LC94 HVAC ROOF AND HVAC REPAIR BID SET PLANS 8APRIL2024.pdf

PDF 5 MB Posted

Attached to
LC-94 MAB ROOFING AND HVAC SYSTEM REPAIR B36003 WSMR, NM
Solicitation number
W911SG24B0004
Issued by

About this file

This document is a 100% design bid set for the LC-94 MAB Roofing and HVAC System Repair project at White Sands Missile Range (WSMR) in New Mexico. The project includes replacing the existing roof with standing seam metal panels, replacing the Lightning Protection System (LPS), and replacing 8 HVAC units (4 wall-mounted and 4 ground-mounted). Key details include:

The project is being procured through Solicitation W911SG24B0004, a small business set-aside under NAICS 238160 with an estimated value between $500,000 and $1,000,000. A site visit is scheduled for July 17, 2024 and bids are due August 8, 2024. The contract will be awarded as Firm Fixed Price. The government agency involved is the Department of the Army Materiel Command Mission and Installation Contracting Command Fort Hood (MICC Fort Hood). The drawings provide detailed specifications for the roof, LPS, and HVAC system replacement.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DESIGNED

CHIEF, ENGINEERING DIVISION

DATE

APPROVED

RECOMMENDED

BRANCH CHIEF

SUBMITTED

PROJECT MANAGER

CHECKED

DRAWN BY

NO. DATE

DRAWING NUMBER

SCALE

SHEET OF

SHEET

DESCRIPTION

REVISIONS

APPROVEDBY

SHEET SIZE

NTS

WHITE SANDS MISSILE RANGE, NEW MEXICO

DIRECTORATE OF PUBLIC WORKS

ENGINEERING SERVICES DIVISION

DRAWING TITLE

WS-36003-2024-G-G1-01

COVER SHEET

& INDEX SHEET

04APRIL2024 ARCH D

JF

DG

JAMES NUNEZ

01 06

ROBERT LOPEZ

B36003

LC-94 MAB ROOFING AND HVAC REPAIR

SHEET INDEX

DRAWING NUMBER TITLE

WS-36003-2024-G-GI-01 COVER SHEET/INDEX SHEET

WS-36003-2024-G-PL-02 LC94 PROJECT LOCATION

WS-36003-2024-G-100-03 GENERAL NOTES

WS-36003-2024-M-MH-04 B36003 HVAC UNITS REPLACEMENT

WS-36003-2024-A-RP-05 B36003 ROOF REPAIR AND LPS

WS-36003-2024-E-DT-06 B36003 ELECTRICAL SYSTEM

AutoCAD SHX Text

WHITE SANDS MISSILE RANGE, NEW MEXICO

AutoCAD SHX Text

DIRECTORATE OF PUBLIC WORKS

AutoCAD SHX Text

ENGINEERING DIVISION

AutoCAD SHX Text W

AutoCAD SHX Text H

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text M

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text B

AutoCAD SHX Text I

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text H

AutoCAD SHX Text P

AutoCAD SHX Text L

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text S

AutoCAD SHX Text M

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text Y

AutoCAD SHX Text

100% DESIGN BID SET

DATE

APPROVED

RECOMMENDED

BRANCH CHIEF

SUBMITTED

PROJECT MANAGER

CHECKED

DRAWN BY

NO. DATE

DRAWING NUMBER

SCALE

SHEET OF

SHEET

DESCRIPTION

REVISIONS

APPROVEDBY

SHEET SIZE

NTS

WHITE SANDS MISSILE RANGE, NEW MEXICO

DIRECTORATE OF PUBLIC WORKS

ENGINEERING SERVICES DIVISION

DRAWING TITLE

WS-36003-2024-G-PL-02

LC94

PROJECT LOCATION

04APRIL2024 ARCH D

JF

DG

JAMES NUNEZ

02 06

ROBERT LOPEZ

AutoCAD SHX Text

%%ULOCATION MAP

AutoCAD SHX Text

%%UVICINITY MAP

DATE

APPROVED

RECOMMENDED

BRANCH CHIEF

SUBMITTED

PROJECT MANAGER

CHECKED

DRAWN BY

NO. DATE

DRAWING NUMBER

SCALE

SHEET OF

SHEET

DESCRIPTION

REVISIONS

APPROVEDBY

SHEET SIZE

NTS

WHITE SANDS MISSILE RANGE, NEW MEXICO

DIRECTORATE OF PUBLIC WORKS

ENGINEERING SERVICES DIVISION

DRAWING TITLE

WS-36003-2024-G-100-03

GENERAL NOTES

04APRIL2024 ARCH D

JF

DG

JAMES NUNEZ

03 06

ROBERT LOPEZ

GENERAL NOTES-

1. CONTRACTOR PERSONNEL ACCESS TO EACH SITE REQUIRES APPROVAL FROM THE

WSMR SECURITY OFFICE AND COMPLY WITH THE REQUIREMENTS OF THE WHITE SANDS

MISSILE RANGE VISITOR/ACCESS CONTROL POLICY (04JUNE2021).

2. THE CONTRACTOR SHALL COORDINATE ALL ACTIVITIES WITH THE CONTRACTING

OFFICER'S REPRESENTATIVE (C.O.R.). NO CONSTRUCTION WORK SHALL BE

ACCOMPLISHED WITHOUT AN APPROVED CONSTRUCTION SCHEDULE. THE

CONTRACTOR SHALL NOTIFY THE C.O.R. OF THE SCHEDULED OUTAGES 72 HOURS IN

ADVANCE.

3. CONTRACTOR SHALL COORDINATE ALL WORK WITH EXISTING CONDITIONS AND

CONSTRUCTION DRAWINGS. CONTRACTOR SHALL PROVIDE ALL EQUIPMENT, MATERIAL

AND LABOR AS REQUIRED FOR COMPLETE FUNCTIONAL SYSTEMS.

4. CONTRACTOR SHALL NOTIFY AND COORDINATE WITH C.O.R. FOR ANY CRANE,

FORKLIFT, SCISSOR LIFT OR MANLIFT USE AT THE SITE WHICH WILL BE NEEDED TO

REMOVE/INSTALL EQUIPMENT. CONTRACTOR SHALL BARRICADE HAZARDOUS

OPERATIONS AREAS.

5. THE CONTRACTOR SHALL PROVIDE ALL NECESSARY SAFETY BARRICADES, ROOF TOP

BARRIERS AND FALL PROTECTION FROM EXPOSED WORK AREAS AND DANGER ZONES

TO PROTECT ALL WORKMEN AND OCCUPANTS OF THE AFFECTED WORK AREA. THE

SAFETY BARRICADES WILL BE MAINTAINED IN SUCH A CONDITION AS TO PROVIDE A

CONSTANT, OPTIMAL WARNING TO ALL PERSONS OF THE CONTINUING CONSTRUCTION.

THE CONTRACTOR SHALL LIMIT ACCESS TO THE WORK AREAS TO ONLY

CONSTRUCTION AND ESSENTIAL PERSONNEL. PPE, HARDHATS AND STEEL TOED

FOOTWEAR WILL BE REQUIRED.

6. ALL MATERIALS AND EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH

MANUFACTURER'S PUBLISHED RECOMMENDATIONS, CONTRACT DOCUMENTS,

INDUSTRY STANDARDS AND ALL FEDERAL, STATE AND LOCAL CODES AND

AMENDMENTS AS ADOPTED BY THE GOVERNMENT FOR SERVICE INTENDED BY THE

CONTRACTING OFFICER (KO). THE INSTALL OF ALL MATERIALS AND EQUIPMENT SHALL

BE MADE BY EXPERIENCED AND LICENSED CRAFTSMAN IN A NEAT WORKMAN LIKE

MANNER, ALL MATERIALS, SUPERVISION, LABOR, TOOL, COST AND SERVICES

NECESSARY TO COMPLETELY INSTALL A FUNCTIONAL SYSTEM SHALL BE FURNISHED

BY THE CONTRACTOR.

7. THE TERM "PROVIDE" USED IN THE DRAWINGS AND SCOPE OF WORK IMPLIES THE

CONTRACTOR IS TO FURNISH, TRANSPORT, INSTALL, CONNECT, WARRANT, AND

START-UP, INCLUSIVELY.

8. THE DRAWINGS ARE DIAGRAMMATIC ONLY BUT SHALL BE FOLLOWED AS CLOSELY AS

ACTUAL CONSTRUCTION CONDITIONS AND WORK OF OTHER TRADES PERMIT. THE

DIMENSIONS IN THE DRAWINGS ARE FOR REFERENCE ONLY AND THE CONTRACTOR

SHALL FIELD VERIFY ALL NECESSARY DIMENSIONS REQUIRED TO PERFORM THE SCOPE

OF WORK.

9. CONTRACTOR SHALL REPORT DISCREPANCIES BETWEEN FIELD CONDITIONS AND NEW

CONSTRUCTION DRAWINGS TO THE KO IN WRITING BEFORE THE RFI DEADLINE DURING

THE SOLICITATION PHASE, PRIOR TO PROVIDING THEIR BID.

10. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING STRUCTURE, EQUIPMENT AND

UTILITIES WITHIN THE FACILITY TO ACCOMMODATE THE SYSTEM REPAIRS PRIOR TO

THE START OF WORK.

11. CONTRACTOR SHALL PROTECT EXISTING STRUCTURE, EQUIPMENT AND UTILITIES

WITHIN THE FACILITY TO ENSURE NO DAMAGE DURING DEMOLITION AND NEW

CONSTRUCTION. ANY DAMAGE THAT IS DONE SHALL BE REPAIRED TO PRIOR

CONDITION AND MATCH EXISTING.

12. UPON COMPLETION OF WORK, CONTRACTOR SHALL PROVIDE WITHIN 10 DAYS,

MANUFACTURER'S OPERATING & MAINTENANCE MANUAL FOR ALL EQUIPMENT

INCLUDING REPLACEMENT PARTS LIST PER SOW 8.8.

13. THE CONTRACTOR SHALL TRANSPORT AND DISPOSE OF ANY CONSTRUCTION WASTE

AND DEBRIS TO AN OFF-SITE SOLID WASTE COLLECTION CENTER THAT HAS BEEN

PERMITTED, BY THE JURISDICTION HAVING AUTHORITY TO ACCEPT AND DISPOSE OF

CONSTRUCTION WASTE AND DEBRIS.

HAZARDOUS MATERIAL TESTING AND ABATEMENT

14. PRIOR TO PERFORMING WORK CONTRACTOR SHALL PERFORM HAZARDOUS BUILDING

MATERIALS SAMPLING OF ALL BUILDING MATERIALS THAT WILL BE DISTURBED IN AREAS

WORKED. TESTING SHALL BE PER SOW PART 10-HAZARDOUS BUILDING MATERIALS

ABATEMENT, CONTRACTOR SHALL FOLLOW GUIDELINES.

15. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ABATING ALL HAZARDOUS BUILDING

MATERIALS FOUND IN THE WORK AREA. ABATEMENT OF HAZARDOUS MATERIALS

(INCLUDING ASBESTOS CONTAINING MATERIAL (ACM), LEAD BASED PAINT (LBP), OR

MOLD SHALL TAKE PLACE PRIOR TO PERFORMING OTHER WORK OF THE PROJECT.

ELECTRICAL WORK

16. PRIOR TO PERFORMING WORK ENSURE THAT ELECTRICAL ENERGY SOURCES TO

EFFECTED SYSTEM HAS BEEN SECURED AND LOCKED OUT/TAGGED OUT (LOTO).

17. IF FOR ANY REASON THE CONTRACTOR REQUIRES TO DIG THEN A UTILITIES LOCATION

SURVEY MUST BE DONE AND COORDINATED WITH THE COR. IF COMMUNICATION LINES

HAVE BEEN LOCATED IN THE AREA TO BE EXCAVATED, HAND DIGGING WILL BE USED

WITHIN A 10-FOOT RADIUS UNTIL THE EXTENT LOCATION OF ALL LINES HAVE BEEN

DETERMINED.

18. LICENSED ELECTRICIAN SHALL INSPECT EXISTING WIRING TYPE AND SIZE AND CIRCUIT

BREAKER RATING TO ENSURE THEY MEETS THE REQUIREMENTS FOR EQUIPMENT AND

CONTROLLER PER NEC. IF REQUIRED FOR HIGHER RATED WIRING, THE ELECTRICIAN

SHALL REMOVE EXISTING WIRING TO THE EXTENT NEEDED AND INSTALL REQUIRED 600

VOLT, THHN COPPER STRANDED ELECTRICAL CONDUCTOR. FOR HIGHER RATED

CIRCUIT BREAKER, ELECTRICIAN SHALL ENSURE THAT THE NEW CIRCUIT BREAKER

DOES NOT UNBALANCE THE PANEL. ALL ELECTRICAL POWER AND CONTROL WIRING

SHALL BE ROUTED THROUGH EMT CONDUIT, USING PROPER CONNECTION METHODS,

J-BOXES, NIPPLES, ETC. ALL ELECTRICAL WORK SHALL BE DONE IN ACCORDANCE WITH

NATIONAL ELECTRIC CODE (NEC) 70 AS REVISED.

19. IN CONJUNCTION WITH THE ROOF REPLACEMENT, THE EXISTING ROOF LPS

COMPONENTS (CONDUCTOR, TERMINALS, TERMINAL BASE, CONNECTORS) WILL BE

REPLACED WITH THE SAME TYPE AND CONFIGURATION AS THOSE DISTURBED DURING

THE ROOF REPLACEMENT. COMPONENTS WILL BE INSTALLED AND COMPLY WITH NFPA

780 AS REVISED. THERMO-WELDS WILL BE DONE AT ALL CONDUCTOR TEES AND

SPLICES IN ACCORDANCE WITH NFPA 780. TESTING OF THE FINISHED LPS SYSTEM WILL

BE DONE TO ENSURE RESISTANCE TO GROUND IS IN COMPLIANCE WITH NFPA 780 AS

REVISED THROUGHTOUT THE SYSTEM.

20.LPS DOWN CONDUCTORS, CENTERPOISE AND GROUDING RODS WILL NOT BE

DISTURBED TO THE GREATEST EXTEND POSSIBLE. IF ANY COMPONENTS ARE FOUND

DAMAGED THEY WILL BE REPLACED WITH NEW AND VERIFIED TO COMPLY WITH NFPA

780 AS REVISED.

MECHANICAL WORK

21. ALL EXISTING HVAC UNITS (FOUR WALL MOUNTED AND 4 GROUND MOUNTED) WILL BE

REMOVED FROM SERVICE AND REPLACED WITH NEW ACCORDING TO THE HVAC

SCHEDULE CONTAINED HEREIN. ENSURE THAT ELECTRICAL POWER AND PROPANE

GAS SUPPLY HAS BEEN ISOLATED FROM THE WORK BEING PERFORMED AND LOTO

(LOCK-OUT/TAG-OUT) HAS BEEN DONE ON ASSOCIATED BREAKERS, DISCONNECT AND

VALVES.

22. THE CONTRACTOR SHALL RECOVER REFRIGERANTS FROM EACH UNIT BEING REMOVED

TO THE GREATEST EXTEND POSSIBLE. REFRIGERANT RECOVERY CYLINDERS WILL BE

PROVIDED BY O.D.S. RESERVE PROGRAM WSMR ENVIRONMENTAL DEPARTMENT.

COORDINATE WITH C.O.R. AND WSMR ENVIRONMENTAL DEPARTMENT IN BUILDING 1870

TO TURN IN RECOVERED REFRIGERANTS TO THE ODS RESERVE PROGRAM.

23. THE CONTRACTOR SHALL RECOVER COMPRESSOR OIL FROM EACH UNIT BEING

REMOVED TO THE GREATEST EXTEND POSSIBLE. RECOVERED OIL BIL BE PLACED IN

D.O.T. APPROVED RECOVERY CYLINDERS. COORDINATE WITH C.O.R. AND WSMR

ENVIRONMENTAL DEPARTMENT HAZARDOUS WASTE MANAGEMENT CENTER IN

BUILDING 1870 FOR DISPOSAL.

24. AFTER REMOVAL OF HVAC UNITS FOR DEMOLITION THE CONTRACTOR SHALL

SECURELY COVER ANY OPEN DUCTWORK TO THE INTERIOR OF THE BUILDING TO

PRECLUDE ENTRANCE OF DEBRIS, WIND AND RAIN FROM INCLEMENT WEATHER UNTIL

NEW UNITS ARE INSTALLED.

25. CONTRACTOR SHALL COORDINATE WITH THE C.O.R. TO HAVE THE SITE PROPANE TANK

COMPLETELY FILLED (AT CONTRACTORS EXPENSE) SO THE NEWLY INSTALLED HVAC

HEATER EQUIPMENT MAY BE FUNCTIONAL CHECKED OUT AND BROUGHT ONLINE AFTER

VERIFIED OPERATIONAL.

26.UPON COMPLETION OF ALL NECESSARY SYSTEM REPAIRS OR MODIFICATIONS, THE

CONTRACTOR SHALL OPERATE THE SYSTEM AND DEMONSTRATE THAT IT IS FULLY

FUNCTIONAL.

27. ALL MECHANICAL WORK SHALL BE DONE IN ACCORDANCE WITH INTERNATIONAL

PLUMBING AND MECHANICAL CODES, AS REVISED. ALL WORK PERFORMED WILL BE

DONE BY CERTIFIED LICENSED TECHNICIANS OF THE TRADE WHICH THEY ARE

PERFORMING.

ARCHITECTURAL WORK

28. ALL ROOF PANELS WILL BE REPLACED WITH STANDING SEAM (MTL) TYPE FROM

MUELLER MANUFACTURER OR EQUIVALENT. PANELS WILL HAVE A CLASS-4 RATING

AND BE 24 GAUGE COMMERCIAL GRADE STEEL. THE PANEL COLOR WILL BE BRIGHT

WHITE. PANELS WILL BE INSTALLED PER MANUFACTURERS INSTRUCTIONS WITH

APPROVED METHODS AND FASTENERS. NEW ROOF WILL BE INSTALLED TO

WITHSTAND WIND LOADS UPTO 110 MPH.

29.EXISTING RAIN GUTTER DOWN SPOUTS WILL USED TO THE GREATEST EXTENT

POSSIBLE. ALL DAMAGED OR BENT RAIN GUTTER AND TRIM ROOF COMPONENTS

WILL BE REPLACED.

30.CONTRACTOR SHALL PROTECT ROOF AND WALL INSULATION DURING DEMOLITION

AND CONSTRUCTION. ALL DAMAGED INSULATION PIECES WILL BE REPLACED.

INSULATION R19 VALUE TO BE MAINTAINED. ALL EXISTING INSULATION SHALL BE

SECURED.

31. THE NEW ROOF WILL HAVE A NEW LOW PROFILE RIDGE VENT PER MANUFACTURER

STANDARD OPTIONS, SIMILARLY CONFIGURED TO THE ONE BEING REPLACED.

32.PRIOR TO REPLACEMENT OF ROOF PANELS, CONTACTOR WILL COORDINATE THE

WORK WITH THE COR TO ENSURE THAT THE CUSTOMER HAS PROTECTED OR

REMOVED EQUIPMENT LOCATED IN THE BUILDING. CONTRACTOR WILL PERFORM

THE ROOF REPLACEMENT IN SEQUENCE TO MINIMIZE EXPOSED AREA AS QUICKLY

AND SAFELY AS POSSIBLE.

₂

₂

DESIGNED

CHIEF, ENGINEERING DIVISION

DATE

APPROVED

RECOMMENDED

BRANCH CHIEF

SUBMITTED

PROJECT MANAGER

CHECKED

DRAWN BY

NO. DATE

DRAWING NUMBER

SCALE

SHEET OF

SHEET

DESCRIPTION

REVISIONS

APPROVEDBY

SHEET SIZE

NTS

WHITE SANDS MISSILE RANGE, NEW MEXICO

DIRECTORATE OF PUBLIC WORKS

ENGINEERING SERVICES DIVISION

DRAWING TITLE

WS-36003-2024-M-MH-04

B36003 HVAC UNITS

REPLACEMENT

04APRIL2024 ARCH D

JF

DG

JAMES NUNEZ

04 06

ROBERT LOPEZ

GENERAL NOTES-

ALSO REFER TO APPLICABLE NOTES ON PAGE 3 OF THIS DRAWING SET

1. DRAWINGS ARE DIAGRAMMATIC ONLY BUT SHALL BE FOLLOWED AS CLOSELY AS ACTUAL CONSTRUCTION CONDITIONS AND WORK OF OTHER TRADES PERMIT. DIMENSIONS IN THE DRAWING ARE FOR REFERENCE AND THE CONTRACTOR SHALL FIELD VERIFY ALL NECESSARY DIMENSIONS, EXISTING STRUCTURE AND EQUIPMENT REQUIRED TO PERFORM

THE SCOPE OF WORK.

2. HVAC UNITS TO BE EQUIVALENT TO MODEL, SIZE AND CONFIGURATION AS INDICATED IN SCHEDULE. SEER RATINGS SHOWN ARE MINIMUM

3. REPLACE RELIEF AIR DAMPER AND MOTORS, ENSURE EXISTING INTEGRATED CONTROLS ARE MAINTAINED WITH HVAC UNITS

4. PROVIDE MERV 8 FILTER

5. PROVIDE HAIL GUARDS ON EACH UNITS CONDENSOR COILS TO PROTECT FROM HAIL DAMAGE

6. PROVIDE FACTORY INSTALLED PHASE MONITOR ON 3 PHASE UNITS

7. AT EACH UNIT REPLACE EXISTING FUSED DISCONNECT SWITCH

8. CONTRACTOR SHALL INSTALL NEW WALL MOUNTED PROGRAMMABLE THERMOSTATS AND CONTROL WIRE IN EXISTING METAL CONDUIT FOR THE HVAC UNITS. NEW THERMOSTATS WILL BE INSTALLED AT THE EXISTING LOCATIONS. THERMOSTATS SHALL BE PROGRAMMABLE PASSWORD PROTECTED AND HAVE AN OVERRIDE BUTTON. THERMOSTATS SHALL

HAVE PROGRAMABLE HIGH/LOW SET POINTS FOR OCCUPIED AND UNOCCUPIED TIMES AND DAYS.

9. AFTER DEMOLITION OF EXISTING HVAC UNITS THE CONTRACTOR SHALL INSPECT THE EXISTING DUCTWORK FOR FITNESS FOR CONTINUE SERVICE AND ENSURE ALL DUCTWORK INTERIOR IS FREE OF DEBRIS. ALL EXTERIOR DUCTWORK SHALL BE FULLY SEALED AND INSULATED WITH 1-1/2" EXTERIOR AND WRAPPED IN ALUMINUM JACKET. R-VALUE OF 3.3

10. EXISTING GAS REGULATORS WILL BE REPLACE WITH LIKE KIND AND CAPACITY.

11. ALL MECHANICAL WORK SHALL BE DONE IN ACCORDANCE WITH INTERNATIONAL MECHANICAL CODE (IMC) AND SHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION (SMACNA) AS REVISED. ALL ELECTRICAL WORK SHALL BE DONE IN ACCORDANCE WITH NATIONAL ELECTRIC CODE (NEC) AS REVISED.

12. HVAC UNITS AND ASSOCIATED SYSTEMS WILL BE INSTALLED PER MANUFACTURERS RECOMMENDATIONS AND SHALL BE INSTALLED BY LICENSED/CERTIFIED HVAC TECHNICIANS

13. CONTRACTOR SHALL MODIFY OR REPLACE THE EXISTING STEEL SUPPORT FRAMES FOR THE HVAC UNITS AS REQUIRED. FRAME IS A WELDED ASSEMBLY FROM STEEL ANGLE OR

EQUIVALENT. GROUND UNITS SHALL BE ELEVATED 12" MINIMUM ABOVE GRADE.

14. ALL FABRICATED METAL FRAMEWORK WILL BE CLEANED OF MILL SLAG, ALL SHARP EDGES REMOVED, PRIMED AND PAINTED WITH A TAN COLOR.

15. A SEALANT WILL BE APPLIED TO ALL EXTERIOR WALL PENETRATIONS FOR DUCTWORK AND CONDUIT WITH A SEALANT THAT MEETS OR EXCEEDS CHEMLINK HIGH PERFORMANCE

WALL AND BLOCK ADHESIVE.

16. CONDENSATE DRAINS WITH P-TRAPS WILL BE INSTALLED ON ALL HVAC UNITS. THE DRAIN LINE WILL BE DIRECTED AT LEAST 5 FEED AWAY FROM THE BUILDING FOUNDATION.

17. CONTRACTOR SHALL PROVIDE PRE-CAST CONCRETE SLABS FOR GROUND HVAC UNITS. SLABS WILL BE PLACED ON LEVEL GRADE AT THE SAME ELEVATION AS THE BUILDING

SLAB.

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text EXISTING ELECTRICAL JUNCTION BOX AND 120/240V DISCONNECT TYPICAL EACH GROUND UNIT

AutoCAD SHX Text

EXISTING PROPANE GAS ISOLATION VALVE AND REGULATOR, TYPICAL EACH GROUND UNIT

AutoCAD SHX Text

TO 120/240V, 1Ø PANEL

AutoCAD SHX Text

TO SITE 1500 GAL. PROPANE TANK DIST = 150'

AutoCAD SHX Text

%%UMECHANICAL FLOOR PLAN

AutoCAD SHX Text

EXISTING 26"Ø SPIRAL ROUND DUCTWORK

AutoCAD SHX Text

EXISTING 26"Ø SPIRAL ROUND DUCTWORK

AutoCAD SHX Text

TO SITE 1500 GAL. PROPANE TANK DIST = 150'

AutoCAD SHX Text

TO 120/240V 1Ø PANEL

AutoCAD SHX Text

THERMOSTAT

AutoCAD SHX Text

THERMOSTAT

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text

THERMOSTAT

AutoCAD SHX Text

THERMOSTAT

AutoCAD SHX Text

480V, 3Ø GENERATOR DISCONNECT

AutoCAD SHX Text

480V-208V TRANSFORMER

AutoCAD SHX Text

120/208V, 3Ø DISCONNECT

AutoCAD SHX Text

120/208V, 3Ø TRANSFORMER

AutoCAD SHX Text

120/240V, 1Ø PANEL

AutoCAD SHX Text

480V, 3Ø DISCONNECT TO PNL 'A'

AutoCAD SHX Text

480V, 3Ø DISCONNECT TO PNL 'A'

AutoCAD SHX Text

480V, 3Ø DISCONNECT TO PNL 'A'

AutoCAD SHX Text

480V, 3Ø DISCONNECT TO PNL 'A'

AutoCAD SHX Text

PANEL "A"

AutoCAD SHX Text

PANEL "B"

AutoCAD SHX Text

PANEL "C"

AutoCAD SHX Text RELIEF AIR DAMPER EXISTING CONTROLS INTEGRATION TO BE MAINTAINED. TYP. 4 LOCATIONS

AutoCAD SHX Text

%%USECTION B-B

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

EXISTING SUPPORT FRAME STL ANGLE 83"X45"X12"

AutoCAD SHX Text

NEW 5T HVAC HEAT PUMP 230V 1Ø TYPICAL 4 PLACES

AutoCAD SHX Text

NEW FLEX DUCT AND TRANSITION PIECE FROM UNIT TO EXISTING DUCT

AutoCAD SHX Text

EXISTING 26" DIAMETER ROUND SPIRAL DUCT

AutoCAD SHX Text

EXISTING SUPPLY AND RETURN DUCT AND WALL PENETRATIONS TYPICAL EACH UNIT

AutoCAD SHX Text

EXISTING ELECTRICAL FUSED DISCONNECT TYPICAL EACH UNIT

AutoCAD SHX Text

EXISTING ELECTRICAL JUNCTION BOX TO 480V, 3Ø PNL A TYPICAL EACH UNIT

AutoCAD SHX Text

EXISTING PROPANE GAS VALVE AND REGULATOR TYP. EACH GROUND UNIT

AutoCAD SHX Text

NEW 5T WALL MOUNT HVAC UNIT 460V 3Ø TYPICAL 4 PLACES

AutoCAD SHX Text

EXISTING SUPPORT FRAME STL ANGLE 60"X30"

AutoCAD SHX Text

EXISTING 26" DIAMETER ROUND SPIRAL DUCT

AutoCAD SHX Text

EXISTING SUPPLY DUCT AND WALL PENETRATION TYPICAL EACH UNIT

AutoCAD SHX Text

EXISTING RETURN AIR DUCT ON WALL WITH PENETRATION TYPICAL EACH UNIT

AutoCAD SHX Text

EXISTING ELECTRICAL FUSED DISCONNECT TYPICAL EACH UNIT

AutoCAD SHX Text

NEW PRE-CAST CONCRETE PAD SIZE TO FIT FRAME

AutoCAD SHX Text

UNIT POSITION

AutoCAD SHX Text

SYSTEM TAG

AutoCAD SHX Text

MODEL NUMBER

AutoCAD SHX Text

FAN PERFORMANCE

AutoCAD SHX Text

AIRFLOW

AutoCAD SHX Text

COOLING COIL PERFORMANCE

AutoCAD SHX Text

GROSS CAPACITY

AutoCAD SHX Text

EFFICIENCY

AutoCAD SHX Text

EDB

AutoCAD SHX Text

EWB

AutoCAD SHX Text

COP

AutoCAD SHX Text

BTUH

AutoCAD SHX Text °F

AutoCAD SHX Text °F

AutoCAD SHX Text

ESP

AutoCAD SHX Text

CFM

AutoCAD SHX Text in H OO

AutoCAD SHX Text

HEAT PUMP PERF.

AutoCAD SHX Text

EER@ AHRI

AutoCAD SHX Text

SEER@ AHRI

AutoCAD SHX Text

EER

AutoCAD SHX Text

ELECTRICAL DATA

AutoCAD SHX Text

MCA

AutoCAD SHX Text A

AutoCAD SHX Text

MOP

AutoCAD SHX Text A

AutoCAD SHX Text UNIT VOLTAGE V/Hz/Ph

AutoCAD SHX Text

WEIGHT NET

AutoCAD SHX Text

LBS

AutoCAD SHX Text

NOTES

AutoCAD SHX Text

1. UNIT TO BE HIGH EFFICIENCY 2-STAGE COOLING W/ 15KW ELEC. HEAT UNIT TO BE HIGH EFFICIENCY 2-STAGE COOLING W/ 15KW ELEC. HEAT 2. UPSIZE UNIT MOTORS AS NEEDED TO PERFORM AT 5900 FEET ELEVATION UPSIZE UNIT MOTORS AS NEEDED TO PERFORM AT 5900 FEET ELEVATION 3. INSTALL NEW ELEC. DISCONNECTS AT EACH LOCATION, INSTALL PER NEC.70 INSTALL NEW ELEC. DISCONNECTS AT EACH LOCATION, INSTALL PER NEC.70 4. INSTALL/REPLACE BAROMETRIC RELIEF AND MAINTAIN INTEGRATED CONTROLS INSTALL/REPLACE BAROMETRIC RELIEF AND MAINTAIN INTEGRATED CONTROLS 5. INSTALL ECONOMIZERS EACH UNIT INSTALL ECONOMIZERS EACH UNIT 6. REPLACE EQIVALENT THERMOSTATS AT CURRENT LOCATIONS REPLACE EQIVALENT THERMOSTATS AT CURRENT LOCATIONS 7. INSTALL NEW HAIL GUARDS PROTECTING ALL CONDENSER COILS INSTALL NEW HAIL GUARDS PROTECTING ALL CONDENSER COILS 8. UNIT FILTRATION: MERV 8 UNIT FILTRATION: MERV 8 9. INSTALL PHASE MONITOR ON EACH 3Ø UNITINSTALL PHASE MONITOR ON EACH 3Ø UNIT

AutoCAD SHX Text

TOTAL CAPACITY

AutoCAD SHX Text

BTUH

AutoCAD SHX Text

HVAC WALL MOUNT UNITS

AutoCAD SHX Text 1, 2, 3, 4

AutoCAD SHX Text

PKG 5 TON WALL MOUNT

AutoCAD SHX Text EUBANK VERTICAL HEAT PUMP UNIT W/ELEC. 15 kw HEAT MODEL: EAA1042H-2060H OR EQUIVALENT

AutoCAD SHX Text 38.4

AutoCAD SHX Text

AutoCAD SHX Text 460/60/3

AutoCAD SHX Text

AutoCAD SHX Text 15.0

AutoCAD SHX Text 11.0

AutoCAD SHX Text 1,619

AutoCAD SHX Text 0.3

AutoCAD SHX Text 54,000

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 3.30

AutoCAD SHX Text 48,000

AutoCAD SHX Text

OAT

AutoCAD SHX Text

AutoCAD SHX Text °F

AutoCAD SHX Text

EAT

AutoCAD SHX Text °F

AutoCAD SHX Text

AutoCAD SHX Text T.C.

AutoCAD SHX Text 54.0

AutoCAD SHX Text S.C.

AutoCAD SHX Text 36.5

AutoCAD SHX Text kBTUH

AutoCAD SHX Text kBTUH

AutoCAD SHX Text

UNIT POSITION

AutoCAD SHX Text

SYSTEM TAG

AutoCAD SHX Text

MODEL NUMBER

AutoCAD SHX Text

FAN PERFORMANCE

AutoCAD SHX Text

AIRFLOW

AutoCAD SHX Text

COOLING COIL PERFORMANCE

AutoCAD SHX Text

GROSS CAPACITY

AutoCAD SHX Text

EFFICIENCY

AutoCAD SHX Text

EDB

AutoCAD SHX Text

EWB

AutoCAD SHX Text

LDB

AutoCAD SHX Text

BTUH

AutoCAD SHX Text °F

AutoCAD SHX Text °F

AutoCAD SHX Text

ESP

AutoCAD SHX Text

CFM

AutoCAD SHX Text in H OO

AutoCAD SHX Text

HEAT PUMP PERF.

AutoCAD SHX Text

EER@ AHRI

AutoCAD SHX Text

SEER@ AHRI

AutoCAD SHX Text

EER

AutoCAD SHX Text

ELECTRICAL DATA

AutoCAD SHX Text

MCA

AutoCAD SHX Text A

AutoCAD SHX Text

MOP

AutoCAD SHX Text A

AutoCAD SHX Text UNIT VOLTAGE V/Hz/Ph

AutoCAD SHX Text

WEIGHT NET

AutoCAD SHX Text

LBS

AutoCAD SHX Text

NOTES

AutoCAD SHX Text

TOTAL CAPACITY

AutoCAD SHX Text

BTUH

AutoCAD SHX Text

HVAC GROUND MOUNT UNITS

AutoCAD SHX Text 5, 6, 7, 8

AutoCAD SHX Text

PKG 5 TON HEAT PUMP

AutoCAD SHX Text YORK HORIZONTAL PACKAGE HEAT PUMP W/DUAL HEAT (PROPANE) MODEL: PHG6B60 SERIES OR EQUIVALENT

AutoCAD SHX Text 44.7

AutoCAD SHX Text 70.0

AutoCAD SHX Text 230/60/1

AutoCAD SHX Text

AutoCAD SHX Text 16.0

AutoCAD SHX Text 12.5

AutoCAD SHX Text 1,800

AutoCAD SHX Text 0.5

AutoCAD SHX Text 59,200

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 56,000

AutoCAD SHX Text

LWB

AutoCAD SHX Text °F

AutoCAD SHX Text

AutoCAD SHX Text

1. UNIT TO BE HIGH EFFICIENCY 2-STAGE COOLING W/ GAS PROPANE HEAT UNIT TO BE HIGH EFFICIENCY 2-STAGE COOLING W/ GAS PROPANE HEAT 2. UPSIZE UNIT MOTORS AS NEEDED TO PERFORM AT 5900 FEET ELEVATION UPSIZE UNIT MOTORS AS NEEDED TO PERFORM AT 5900 FEET ELEVATION 3. INSTALL NEW DISCONNECTS AT EACH UNIT LOCATION, INSTALL PER NEC.70 INSTALL NEW DISCONNECTS AT EACH UNIT LOCATION, INSTALL PER NEC.70 4. INSTALL PROPANE GAS CONVERSION KIT INSTALL PROPANE GAS CONVERSION KIT 5. INSTALL/REPLACE BAROMETRIC RELIEF HOOD AND CONTROLS INSTALL/REPLACE BAROMETRIC RELIEF HOOD AND CONTROLS 6. REPLACE EQUIVALENT WALL THERMOSTATS AT CURRENT LOCATIONS REPLACE EQUIVALENT WALL THERMOSTATS AT CURRENT LOCATIONS 7. INSTALL LOW AMBIENT KIT (S1-2LA04701024) INSTALL LOW AMBIENT KIT (S1-2LA04701024) 8. INSTALL NEW HAIL GUARDS PROTECTING ALL CONDENSER COILS INSTALL NEW HAIL GUARDS PROTECTING ALL CONDENSER COILS 9. UNIT FILTRATION: MERV 8UNIT FILTRATION: MERV 8

AutoCAD SHX Text °F

AutoCAD SHX Text

EAT

AutoCAD SHX Text °F

AutoCAD SHX Text

AutoCAD SHX Text 31,700

AutoCAD SHX Text

AutoCAD SHX Text

GAS PUMP PERF.

AutoCAD SHX Text

HEAT INPUT HIGH FIRE

AutoCAD SHX Text

BTUH

AutoCAD SHX Text 125,000

AutoCAD SHX Text

HEAT INPUT LOW FIRE

AutoCAD SHX Text 82,000

AutoCAD SHX Text

BTUH

AutoCAD SHX Text T.C.

AutoCAD SHX Text 54.7

AutoCAD SHX Text S.C.

AutoCAD SHX Text kBTUH

AutoCAD SHX Text 40.4

AutoCAD SHX Text kBTUH

AutoCAD SHX Text

GRILLE AND FILTER

AutoCAD SHX Text

DAMPER LOUVERS

AutoCAD SHX Text

FAN BLADE & MOTOR

AutoCAD SHX Text

DAMPER MOTOR

AutoCAD SHX Text

SHROUD

AutoCAD SHX Text

%%URELIEF AIR DAMPER DETAIL

AutoCAD SHX Text

MAINTAIN INTEGRATED CONTROL WITH HVAC UNITS

AutoCAD SHX Text

TO PNL 'C' CKT 9 OR 11 120V, 1Ø

DATE

APPROVED

RECOMMENDED

BRANCH CHIEF

SUBMITTED

PROJECT MANAGER

CHECKED

DRAWN BY

NO. DATE

DRAWING NUMBER

SCALE

SHEET OF

SHEET

DESCRIPTION

REVISIONS

APPROVEDBY

SHEET SIZE

NTS

WHITE SANDS MISSILE RANGE, NEW MEXICO

DIRECTORATE OF PUBLIC WORKS

ENGINEERING SERVICES DIVISION

DRAWING TITLE

WS-36003-2024-A-RP-05

B36003

ROOF REPAIR & LPS

04APRIL2024 ARCH D

JF

DG

JAMES NUNEZ

05 06

ROBERT LOPEZ

GENERAL NOTES-

ALSO REFER TO APPLICABLE NOTES ON PAGE 3 OF THIS DRAWING SET

ROOF REPLACEMENT

1. DRAWINGS ARE DIAGRAMMATIC ONLY BUT SHALL BE FOLLOWED AS CLOSELY AS ACTUAL CONSTRUCTION CONDITIONS

AND WORK OF OTHER TRADES PERMIT. DIMENSIONS IN THE DRAWING ARE FOR REFERENCE AND THE CONTRACTOR SHALL FIELD VERIFY ALL NECESSARY DIMENSIONS, EXISTING STRUCTURE AND EQUIPMENT REQUIRED TO PERFORM THE

SCOPE OF WORK.

2. ALL ROOF PANELS WILL BE REPLACED WITH STANDING SEAM (MTL) TYPE FROM MUELLER MANUFACTURER OR EQUIVALENT. PANELS WILL HAVE A CLASS-4 RATING AND BE 24 GAUGE COMMERCIAL GRADE STEEL. THE PANEL COLOR WILL BE BRIGHT WHITE. PANELS WILL BE INSTALLED PER MANUFACTURERS INSTRUCTIONS WITH APPROVED METHODS

AND FASTENERS.

3. EXISTING RAIN GUTTER DOWN SPOUTS WILL USED TO THE GREATEST EXTENT POSSIBLE. ALL DAMAGED OR BENT RAIN

GUTTER AND TRIM ROOF COMPONENTS WILL BE REPLACED.

4. ALL DAMAGED INSULATION PIECES WILL BE REPLACED. INSULATION R19 VALUE TO BE MAINTAINED.

5. THE NEW ROOF WILL HAVE A LOW PROFILE RIDGE VENT.

ROOF LPS SYSTEM REPLACEMENT

6. THE EXISTING ROOF LPS SYSTEM (CONDUCTOR, TERMINALS, TERMINAL BASE, CONNECTORS AND MISCELANEOUS LPS

SYSTEM COMPONETS) WILL BE REPLACED WITH SAME TYPE AND CONFIGURATION. THERMO-WELDS WILL BE DONE AT ALL

CONDUCTOR TEES AND SPLICES.

7. DOWN CONDUCTORS, CENTERPOISE AND GROUNDING RODS WILL NOT BE DISTURBED TO THE GREATEST EXTENT POSSIBLE. IF ANY COMPONENTS ARE FOUND DAMAGED THEY WILL BE REPLACED WITH NEW AND VERIFIED TO COMPLY

WITH SPECIFICATIONS.

8. THE FINISHED LPS SYSTEM WILL BE INSTALLED IN COMPLIANCE WITH NFPA 780 REQUIREMENTS AND TESTING WILL BE PERFORMED TO ENSURE REQUIRED RESISTANCE TO GROUND OF NO GREATER THAN 1.0 OHMS THROUGHOUT THE

SYSTEM.

AutoCAD SHX Text

%%UROOF PLAN

AutoCAD SHX Text

LPS COPPER CONDUCTOR

AutoCAD SHX Text

24" LPS TERMINAL WITH BASE TYPICAL, 25 LOCATIONS

AutoCAD SHX Text

%%UBLDG EXTERIOR FRONT VIEW

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

LOW PROFILE RIDGE VENT

AutoCAD SHX Text

24" LPS TERMINAL WITH BASE

AutoCAD SHX Text

%%UBLDG EXTERIOR SIDE VIEW

AutoCAD SHX Text

RAIN GUTTER

AutoCAD SHX Text

RAIN GUTTER DOWNSPOUT 4 PLACES, EACH SIDE

AutoCAD SHX Text

EXISTING GROUNDING RODS AND COUNTERPOISE CONDUCTOR

AutoCAD SHX Text

LPS DOWN CONDUCTOR 6 LOCATIONS

AutoCAD SHX Text 5 TON HEAT PUMP W/ 12kW ELECTRIC HEAT 460V, 3Ø WALL MOUNT TYPICAL 4 PLACES

AutoCAD SHX Text

5 TON HEAT PUMP W/ DUAL HEAT, PROPANE 230V, 1Ø GROUND MOUNT TYPICAL 4 PLACES

AutoCAD SHX Text RELIEF AIR ECONOMIZER W/ GRILLE, DAMPER, MOTOR & FILTERS SEE DETAIL TYPICAL 4 PLACES

A/C #1 A/C #2

A/C #3 A/C #4

EXH. DAMPERS (2)

EXH. DAMPERS (2)

HVAC UNIT

HVAC UNIT

HVAC UNIT

HVAC UNIT

HVAC UNIT

HVAC UNIT

HVAC UNIT

HVAC UNIT

HVAC UNIT

HVAC UNIT

HVAC UNIT

HVAC UNIT

DESIGNED

CHIEF, ENGINEERING DIVISION

DATE

APPROVED

RECOMMENDED

BRANCH CHIEF

SUBMITTED

PROJECT MANAGER

CHECKED

DRAWN BY

NO. DATE

DRAWING NUMBER

SCALE

SHEET OF

SHEET

DESCRIPTION

REVISIONS

APPROVEDBY

SHEET SIZE

NTS

WHITE SANDS MISSILE RANGE, NEW MEXICO

DIRECTORATE OF PUBLIC WORKS

ENGINEERING SERVICES DIVISION

DRAWING TITLE

WS-36003-2024-E-DT-06

B36003

ELECTRICAL SYSTEM

04APRIL2024 ARCH D

JF

DG

JAMES NUNEZ

06 06

ROBERT LOPEZ

GENERAL NOTES

ALSO REFER TO APPLICABLE NOTES ON PAGE 3 OF THIS DRAWING SET

1. PRIOR TO PERFORMING WORK ENSURE THAT ELECTRICAL ENERGY SOURCES TO EFFECTED SYSTEM HAS BEEN SECURED

AND LOCKED OUT/TAGGED OUT (LOTO).

2. ALL ELECTRICAL WORK SHALL BE DONE IN ACCORDANCE WITH NATIONAL ELECTRIC CODE (NEC) 70 AS REVISED.

3. 480V 3 PHASE POWER IS PROVIDED BY REMOTE GENERATOR. FOR EQUIPMENT OPERATION AND CHECKOUT CONTRACTOR SHALL PROVIDE A PROPERLY SIZED GENERATOR UNIT WITH FUEL AND NEEDED ELECTRICAL UNBIBLICAL TO THE SITE.

120/240V 1 PHASE POWER IS PROVIDED FROM EXISTING POWER LINES.

4. GOVERNMENT SURVEYED THE MDPS AND WAS ABLE TO IDENTIFY ONLY A FEW CIRCUITS DUE TO BAD LABELS OR NONE AT ALL. THEREFORE, CONTRACTOR WILL NEED TO FIELD VERIFY AND TRACE THE EXHAUST SYSTEM ELECTRICAL CIRCUITS

AND ASSOCIATED CIRCUIT BREAKERS.

5. CERTIFIED ELECTRICIAN SHALL INSPECT EXISTING WIRING TYPE AND SIZE AND CIRCUIT BREAKER RATING TO ENSURE THEY MEETS THE REQUIREMENTS FOR NEW EQUIPMENT AND CONTROLLERS PER NEC. FOR HIGHER RATED WIRING (IF NEEDED) THE ELECTRICIAN SHALL REMOVE EXISTING WIRING TO THE EXTENT NEEDED AND INSTALL REQUIRED 600 VOLT, THHN COPPER STRANDED ELECTRICAL CONDUCTOR. FOR HIGHER RATED CIRCUIT BREAKER, ELECTRICIAN SHALL ENSURE THAT THE NEW CIRCUIT BREAKER DOES NOT UNBALANCE THE PANEL. ALL ELECTRICAL POWER AND CONTROL WIRING SHALL BE ROUTED THROUGH EMT CONDUIT, USING PROPER CONNECTION METHODS, J-BOXES, NIPPLES, ETC.

6. DEMOLITION EXISTING CONTROLLERS AND DEDICATED DISCONNECTS TO HVAC EQUIPMENT BEING REPLACED. LABEL ALL CIRCUITS PRIOR TO TRANSFER TO NEW CONTROLLERS AND DISCONNECTS. USE EXISTING WIRE FEED FROM DISTRIBUTION PANELS AND CONDUIT FOR NEW CONTROLLERS IF IN GOOD CONDITION, REPLACE IF NEEDED. NEW CONTROLLERS WILL BE WALL MOUNTED AT OR NEAR THE EXISTING LOCATIONS. THE NEW CONTROLLERS SHALL BE BUILT AND SUPPLIED BY UL

RECOGNIZED A LISTED HVAC SYSTEM MANUFACTURER.

7. INSTALL NEW EMT CONDUIT TO MATCH EXISTING OR PER MANUFACTURER RECOMMENDATIONS FROM EXISTING CONDUIT UP TO NEW EQUIPMENT AND COMPONENTS AS NEEDED. USE PROPER CONNECTION METHODS SUCH AS J-BOX, NIPPLES, ETC. FOR CONTINUATION OF CONDUIT AND SEAL PROPERLY. THE USE OF FLEX CONDUIT IS ALLOWED ACCORDING PER

NEC.

8. EACH HVAC UNIT SHALL HAVE AN ELECTRICAL NEMA 3R DISCONNECT NEAR THE UNIT.

9. ALL GROUNDS FOR EQUIPMENT, BONDING AND NEUTRALS SHALL BE SIZED ACCORDING TO NEC ARTICLE 250.

10. THE CONTRACTOR SHALL VERIFY THAT THE HVAC SYSTEM CONTROLS AND INTERLOCKS ARE OPERATING CORRECTLY.

AutoCAD SHX Text

CIRC

AutoCAD SHX Text

TRIP

AutoCAD SHX Text

NO.

AutoCAD SHX Text

SERVICES

AutoCAD SHX Text A

AutoCAD SHX Text

SERVICES

AutoCAD SHX Text

TRIP

AutoCAD SHX Text

NO.

AutoCAD SHX Text

PANEL: '1 PHASE 120/240V'

AutoCAD SHX Text

CIRC

AutoCAD SHX Text

CIRCUIT BREAKER INTERRUPT RATING: 200A

AutoCAD SHX Text

PHASES: 1

AutoCAD SHX Text

VOLTAGE: 120/240V

AutoCAD SHX Text B

AutoCAD SHX Text

NO.

AutoCAD SHX Text

AMPS

AutoCAD SHX Text

POLES

AutoCAD SHX Text

AMPS

AutoCAD SHX Text

POLES

AutoCAD SHX Text

NO.

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPARE

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

LOT VAN

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

COMPRESSOR

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

BATHROOM

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

CIRC

AutoCAD SHX Text

TRIP

AutoCAD SHX Text

NO.

AutoCAD SHX Text

SERVICES

AutoCAD SHX Text A

AutoCAD SHX Text

SERVICES

AutoCAD SHX Text

TRIP

AutoCAD SHX Text

NO.

AutoCAD SHX Text

PANEL: 'C'

AutoCAD SHX Text

CIRC

AutoCAD SHX Text

MAIN BREAKER: 60A 3-POLE

AutoCAD SHX Text

PHASES: 3, 4 WIRE

AutoCAD SHX Text

VOLTAGE: 208Y/120V

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text

NO.

AutoCAD SHX Text

AMPS

AutoCAD SHX Text

POLES

AutoCAD SHX Text

AMPS

AutoCAD SHX Text

POLES

AutoCAD SHX Text

NO.

AutoCAD SHX Text

PLUGS (7)

AutoCAD SHX Text X

AutoCAD SHX Text

PLUGS (8)

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

PLUGS (7)

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

PLUGS (6)

AutoCAD SHX Text

EMERGENCY INVERTER

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

DATA LOGGER

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

PLUGS (7)

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPARE

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

SPARE

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

FLUOR. LIGHTS

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

PLUGS (7)

AutoCAD SHX Text

WARNING LIGHTS

AutoCAD SHX Text

LIGHTING CONTROLS

AutoCAD SHX Text

BAY DOORS WEST

AutoCAD SHX Text

BAY DOORS EAST

AutoCAD SHX Text

FLUOR LIGHTS

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

FLUOR. LIGHTS

AutoCAD SHX Text X

AutoCAD SHX Text

FLUOR LIGHTS

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

FLUOR LIGHTS

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPARE

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

FLUOR LIGHTS

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

CIRC

AutoCAD SHX Text

TRIP

AutoCAD SHX Text

NO.

AutoCAD SHX Text

SERVICES

AutoCAD SHX Text A

AutoCAD SHX Text

SERVICES

AutoCAD SHX Text

TRIP

AutoCAD SHX Text

NO.

AutoCAD SHX Text

PANEL: 'A'

AutoCAD SHX Text

CIRC

AutoCAD SHX Text

225A MAIN LUGS ONLY

AutoCAD SHX Text

PHASES: 3, 4 WIRE

AutoCAD SHX Text

VOLTAGE: 480Y/277

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text

NO.

AutoCAD SHX Text

AMPS

AutoCAD SHX Text

POLES

AutoCAD SHX Text

AMPS

AutoCAD SHX Text

POLES

AutoCAD SHX Text

NO.

AutoCAD SHX Text

SPARE

AutoCAD SHX Text X

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPARE

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

SPARE

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPARE

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPARE

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPARE

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPARE

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

EXT. XFORMER 480-208

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

EXT. XFORMER 480-208

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

BRIDGE CRANE

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

TRANSFORMER (NOT USED)

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

EXT. XFORMER 480-208

AutoCAD SHX Text

BRIDGE CRANE

AutoCAD SHX Text

BRIDGE CRANE

AutoCAD SHX Text

TRANSFORMER (NOT USED)

AutoCAD SHX Text

TRANSFORMER (NOT USED)

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text X

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

T/E POWER RECEPTACLE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

T/E POWER RECEPTACLE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

T/E POWER RECEPTACLE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text KEYED NOTES 1. MOTOR GENERATOR SET MOTOR GENERATOR SET 2. GENERATOR SET UMBILICAL CABLE CONNECTION GENERATOR SET UMBILICAL CABLE CONNECTION 3. ELECTRICAL SERVICE DISCONNECT (480V). 400A 600 VOLTS 3 POLE 4 WIRE ELECTRICAL SERVICE DISCONNECT (480V). 400A 600 VOLTS 3 POLE 4 WIRE FUSIBLE TYPE WITH ONE SET OF NO/NC INTERLOCK CONTACTS. NEMA3R ENCLOSURE. CLASS R REJECTION FUSECLIPS. 225 AMP CLASS RK1 FUSES. 4. SOLID NEUTRAL CONNECTION. BOND TO SWITCH ENCLOSURE SOLID NEUTRAL CONNECTION. BOND TO SWITCH ENCLOSURE 5. GROUNDED ELECTRODE SYSTEM. #2 AWG IN INCH CONDUIT. EXTEND TO GROUNDED ELECTRODE SYSTEM. #2 AWG IN INCH CONDUIT. EXTEND TO 34 INCH CONDUIT. EXTEND TO GROUNDING CENTERPOISE. BOND CONDUIT TO DONDUCTOR AT BOTH ENDS. 6. 2 INCH COINDUIT. WIRE WITH AND 1 #4 (GROUND) 2 INCH COINDUIT. WIRE WITH AND 1 #4 (GROUND) 12 INCH COINDUIT. WIRE WITH AND 1 #4 (GROUND) 40 AND 1 #4 (GROUND) 7. 30A 3-POLE CIRCUIT BREAKER 30A 3-POLE CIRCUIT BREAKER 8. DRY-TYPE TRANSFORMER - WITH ELECTROSTATIC SHIELD. 480V THREE DRY-TYPE TRANSFORMER - WITH ELECTROSTATIC SHIELD. 480V THREE PHASE DELTA PRIMARY, 208Y/120 VOLTS THREE PHASE FOUR WIRE SECONDARY. 15 KVA RATING 9. INCH CONDUIT. WIRE WITH 3 #10 AND 1 #10 (GROUND) THHN COPPER. 34 INCH CONDUIT. WIRE WITH 3 #10 AND 1 #10 (GROUND) THHN COPPER. 10. 1 INCH CONDUIT. WIRE WITH 4 #6 AND 1 #10 (GROUND) THHN COPPER. 1 INCH CONDUIT. WIRE WITH 4 #6 AND 1 #10 (GROUND) THHN COPPER. 11. GROUNDING ELECTRODE SYSTEM. #8 AWG IN INCH CONDUIT. EXTEND TO GROUNDING ELECTRODE SYSTEM. #8 AWG IN INCH CONDUIT. EXTEND TO 34 INCH CONDUIT. EXTEND TO AND CONNECT WITH EXOTHERMIC WELD TO NEAREST GROUNDED BUILDING COLUMN. BOND CONDUIT TO CONDUCTOR AT BOTH ENDS.

AutoCAD SHX Text

GENERATOR POWER ONE LINE DIAGRAM DIAGRAMATIC ONLY

AutoCAD SHX Text 225A

AutoCAD SHX Text 400A

AutoCAD SHX Text

PANEL 'A'

AutoCAD SHX Text

PANEL 'C'

AutoCAD SHX Text 60A

AutoCAD SHX Text G

Sheets and Views
LC94 HVAC ROOF AND HVAC REPAIR BID SET PLANS 8APRIL2024-COVER
LC94 HVAC ROOF AND HVAC REPAIR BID SET PLANS 8APRIL2024-LOCATION
LC94 HVAC ROOF AND HVAC REPAIR BID SET PLANS 8APRIL2024-NOTES
LC94 HVAC ROOF AND HVAC REPAIR BID SET PLANS 8APRIL2024-HVAC
LC94 HVAC ROOF AND HVAC REPAIR BID SET PLANS 8APRIL2024-ROOF LPS
LC94 HVAC ROOF AND HVAC REPAIR BID SET PLANS 8APRIL2024-ELEC