVICES.
5. SEE SPECIFICATIONS SECTION 08 71 00 DOOR HARDWARE FOR DOOR HARWARE
SET NOTED IN DOOR SPECIFICATIONS OPENING SCHEDULE.
6. GLASS TYPES FOR DOORS AND FRAMEARE INDICATED. REFER TO STOREFRONT
TYPES & FRAME TYPES & DOOR SCHEDULE. SEE SPECIFICATIONS DIVISION 08
SECTIONS FOR GLASS TYPE DESCRIPTIONS AND GLASS NOTES FOR
ABBREVIATIONS.
7. ALL HOLLOW METAL DOORS AND FRAMES ARE TO BE PAINTED.
P PAINT
R RELITE
PR PAIR
SIM SIMILAR
STL STEEL
TEMP TEMPERED
THCK THICKNESS
W WIDTH
WD WOOD
F.F.
FLUSH - INSULATED
HOLLOW METAL DOOR
H E
IG
H
T
WIDTH
A NARROW LITE -
INSULATED HOLLOW
METAL DOOR
B
H E
IG
H
T P
E R
S C
H E
D U
L E
WIDTH
4" 8"
3' -4
3'
-0
8"
H E
IG
H
T P
E R
S C
H E
D U
L E
PER SCHED.
WIDTH
FULL LITE - INSULATED
HOLLOW METAL DOOR
C
6" 2'-0" 6"
5' -6
8"
H E
IG
H
T P
E R
S C
H E
D U
L E
PER SCHED.
WIDTH
F
1/2" CLEAR
TEMPERED
GLAZING
3' -6
8"
HALF LITE
6" 6"
F.F.
2' - 0"
W1
A-541
D O
O R
H E
IG
H
T
2" DOOR WIDTH 2"
F.F.
HOLLOW METALF1
A-541
A-541
D O
O R
H E
IG
H
T
2" DOOR WIDTH 2"
CASED OPENINGF5
A-541
A-541
906 Columbia Street SW, Suite 400
Olympia, Washington 98501
360.352.8883 architects
KMB Project #
SHEET NO.
REVISIONS:
DATE:
ORIGINAL SHEET SIZE = 24 x 36
HALF SIZE REDUCTIONS = 11 x 17
P
LO
T D
A T
E
ARCHITECT
STATE OF WASHINGTON
REGISTERED
JAMES HILL
10347
/3
/2
:4
8:
P M
7-31-2026
BID SET
A-601
DOOR SCHEDULE
LE
W
IS
C
O U
N
TY
R A
IN
IE
R N
O R
TH
B
U
IL
D
IN
G T
I
LE
W
IS
C O
U N
TY
F
A C
IL
IT
IE
S
D
EP
A R
TM
EN
T
N W
N O
R
TH
S
TR
EE
T, C H
EH
A
LI
S
, W A
Fa ci lit ie s D ep ar tm en t
J2037C
GENERAL DOOR NOTES
1. ALL DOOR HARDWARE TO CONFORM WITH A.D.A. STANDARDS.
2. ALL DOOR HARDWARE HEIGHTS TO CONFORM WITH A.D.A. STANDARDS.
3. PRIOR TO CONSTRUCTION, SUBMIT DOOR HARDWARE TO ARCHITECT FOR APPROVAL.
4. CONFIRM DOOR FRAME DIMENSIONS AND COMPATIBILITY WITH DOOR HARDWARE PRIOR TO
IMPLEMENTATION.
5. SHOP PRIME ALL HOLLOW METAL FRAMES.
6. REFER TO FINISH LEGEND FOR ALL DOOR AND FRAME FINISH REFERENCES.
7. PROVIDE ACOUSTICAL INSULATION AND SEALANTS AT DOOR AND RELITE FRAMES INSTALLED IN
STC-RATED WALL ASSEMBLIES.
8. DOORS THAT ARE NOT AUTOMATIC SHALL HAVE ACCESSIBLE FEATURES AND HARDWARE PER
CURRENT IBC AND ANSI 117
9. EXITING DOORS SHALL HAVE APPROVED PANIC HARDWARE PER CURRENT IBC
10. TACTILE SIGNS SHALL BE INSTALLED AS PER CURRENT IBC AND ANSI 117
DOOR SCHEDULE - BUILDING 2
DOOR
NO.
DOOR FRAME
HDW COMMENTSW H TYPE THCK MATL FIN GLASS TYPE MATL FIN GLASS
101A 3' - 0" 7' - 0" C 1 3/4" WD CC TEMP F1 HM P - - 6
102A 3' - 0" 7' - 0" C 1 3/4" WD CC TEMP F1 HM P - - 6
103A 3' - 0" 7' - 0" C 1 3/4" WD CC TEMP F1 HM P - - 8
104A 3' - 0" 7' - 0" F 1 3/4" WD CC TEMP F1 HM P - - 6
105A 3' - 0" 7' - 0" F 1 3/4" WD CC TEMP F1 HM P - - 6
106A 3' - 0" 7' - 0" F 1 3/4" WD CC TEMP F1 HM P - - 6
107A 3' - 0" 7' - 0" F 1 3/4" WD CC TEMP F1 HM P - - 6
108A 3' - 0" 7' - 0" F 1 3/4" WD CC TEMP F1 HM P - - 6
109A 3' - 0" 7' - 0" F 1 3/4" WD CC TEMP F1 HM P - - 6
110A 3' - 0" 7' - 0" F 1 3/4" WD CC TEMP F1 HM P - - 6
111A 3' - 0" 7' - 0" C 1 3/4" WD CC TEMP F1 HM P - - 6
112A 3' - 0" 7' - 0" A 1 3/4" WD CC - - F1 HM P - - 14
112B 3' - 0" 7' - 0" A 1 3/4" WD CC - - F1 HM P - - 14
114A 3' - 0" 7' - 0" A 1 3/4" WD CC - - F1 HM P - - 4
115A 3' - 0" 7' - 0" A 1 3/4" WD CC - - F1 HM P - - 9
116A 3' - 0" 7' - 0" A 1 3/4" WD CC - - F1 HM P - - 4
117A 3' - 0" 7' - 0" A 1 3/4" WD CC - - F1 HM P - - 14
117B 3' - 0" 7' - 0" A 1 3/4" WD CC - - F1 HM P - - 14
118A 3' - 0" 7' - 0" A 1 3/4" WD CC - - F1 HM P - - 14
123A 3' - 0" 7' - 0" C 1 3/4" WD CC TEMP F1 HM P - - 17
124A 3' - 0" 7' - 0" F 1 3/4" WD CC TEMP F1 HM P - - 6
1/4" = 1'-0"3
DOOR TYPES
1/4" = 1'-0"2
RELITE TYPES
1/4" = 1'-0"1
FRAME TYPES
CONC - SEALED CONCRETE
LINO2 - LINOLEUM
CPT2 - CARPET
TL1 - TILE
MATERIAL TRANSITION STRIP
CORNER GAURD
FLOOR FINISHES
CONC - GROUND AND SEALED CONCRETE
LINO2 - LINOLEUM - FORBO, MARMOLEUM, STYLE: REAL, COLOR: MIST GREY
CPT2 - CARPET - MANNINGTON, STYLE: SKETCH, COLOR: BOROUGH
TL1 - TILE - DALTILE, STYLE: PORTFOLIO, 12" X 24", COLOR: ASH GREY
BASE FINISHES
RB1 - RUBBER BASE - ARMSTRONG, STYLE: COVED WALL BASE, COLOR:
FLAGSTONE
RB3 - RUBBER BASE - ARMSTRONG, STYLE: COVED WALL BASE, COLOR: GRAY
MIST
TB1 - BASE TILE - DALTILE, STYLE: PORTFOLIO, COVE BASE, COLOR: ASH
GREY
WALL FINISHES
PT1 - PAINT - SHERWIN WILLIAMS, COLOR: 0054 TWILIGHT GREY
TL2 - WALL TILE - DALTILE, STYLE: PORTFOLIO, 6" X 24", COLOR: ASH GREY
CASEWORK FINISHES
PLAM2 - PLASTIC LAMINATE - WILSONART, COLOR: BRAZILWOOD
SSF1 - SOLID SURFACE - WILSONART, COLOR: CHILLED EARTH
CEILING FINISHES
ACT1 - 2X4 ACOUSTIC CEILING TILE - ARMSTRONG, STYLE: CIRRUS SECOND
LOOK II
R E
F E
R T
O A
-1
R E
F E
R T
O A
-1
HELP DESK
STORAGE
ELECTRIC
RESTROOM
CUSTODIAN
RESTROOM
SERVER
OFFICE
OFFICE
OFFICE
OFFICE
HALLWAY
OFFICE
OFFICE
OFFICE
OFFICE
HALLWAY
HALLWAY
BREAK
ROOM
OFFICE
DIRECTOR
MEETING
ROOM
A-585
A-585
A-585
A-585
OFFICE
HALLWAY
1. ALL INTERIOR SHALL MEET THE CURRENT IBC FOR FLAME SPREAD AND
SMOKE DEVELOPMENT MINIMUM STANDARDS.
2. REFER TO 9/A-585 FOR TYPICAL FLOOR TRANSITIONS
906 Columbia Street SW, Suite 400
Olympia, Washington 98501
360.352.8883 architects
KMB Project #
SHEET NO.
REVISIONS:
DATE:
ORIGINAL SHEET SIZE = 24 x 36
HALF SIZE REDUCTIONS = 11 x 17
P
LO
T D
A T
E
ARCHITECT
STATE OF WASHINGTON
REGISTERED
JAMES HILL
10347
/3
/2
:4
8:
P M
7-31-2026
BID SET
A-621
FINISH PLAN & SCHEDULE
LE
W
IS
C
O U
N
TY
R A
IN
IE
R N
O R
TH
B
U
IL
D
IN
G T
I
LE
W
IS
C O
U N
TY
F
A C
IL
IT
IE
S
D
EP
A R
TM
EN
T
N W
N O
R
TH
S
TR
EE
T, C H
EH
A
LI
S
, W A
Fa ci lit ie s D ep ar tm en t
J2037C
LEGEND-FINISH PLAN
INTERIOR FINISH SCHEDULE
FINISH SCHEDULE - BUILDING 2
ROOM
NO. ROOM NAME
FLOOR
FINISH
BASE
FINISH
NORTH WALL EAST WALL SOUTH WALL WEST WALL
NOTESMATL FIN MATL FIN MATL FIN MATL FIN
101 OFFICE CPT2 RB1 PT1 PT1 PT1 (EXISTING)
102 DIRECTOR CPT2 RB1 (EXISTING) PT1 PT1 (EXISTING)
103 MEETING ROOM CPT2 RB1 (EXISTING) (EXISTING) PT1 PT1
104 OFFICE CPT2 RB1 PT1 (EXISTING) PT1 PT1
105 OFFICE CPT2 RB1 PT1 (EXISTING) PT1 PT1
106 OFFICE CPT2 RB1 PT1 (EXISTING) PT1 PT1
107 OFFICE CPT2 RB1 PT1 (EXISTING) PT1 PT1
108 OFFICE CPT2 RB1 PT1 (EXISTING) PT1 PT1
109 OFFICE CPT2 RB1 PT1 (EXISTING) PT1 PT1
110 OFFICE CPT2 RB1 PT1 (EXISTING) PT1 PT1
111 OFFICE CPT2 RB1 PT1 (EXISTING) (EXISTING) PT1
112 SERVER CONC RB1 PT1 PT1 (EXISTING) PT1
113 BREAK ROOM LINO2 RB1 PT1 PT1 (EXISTING) (EXISTING)
114 RESTROOM TL1 TB1 TL2 / PT1 TL2 / PT1 TL2 / PT1 TL2 / PT1
115 CUSTODIAN CONC RB1 PT1 PT1 PT1 PT1
116 RESTROOM TL1 TB1 TL2 / PT1 TL2 / PT1 TL2 / PT1 TL2 / PT1
117 STORAGE CONC RB1 PT1 PT1 PT1 PT1
118 ELECTRIC CONC RB1 PT1 PT1 PT1 PT1
119 HELP DESK CONC RB1 - - PT1 PT1 PT1
120 HALLWAY CONC RB1 PT1 PT1 - - (EXISTING)
121 HALLWAY CONC RB1 PT1 PT1 - - PT1
122 HALLWAY CONC RB1 PT1 PT1 PT1 PT1
123 HALLWAY CONC RB1 PT1 (EXISTING) PT1 PT1
124 OFFICE CPT2 RB1 (EXISTING) PT1 PT1 PT1
1/8" = 1'-0"1
ENLARGED FLOOR PLAN BLDG 2 - FINISH PLAN
NOTES - FINISH PLAN
STRUCTURAL ABBREVIATIONS:
H HORIZONTAL
HC HOLLOW CORE (PRECAST PRESTRESSED)
HD HOLD DOWN
HDR HEADER
HF HEM FIR
HGR HANGER
HK HOOK
HP HP SHAPE
HORIZ HORIZONTAL
HS HEADED ANCHOR STUD
HSS HOLLOW STRUCTURAL SECTION
HT HEIGHT
CBC INTERNATIONAL BUILDING CODE
ID INSIDE DIAMETER
IF INSIDE FACE
IN INCH
INFO INFORMATION
INT INTERIOR
JST JOIST
JT JOINT
K KIP (1,000 LBS)
KSI KIPS PER SQUARE INCH
KSF KIPS PER SQUARE FOOT
L ANGLE
LB POUND
LD DEVELOPMENT LENGTH
LDH HOOKED BAR DEVELOPMENT LENGTH
LF LINEAR FOOT
LFRS LATERAL FORCE RESISTING SYSTEM
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LOC LOCATION OR LOCATE
LONG LONGITUDINAL
LSL LAMINATED STRAND LUMBER OR LONG SLOTTED (HOLES)
LT WT LIGHTWEIGHT
LVL LAMINATED VENEER LUMBER OR LEVEL
LWC LIGHT WEIGHT CONCRETE
MATL MATERIAL
MAX MAXIMUM
MB MACHINE BOLT
MC MISCELLANEOUS CHANNEL
MECH MECHANICAL
MEP MECHANICAL, ELECTRICAL, AND PLUMBING
MEZZ MEZZANINE
MF MOMENT FRAME
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MK MARK
MOM MOMENT
MTL METAL
MWFRS MAIN WIND FORCE RESISTING SYSTEM
(N) NEW
N NORTH
N/S NORTH/SOUTH
NIC NOT IN CONTRACT
NLT NAIL LAMINATED TIMBER
NO NUMBER
NOM NOMINAL
NS NEAR SIDE OR NON-SHRINK
NTS NOT TO SCALE
NWC NORMAL WEIGHT CONCRETE
OC ON CENTER
OCBF ORDINARY CONCENTRIC BRACED FRAME
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OPNG OPENING
OPP OPPOSITE OR OPPOSITE HANDED
OPT OPTION OR OPTIONAL
OVS OVERSIZED (HOLE)
P PIPE
P/C PRECAST CONCRETE
PAF POWDER ACTUATED FASTENER
PAR PARAPET OR PARALLEL
PC PILE CAP OR PIECE
PCF POUNDS PER CUBIC FOOT
PEN PENETRATION
PERP PERPENDICULAR
PJP PARTIAL JOINT PENETRATION
PL PLATE
PLF POUNDS PER LINEAR FOOT
PLYWD PLYWOOD
PNL PANEL
PREFAB PREFABRICATED
PROJ PROJECTION
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PSL PARALLEL STRAND LUMBER (PARALLAM)
PT PRESSURE TREATED OR POST TENSIONED OR POINT
R RADIUS
RBS REDUCED BEAM SECTION
RC REINFORCED CONCRETE
REBAR REINFORCING BAR
REF REFERENCE OR REFER TO
REINF REINFORCE OR REINFORCING (STEEL)
REM REMAIN OR REMAINDER
REQ’D REQUIRED
RET RETAINING
RND ROUND
RO ROUGH OPENING
RTN RETURN
S SOUTH
SAD SEE ARCHITECTURAL DRAWINGS
SC SLIP CRITICAL
SCBF SPECIAL CONCENTRIC BRACED FRAME
SCHED SCHEDULE
SDQ SPECIAL DUCTILE QUALITY
SDS SELF-DRILLING SCREW
SECT SECTION
SEOR STRUCTURAL ENGINEER OF RECORD
SFRS SEISMIC FORCE RESISTING SYSTEM
SHT SHEET
SHTG SHEATHING
SIM SIMILAR
SMF SPECIAL MOMENT FRAME
SOG SLAB ON GRADE
SOMD SLAB ON METAL DECK
SP SPACE OR SPACES
SPEC SPECIFICATION
SQ SQUARE
STRUCTURAL ABBREVIATIONS:
& AND
@ AT
° OR DEG DEGREES
Ø OR DIA DIAMETER
# NUMBER OR POUND
± PLUS OR MINUS
AB ANCHOR BOLT (IN CONCRETE)
ADD’L ADDITIONAL
AESS ARCHITECTURALLY EXPOSED STRUCTURAL STEEL
AFF ABOVE FINISH FLOOR
AGG AGGREGATE
AHJ AUTHORITY HAVING JURISDICTION
ALT ALTERNATE
ALUM ALUMINUM
ANCH ANCHOR
ARCH’L ARCHITECTURAL
APPROX APPROXIMATE
AVG AVERAGE
B BOTTOM BARS
B/ BOTTOM OF
BF BRACED FRAME
BLDG BUILDING
BLKG BLOCKING
BM BEAM
BOD BOTTOM OF DECK
BOF BOTTOM OF FOOTING
BOS BOTTOM OF STEEL
BOT BOTTOM
BP BASE PLATE
BRB BUCKLING RESTRAINED BRACE
BRBF BUCKLING RESTRAINED BRACED FRAME
BRG BEARING
BSMT BASEMENT
BTWN BETWEEN
BU BUILT UP
C CHANNEL OR CAMBER
C/C CENTER TO CENTER
C&C COMPONENTS AND CLADDING
CANT CANTILEVER
CB CASTELLATED BEAM
CFMF COLD-FORMED METAL FRAMING
CG CENTER OF GRAVITY
CIP CAST IN PLACE
CJ CONSTRUCTION JOINT
CJP COMPLETE JOINT PENETRATION
CL CENTERLINE
CLG CEILING
CLR CLEAR OR CLEARANCE
CLT CROSS LAMINATED TIMBER
CMU CONCRETE MASONRY UNIT
COL COLUMN
COMP COMPRESSION
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
COORD COORDINATE
CTR CENTER OR CENTERED
CY CUBIC YARD
D PENNY (NAIL)
DB BAR DIAMETER OR DIVIDER BEAM
DBA DEFORMED BAR ANCHOR
DBL DOUBLE
DEG DEGREE OR DEGREES
DEMO DEMOLISH OR DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DEV DEVELOPMENT
DF DOUGLAS FIR
DIA DIAMETER (ALSO SHOWN AS Ф)
DIAG DIAGONAL
DIAPH DIAPHRAGM
DIM DIMENSION
DIST DISTANCE
DL DEAD LOAD
DLT DOWEL LAMINATED TIMBER
DN DOWN
DO DITTO
DP DEEP OR DEPTH
DT DOUBLE TEE (PRESTRESSED PRECAST)
DWG DRAWING
DWL DOWEL
(E) EXISTING
E EAST
E/W EAST/WEST
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR OR ELEVATION
EMBED EMBEDDED
ENGR ENGINEER
EOR ENGINEER OF RECORD
EOS EDGE OF SLAB
EQ EQUAL OR EARTHQUAKE
EQUIP EQUIPMENT
ES EACH SIDE
ETC ET CETERA
EW EACH WAY
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
FB FLAT BAR
FF FINISH FLOOR
FIN FINISH OR FINISHED
FL FLOOR
FLG FLANGE
FN FACE NAIL
FNDN FOUNDATION
FRP FIBER REINFORCED POLYMER
FRT FIRE RETARDANT TREATED
FS FAR SIDE
FT FOOT OR FEET
FTG FOOTING
GA GAUGE
GALV GALVANIZED
GB GRADE BEAM
GC GENERAL CONTRACTOR
GEN GENERAL
GEOTECH GEOTECHNICAL
GLB GLUE LAMINATED BEAM
GR GRADE
GWB GYPSUM WALL BOARD
STRUCTURAL ABBREVIATIONS:
SR STUD RAIL
SS STAINLESS STEEL
SSL SHORT SLOTTED (HOLES)
STD STANDARD
STIFF STIFFENER
STIFF PL STIFFENER PLATE
STIRR STIRRUP
STL STEEL
STR STRAIGHT
STRUCT STRUCTURAL
SUB SUBCONTRACTOR
SUPP SUPPORT
SW SHEAR WALL
SYM SYMMETRICAL
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
TEMP TEMPERATURE OR TEMPORARY
T TOP BARS
T/ TOP OF
THK THICK OR THICKNESS
THKND THICKENED
THRD THREADED
THRU THROUGH
TOB TOP OF BEAM
TOC TOP OF CONCRETE OR TOP OF CURB
TOF TOP OF FOOTING OR TOP OF FRAMING
TOL TOLERANCE
TOS TOP OF STEEL
TOW TOP OF WALL
TRANS TRANSVERSE
TW WEB THICKNESS
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
UT ULTRASONIC TEST
VERT VERTICAL
VIF VERIFY IN FIELD
W WEST
W/ WITH
W/C WATER TO CEMENT
W/O WITHOUT
WD WOOD
WF WIDE FLANGE
WP WORK POINT
WT WEIGHT OR WT SHAPE
WWR WELDED WIRE REINFORCING
S T R U C T U R A L G E N E R A L N O T E S
BUILDING CODE AND STANDARDS:
1. DESIGN AND CONSTRUCTION SHALL CONFORM TO 2018 INTERNATIONAL BUILDING CODE AND ALL
APPLICABLE REFERENCED STANDARDS.
GENERAL NOTES AND REQUIREMENTS:
1. THE CONTRACT DOCUMENTS ARE COMPLEMENTARY: THE STRUCTURAL DRAWINGS ARE TO
BE USED IN CONJUNCTION WITH THE PROJECT SPECIFICATIONS, ARCHITECTURAL
DRAWINGS, AND DRAWINGS PREPARED BY OTHER DISCIPLINES.
2. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY AND COORDINATE THE
INFORMATION AND DIMENSIONS SHOWN IN THE CONTRACT DOCUMENTS PRIOR TO
PROCEEDING WITH CONSTRUCTION. WHERE CONFLICTS OR DISCREPANCIES ARE FOUND
WITHIN THE CONTRACT DOCUMENTS, THE MOST STRINGENT REQUIREMENT SHALL BE
ASSUMED TO GOVERN. THE CONTRACTOR SHALL REPORT ANY DISCREPANCIES OR
CONFLICTS TO THE ARCHITECT OR ENGINEER.
3. COORDINATION BETWEEN TRADES (INCLUDING DIMENSIONS AND LOCATIONS OF OPENINGS
AND INSERTS) IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR.
4. THE CONTRACTOR IS RESPONSIBLE TO VERIFY SITE CONDITIONS, INCLUDING DIMENSIONS, CONDITIONS, AND ELEVATIONS OF GRADE, AND LOCATION, DEPTH, AND EXTENTS OF
UTILITIES PRIOR TO PROCEEDING WITH CONSTRUCTION.
5. THE STRUCTURAL DRAWINGS ARE TO BE USED IN CONJUNCTION WITH THE ARCHITECTURAL
DRAWINGS. THE STRUCTURAL DRAWINGS INDICATE LOCATIONS OF PRIMARY STRUCTURAL
ELEMENTS ONLY. ADDITIONAL INFORMATION REQUIRED FOR LAYOUT AND DETAILING MAY
REQUIRE DIMENSIONAL INFORMATION SHOWN IN THE ARCHITECTURAL DRAWINGS.
6. THESE DRAWINGS SHOW THE COMPLETED STRUCTURE, NOT THE MEANS AND METHODS
NECESSARY FOR ITS CONSTRUCTION. MEANS AND METHODS ARE THE SOLE RESPONSIBILITY
OF THE CONTRACTOR, AND INCLUDE, BUT ARE NOT LIMITED TO:
A. STABILITY OF THE STRUCTURE DURING CONSTRUCTION, INCLUDING TEMPORARY
SHORING OR BRACING OF THE STRUCTURE TO RESIST LOADS DURING CONSTRUCTION
B. USE OR EVALUATION OF EQUIPMENT OR PROCEDURES DURING CONSTRUCTION
C. SEQUENCING OF CONSTRUCTION
D. FORMWORK AND REQUIRED BRACING
E. JOB SITE SAFETY AND ADHERENCE TO ALL SAFETY STANDARDS
7. TEMPORARY LOADS ON THE STRUCTURE, INCLUDING CONSTRUCTION EQUIPMENT,
PERSONNEL, AND STAGING LOADS, SHALL NOT EXCEED THE DESIGN LIVE LOAD OF THE
AFFECTED AREA. WHERE THESE LOADS WILL EXCEED THE DESIGN LIVE LOAD, THE
CONTRACTOR IS RESPONSIBLE TO PROVIDE SHORING TO SUPPORT THE CONSTRUCTION
LOADS.
8. SITE VISITS AND STRUCTURAL OBSERVATIONS ARE PERFORMED TO CONFORM GENERAL
CONFORMANCE WITH THE CONTRACT DOCUMENTS AND WILL NOT PROVIDE REVIEW OR
APPROVAL OF THE CONTRACTOR’S MEANS AND METHODS.
9. WHERE DETAILS, NOTES, OR SHEETS ARE NOTED AS “TYP” OR “TYPICAL”, THEY ARE TO BE
APPLIED THROUGHOUT THE PROJECT UNLESS NOTED OTHERWISE. TYPICAL DETAILS MAY
NOT BE INDICATED AT ALL LOCATIONS THEY OCCUR, AND MAY NOT BE INDICATED AT ALL.