Kissimmee_City_Hall_Mechanical_and_Electrical_Drawings.pdf

PDF 10 MB Posted

Attached to
Modernization of City Hall Elevators
Solicitation number
RFP2025-005
Issued by
Polk County, Florida

About this file

The file contains mechanical and electrical engineering drawings for the Kissimmee City Hall Elevator Replacements project located at 101 N Church Street in Kissimmee, Florida. The drawings, prepared by SGM Engineering, Inc., detail comprehensive mechanical and electrical specifications for replacing existing elevator equipment, including removing old elevator components and associated equipment, installing a new sump pump in the elevator pit, and providing a new DX split system to condition the elevator machine room. The project scope involves electrical infrastructure updates, fire alarm system modifications, and electrical system reconfigurations to support the elevator modernization.

The engineering drawings specify technical requirements for electrical and mechanical systems, including panel schedules, one-line electrical diagrams, conduit and penetration details, and specific installation guidelines. The project involves replacing elevator equipment for two hydraulic passenger elevators, with work encompassing electrical reconnections, control module updates, fire alarm device replacements, and ensuring compliance with safety codes including Chapter 399 of Florida Statutes and ASME A17.3-2015 standards. The drawings provide intricate details on power distribution, fire alarm device placement, conduit routing, and system integration, indicating a comprehensive approach to modernizing the city hall's vertical transportation infrastructure.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

KISSIMMEE CITY HALL ELEVATOR REPLACEMENT

KISSIMMEE CITY HALL

KISSIMMEE, FLORIDA 34741

KISSIMMEE, FLORIDA, 34741

MECHANICAL -

ELECTRICAL -

101 N CHURCH STREET

MECHANICAL

M-001 MECHANICAL SYMBOLS AND SPECIFICATIONS

MD-201 MECHANICAL FIRST LEVEL DEMO FLOOR PLAN

M-201 MECHANICAL FIRST LEVEL FLOOR PLAN

M-701 MECHANICAL CONTROLS, SCHEDULES, AND DETAILS

ELECTRICAL

E-001 ELECTRICAL SYMBOLS AND SPECIFICATIONS

ED-201 ELECTRICAL FIRST LEVEL DEMO PARTIAL FLOOR PLANS

E-201 ELECTRICAL FIRST LEVEL PARTIAL FLOOR PLANS

E-501 ELECTRICAL PARTIAL ONE-LINE DIAGRAM

E-701 PANEL SCHEDULES

E-801 ELECTRICAL DETAILS

E-802 ELECTRICAL DETAILS

PROJECT MANAGER

Michael Holness Facilities Construction & Maintenance Manager

City of Kissimmee 104 N Alaska Ave Kissimmee, Florida 34741

407.518.2509 Office

689.287.8865 Work Cell

SGM ENGINEERING, INC.

SGM ENGINEERING, INC.

COVER

T-001 TITLE SHEET

CONSULTANTS

INDEX OF DRAWINGSPROJECT LOCATION

GENERAL SCOPE OF WORK

THE OBJECTIVES OF THIS PROJECT AS IDENTIFIED ON THE DRAWINGS, INCLUDES:

1. REMOVE OLD ELEVATOR AND ASSOCIATED EQUIPMENT AND REPLACE WITH NEW EQUIPMENT.

2. INSTALL NEW SUMP PUMP IN ELEVATOR PIT.

3. PROVIDE NEW DX SPLIT SYSTEM TO CONDITIONING ELEVATOR MACHINE ROOM.

THIS BRIEF DESCRIPTION OF THE SCOPE OF WORK IS NOT ALL INCLUSIVE AND IS COMPLIMENTED BY THE SET OF CONSTRUCTION DOCUMENTS AND SPECIFICATIONS

KISSIMMEE CITY HALL

ELEVATOR

REPLACEMENTS

N

C H

U R

C H

S T

R E

E T

K

IS

S

IM

M E

E

F L O

R

ID

A

5301 WATERFORD DISTRICT DR.

SUITE 750

MIAMI, FL 33126

TEL: 954-421-1944

FAX: 954-421-1924

CA-00006208

WWW.SGMENGINEERING.COM

COPYRIGHT © 2024 SGM ENGINEERING, INC.

ELEVATOR

REPLACEMENTS

N

C H

U R

C H

S T

R E

E T

K

IS

S

IM

M E

E

F L O

R

ID

A

5301 WATERFORD DISTRICT DR.

SUITE 750

MIAMI, FL 33126

TEL: 954-421-1944

FAX: 954-421-1924

CA-00006208

WWW.SGMENGINEERING.COM

COPYRIGHT © 2024 SGM ENGINEERING, INC.

MECHANICAL ABBREVIATIONS

DUCTWORK

MECHANICAL SYMBOLS LEGEND

MECHANICAL LEGEND

MECHANICAL GENERAL NOTES

MECHANICAL SCOPE OF WORK:

WN

WN

TV STUDIO

MEDIA COORDINATOR

MASTER CONTROL

MAIL

OFFICE

ELEVATOR

EQUIP.ROOM

FIRE PUMP

OFFICE

OPEN OFFICE

TOHOPOKELIGA

CONFERENCE ROOM

MEN

WOMEN

VIDEO EDIT

JANITOR

PERMITTING

CODE ENFORCEMENT

WORK

OFFICE

OFFICE

OFFICE

OFFICE

MECHANICAL

COMMUNICATION

ELECTRICAL

CONFERENCE

OFFICE

OFFICE

OFFICE

OFFICE

LOBBY

114' - 11 1/4"

17' - 1 1/2"

67' - 11 1/4"

200' - 0"

4' - 0 1/8" 11' - 8" 4' - 0 1/4" 11' - 7 7/8" 4' - 0 1/4" 11' - 7 3/4" 3' - 10 3/8" 11' - 9 1/2" 4' - 0 1/4" 7' - 10 5/8"

4'

1/

2"

/2

106' - 0 3/4"

8"4' - 0"8" 10' - 4" 8"4' - 0"8" 10' - 4" 8"4' - 0"8" 10' - 4" 8"4' - 0"8" 10' - 4" 8"4' - 0"8" 10' - 4" 8"

113' - 8"

8" 10' - 4" 8"4' - 0"8" 10' - 4" 8"4' - 0"8" 10' - 4" 8"4' - 0"8" 10' - 4" 8" 8' - 0"

66' - 8"

4' - 5 3/4"4' - 0" 11' - 7 7/8" 4' - 0 1/4" 11' - 7 7/8" 8' - 0" 4' - 8" 7' - 2"

55' - 7 3/4"

/4

/2

7/

8"UP

ADMIN

WORK ROOM

CHILLER

YARD

T

D X-

1-

C U

-1 -1

FD(E)

FD(E)

NEW FUNNEL

FLOOR DRAIN

SP-1

GENERAL NOTES:

a. REFER TO SHEET M001 FOR

MECHANICAL SYMBOLS &

LEGEND AND GENERAL NOTES.

b. REFER TO PROJECT

SPECIFICATIONS FOR

EQUIPMENT AND INSTALLATION

REQUIREMENTS. IF THERE IS ANY

DISCREPANCY BETWEEN

SPECIFICATIONS AND DRAWINGS,

THE MOST STRINGENT

REQUIREMENT SHALL APPLY.

c. COORDINATE WORK SCHEDULE

WITH FIU PROJECT MANAGER.

DISRUPTION OF COOLING TO THE

ADJACENT SPACES IS NOT

ALLOWED.

d. DRAWINGS ARE DIAGRAMMATIC

AND REPRESENT THE GENERAL

LAYOUT OF MECHANICAL

COMPONENTS, FOR EXACT

BUILDING DIMENSIONS SEE

ARCHITECTURAL AND

STRUCTURAL DRAWINGS.

e. LOCATE EQUIPMENT SO THAT

MANUFACTURER SERVICE

CLEARANCES ARE MAINTAINED.

f. COORDINATE WITH ELECTRICAL

CONTRACTOR LOCATION OF

DISCONNECTS. DO NOT BLOCK

SERVICE CLEARANCE TO

EQUIPMENT.

g. PROVIDE NEW THERMOSTATS

AND TEMPERATURE SENSOR AS

SHOWN IN DRAWINGS

PLAN KEY NOTES:

1. PROVIDE NEW WALL MOUNTED DX-1-1,. REFER TO MECHANICAL SCHEDULE AND DETAILS

FOR FURTHER REFERENCES.

2. PROVIDE NEW INSULATED 34"Ø COPPER TYPE L CONDENSATE LINE. RUN UP TO THE

NEAREST EXISTING FLOOR DRAIN . REFER TO MECHANICAL DETAILS FOR FURTHER

REFERENCES. FIELD VERIFY LOCATION OF EXISTING FLOOR DRAIN. RUN CONDENSATE

LINE ABOVE CEILING UP TO EXISTING FLOOR DRAIN. CONFIRM CONDENSATE PIPE

MOUNTING HEIGHT ABOVE CEILING ALLOWS FOR NO LESS THAN 18 INCH PER FOOT SLOPE.

3. PROVIDE NEW REFRIGERANT LINES. RUN THOUGH THE WALL FROM THE DX UNIT TO

OUTDOOR CONDENSING UNIT. CONDENSING UNIT SHALL BE LOCATED IN THE THE CHILLER

YARD. FOLLOW THE MANUFACTURER'S RECOMMENDATIONS IN LONG LINE APPLICATION

GUIDELINE. IF THE MANUFACTURER MAKES NO RECOMMENDATIONS FOR LONG

REFRIGERANT LINE RUN, CHOOSE ANOTHER CU MANUFACTURER. EXPOSED

REFRIGERANT LINES SHALL BE PAINTED WITH UV PROTECTION COATING.

4. PROVIDE NEW THERMOSTATS AND ASSOCIATED COMPONENTS.

5. PROVIDE NEW 12" THICK CONCRETE PAD. EXTEND PAD A MINIMUM OF 6" BEYOND THE

EQUIPMENT. REFER TO SHEET M801 FOR PAD DETAILS.

6. PROVIDE NEW FUNNEL DRAIN FOR SUMP PUMPS DISCHARGE. SAW CUT FLOOR SLAB TO

INSTALL NEW FLOOR DRAIN AND NEW UNDERGROUND SANITARY PIPING.

7. ROUTE 2" SUMP PUMP DISCHARGE ABOVE CEILING TO NEW FUNNEL DRAIN IN MECHANICAL

ROOM

8. PROVIDE NEW TRACTION SUMP PUMP IN ELEVATOR SUMP PIT. PROVIDE NEW DISCHARGE

PIPING, LIBERTY OILTECTOR ALARM SYSTEM, GATE VALVE, CHECK VALVE AND ALL OTHER

ASSOCIATED COMPONENTS. SEE SHEET M-702 FOR MORE INFORMATION.

9. CONDENSING UNIT REFRIGERANT LINES SHALL RUN UNDERGROUND AFTER EXITING THE

BUILDING. RUN LINES UNDER SIDEWALK AND THROUGH THE CMU WALL INTO THE CHILLER

PLANT.

KISSIMMEE CITY HALL

ELEVATOR

REPLACEMENTS

N

C H

U R

C H

S T

R E

E T

K

IS

S

IM

M E

E F L O

R

ID

A

5301 WATERFORD DISTRICT DR.

SUITE 750

MIAMI, FL 33126

TEL: 954-421-1944

FAX: 954-421-1924

CA-00006208

WWW.SGMENGINEERING.COM

COPYRIGHT © 2024 SGM ENGINEERING, INC.

MECHANICAL PARTIAL FIRST LEVEL FLOOR PLAN

WN

REPLACEMENTS

N

C H

U R

C H

S T

R E

E T

K

IS

S

IM

M E

E

F L O

R

ID

A

5301 WATERFORD DISTRICT DR.

SUITE 750

MIAMI, FL 33126

TEL: 954-421-1944

FAX: 954-421-1924

CA-00006208

WWW.SGMENGINEERING.COM

COPYRIGHT © 2024 SGM ENGINEERING, INC.

WALL MTD MINI DUCTLESS INDOOR UNIT DETAIL

NOT TO SCALE

1 Not Scale

FLOOR RECEPTOR DETAIL2

FULL SIZE CLEAN OUT

DRAIN LINE SHALL BE AT LEAST THE

SAME SIZE AS THE NIPPLE ON EQUIPMENT

EQUIPMENT

UNION

PITCHED DOWN

TOWARD DRAIN

NOT TO SCALE

ROUTE AS SHOWN ON

PLANS OR NOTES

DRAW-THRU CONDENSATE DRAIN TRAP DETAIL

H

H = TOTAL STATIC PRESSURE +1", 2" MIN.

H/2

WITH THREADED PLUG

(HAND-TIGHTEN)

1/4" HOLE IN CAP

CONTROLS SPLIT SYSTEM (DX-1-1)1

NTS

MECHANICAL SCHEDULES2

C. UNIT MODES OF OPERATION:

1. PROVIDE FOR UNIT, THREE PRINCIPAL OPERATIONAL MODES:

OCCUPIED MODE, UNOCCUPIED MODE. AHU FIRE ALARM SHUTDOWN

MODE. ALL MODES SHALL EACH BE COMMANDED BY THE DDC.

2. OCCUPIED MODE: WHEN SCHEDULED BY THE DDC, THE SYSTEM

“OCCUPIED MODE” SHALL BE ENABLED; THE SUPPLY FAN SHALL BE

ACTIVATED AND TEMPERATURE CONTROL ALGORITHMS ENABLED.

3. UNOCCUPIED MODE: WHEN SCHEDULED OR SIGNALED BY THE DDC,

OR MANUALLY COMMANDED AT THE OPERATOR WORKSTATION,

SYSTEM OPERATION SHALL BE DISABLED. THE FAN SHALL STOP

AND CONTROL ALGORITHMS DEACTIVATED.

4. UPON RECEIVING SIGNAL FROM FIRE ALARM UNIT IS TO SHUT DOWN

AND BE MANUALLY RESTARTED.

2.3 Suggested Locations for Best Reliability

Ensure the top discharge area is unrestricted for at least five (5) feet above the unit.

Three (3) feet clearance must be provided in front of the control box (access panels) and any other side requiring service.

Min. 12” to Shrubbery

Min 5’ Unrestricted

Min 3’ Unrestricted

Access Panel

Position the outdoor unit a minimum of 3'-0” from any wall or surrounding shrubbery to ensure adequate airflow.

Outdoor unit location must be far enough away from any structure to prevent excess roof runoff water from pouring directly on the unit.

Min. 12” to Shrubbery

Min. 3'-0” to Wall

CONDENSING UNIT CLEARANCE DETAIL

NOT TO SCALE

For continuation see detail 6 and sheet M201

TYPICAL CONDENSING UNIT PAD

DETAIL

6"THICK CONCRETE PAD

(2" ABOVE GROUND

4" BELOW GROUND)

3/8" ISOLATION

2-INCH CHAMFERED LIP

AROUND EDGES

JOINT (TYP.)

#4 @ 12" O.C. EA. WAY

AT CENTER(TYP.)

6" EQUIPMENT LIMIT

NOTE:

1. PAD TO BE SIZED TO ACCOMMODATE POWER, REFRIGERANT

LINES, CONTROLS AND RECEPTACLES.

2. PROVIDE SHOP DRAWING FOR EQUIPMENT LAYOUT

INCLUDING REFRIGERANT LINES, POWER, AND CONTROLS.

3. ADD HURRICANE STRAPS.

TO SUIT EQUIP. FURN.

CONDENSING UNIT PAD DETAIL

6" TYP

TO SUIT EQUIP FURN.

3000 PSI CONCRETE WITH NO GREATER

NOT TO SCALE

MINIMUM 6"

THICK REINF.

CONCRETE PAD

SEE PLAN

FOR UNIT

LOCATION

4" SCH. 40 PVC CHASE,

INSTALL WITH LONG

RADIUS ELLS. SEAL

OPENING WITH WATER

PROOF EXPANDING

FOAM. ALSO,

REFRIGERANT PIPING

TO AIR HANDLING

UNIT

THAN 2-INCH LIP CHAMFERED EDGE AROUND

EQUIPMENT

HVAC CONDENSING UNIT

PROVIDE ALUMINUM

JACKET TO ALL EXPOSED

REFRIGERANT PIPING

NOTE:

1. SUBMIT SHOP DRAWING FOR PAD FOR APPROVAL PRIOR TO

CONSTRUCTION.

TYPICAL CONDENSING UNIT

ANCHORING DETAIL

NOTE:

1. ALL SUPPORTS, BRACKET AND FASTENERS SHALL BE

STAINLESS STEEL ON THE CU PAD.

WN

REPLACEMENTS

N

C H

U R

C H

S T

R E

E T

K

IS

S

IM

M E

E

F L O

R

ID

A

5301 WATERFORD DISTRICT DR.

SUITE 750

MIAMI, FL 33126

TEL: 954-421-1944

FAX: 954-421-1924

CA-00006208

WWW.SGMENGINEERING.COM

COPYRIGHT © 2024 SGM ENGINEERING, INC.

MANUFACTURER

SUMP PUMP SCHEDULE

GPMMARK MOTORHEAD

LIBERTY PUMPS #LEH102M2-3100SP-1 1 HP40 208V / 1PH

DISCHARGE

UNION

CHECK VALVE

GATE VALVE

WALL

CONDUIT

PUMP STOP LEVEL

PUMP START LEVEL

FLOAT

SWITCH

(TYPICAL)

ELEVATOR SUMP.

REFER TO

STRUCTURAL

DRAWINGS.

ALARM LEVEL

MOUNTING

BRACKET

ELEVATOR SHAFT

ELEVATOR

EQUIPMENT ROOM

SUBMERSIBLE SUMP

PUMP WITH

HYDROCARBON SENSOR

SUMP PUMP

CONTROL

PANEL

ELEVATOR PIT SLAB

2" FORCE MAIN

NOTE:

ROOMS MAY NOT BE

ADJACENT. PROVIDE

ADEQUATE LENGTH

CONDUIT AND WIRE

GRATE

SLAB

NOT TO SCALE

ELEVATOR SUMP PUMP DETAIL

WN

TV

TV

POWER DEVICES

SINGLE RECEPTACLE

JUNCTION BOX

DUPLEX RECEPTACLE

DISCONNECT SWITCH

DOOR BELL PUSH BUTTON

EQUIPMENT CONNECTION

SPECIAL PURPOSE RECEPTACLE

DOUBLE DUPLEX RECEPTACLE

MOTOR STARTER

SHUNT TRIP. MTD. AT 6'-5" AFF/AFG TO TOP OF ENCLOSURE

DOOR BELL

TRANSFORMER

DUPLEX RECEPTACLE, GROUND FAULT, ABOVE COUNTER

DUPLEX RECEPTACLE, GROUND FAULT

SINGLE 250V NON-LOCKING TYPE RECEPTACLE

ABOVE COUNTER DUPLEX RECEPTACLE

DUPLEX RECEPTACLE, HALF SWITCHED

MOTOR

120/208V PANELBOARD, SURFACE MOUNT

277/480V PANELBOARD, SURFACE MOUNT

POWER/DATA POLE

PULL BOX

CEILING MOUNTED RECEPTACLE

RECESSED FLOOR RECEPTACLE

FLOOR MOUNTED JUNCTION BOX

120/208V PANELBOARD, RECESSED

277/480V PANELBOARD, RECESSED

FEEDER OR BRANCH CIRCUIT CONCEALED IN WALL,

CEILING OR FLOOR

STARTER/DISCONNECT SWITCH

GENERATOR

CLOCK

LOCKBOX

DUPLEX RECEPTACLE, GROUND FAULT

WITH CAST ALUMINUM PADLOCKABLE (1

4" HASP)

WEATHERPROOF "IN USE" COVER. TAYMAC MX3200 OR

EQUAL

DUPLEX RECEPTACLE, GROUND FAULT

LOCATE WITHIN ELECTRIC WATER COOLER PER

MANUFACTURER'S INSTRUCTIONS

DUPLEX RECEPTACLE FOR COMPUTER WORKSTATION

DUPLEX RECEPTACLE FOR TV LOCATED AT 18"AFF. LOCATE IN

COMMON BOX WITH CCTV

DUPLEX RECEPTACLE FOR TV LOCATED AT 84" AFF

UNLESS NOTED OTHERWISE.

GROUND BUS BAR

GROUND ROD WITH TEST INSPECTION WELL. SEE

SPECIFICATIONS.

QUAD RECEPTACLE, GROUND FAULT

WITH CAST ALUMINUM PADLOCKABLE (1

4" HASP) WEATHER-

PROOF "IN USE" COVER. TAYMAC MX 6200 OR EQUAL.

POWER DISTRIBUTION

MISCELLANEOUS SYMBOL LEGEND

ABBREVIATIONS

AMPERES

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

BELOW FINISHED GRADE

ELECTRIC UNIT HEATER

ELECTRIC WATER COOLER

ELECTRIC WATER HEATER

ELECTRICAL METALLIC TUBING

BELOW FINISHED CEILING

EWH

FLUOR

FA

EXIST

EXH

EQUIP

EWC

EUH

EMT

EF

FLUORESCENT

FIRE ALARM

EXHAUST

EXISTING

EXHAUST FAN

EQUIPMENT

CLG

DISC

DWG

EA

CU

CL

CAB

CKT

BFG

CEILING

CENTERLINE

DISCONNECT(ING)

DRAWING(S)

EACH

COPPER

CABINET

CIRCUIT

CONDUIT

AFG

BFC

A

AFF

NATIONAL ELECTRICAL CODE

POLYVINYL CHLORIDE

UNLESS OTHERWISE NOTED

XFMR

V

WP

VA

TEL

UON

TRANSFORMER

TELEPHONE

VOLT-AMPERES

WEATHER PROOF

VOLTS

PVC

PNL

REC

NEC

MTR

MTG

MTD

MISC

MIN

RECEPTACLE

PANEL

MINIMUM

MISCELLANEOUS

MOUNTED

MOUNTING

MOTOR

HEATING/VENTILATING/

KILO-VOLTS-AMPERES

KILO-WATT-HOURS

MOTOR CONTROL CENTERMCC

MH

MFR

MAX

LTG

kVA kWH kW kV

JB

METAL HALIDE

LIGHTING

MANUFACTURER

MAXIMUM

JUNCTION BOX

KILO-VOLTS

KILO-WATTS

HVAC

HV

INC

HP HORSEPOWER

HIGH VOLTAGE

INCANDESCENT

FLA FULL LOAD AMPERES

ABOVE FINISHED CEILINGAFC

W WATTS

TYP TYPICAL

GFCI GROUND FAULT CIRCUIT

INTERRUPTER

CURRENT TRANSFORMERSCT's

KILO-VOLTS-AMPERES REACTIVEkVAR

RGS RIGID GALVANIZED STEEL

C m METER mm MILLIMETER

AIC AMPERES INTERUPTING

CAPACITY

MCB MAIN CIRCUIT BREAKER

MCP MOTOR CIRCUIT PROTECTOR

AIR CONDITIONING

HAND-OFF-AUTOMATIC

HIGH INTENSITY DISCHARGE

HIGH PRESSURE SODIUM

HID

HOA

HPS

GND

HGT

GROUND

HEIGHT

GFP GROUND FAULT PROTECTION

VFD VARIABLE FREQUENCY DRIVE

AMERICAN WIRE GAUGEAWG

PULL STATION INSIDEPSI

EXP EXPLOSION PROOFAUDIO ENHANCEMENTAE

1R1-1,3,5

1M1-1:3:5

1R1-1

1M1-1:3

1R1-1,3

HOMERUN CONSISTING OF ONE SINGLE-PHASE, 1-POLE

CIRCUIT, SEE SPECIFICATIONS AND/OR FEEDER

SCHEDULES FOR WIRE SIZES. PANELBOARD AND CIRCUIT

DESIGNATION ARE INDICATED.

HOMERUN CONSISTING OF THREE SINGLE-PHASE CIRCUITS:

SEE SPECIFICATIONS AND/OR FEEDER SCHEDULES FOR

WIRE SIZES. PANELBOARD AND CIRCUIT DESIGNATIONS

ARE INDICATED.

HOMERUN CONSISTING OF ONE THREE-PHASE CIRCUITS:

SEE SPECIFICATIONS AND/OR FEEDER SCHEDULES FOR

WIRE SIZES. PANELBOARD AND CIRCUIT DESIGNATIONS

ARE INDICATED.

HOMERUN CONSISTING OF ONE SINGLE-PHASE, 2-P0LE

CIRCUIT: SEE SPECIFICATIONS AND/OR FEEDER

SCHEDULES FOR WIRE SIZES. PANELBOARD AND

CIRCUIT DESIGNATIONS ARE INDICATED.

HOMERUN CONSISTING OF TWO SINGLE-PHASE CIRCUITS:

SEE SPECIFICATIONS AND/OR FEEDER SCHEDULES FOR

WIRE SIZES. PANELBOARD AND CIRCUIT DESIGNATION ARE

INDICATED.

SCALE: DETAIL TITLE REFERENCE

DETAIL NUMBER

SHEET NUMBER WHERE DETAIL IS REFERENCED

ADDITIONAL SHEET REFERENCES

DETAIL NUMBER

SHEET NUMBER TO WHERE DETAIL IS REFERENCED

XX.XX

XX

WP

WP

EWC

C

QUAD RECEPTACLE, GROUND FAULT

C

POWER POLE

J

J

PB

C

ST

DB

G

ALUMINUMAL

PD

PP

T

SPD SURGE PROTECTION DEVICE, SEE SPECIFICATIONS.

SPD SURGE PROTECTION DEVICE

ECB

MMS

ENCLOSED CIRCUIT BREAKER

MANUAL MOTOR STARTER SWITCH

NOTIFICATION APPLIANCE CIRCUITNAC

SWITCH, 1 POLE, LETTER INDICATES SWITCHLEG

CONTROLLED.

SWITCH, KEYSWITCH

P

SWITCH

a

SWITCH, 2 POLE

SWITCH, 3-WAY

SWITCH, 4-WAY

K

SWITCH - PILOT LIGHT

M MOTOR RATED SWITCH

SWITCH, 3-WAY, LETTER INDICATES SWITCHLEG

CONTROLLED

SWITCH, KEYSWITCH, 3-WAY

NIGHT LIGHT, UNSWITCHEDNL

SWITCHES

SWITCH - LINE VOLTAGE TIMER, 120/277 VAC.

WATTSTOPPER TS-400 OR EQUAL.

SWITCH, EXPLOSION PROOF

QUAD RECEPTACLE FOR COMPUTER WORKSTATION

C

3a

3K

EXP

LB

VARIABLE FREQUENCY DRIVEVFD

SWITCH, LOW VOLTAGE MOMENTARYL

SWITCH, WEATHERPROOF

1. ALL ELECTRICAL WORK AND MATERIALS SHALL BE IN COMPLIANCE WITH ALL

GOVERNING CODES AND STANDARDS. THIS SHALL INCLUDE BUT NOT BE LIMITED

TO THE FOLLOWING:

A. NFPA 70 NATIONAL ELECTRICAL CODE (2020 EDITION)

B. FLORIDA BUILDING CODE (EIGHTH EDITION 2023)

C. NFPA 101 LIFE SAFETY CODE (2021EDITION)

D. NFPA 72 NATIONAL FIRE CODE (2019 EDITION)

E. FLORIDA FIRE PREVENTION CODE (EIGHTH EDITION 2023)

F. LOCAL REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION.

G. NFPA 1 NATIONAL FIRE CODE (2018 EDITION)

2. ANY CONSTRUCTION WORK DURING SCHOOL HOURS OF OPERATION MUST BE

SEQUENCED IN SUCH A WAY THAT IT WILL NOT INTERFERE WITH DAILY SCHOOL

ACTIVITIES. IF WORK IS CONDUCTED DURING SCHOOL HOURS OF OPERATIONS

THE CONTRACTOR MUST COORDINATE THE WORK WITH THE PM, A/E AND SCHOOL

REPRESENTATIVE.

3. THE CONTRACTOR RESPONSIBLE FOR THE EXECUTION OF THIS WORK SHALL

BECOME THOROUGHLY FAMILIAR WITH THE PROJECT SPECIFICATIONS BEFORE

COMMENCING ANY WORK. THE PROJECT SPECIFICATIONS AND DRAWINGS FORM

THE BASIS OF THIS CONTRACT REQUIREMENTS AND INCLUDE THE TYPE AND

GRADE OF MATERIALS TO BE INSTALLED, EQUIPMENT TO BE FURNISHED, THE

MANNER BY WHICH TO BE INSTALLED AND WHERE TO BE LOCATED. IN THE EVENT

OF A CONFLICT BETWEEN THE PROJECT SPECIFICATIONS AND DRAWINGS,

ASSUME THE MOST STRINGENT AND/OR COSTLY REQUIREMENT APPLIES.

4. THE CONTRACTOR SHALL CONSULT ALL TRADES FURNISHING EQUIPMENT AND

OBTAIN FROM THEM ALL DATA PERTAINING TO FURNISHED EQUIPMENT. THE

CONTRACTOR SHALL PROVIDE ALL CONDUIT, WIRING, DISCONNECT SWITCHES,

AND ASSOCIATED HARDWARE AS REQUIRED FOR COMPLETE AND OPERATING

SYSTEMS. COORDINATE AND INSTALL CONDUIT AND BOXES TO CLEAR EMBEDDED

DUCTS, OPENINGS AND OTHER STRUCTURAL FEATURES.

5. WHERE THE CONTRACTOR DETERMINES THAT HIS SYSTEM WILL REQUIRE

ADDITIONAL 120VAC POWER SUPPLIES IN LOCATIONS OTHER THAT AT THE FIRE

ALARM CONTROL PANEL, HE SHALL COORDINATE THESE REQUIREMENTS FOR

ADDITIONAL POWER AND ALL COSTS FOR NEW BREAKERS, CONDUIT, WIRE,

SURGE SUPPRESSORS AND ANY OTHER REQUIREMENTS SHALL BE INCLUDED IN

THIS CONTRACTORS BID.

6. EQUIPMENT LABELS AND INSTRUCTIONS REGARDING THE APPLICATION AND

INSTALLATION OF THE LISTED EQUIPMENT SHALL BE FOLLOWED TO INSURE THAT

THE EQUIPMENT IS BEING INSTALLED IN ACCORDANCE WITH THE

MANUFACTURER'S LISTING INSTRUCTIONS. THE TEMPERATURE RATING OF THE

EQUIPMENT TERMINATIONS MUST BE CAREFULLY CORRELATED WITH THE

CONDUCTOR AMPACITY TO PREVENT OVERHEATING AND PREMATURE FAILURE.

7. THE BUSINESS OPERATION OF THE BUILDING SHALL NOT BE DISRUPTED DURING

THE EXECUTION OF THIS WORK WITHOUT PRIOR NOTIFICATION AND APPROVAL BY

THE OWNER.

8. ALL EXISTING ITEMS DESIGNATED TO REMAIN, SUCH AS LIGHTING FIXTURES,

OUTLETS, SWITCHES, FIRE ALARM DEVICES, ETC. THAT ARE IN CONFLICT WITH

NEW CEILING OR WALLS, SHOULD BE RELOCATED AND LEFT IN OPERATION.

CONTRACTOR TO WALK THE SITE AND BECOME FAMILIAR WITH RELOCATION OF

EXISTING DEVICES PRIOR TO CONSTRUCTION.

9. WHERE CIRCUITS ARE INDICATED TO BE INSTALLED IN EXISTING PANELS, VERIFY

ACTUAL SPARES OR SPACES IN SAID PANELBOARDS AND USE THE SPARE

DEVICES OR FURNISH NEW CIRCUIT BREAKERS AS INDICATED ON THE DRAWINGS.

10. UNLESS SPECIFICALLY INDICATED AS EXISTING, ALL EQUIPMENT, CONDUIT, WIRE

AND ALL ACCESSORIES, REQUIRED AS PART OF THE INSTALLATION, AND USE OF

STATED EQUIPMENT, SHALL BE PROVIDED BY THE CONTRACTOR AS A PART OF

THIS PROJECT.

11. WHERE THE CONTRACTOR PROPOSES ALTERNATE SOLUTIONS, DIFFERENT

ROUTINGS OF CONDUIT, DIFFERENT LOCATIONS OF EQUIPMENT, ETC., THE

CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OF THE RAMIFICATIONS OF THE

PROPOSED CHANGE THAT ARE NOT INCLUDED IN HIS PROPOSAL, BUT BECOME

APPARENT AT A LATER DATE, AND SHALL BEAR THE CONSEQUENCES OF

CORRECTING ANY AND ALL CONFLICTS, DEFICIENCIES OR OTHER PROBLEMS AT

NO INCREASE IN COST OR INCREASE IN CONSTRUCTION TIME ALLOTTED.

12. THE CONTRACTOR SHALL INCLUDE IN HIS SCOPE; (1) THE LABOR AND MATERIALS

REQUIRED FOR CREATING OPENINGS FOR CONDUIT PENETRATIONS THROUGH

WALLS, SLABS AND ROOF STRUCTURES; AS WELL AS THE SEALING OF THESE

PENETRATIONS; (2) THE ROUTING OF CONDUITS AROUND INPENETRATABLE

OBSTACLES, SUCH AS POURED-IN-PLACE BEAMS, COLUMNS, LINTELS AND

SIMILAR OBSTRUCTIONS AND; (3) THE SEALING OF PENETRATIONS OF CONDUITS

INTO WHICH NEW WIRE IS PULLED AS A PART OF THIS PROJECT, TO INCLUDE

FIREPROOFING WHERE NECESSARY.

13. IF THE INTENT OF THE ENGINEER WITH REGARD TO ANY DETAIL IS NOT CLEAR,

OR IS CAPABLE OF MORE THAN ONE INTERPRETATION, SUCH MATTERS SHALL BE

BROUGHT TO THE ENGINEER IN WRITING BEFORE THE SUBMISSION OF BIDS, AND

THE ENGINEER SHALL ISSUE CORRECTION OR CLARIFICATION IN WRITING.

OTHERWISE, NO EXTRA COSTS OR EXTENSIONS OF TIME WILL BE BE ALLOWED

FOR THE WORK OR MATERIAL THAT THE A/E WILL REQUIRE, PROVIDED THAT IT

COMES WITHIN A REASONABLE INTERPRETATION OF THE DRAWINGS AND

SPECIFICATIONS.

14. NO WIRING SHALL BE DONE PRIOR TO THE CONTRACTOR'S REVIEW OF THE

PROJECT EQUIPMENT SHOP DRAWINGS AND COORDINATION WITH THE DESIGN

DOCUMENTS. ANY DISCREPANCIES SHALL BE BROUGHT TO THE

ARCHITECT/ENGINEER ATTENTION FOR FINAL RESOLUTION. WORK THAT HAS TO

BE REPLACED DUE TO LACK OF PROPER SHOP DRAWINGS CO-ORDINATION SHALL

BE DONE AT CONTRACTORS EXPENSE

15. EXISTING SYSTEMS SHOWN ARE BASED ON VISUAL INSPECTION AND EXISTING

DRAWINGS, BUT THEY MAY NOT REFLECT THE ACTUAL CONDITIONS IN EVERY

CASE. THE CONTRACTOR SHALL INSPECT THE SITE AND EXAMINE THE WORK

BEFORE SUBMITTING HIS PROPOSAL. THE CONTRACTOR SHALL NOTE THE

LOCATION OF EXISTING FACILITIES, THE EXTENT OF HIS WORK, AND

INTERFERENCE BY OTHER TRADES WITH HIS WORK. ANY DISCREPANCIES

SHOULD BE DISCUSSED WITH THE ENGINEER. SUBMISSION OF A PROPOSAL WILL

BE CONSTRUED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN MADE AND

LATER CLAIMS FOR LABOR, EQUIPMENT OR MATERIALS REQUIRED BECAUSE OF

DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED.

16. FURNISH AND INSTALL EQUIPMENT DISCONNECT SWITCHES IN STRICT

COMPLIANCE WITH APPLICABLE CODE REQUIREMENTS.

17. FIRESTOP ALL PENETRATIONS (MADE BY THIS CONTRACTOR) THROUGH

FIRE-RATED WALLS, FLOORS AND CEILINGS. THIS CONTRACTOR SHALL BE

RESPONSIBLE FOR ALL CUTTING AND PATCHING RELATED TO THIS

CONTRACTOR'S WORK. PATCH ALL UNUSED OPENINGS (CREATED BY THIS

CONTRACTOR) TO MATCH SURROUNDING CONDITIONS.

18. ABSOLUTELY NO SPLICES WILL BE ALLOWED IN ANY SYSTEMS WIRES. PROVIDE

FULL LENGTH WIRING BETWEEN DEVICES AND TERMINALS.

19. HEIGHTS REQUIRED BY EQUIPMENT SUPPLIERS TAKE PRECEDENCE OVER ALL

OTHER DIMENSIONS.

20. ITEMS IN TILE SURFACES SHALL BE INSTALLED AS CLOSE AS POSSIBLE TO THE

DIMENSION GIVEN AND SHALL BE HORIZONTALLY AND VERTICALLY CENTERED

AND ALIGNED WITH THE TILE JOINTS.

21. ALL FEEDERS ARE TO HAVE LESS THAN 2% TOTAL VOLTAGE DROP AND ALL

BRANCH CIRCUITS SHALL HAVE LESS THAN 3% VOLTAGE DROP. WIRING TO

RECEPTACLES SHALL BE #12 THWN MINIMUM.

22. EXCEPT WHERE SPECIFICALLY NOTED OTHERWISE, THE CONTRACTOR SHALL

PROVIDE NEW CONDUIT FOR ALL CONDUCTORS THAT ARE INSTALLED AS A PART

OF THIS PROJECT. INSULATED PLASTIC BUSHINGS ARE TO BE PROVIDED ON ALL

CONDUIT STUB-OUTS AND STUB-UPS.

23. THE INSTALLATION OF ALL DEVICES, INCLUDING MOUNTING HEIGHTS, SHALL BE

FULLY ADA AND NFPA COMPLIANT.

24. THE CONTRACTOR SHALL VERIFY THE EXACT DIRECTION OF ALL DOOR SWINGS

PRIOR TO ROUGH-IN OF BOXES MOUNTED IN WALLS.

25. THE CONTRACTOR SHALL THOROUGHLY CLEAN ALL EQUIPMENT TO BE

COMPLETELY FREE OF INTERNAL DEBRIS AND EXTERIOR PAINT, MARKS, DIRT

AND ALL SCRATCHES SHALL BE TOUCHED UP.

26. ALL EMPTY/SPARE CONDUITS SHALL HAVE PULL STRINGS WITH LABELING TAGS

AT EACH END.

27. ALL RACEWAYS SHALL HAVE A GREEN INSULATED COPPER

EQUIPMENT-GROUNDING CONDUCTOR.

28. EXPANSION FITTINGS SHALL BE PROVIDED IN EXPOSED CONDUIT RUNS OVER 100

FEET, AT BUILDING EXPANSION JOINTS AND IN CONDUIT RUNS BETWEEN

BUILDINGS.

29. MOTOR SIZES AND LOCATIONS SHOWN ON THE DRAWINGS ARE BASED ON

INFORMATION OBTAINED DURING DESIGN. VERIFY THE ACTUAL LOCATIONS AND

PROVIDE WIRING AND PROTECTION OF PROPER SIZES AS REQUIRED. WIRE

MOTORS FOR PROPER DIRECTION OF ROTATION AND CHECK ROTATION AT

START-UP.

30. ALL BRANCH CIRCUITS AND FEEDERS SHALL BE PROVIDE WITH SEPARATE

GROUNDING CONDUCTORS.

31. AIR HANDLERS - AHU'S MUST BE INTERFACE WITH EMS AND FIRE ALARM. ALL NEW

AND EXISTING AIR HANDLERS AND FANS SHALL SHUTDOWN UPON ACTIVATION OF

THE FIRE ALARM SYSTEM. COMPLY WITH NFPA 90A.

32. WITHIN 30 DAYS OF ACCEPTANCE OF PROJECT, COMPLETION RECORD DRAWINGS,

OPERATION AND MAINTENANCE MANUALS SHALL BE PROVIDED BY THE

CONTRACTOR TO THE OWNER IN ACCORDANCE WITH FBC C405.7.4.

33. VERIFY AND CONFIRM ALL WORKING CLEARANCES ARE MAINTAINED FOR ALL

NEW, RENOVATED AND RELOCATED ELECTRICAL EQUIPMENT IN COMPLIANCE

WITH NEC TABLE 110.26(A).

34. CONTRACTOR SHALL REPLACE LIGHTING FIXTURES DAMAGED. IT SHALL ALSO

RELOCATE ANY EXISTING LIGHT FIXTURE THAT IS IN THE WAY OF PROPOSED NEW

DUCT WORK.

35. CONTRACTOR TO NOTIFY OWNER PRIOR TO DISCONNECT ANY ALARM DEVICE.

36. PROVIDE TYPED PANEL DIRECTORIES FOR ALL PANELBOARDS AFFECTED BY

DEMOLITION OR NEW WORK. DIRECTORIES SHALL REFLECT TRUE PROJECT

AS-BUILT CONDITIONS FOR ALL BRANCH CIRCUITS. DIRECTORIES SHALL INCLUDE

WHERE EACH PANEL IS FED FROM, AND EACH BRANCH CIRCUIT LOAD

DESCRIPTION SHALL INCLUDE THE ROOM NUMBERS FOR EACH LOAD SERVED.

ROOM NUMBERS SHALL BE BASED ON ACTUAL ROOM SIGNAGE INSTALLED IN

FIELD. BREAKERS IN EXISTING PANELS NO LONGER USE SHALL BE LABELED

“SPARE” AND TURNED OFF.

37. PROVIDE DEMO/ REMOVAL OF ALL ABANDONED CONDUIT, BOXES, DEVICES,

CABINETS, AND THE REPAIR OF ALL HOLES IN WALLS TO MAINTAIN FIRE RATINGS

INCLUDING PAINTING TO MATCH EXISTING CONDITIONS..

38. WHERE EXISTING WIRING IS CALLED TO BE REUSED, THE FEEDER AND

GROUNDING SYSTEM SHALL BE TESTED FOR PROPER OPERATION AND

PERFORMANCE.

39. PRIOR TO ENERGIZING ANY NEW ELECTRICAL EQUIPMENT, AN INDEPENDENT

TESTING FIRM SHALL PERFORM VISUAL AND MECHANICAL INSPECTIONS AND

ELECTRICAL TESTS ON ALL NEWLY INSTALLED EQUIPMENT SUPPLIED WITHIN THIS

CONTRACT. THE CONTRACTOR SHALL PROVIDE A COMPLETE TORQUE REPORT

FOR ALL WIRE TERMINATIONS TO NEWLY INSTALLED OR RELOCATED EQUIPMENT.

ALL INSPECTIONS AND TEST SHALL BE COMPLETED BY AN INDEPENDENT TESTING

ORGANIZATION CERTIFIED BY THE INTERNATIONAL ELECTRICAL TESTING

ASSOCIATION (NETA) OR (NICET).

GENERAL NOTES

ELECTRICAL SCOPE OF WORK

1. PROVIDE RENOVATED POWER INFRASTRUCTURE AND

CONNECTIONS TO EXISTING ELEVATORS AND ASSOCIATED

EQUIPMENT. THIS IS NOT ALL INCLUSIVE OF THE SCOPE OF

WORK. REFER TO CONTRACT DOCUMENTS FOR FURTHER

CLARIFICATION.

E200

TITLE

E200

135° HEAT DETECTOR

SMOKE DETECTOR

FIRE ALARM SYSTEM

FIRE ALARM CONTROL PANEL "FACP"

CONTROL MODULE RELAY

VAPORTIGHT, LED, WET LOCATION,

GENERAL PURPOSE WALL MOUNTED

LITHONIA

OLVTWM-4000K-MVOLT 120/277V 48W LEDA

DESIGN SELECTION VOLTS LAMPS/FIXTURE

LIGHTING FIXTURE SCHEDULE

TYPE DESCRIPTION

LIGHTING FIXTURE NOTES:

a. FINAL FIXTURE FINISHES SHALL BE

SELECTED DURING SUBMITTAL

PROCESS BY ARCHITECT FROM

EXTENDED STANDARD COLOR

CHART FOR EACH FIXTURE.

b. ALL FIXTURES, WHETHER STANDARD

OR NOT, REQUIRE LISTING BY A

NATIONALLY RECOGNIZED TESTING

LABORATORY.

c. ALL FIXTURE NOTED AS

EMERGENCY FIXTURES SHALL

SUPPLY A MINIMUM OF 90MIN

BACK-UP BATTERY POWER.

d. WHEN FIXTURE MODEL DIFFERS

FROM FIXTURE DESCRIPTION, THEN

THE FIXTURE DESCRIPTION SHALL

GOVERN.

LIGHTING FIXTURES

CEILING MOUNTED RECESSED, DOWN LIGHT

SURFACE MOUNTED LIGHTING FIXTURE

CEILING MOUNTED RECESSED, EMERGENCY DOWN LIGHT

WALL MOUNTED SCONCE FIXTURE, BATTERY/EMERGENCY

SINGLE FACE EXIT LIGHT FIXTURE ARROW

INDICATES DIRECTION OF EGRESS

DOUBLE FACE EXIT LIGHT FIXTURE ARROW

INDICATES DIRECTION OF EGRESS

4' FLUORESCENT STRIP FIXTURE

4' FLUORESCENT STRIP FIXTURE, BATTERY/EMERGENCY

4' FLUORESCENT STRIP FIXTURE, WALL MOUNTED

4' FLUORESCENT STRIP FIXTURE, WALL MOUNTED,

BATTERY/EMERGENCY

NOTES

VAPORTIGHT, LED, WET LOCATION,

1X4 PENDANT MOUNTED

LITHONIA

CSVT-4000LM-MVOLT-40K-80

CRI

120/277V 48W LEDBE ON EMERGENCY

CIRCUIT

KISSIMMEE CITY HALL

ELEVATOR

REPLACEMENTS

N

C H

U R

C H

S T

R E

E T

K

IS

S

IM

M E

E

F L O

R

ID

A

5301 WATERFORD DISTRICT DR.

SUITE 750

MIAMI, FL 33126

TEL: 954-421-1944

FAX: 954-421-1924

CA-00006208

WWW.SGMENGINEERING.COM

COPYRIGHT © 2024 SGM ENGINEERING, INC.

JA

JA

OFFICE

ELEVATOR

EQUIP.ROOM

FIRE PUMP

OPEN OFFICE

TOHOPOKELIGA

CONFERENCE ROOM

MEN

WOMEN

VIDEO EDIT

JANITOR

PERMITTING

CONFERENCE

OFFICE

LOBBYADMIN

1L1-91,93,95

ELEVATOR

#2

ELEVATOR

#1

ELEVATOR

#1 & #2 CAB

LIGHTING

1HE1-5

1HM1-56:58:60

1HE1-7:9:11

1LE1-15,173

GENERAL NOTES:

a. REFER TO SYMBOL LEGEND ON SHEET E001.

b. REFER TO SPECIFICATIONS.

c. REFER TO EQUIPMENT SCHEDULES FOR DISCONNECT, CONDUIT AND WIRE SIZES.

d. ALL FEEDERS ARE TO HAVE LESS THAN 2% TOTAL

VOLTAGE DROP AND ALL BRANCH CIRCUITS SHALL HAVE

LESS THAN 3% VOLTAGE DROP.

e. EXISTING EQUIPMENT AND SYSTEMS SHOWN ARE BASED

ON VISUAL INSPECTION AND EXISTING DRAWINGS. THE

CONTRACTOR SHALL INSPECT THE SITE AND EXAMINE

THE SYSTEMS BEFORE PERFORMING ANY WORK.

SOURCES OF VARIOUS BRANCH CIRCUITS COULD NOT BE

CONFIRMED BY VISUAL INSPECTION. THE CONTRACTOR

SHALL FIELD VERIFY (TRACE) "EXISTING TO REMAIN"

BRANCH CIRCUITS AND FEEDERS (CONDUIT AND WIRE)

TO MAKE SAFE (LOCKOUT-TAGOUT) BEFORE ANY

DEMOLITION OR NEW WORK.

f. ALL SYMBOLS SHOWN IN " LIGHT" COLOR INDICATE

EXISTING TO REMAIN. SYMBOLS SHOWN "DARK"

INDICATES EQUIPMENT BEING MODIFIED, OR NEW.

g. ENSURE PROPER WORKING CLEARANCE FOR ALL

ELECTRICAL DEVICES AND EQUIPMENT.

h. ALL POWER AND CONTROL CONDUITS OUTSIDE OF THE

MACHINE ROOM AND ELEVATOR PIT SHALL BE

CONCEALED.

i. CONTRACTOR TO PROVIDE TRACING SERVICES PRIOR

TO ANY WORK TO CONFIRM EXISTING CIRCUITS.

g. EXISTING FIRE ALARM SYSTEM SHALL BE TESTED PRIOR

COMMENCEMENT OF WORK. CONTRACTOR TO NOTIFY

THE OWNER AND A/E OF ANY EXISTING ALARM,

SUPERVISORY OR TROUBLE CONDITION IN THE ALARM

PANEL PRIOR TO COMMENCING WORK ON THE FIRE

ALARM SYSTEM. ALARM PANEL SHALL BE CLEARED OF

ALL TROUBLES BEFORE COMMENCING WORK.

i. PROVIDE, INSTALL AND TERMINATE ALL FIRE ALARM

EQUIPMENT INCLUDING, BUT NOT LIMITED TO

RACEWAYS, WIRE CABLE, MODULES, RELAYS, ETC. MAKE

FINAL CONNECTIONS FOR A FULLY FUNCTIONAL SYSTEM.

PLAN KEY NOTES:

1. DISCONNECT AND REMOVE EXISTING LIGHT FIXTURE

AND ASSOCIATED LIGHTING SWITCH IN ELEVATOR PIT.

CONTRACTOR TO PROTECT THE EXISTING CIRCUIT,

FOR USE IN RENOVATION.

2. EXISTING WEATHER PROOF RECEPTACLE TO BE

REPLACED WITH NEW. CONTRACTOR TO PROTECT THE

EXISTING CIRCUIT, FOR USE IN RENOVATION.

3. EXISTING FIRE ALARM DEVICES TO BE REPLACED WITH

NEW.

4. EXISTING ELEVATOR MOTOR TO BE REPLACED WITH

NEW LIKE AND KIND ELEVATOR MOTOR. CONTRACTOR

TO DISCONNECT EXISTING FEEDER AND PROTECT

WHILE OLD EQUIPMENT IS REPLACED.

5. EXISTING CAB LIGHTING DISCONNECTs TO BE

REPLACED WITH NEW IN-KIND. CONTRACTOR TO

PROTECT EXISTING CIRCUIT AND COMPONENTS.

6. EXISTING ELEVATOR CONTROL MODULE AND RECALL

CONNECTIONS TO BE TEMPORARILY DISCONNECTED

WHILE NEW WORK IS BEING CONDUCTED.

CONTRACTOR TO PROTECT ALL COMPONENTS FOR

USE IN NEW ELEVATOR MOTORS.

7. EXISTING PENDANT MOUNT LIGHT FIXTURES TO BE

REPLACED WITH NEW IN SAME LOCATION.

CODE ENFORCEMENT

COMMUNICATION

ELECTRICAL

PNL

HC1

PNL

1HQ1

PNL

1HE1

PNL

EDP

PNL

1H1

PNL

MDP

PNL

1HM1

PNL

1LE1

PNL

1LC1

FACP

FATC-1

PNL

1L1 (3 SECTIONS)

KISSIMMEE CITY HALL

ELEVATOR

REPLACEMENTS

N

C H

U R

C H

S T

R E

E T

K

IS

S

IM

M E

E

F L O

R

ID

A

5301 WATERFORD DISTRICT DR.

SUITE 750

MIAMI, FL 33126

TEL: 954-421-1944

FAX: 954-421-1924

CA-00006208

WWW.SGMENGINEERING.COM

COPYRIGHT © 2024 SGM ENGINEERING, INC.

ELECTRICAL FIRST LEVEL DEMO PARTIAL FLOOR PLAN

ENLARGED ELECTRICAL RM. 106

JA

GENERAL NOTES:

a. REFER TO SYMBOL LEGEND ON SHEET E001.

b. REFER TO SPECIFICATIONS.

c. REFER TO EQUIPMENT SCHEDULES FOR DISCONNECT, CONDUIT AND WIRE SIZES.

d. ALL FEEDERS ARE TO HAVE LESS THAN 2% TOTAL

VOLTAGE DROP AND ALL BRANCH CIRCUITS SHALL HAVE

LESS THAN 3% VOLTAGE DROP.

e. EXISTING EQUIPMENT AND SYSTEMS SHOWN ARE BASED

ON VISUAL INSPECTION AND EXISTING DRAWINGS. THE

CONTRACTOR SHALL INSPECT THE SITE AND EXAMINE

THE SYSTEMS BEFORE PERFORMING ANY WORK.

SOURCES OF VARIOUS BRANCH CIRCUITS COULD NOT BE

CONFIRMED BY VISUAL INSPECTION. THE CONTRACTOR

SHALL FIELD VERIFY (TRACE) "EXISTING TO REMAIN"

BRANCH CIRCUITS AND FEEDERS (CONDUIT AND WIRE)

TO MAKE SAFE (LOCKOUT-TAGOUT) BEFORE ANY

DEMOLITION OR NEW WORK.

f. ALL SYMBOLS SHOWN IN " LIGHT" COLOR INDICATE

EXISTING TO REMAIN. SYMBOLS SHOWN "DARK"

INDICATES EQUIPMENT BEING MODIFIED, OR NEW.

g. ENSURE PROPER WORKING CLEARANCE FOR ALL

ELECTRICAL DEVICES AND EQUIPMENT.

h. ALL POWER AND CONTROL CONDUITS OUTSIDE OF THE

MACHINE ROOM AND ELEVATOR PIT SHALL BE

CONCEALED.

i. CONTRACTOR TO PROVIDE TRACING SERVICES PRIOR

TO ANY WORK TO CONFIRM EXISTING CIRCUITS.

g. EXISTING FIRE ALARM SYSTEM SHALL BE TESTED PRIOR

COMMENCEMENT OF WORK. CONTRACTOR TO NOTIFY

THE OWNER AND A/E OF ANY EXISTING ALARM,

SUPERVISORY OR TROUBLE CONDITION IN THE ALARM

PANEL PRIOR TO COMMENCING WORK ON THE FIRE

ALARM SYSTEM. ALARM PANEL SHALL BE CLEARED OF

ALL TROUBLES BEFORE COMMENCING WORK.

i. PROVIDE, INSTALL AND TERMINATE ALL FIRE ALARM

EQUIPMENT INCLUDING, BUT NOT LIMITED TO

RACEWAYS, WIRE CABLE, MODULES, RELAYS, ETC. MAKE

FINAL CONNECTIONS FOR A FULLY FUNCTIONAL SYSTEM.

PLAN KEY NOTES:

1. PROVIDE CONNECTION TO NEW LIGHT FIXTURES AND

SWITCHES. PROVIDE SWITCH IN LOCATION THAT IS

ACCESSIBLE THROUGH PIT. COORDINATE EXACT

LOCATION OF ALL FIXTURES WITH ELEVATOR INSTALLER.

2. PROVIDE NEW 30A DISCONNECT SWITCH AND RE-USE

EXISTING CONDUCTORS AND CONDUIT TO RE-CONNECT

ELEVATOR CAB LIGHTS.

3. PROVIDE NEW DISCONNECT SWITCH FOR ELEVATOR

EQUIPMENT. PROVIDE NEW ENCLOSED CIRCUIT

BREAKER. REFER TO EQUIPMENT FEEDER SCHEDULE

AND COORDINATE WITH ELEVATOR MANUFACTURER.

4. PROVIDE NEW GFI WEATHER PROOF RECEPTACLE.

RE-USE EXISTING BRANCH CIRCUIT AND PROVIDE NEW

BACK BOX, CONDUIT AND WIRE AS REQUIRED.

5. CONTROL MODULES TO BE RE-CONNECTED TO NEW

ELEVATOR CONTROLLERS AND MOTORS.

6. PROVIDE NEW HEAT AND SMOKE DETECTORS IN

ELEVATOR SHAFT AND NEW SMOKE DETECTORS IN

ELEVATOR MACHINE ROOM AND ELEVATOR LOBBIES.

PROVIDE NEW J-BOX ROUGHED IN WALL INCLUDING ALL

WIRING, CONDUIT AND CONNECTIONS AND CONNECT TO

EXISTING FIRE ALARM SYSTEM..

7. PROVIDE NEW DESIGNATED AND ALTERNATE LEVEL

RECALL RELAYS FOR BUILDING ELEVATOR RECALL.

8. ELEVATOR EQUIPMENT TO BE PROVIDED WITH

BATTERIES. POWER TRANSFER TO BATTERIES WILL

OCCUR WITHIN 60 SECONDS OF LOSS OF NORMAL

POWER.

9. PROVIDE NEW FEED FROM DISCONNECT SWITCH TO

ELEVATOR UNIT.

10. PROVIDE NEW FEEDER CONNECTION (CONDUIT AND

WIRE) TO NEW MECHANICAL EQUIPMENT IN NEW

LOCATION.

11. PROVIDE FIRE FIGHTER EMERGENCY OPERATION FOR

PHASE I ELEVATOR RECALL AS REQUIRED BY NFPA

101-9.4.3.2.

12. NEW SUMP PUMP TO BE PROVIDED, WITH NEW FEEDER

(CONDUIT AND WIRE) THEN CONNECTED TO EXISTING

SUMP PUMP CONTROLS AND EMERGENCY POWER.CODE ENFORCEMENT

COMMUNICATION

ELECTRICAL

106PNL

HC1

PNL

1HQ1

PNL

1HE1

PNL

EDP

PNL

1L1 (3 SECTIONS)

PNL

1H1

PNL

MDP

PNL

1HM1

PNL

1LE1

PNL

1LC1

FACP

FATC-1

PERMITTING

CONFERENCE

OFFICE

LOBBYADMIN

1L1-91,93,95

K

A

A

A

A

SP-1

1HE1-16:18

OFFICE

ELEVATOR

EQUIP.ROOM

FIRE PUMP

VIDEO EDIT

CHILLER

YARD

ELEVATOR

#2

ELEVATOR

#1

ELEVATOR

#1 & #2 CAB

LIGHTING

1HE1-5

1HM1-56:58:60

1HE1-7:9:11

1LE1-15,17

3 8

DX-1-1

CU-1-1

BE

BE

1HE1-8:10

1L1-274

1HE1-12:14

KISSIMMEE CITY HALL

ELEVATOR

REPLACEMENTS

N

C H

U R

C H

S T

R E

E T

K

IS

S

IM

M E

E

F L O

R

ID

A

5301 WATERFORD DISTRICT DR.

SUITE 750

MIAMI, FL 33126

TEL: 954-421-1944

FAX: 954-421-1924

CA-00006208

WWW.SGMENGINEERING.COM

COPYRIGHT © 2024 SGM ENGINEERING, INC.

ENLARGED ELECTRICAL RM. 106

ENLARGED ELEVATOR SHAFTS

ENLARGED ELEVATOR EQUIPMENT RM.

JA

REPLACEMENTS

N

C H

U R

C H

S T

R E

E T

K

IS

S

IM

M E

E

F L O

R

ID

A

5301 WATERFORD DISTRICT DR.

SUITE 750

MIAMI, FL 33126

TEL: 954-421-1944

FAX: 954-421-1924

CA-00006208

WWW.SGMENGINEERING.COM

COPYRIGHT © 2024 SGM ENGINEERING, INC.

G

480/277V, 3Ø, 4W

500KVA GENERATOR

ST

BOND NEUTRAL TO GROUND

AT GENERATOR

FIRE PUMP

CONTROLLER

ATS-C

150A, 4P

GENERAL NOTES:

a. REFER TO SYMBOL LEGEND AND NOTES ON SHEET E-001.

b. REFER TO BOOK SPECIFICATIONS.

c. REFER TO PANEL FEEDER SCHEDULE ON THIS SHEET FOR

PANEL FEEDER CONDUIT AND WIRE SIZES.

d. REFER TO EQUIPMENT SCHEDULES ON THIS SHEET FOR

DISCONNECT, CONDUIT AND WIRE SIZES.

e. ALL FEEDERS ARE TO HAVE LESS THAN 2% TOTAL

VOLTAGE DROP AND ALL BRANCH CIRCUITS SHALL HAVE

LESS THAN 3% VOLTAGE DROP.

f. ALL SYMBOLS SHOWN IN "LIGHT" COLOR INDICATE

EXISTING TO REMAIN; NO WORK REQUIRED UNLESS NOTED

OTHERWISE.

g. ALL SYMBOLS SHOWN IN "DARK" COLOR INDICATE EXISTING

EQUIPMENT TO BE MODIFIED, UNLESS NOTED OTHERWISE.

h. FIELD VERIFY EXISTING CONDITIONS PRIOR TO

DEMOLITION.

i. COORDINATE WORK WITH ALL OTHER TRADES BEFORE

ANY ROUGH-INS.

PLAN KEY NOTES: #

1. PROVIDE NEW CIRCUIT BREAKER TO PANEL SHOWN.

REFER TO PANEL SCHEDULE ON SHEETS E701 FOR MORE

DETAILS.

2. REFER TO EQUIPMENT FEEDER SCHEDULE FOR MORE

INFORMATION ON NEW FEEDER SIZES FOR ELEVATOR.

1 1 1 1 1

ELECTRICAL PARTIAL ONE-LINE DIAGRAM

JA

JA

JA

JA

REPLACEMENTS

N

C H

U R

C H

S T

R E

E T

K

IS

S

IM

M E

E

F L O

R

ID

A

5301 WATERFORD DISTRICT DR.

SUITE 750

MIAMI, FL 33126

TEL: 954-421-1944

FAX: 954-421-1924

CA-00006208

WWW.SGMENGINEERING.COM

COPYRIGHT © 2024 SGM ENGINEERING, INC.

JA

JA

JA

JA

REPLACEMENTS

N

C H

U R

C H

S T

R E

E T

K

IS

S

IM

M E

E

F L O

R

ID

A

5301 WATERFORD DISTRICT DR.

SUITE 750

MIAMI, FL 33126

TEL: 954-421-1944

FAX: 954-421-1924

CA-00006208

WWW.SGMENGINEERING.COM

COPYRIGHT © 2024 SGM ENGINEERING, INC.

18"

46" 46"

3" DUPLEX

RECEPTACLE FIRE ALARM

PULL BOX

TYPICAL

DOOR

CABINET- SEE

ARCH. PLANS

FOR SIZE

DUPLEX

RECEPTACLE

FAN

SWITCH

LIGHT

SWITCHCOMPUTER

DATA OUTLET

6"

18"

LIGHT

SWITCH

SEALANT

PENETRATION WITH

SEAL OUTSIDE OF PYRO-PAC MODEL FS.

(ACCESSIBLE FROM ONLY

LINK-SEAL TYPE

WALL SLEEVE.

MODEL-WS.

ONE SIDE)

SEAL OUTSIDE OF

SEALANT

JOINT WITH MASTIC

INTERIOR FACE OF CONCRETE

LINK-SEAL TYPE

WALL PENETRATION.

SEAL MODEL-LS.

WATER STOP AND

ANCHOR COLLAR

FOUNDATION WALL

PIPE SLEEVE

CONCRETE

FLOOR SLAB

RISER CLAMP

CONDUIT

UL APPROVED

FIRE-STOPPING SYSTEM.

1/4" CONCRETE ANCHOR & 1/4" BOLT (UP TO 1 - 1/2" EMT)

3/8" CONCRETE ANCHOR & 3/8" BOLT (2" - 4" EMT)

1/4" ROD FOR 3/4" TO 1 - 1/2" EMT CONDUIT

3/8" ROD FOR 2" TO 4" EMT CONDUIT

CONDUIT CLAMP

12 GA. GALV. STEEL

ELECTRICAL METAL TUBING (EMT)

46"

FIRE

PULL DOWN

FIRE ALARM

A/C SUPPLY

OR RETURN

DIFFUSER

CEILING

MANUAL

PULL

STATION

FIRE

PHONE

JACK

FINISHED FLOOR

NFPA 72 AUDIBLE ONLY

APPLIANCE 6" MIN BELOW

FINISHED CEILINGFIREFIRE

NO

LE

SS

TH

AN

" A

ND

NO

GR

EA

TE

R T

HA

N 9 6" A

.F.F

OR

6"

BE

LO

W

CE

ILIN

G, WH

ICH

EV

ER

IS L

OW

ER

, TO

BO

TT

OM

OF

VIS

UA

L L

EN

S

AUDIBLE/VISUAL &

VISUAL ONLY

APPLIANCES.

SYNCHRONIZE MORE

THAN TWO APPLIANCES

N ANY FIELD OF VIEW.

" A

.F .F

. T O

TO

P

OF

B

OX

" T

O

TO

P

OF

B

AC

K

BO

X

AU

DI

BL

E

ON

LY

D

EV

IC

ES

" M

I.

AB

OV

E

FI

NI

SH

ED

F

LO

OR

FOR CEILING HEIGHTS

LESS THAN 86" THE VISUAL

LENS MOUNTING HEIGHT SHALL

BE WITHIN 6" OF THE CEILING.

NFPA 72 AUDIBLE ONLY APPLIANCE

6" MIN BELOW FINISHED CEILING 5' MIN.

SMOKE/HEAT

DETECTORS NEVER HERE

CEILING MOUNTED

SMOKE/HEAT DETECTORS

WALL MOUNTED

SMOKE/HEAT DETECTORS

FINISHED WALL

4"

4"

" M

AX

5' MAX. TO EXIT DOOR

MAGNETIC

DOOR

HOLDER

DOOR

WIDTH

LESS 3"

5"

ANNUNCIATOR PANEL

ELEVATOR CONTROL

GAS

SOLENOID

VALVE

NOTIFICATION DEVICE

SLC

CONTROL

MODULE

AHU

SHUTDOWN

RELAY

FIRE ALARM

TERMINAL

CABINET/

NAC PANEL

TYPICAL

#6 COPPER TO LOCAL SYSTEMS

GROUND BUSBAR IN IDF

120V POWER FOR NFPA-72

(PROVIDE SURGE PROTECTION

AT EACH 120V INPUT) (TYPICAL)

DETAIL NOTES:

ALL FIRE ALARM WIRING SHALL BE

RUN IN 3/4" CONDUIT MINIMUM

TO NEXT

DEVICE

TO NEXT

DEVICE

INITIATING DEVICE

TO NEXT

DEVICE

SEALANT

PENETRATION WITH

SEAL OUTSIDE OF PYRO-PAC MODEL FS.

(ACCESSIBLE FROM ONLY

LINK-SEAL TYPE

WALL SLEEVE.

MODEL-WS.

ONE SIDE)

SEAL OUTSIDE OF

SEALANT

JOINT WITH MASTIC

INTERIOR FACE OF CONCRETE

LINK-SEAL TYPE

WALL PENETRATION.

SEAL MODEL-LS.

WATER STOP AND

ANCHOR COLLAR

FOUNDATION WALL

2" 2"

USE TWO (2) INTERMEDIATE HANGER RODS FOR HANGERS OVER 37"

USE ONE (1) INTERMEDIATE HANGER ROD FOR HANGERS 25" TO 36"

12 GA. GALV. STEEL

CHANNEL CONDUIT CLAMP

3/8" ROD

CONDUIT HANGER

1 1/2" X 1 1/2" 12 GA. GALV. STEEL CHANNEL

REFER TO CONDUIT SPACING SCHEDULE

ELECTRICAL METAL TUBING (EMT

FOR EMT SPACING REQUIRMENTS

(TYPICAL)

OR

HANG FROM BEAM CLAMP OR ROOF JOIST AS REQUIRED.

JA

REPLACEMENTS

N

C H

U R

C H

S T

R E

E T

K

IS

S

IM

M E

E

F L O

R

ID

A

5301 WATERFORD DISTRICT DR.

SUITE 750

MIAMI, FL 33126

TEL: 954-421-1944

FAX: 954-421-1924

CA-00006208

WWW.SGMENGINEERING.COM

COPYRIGHT © 2024 SGM ENGINEERING, INC.

* NOTE

THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS

FROM THE 2004 EDITION OF THE UL FIRE RESISTANCE DIRECTORY.

System No.W-L-1001 June 15, 2005

F Ratings - 1, 2, 3 and 4 Hr (See Items 2 and 3) T Ratings - 0, 1, 2, 3, and 4 Hr (See Item 3) L Rating At Ambient - less than 1 CFM/sq ft L Rating At 400 F - less than 1 CFM/sq ft

1. Wall Assembly - The 1, 2, 3 or 4 hr fire-rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner described in the individual U300 or U400 Series Wall or Partition Designs in the UL Fire Resistance Directory and shall include the following construction features:

A. Studs - Wall framing may consist of either wood studs (max 2 hr fire rated assemblies) or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102

mm) lumber spaced 16 in. (406 mm) OC with nom 2 by 4 in. (51 by 102 mm) lumber end plates and cross braces. Steel studs to be min 3-5/8 in. (92 mm) wide by 1-3/8 in. (35

mm) deep channels spaced max 24 in. (610 mm) OC.

B. Gypsum Board* - Nom 1/2 or 5/8 in. (13 or 16 mm) thick, 4 ft. (122 cm) wide with square or tapered edges. The gypsum wallboard type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 26 in. (660 mm).

2. Through Penetrant - One metallic pipe, conduit or tubing installed either concentrically or eccentrically within the firestop system. The annular space between pipe, conduit or tubing and periphery of opening shall be min of 0 in. (0 mm) (point contact) to max 2 in.

(51 mm). Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly.

The following types and sizes of metallic pipes, conduits or tubing may be used:

A. Steel Pipe - Nom 24 in. (610 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.

B. Iron Pipe - Nom 24 in. (610 mm) diam (or smaller) service weight (or heavier) cast iron soil pipe, nom 12 in. (305 mm) diam (or smaller) or Class 50 (or heavier) ductile iron pressure pipe.

C. Conduit - Nom 6 in. (152 mm) diam (or smaller) steel conduit or nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing D. Copper Tubing - Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing E. Copper Pipe - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe.

F. Through Penetrating Product* - Flexible Metal Piping - The following types of steel flexible metal gas piping may be used:

1. Nom 2 in. (51 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both sides of floor or wall assembly.

OMEGA FLEX INC

2. Nom 1 in. (25 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both sides of floor or wall assembly.

TITEFLEX CORP

A BUNDY CO

3. Nom 1 in. (25 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both sides of floor or wall assembly.

WARD MFG INC

3. Fill,Void or Cavity Material* - Caulk or Sealant - Min 5/8. 1-1/4,1-7/8 and 2-1/2 in. (16, 32, 48 and 64 mm) thickness of caulk for 1, 2, 3 and 4 hr rated assemblies, respectively, applied within annulus, flush with both surfaces of wall. Min 1/4 in. (6 mm) diam bead of caulk applied to gypsum board/penetrant interface at point contact location on both sides of wall.

The hourly F Rating of the firestop system is dependent upon the hourly fire rating of the wall assembly in which it is installed, as shown in the following table.

The hourly T Rating of the firestop system is dependent upon the type or size of the pipe or conduit and the hourly fire rating of the wall assembly in which it is installed, as tabulated below:

+When copper pipe is used, T Rating is 0 hr.

3M COMPANY - CP 25WB+ caulk or FB-3000 WT sealant, *Bearing the UL Classification Marking

SECTION A-A

1A

1BA

Max Pipe or Conduit Diam in.

(mm) F Rating Hr T Rating Hr

1 (25) 1 or 2 0+, 1 or 2 1 (25) 3 or 4 3 or 4 4 (102) 1 or 2 0 6 (152) 3 or 4 0

12 (305) 1 or 2 0

A

SECTION A-A

A

A

System No. C-AJ-1044 June 15, 2005

F Ratings - 2, 3, and 4 Hr (See Items 2A and 4) T Rating - 0 Hr

L Rating At Ambient - 2 CFM/sq ft L Rating At 400 F - less than 1 CFM/sq ft

W Rating - Class I (See Item 4)

1. Floor or Wall Assembly - Lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Except as noted in table under Item 4, min thickness of solid concrete floor or wall assembly is 4-1/2 in. (114 mm). Floor may also be constructed of any min 6 in. (152 mm) thick UL Classified hollow core Precast Concrete Units*. When floor is constructed of hollow core precast concrete units, packing material (Item 3) and caulk fill material (Item 4) to be installed symmetrically on both sides of floor, flush with floor surface. Wall assembly may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is in solid lightweight or normal weight concrete. Floor is 32 in. (813 mm). Max diam of opening in floor constructed of hollow-core precast concrete units is 7 in. (178 mm).

See Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for names of manufacturers.

1A. Steel Sleeve (Optional, not shown) - Max 15 in. (381 mm) ID (or smaller) Schedule 10 (or heavier) steel sleeve cast or grouted into floor or wall assembly. Sleeve may extend a max of 2 in. (51 mm) above top of floor or beyond either surface of wall. Max 16 in. (406 mm) ID (or smaller) min 0.028 (0.71 mm) wall thickness (or heavier) galvanized steel sleeve cast or grouted into floor or wall assembly. Sleeve may extend a max of 1/2 in. (13 mm) beyond either surface of floor or wall.

2. Through Penetrants - One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. Max annular space between pipe, conduit or tubing and edge of through opening or sleeve is dependent on the parameters shown in Item 4. Min annular space between pipe or conduit and edge of through opening is 0 in. (0 mm) (point contact). Pipe conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used:

A. Steel Pipe - Nom 30 in. (762 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.

B. Iron Pipe - Nom 30 in. (762 mm) diam (or smaller) cast or ductile iron pipe.

C. Conduit - Nom 6 in. (152 mm) diam (or smaller) rigid steel conduit.

D. Conduit - Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing.

E. Copper - Tubing Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tube.

F. Copper Pipe - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe.

3. Packing Material - Polyethylene backer rod or nom 1 in. (25 mm) thickness of tightly-packed mineral wool batt or glass fiber insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of caulk fill material (Item 4).

4. Fill,Void or Cavity Material* - Caulk or Sealant - Applied to fill the annular space flush with top surface of floor. In wall assemblies, required caulk thickness to be installed symmetrically on both sides of wall, flush with wall surface. At point contact location between penetrant and sleeve or between penetrant and concrete, a min 1/4

in. (6 mm) diam bead of caulk shall be applied at top surface of floor and at both surfaces of wall. The hourly F Ratings and the min required caulk thicknesses are dependent upon a number of parameters, as shown in the following table:

(a)Min 2 in. (51 mm) thickness of mineral wool batt insulation required in annular space.

(b)Min 1 in. (25 mm) thickness of mineral wool batt insulation required in annular space on both sides of floor or wall assembly. Min 1 in. (25 mm) thickness of caulk to be installed flush with each surface of floor or wall assembly.

3M COMPANY - CP 25WB+ caulk or FB-3000 WT sealant. (Note: W Rating applies only when FB-3000 WT sealant is used.)

*Bearing the UL Classification Marking

Min Floor or Wall Thkns In. (mm)

Nom Pipe Tube or Conduit Diam in. (mm)

Max Annular Space in. (mm)

Min Caulk Thkns in. (mm)

F Rating Hr

2-1/2 (64) 1/2-12 (13-305) 1-3/8 (35) 1/2 (13) 2 2-1/2 (64) 1/2-12 (13-305) 3-1/4 (83) 1 (25) 2 4-1/2 (114) 1/2-6 (13-152) 1-3/8 (35) 1/4 (6) (a) 2 4-1/2 (114) 1/2-12 (13-305) 1-1/4 (32) 1/2 (13) 3 4-1/2 (114) 1/2-20 (13-508) 2 (51) 1 (25) 3 4-1/2 (114) 1/2-20 (13-508) 2 (51) 1 (25) 3 4-1/2 (114) 1/2-12 (13-305) 3-1/4 (83) 1 (25) 3 4-1/2 (114) 22-30 (558-762) 2 (51) 2 (51) 3 5-1/2 (140) 1/2-6 (13-152) 1-3/8 (35) 1 (25) (b) 4

* NOTE

THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS

FROM THE 2004 EDITION OF THE UL FIRE RESISTANCE DIRECTORY.

System No. C-AJ-1275 August 26, 2004 F Rating - 2 Hr T Rating - 0 Hr

1. Floor or Wall Assembly - Min 4-1/2 in. thick reinforced lightweight or normal weight (100-150 pcf) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 8 in.

See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.

2. Through Penetrant - One metallic pipe, conduit or tubing installed either concentrically or eccentrically within the firestop system. The annular space between pipe, conduit or tubing and periphery of opening shall be min 0 in. (point contact) to max 1-7/8 in. Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly.

The following types and sizes of metallic pipes, conduits or tubing may be used:

A. Steel Pipe - Nom 6 in. diam (or smaller) Schedule 10 (or heavier) steel pipe.

B. Iron Pipe - Nom 6 in. diam (or smaller) service weight (or heavier) cast iron soil pipe, nom 6 in diam (or smaller) or Class 50 (or heavier) ductile iron pressure pipe.

C. Conduit - Nom 6 in. diam (or smaller) steel conduit or nom 4 in. diam (or smaller) steel electrical metallic tubing.

D. Copper Tubing - Nom 6 in. diam (or smaller) Type L (or heavier) copper tubing.

E. Copper Pipe - Nom 6 in. diam (or smaller) Regular (or heavier) copper pipe.

3. Firestop System - The details of the firestop system shall be as follows:

A. Packing Material - Min 4-1/2 in. thickness of min 4 pcf mineral wool batt insulation firmly packed into opening as a permanent form. Packing material to be flush with top surface of floor or from both surfaces of wall.

B. Fill,Void or Cavity Materials* - Min 1/16 in. dry (1/8 in. wet) thickness of fill material sprayed or brushed into annular space on top surface of floor or both surfaces of wall to completely cover mineral wool and overlap a min of 1 in. onto penetrant and top surface of floor or both surfaces of wall.

3M COMPANY - FireDam™ Spray 100

*Bearing the UL Classification Mark

3A

3B

3A

3B 1

SECTION A-A

A

A

SECTION

A-A

1 44

A

A

1. Floor or Wall Assembly — Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening ) is 27-1/4 in. (692 mm).

See Concrete Block (CAZT) category in the Fire Resistance Directory for names of manufacturers.

1A. Steel Sleeve — (Optional, Not Shown) - Nom 28 in. (711 mm) diam (or smaller) Schedule 10 (or heavier) steel sleeve cast or grouted into floor or wall assembly. As an alternate, nom 28 in. (711 mm) diam (or smaller) sleeve fabricated from nom 0.028 in. (0.71 mm) thick galv steel cast or grouted into floor or wall assembly flush with floor or wall surfaces.

2. Through-Penetrant — One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. An annular space of min 0 in. (point contact) to max 3-1/4 in. (83 mm) is required within the firestop system . When optional steel sleeve is used, min annular space shall be 1/2 in. (13 mm). Pipe, conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used:

A. Steel Pipe — Nom 24 in. (610 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. When Type FB-1000 NS or FB-1003 SL sealant (see Item 4) is used, pipe diam shall not exceed nom 8 in. (203 mm).

B. Conduit — Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing or nom 6 in. (152 mm) diam (or smaller) steel conduit.

C. Copper Tubing — Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing. When Type FB-1000 NS or FB-1003 SL sealant (see Item 4) is used, tubing diam shall not exceed nom 4 in.

(102 mm).

D. Copper Pipe — Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe. When Type FB-1000 NS or FB-1003 SL sealant (see Item 4) is used, pipe diam shall not exceed nom 4 in. (102 mm).

E. Iron Pipe — Nom 24 in. (610 mm) diam (or smaller) cast or ductile iron pipe. When Type FB-1000 NS or FB-1003 SL sealant (see Item 4) is used, pipe diam shall not exceed nom 8 in. (203 mm).

3. Packing Material — Min 3 in. (76 mm) thickness of min 4 pcf (64 kg/m3) mineral wool batt insulation firmly packed into opening as a permanent form.