This document is a Lead-Based Paint (LBP) Testing Data Sheet for a roof replacement project at Building 122, the Office of the Staff Judge Advocate facility. The testing was conducted on 4/9/2025 using a Viken/Pb200e XRF instrument with serial number 2759, performed by inspectors Frank Lujan and Paul Rodriguez. The data sheet reveals multiple wood fascia and soffit testing locations, with three soffit areas (east, north, and west ends) testing positive for lead-based paint, showing XRF readings between 5.9 and 6.4 mg/cm². The testing conforms to the Texas Department of State Health Services lead measurement standard of 1.0 mg/cm², and the components were assessed in conditions ranging from fair to intact. This testing data will likely be crucial for the upcoming roof replacement solicitation (W911SG25BA017) to ensure proper lead-based paint handling and removal protocols during the construction process.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LBP TESTING DATA SHEET
Facility Information: Roof Replacement-Soffit & Fascia LBP testing
Facility Name: Office of the Staff Judge Advocate
Building Number: 122
XRF Model and M/N:
Viken/Pb200e Date of Assessment: 4/9/2025
XRF Instrument S/N: 2759 Inspector Name(s): Frank Lujan/Paul Rodriguez
Data Sheet
SA
M
P
LE
I D
SU
B
ST
R
A
TE
C O
M P
N
EN
T
C O
LO
R
O F
C O
M P
O N
EN
T
TE
ST
L O
C A
TI
N
D
ES
C R
IP
TI
X R
F R
EA
D
IN
G
(m g/ cm
²)
LA
SS
IF
IC
A
TI
N D
IT
IO
N/A N/A N/A Green Calibration (< 0.00) .1 ACCEPTABLE N/A
N/A N/A N/A Green Calibration (0.8 to 1.2) 1.0 ACCEPTABLE N/A
LBP-01 Wood Fascia Green East end 0 NEGATIVE FAIR
LBP-02 Wood Soffit Green East end 6.0 POSITIVE INTACT
LBP-03 Wood Fascia Green North end 0 NEGATIVE INTACT
LBP-04 Wood Soffit Green North end 6.4 POSITIVE FAIR
LBP-05 Wood Fascia Green West end 0 NEGATIVE FAIR
LBP-06 Wood Soffit Green West end 5.9 POSITIVE FAIR
NOTES:
DPW-ED conforms to Texas Department of State Health Services lead measurement standard, 1.0mg/cm2 by X-ray fluorescence.