Kissimmee_City_Hall_Mechanical_and_Electrical_Drawings.pdf
PDF 10 MB Posted
- Attached to
- Modernization of City Hall Elevators
- Solicitation number
- RFP2025-005
- Issued by
- Polk County, Florida
About this file
The file contains mechanical and electrical engineering drawings for the Kissimmee City Hall Elevator Replacements project located at 101 N Church Street in Kissimmee, Florida. The drawings, prepared by SGM Engineering, Inc., detail comprehensive mechanical and electrical specifications for replacing existing elevator equipment, including removing old elevator components and associated equipment, installing a new sump pump in the elevator pit, and providing a new DX split system to condition the elevator machine room. The project scope involves electrical infrastructure updates, fire alarm system modifications, and electrical system reconfigurations to support the elevator modernization.
The engineering drawings specify technical requirements for electrical and mechanical systems, including panel schedules, one-line electrical diagrams, conduit and penetration details, and specific installation guidelines. The project involves replacing elevator equipment for two hydraulic passenger elevators, with work encompassing electrical reconnections, control module updates, fire alarm device replacements, and ensuring compliance with safety codes including Chapter 399 of Florida Statutes and ASME A17.3-2015 standards. The drawings provide intricate details on power distribution, fire alarm device placement, conduit routing, and system integration, indicating a comprehensive approach to modernizing the city hall's vertical transportation infrastructure.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
KISSIMMEE CITY HALL ELEVATOR REPLACEMENT
KISSIMMEE CITY HALL
KISSIMMEE, FLORIDA 34741
KISSIMMEE, FLORIDA, 34741
MECHANICAL -
ELECTRICAL -
101 N CHURCH STREET
MECHANICAL
M-001 MECHANICAL SYMBOLS AND SPECIFICATIONS
MD-201 MECHANICAL FIRST LEVEL DEMO FLOOR PLAN
M-201 MECHANICAL FIRST LEVEL FLOOR PLAN
M-701 MECHANICAL CONTROLS, SCHEDULES, AND DETAILS
ELECTRICAL
E-001 ELECTRICAL SYMBOLS AND SPECIFICATIONS
ED-201 ELECTRICAL FIRST LEVEL DEMO PARTIAL FLOOR PLANS
E-201 ELECTRICAL FIRST LEVEL PARTIAL FLOOR PLANS
E-501 ELECTRICAL PARTIAL ONE-LINE DIAGRAM
E-701 PANEL SCHEDULES
E-801 ELECTRICAL DETAILS
E-802 ELECTRICAL DETAILS
PROJECT MANAGER
Michael Holness Facilities Construction & Maintenance Manager
City of Kissimmee 104 N Alaska Ave Kissimmee, Florida 34741
407.518.2509 Office
689.287.8865 Work Cell
SGM ENGINEERING, INC.
SGM ENGINEERING, INC.
COVER
T-001 TITLE SHEET
CONSULTANTS
INDEX OF DRAWINGSPROJECT LOCATION
GENERAL SCOPE OF WORK
THE OBJECTIVES OF THIS PROJECT AS IDENTIFIED ON THE DRAWINGS, INCLUDES:
1. REMOVE OLD ELEVATOR AND ASSOCIATED EQUIPMENT AND REPLACE WITH NEW EQUIPMENT.
2. INSTALL NEW SUMP PUMP IN ELEVATOR PIT.
3. PROVIDE NEW DX SPLIT SYSTEM TO CONDITIONING ELEVATOR MACHINE ROOM.
THIS BRIEF DESCRIPTION OF THE SCOPE OF WORK IS NOT ALL INCLUSIVE AND IS COMPLIMENTED BY THE SET OF CONSTRUCTION DOCUMENTS AND SPECIFICATIONS
KISSIMMEE CITY HALL
ELEVATOR
REPLACEMENTS
N
C H
U R
C H
S T
R E
E T
K
IS
S
IM
M E
E
F L O
R
ID
A
5301 WATERFORD DISTRICT DR.
SUITE 750
MIAMI, FL 33126
TEL: 954-421-1944
FAX: 954-421-1924
CA-00006208
WWW.SGMENGINEERING.COM
COPYRIGHT © 2024 SGM ENGINEERING, INC.
ELEVATOR
REPLACEMENTS
N
C H
U R
C H
S T
R E
E T
K
IS
S
IM
M E
E
F L O
R
ID
A
5301 WATERFORD DISTRICT DR.
SUITE 750
MIAMI, FL 33126
TEL: 954-421-1944
FAX: 954-421-1924
CA-00006208
WWW.SGMENGINEERING.COM
COPYRIGHT © 2024 SGM ENGINEERING, INC.
MECHANICAL ABBREVIATIONS
DUCTWORK
MECHANICAL SYMBOLS LEGEND
MECHANICAL LEGEND
MECHANICAL GENERAL NOTES
MECHANICAL SCOPE OF WORK:
WN
WN
TV STUDIO
MEDIA COORDINATOR
MASTER CONTROL
OFFICE
ELEVATOR
EQUIP.ROOM
FIRE PUMP
OFFICE
OPEN OFFICE
TOHOPOKELIGA
CONFERENCE ROOM
MEN
WOMEN
VIDEO EDIT
JANITOR
PERMITTING
CODE ENFORCEMENT
WORK
OFFICE
OFFICE
OFFICE
OFFICE
MECHANICAL
COMMUNICATION
ELECTRICAL
CONFERENCE
OFFICE
OFFICE
OFFICE
OFFICE
LOBBY
114' - 11 1/4"
17' - 1 1/2"
67' - 11 1/4"
200' - 0"
4' - 0 1/8" 11' - 8" 4' - 0 1/4" 11' - 7 7/8" 4' - 0 1/4" 11' - 7 3/4" 3' - 10 3/8" 11' - 9 1/2" 4' - 0 1/4" 7' - 10 5/8"
4'
1/
2"
/2
106' - 0 3/4"
8"4' - 0"8" 10' - 4" 8"4' - 0"8" 10' - 4" 8"4' - 0"8" 10' - 4" 8"4' - 0"8" 10' - 4" 8"4' - 0"8" 10' - 4" 8"
113' - 8"
8" 10' - 4" 8"4' - 0"8" 10' - 4" 8"4' - 0"8" 10' - 4" 8"4' - 0"8" 10' - 4" 8" 8' - 0"
66' - 8"
4' - 5 3/4"4' - 0" 11' - 7 7/8" 4' - 0 1/4" 11' - 7 7/8" 8' - 0" 4' - 8" 7' - 2"
55' - 7 3/4"
/4
/2
7/
8"UP
ADMIN
WORK ROOM
CHILLER
YARD
T
D X-
1-
C U
-1 -1
FD(E)
FD(E)
NEW FUNNEL
FLOOR DRAIN
SP-1
GENERAL NOTES:
a. REFER TO SHEET M001 FOR
MECHANICAL SYMBOLS &
LEGEND AND GENERAL NOTES.
b. REFER TO PROJECT
SPECIFICATIONS FOR
EQUIPMENT AND INSTALLATION
REQUIREMENTS. IF THERE IS ANY
DISCREPANCY BETWEEN
SPECIFICATIONS AND DRAWINGS,
THE MOST STRINGENT
REQUIREMENT SHALL APPLY.
c. COORDINATE WORK SCHEDULE
WITH FIU PROJECT MANAGER.
DISRUPTION OF COOLING TO THE
ADJACENT SPACES IS NOT
ALLOWED.
d. DRAWINGS ARE DIAGRAMMATIC
AND REPRESENT THE GENERAL
LAYOUT OF MECHANICAL
COMPONENTS, FOR EXACT
BUILDING DIMENSIONS SEE
ARCHITECTURAL AND
STRUCTURAL DRAWINGS.
e. LOCATE EQUIPMENT SO THAT
MANUFACTURER SERVICE
CLEARANCES ARE MAINTAINED.
f. COORDINATE WITH ELECTRICAL
CONTRACTOR LOCATION OF
DISCONNECTS. DO NOT BLOCK
SERVICE CLEARANCE TO
EQUIPMENT.
g. PROVIDE NEW THERMOSTATS
AND TEMPERATURE SENSOR AS
SHOWN IN DRAWINGS
PLAN KEY NOTES:
1. PROVIDE NEW WALL MOUNTED DX-1-1,. REFER TO MECHANICAL SCHEDULE AND DETAILS
FOR FURTHER REFERENCES.
2. PROVIDE NEW INSULATED 34"Ø COPPER TYPE L CONDENSATE LINE. RUN UP TO THE
NEAREST EXISTING FLOOR DRAIN . REFER TO MECHANICAL DETAILS FOR FURTHER
REFERENCES. FIELD VERIFY LOCATION OF EXISTING FLOOR DRAIN. RUN CONDENSATE
LINE ABOVE CEILING UP TO EXISTING FLOOR DRAIN. CONFIRM CONDENSATE PIPE
MOUNTING HEIGHT ABOVE CEILING ALLOWS FOR NO LESS THAN 18 INCH PER FOOT SLOPE.
3. PROVIDE NEW REFRIGERANT LINES. RUN THOUGH THE WALL FROM THE DX UNIT TO
OUTDOOR CONDENSING UNIT. CONDENSING UNIT SHALL BE LOCATED IN THE THE CHILLER
YARD. FOLLOW THE MANUFACTURER'S RECOMMENDATIONS IN LONG LINE APPLICATION
GUIDELINE. IF THE MANUFACTURER MAKES NO RECOMMENDATIONS FOR LONG
REFRIGERANT LINE RUN, CHOOSE ANOTHER CU MANUFACTURER. EXPOSED
REFRIGERANT LINES SHALL BE PAINTED WITH UV PROTECTION COATING.
4. PROVIDE NEW THERMOSTATS AND ASSOCIATED COMPONENTS.
5. PROVIDE NEW 12" THICK CONCRETE PAD. EXTEND PAD A MINIMUM OF 6" BEYOND THE
EQUIPMENT. REFER TO SHEET M801 FOR PAD DETAILS.
6. PROVIDE NEW FUNNEL DRAIN FOR SUMP PUMPS DISCHARGE. SAW CUT FLOOR SLAB TO
INSTALL NEW FLOOR DRAIN AND NEW UNDERGROUND SANITARY PIPING.
7. ROUTE 2" SUMP PUMP DISCHARGE ABOVE CEILING TO NEW FUNNEL DRAIN IN MECHANICAL
ROOM
8. PROVIDE NEW TRACTION SUMP PUMP IN ELEVATOR SUMP PIT. PROVIDE NEW DISCHARGE
PIPING, LIBERTY OILTECTOR ALARM SYSTEM, GATE VALVE, CHECK VALVE AND ALL OTHER
ASSOCIATED COMPONENTS. SEE SHEET M-702 FOR MORE INFORMATION.
9. CONDENSING UNIT REFRIGERANT LINES SHALL RUN UNDERGROUND AFTER EXITING THE
BUILDING. RUN LINES UNDER SIDEWALK AND THROUGH THE CMU WALL INTO THE CHILLER
PLANT.
KISSIMMEE CITY HALL
ELEVATOR
REPLACEMENTS
N
C H
U R
C H
S T
R E
E T
K
IS
S
IM
M E
E F L O
R
ID
A
5301 WATERFORD DISTRICT DR.
SUITE 750
MIAMI, FL 33126
TEL: 954-421-1944
FAX: 954-421-1924
CA-00006208
WWW.SGMENGINEERING.COM
COPYRIGHT © 2024 SGM ENGINEERING, INC.
MECHANICAL PARTIAL FIRST LEVEL FLOOR PLAN
WN
REPLACEMENTS
N
C H
U R
C H
S T
R E
E T
K
IS
S
IM
M E
E
F L O
R
ID
A
5301 WATERFORD DISTRICT DR.
SUITE 750
MIAMI, FL 33126
TEL: 954-421-1944
FAX: 954-421-1924
CA-00006208
WWW.SGMENGINEERING.COM
COPYRIGHT © 2024 SGM ENGINEERING, INC.
WALL MTD MINI DUCTLESS INDOOR UNIT DETAIL
NOT TO SCALE
1 Not Scale
FLOOR RECEPTOR DETAIL2
FULL SIZE CLEAN OUT
DRAIN LINE SHALL BE AT LEAST THE
SAME SIZE AS THE NIPPLE ON EQUIPMENT
EQUIPMENT
UNION
PITCHED DOWN
TOWARD DRAIN
NOT TO SCALE
ROUTE AS SHOWN ON
PLANS OR NOTES
DRAW-THRU CONDENSATE DRAIN TRAP DETAIL
H
H = TOTAL STATIC PRESSURE +1", 2" MIN.
H/2
WITH THREADED PLUG
(HAND-TIGHTEN)
1/4" HOLE IN CAP
CONTROLS SPLIT SYSTEM (DX-1-1)1
NTS
MECHANICAL SCHEDULES2
C. UNIT MODES OF OPERATION:
1. PROVIDE FOR UNIT, THREE PRINCIPAL OPERATIONAL MODES:
OCCUPIED MODE, UNOCCUPIED MODE. AHU FIRE ALARM SHUTDOWN
MODE. ALL MODES SHALL EACH BE COMMANDED BY THE DDC.
2. OCCUPIED MODE: WHEN SCHEDULED BY THE DDC, THE SYSTEM
“OCCUPIED MODE” SHALL BE ENABLED; THE SUPPLY FAN SHALL BE
ACTIVATED AND TEMPERATURE CONTROL ALGORITHMS ENABLED.
3. UNOCCUPIED MODE: WHEN SCHEDULED OR SIGNALED BY THE DDC,
OR MANUALLY COMMANDED AT THE OPERATOR WORKSTATION,
SYSTEM OPERATION SHALL BE DISABLED. THE FAN SHALL STOP
AND CONTROL ALGORITHMS DEACTIVATED.
4. UPON RECEIVING SIGNAL FROM FIRE ALARM UNIT IS TO SHUT DOWN
AND BE MANUALLY RESTARTED.
2.3 Suggested Locations for Best Reliability
Ensure the top discharge area is unrestricted for at least five (5) feet above the unit.
Three (3) feet clearance must be provided in front of the control box (access panels) and any other side requiring service.
Min. 12” to Shrubbery
Min 5’ Unrestricted
Min 3’ Unrestricted
Access Panel
Position the outdoor unit a minimum of 3'-0” from any wall or surrounding shrubbery to ensure adequate airflow.
Outdoor unit location must be far enough away from any structure to prevent excess roof runoff water from pouring directly on the unit.
Min. 12” to Shrubbery
Min. 3'-0” to Wall
CONDENSING UNIT CLEARANCE DETAIL
NOT TO SCALE
For continuation see detail 6 and sheet M201
TYPICAL CONDENSING UNIT PAD
DETAIL
6"THICK CONCRETE PAD
(2" ABOVE GROUND
4" BELOW GROUND)
3/8" ISOLATION
2-INCH CHAMFERED LIP
AROUND EDGES
JOINT (TYP.)
#4 @ 12" O.C. EA. WAY
AT CENTER(TYP.)
6" EQUIPMENT LIMIT
NOTE:
1. PAD TO BE SIZED TO ACCOMMODATE POWER, REFRIGERANT
LINES, CONTROLS AND RECEPTACLES.
2. PROVIDE SHOP DRAWING FOR EQUIPMENT LAYOUT
INCLUDING REFRIGERANT LINES, POWER, AND CONTROLS.
3. ADD HURRICANE STRAPS.
TO SUIT EQUIP. FURN.
CONDENSING UNIT PAD DETAIL
6" TYP
TO SUIT EQUIP FURN.
3000 PSI CONCRETE WITH NO GREATER
NOT TO SCALE
MINIMUM 6"
THICK REINF.
CONCRETE PAD
SEE PLAN
FOR UNIT
LOCATION
4" SCH. 40 PVC CHASE,
INSTALL WITH LONG
RADIUS ELLS. SEAL
OPENING WITH WATER
PROOF EXPANDING
FOAM. ALSO,
REFRIGERANT PIPING
TO AIR HANDLING
UNIT
THAN 2-INCH LIP CHAMFERED EDGE AROUND
EQUIPMENT
HVAC CONDENSING UNIT
PROVIDE ALUMINUM
JACKET TO ALL EXPOSED
REFRIGERANT PIPING
NOTE:
1. SUBMIT SHOP DRAWING FOR PAD FOR APPROVAL PRIOR TO
CONSTRUCTION.
TYPICAL CONDENSING UNIT
ANCHORING DETAIL
NOTE:
1. ALL SUPPORTS, BRACKET AND FASTENERS SHALL BE
STAINLESS STEEL ON THE CU PAD.
WN
REPLACEMENTS
N
C H
U R
C H
S T
R E
E T
K
IS
S
IM
M E
E
F L O
R
ID
A
5301 WATERFORD DISTRICT DR.
SUITE 750
MIAMI, FL 33126
TEL: 954-421-1944
FAX: 954-421-1924
CA-00006208
WWW.SGMENGINEERING.COM
COPYRIGHT © 2024 SGM ENGINEERING, INC.
MANUFACTURER
SUMP PUMP SCHEDULE
GPMMARK MOTORHEAD
LIBERTY PUMPS #LEH102M2-3100SP-1 1 HP40 208V / 1PH
DISCHARGE
UNION
CHECK VALVE
GATE VALVE
WALL
CONDUIT
PUMP STOP LEVEL
PUMP START LEVEL
FLOAT
SWITCH
(TYPICAL)
ELEVATOR SUMP.
REFER TO
STRUCTURAL
DRAWINGS.
ALARM LEVEL
MOUNTING
BRACKET
ELEVATOR SHAFT
ELEVATOR
EQUIPMENT ROOM
SUBMERSIBLE SUMP
PUMP WITH
HYDROCARBON SENSOR
SUMP PUMP
CONTROL
PANEL
ELEVATOR PIT SLAB
2" FORCE MAIN
NOTE:
ROOMS MAY NOT BE
ADJACENT. PROVIDE
ADEQUATE LENGTH
CONDUIT AND WIRE
GRATE
SLAB
NOT TO SCALE
ELEVATOR SUMP PUMP DETAIL
WN
TV
TV
POWER DEVICES
SINGLE RECEPTACLE
JUNCTION BOX
DUPLEX RECEPTACLE
DISCONNECT SWITCH
DOOR BELL PUSH BUTTON
EQUIPMENT CONNECTION
SPECIAL PURPOSE RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
MOTOR STARTER
SHUNT TRIP. MTD. AT 6'-5" AFF/AFG TO TOP OF ENCLOSURE
DOOR BELL
TRANSFORMER
DUPLEX RECEPTACLE, GROUND FAULT, ABOVE COUNTER
DUPLEX RECEPTACLE, GROUND FAULT
SINGLE 250V NON-LOCKING TYPE RECEPTACLE
ABOVE COUNTER DUPLEX RECEPTACLE
DUPLEX RECEPTACLE, HALF SWITCHED
MOTOR
120/208V PANELBOARD, SURFACE MOUNT
277/480V PANELBOARD, SURFACE MOUNT
POWER/DATA POLE
PULL BOX
CEILING MOUNTED RECEPTACLE
RECESSED FLOOR RECEPTACLE
FLOOR MOUNTED JUNCTION BOX
120/208V PANELBOARD, RECESSED
277/480V PANELBOARD, RECESSED
FEEDER OR BRANCH CIRCUIT CONCEALED IN WALL,
CEILING OR FLOOR
STARTER/DISCONNECT SWITCH
GENERATOR
CLOCK
LOCKBOX
DUPLEX RECEPTACLE, GROUND FAULT
WITH CAST ALUMINUM PADLOCKABLE (1
4" HASP)
WEATHERPROOF "IN USE" COVER. TAYMAC MX3200 OR
EQUAL
DUPLEX RECEPTACLE, GROUND FAULT
LOCATE WITHIN ELECTRIC WATER COOLER PER
MANUFACTURER'S INSTRUCTIONS
DUPLEX RECEPTACLE FOR COMPUTER WORKSTATION
DUPLEX RECEPTACLE FOR TV LOCATED AT 18"AFF. LOCATE IN
COMMON BOX WITH CCTV
DUPLEX RECEPTACLE FOR TV LOCATED AT 84" AFF
UNLESS NOTED OTHERWISE.
GROUND BUS BAR
GROUND ROD WITH TEST INSPECTION WELL. SEE
SPECIFICATIONS.
QUAD RECEPTACLE, GROUND FAULT
WITH CAST ALUMINUM PADLOCKABLE (1
4" HASP) WEATHER-
PROOF "IN USE" COVER. TAYMAC MX 6200 OR EQUAL.
POWER DISTRIBUTION
MISCELLANEOUS SYMBOL LEGEND
ABBREVIATIONS
AMPERES
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
BELOW FINISHED GRADE
ELECTRIC UNIT HEATER
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
ELECTRICAL METALLIC TUBING
BELOW FINISHED CEILING
EWH
FLUOR
FA
EXIST
EXH
EQUIP
EWC
EUH
EMT
EF
FLUORESCENT
FIRE ALARM
EXHAUST
EXISTING
EXHAUST FAN
EQUIPMENT
CLG
DISC
DWG
EA
CU
CL
CAB
CKT
BFG
CEILING
CENTERLINE
DISCONNECT(ING)
DRAWING(S)
EACH
COPPER
CABINET
CIRCUIT
CONDUIT
AFG
BFC
A
AFF
NATIONAL ELECTRICAL CODE
POLYVINYL CHLORIDE
UNLESS OTHERWISE NOTED
XFMR
V
WP
VA
TEL
UON
TRANSFORMER
TELEPHONE
VOLT-AMPERES
WEATHER PROOF
VOLTS
PVC
PNL
REC
NEC
MTR
MTG
MTD
MISC
MIN
RECEPTACLE
PANEL
MINIMUM
MISCELLANEOUS
MOUNTED
MOUNTING
MOTOR
HEATING/VENTILATING/
KILO-VOLTS-AMPERES
KILO-WATT-HOURS
MOTOR CONTROL CENTERMCC
MH
MFR
MAX
LTG
kVA kWH kW kV
JB
METAL HALIDE
LIGHTING
MANUFACTURER
MAXIMUM
JUNCTION BOX
KILO-VOLTS
KILO-WATTS
HVAC
HV
INC
HP HORSEPOWER
HIGH VOLTAGE
INCANDESCENT
FLA FULL LOAD AMPERES
ABOVE FINISHED CEILINGAFC
W WATTS
TYP TYPICAL
GFCI GROUND FAULT CIRCUIT
INTERRUPTER
CURRENT TRANSFORMERSCT's
KILO-VOLTS-AMPERES REACTIVEkVAR
RGS RIGID GALVANIZED STEEL
C m METER mm MILLIMETER
AIC AMPERES INTERUPTING
CAPACITY
MCB MAIN CIRCUIT BREAKER
MCP MOTOR CIRCUIT PROTECTOR
AIR CONDITIONING
HAND-OFF-AUTOMATIC
HIGH INTENSITY DISCHARGE
HIGH PRESSURE SODIUM
HID
HOA
HPS
GND
HGT
GROUND
HEIGHT
GFP GROUND FAULT PROTECTION
VFD VARIABLE FREQUENCY DRIVE
AMERICAN WIRE GAUGEAWG
PULL STATION INSIDEPSI
EXP EXPLOSION PROOFAUDIO ENHANCEMENTAE
1R1-1,3,5
1M1-1:3:5
1R1-1
1M1-1:3
1R1-1,3
HOMERUN CONSISTING OF ONE SINGLE-PHASE, 1-POLE
CIRCUIT, SEE SPECIFICATIONS AND/OR FEEDER
SCHEDULES FOR WIRE SIZES. PANELBOARD AND CIRCUIT
DESIGNATION ARE INDICATED.
HOMERUN CONSISTING OF THREE SINGLE-PHASE CIRCUITS:
SEE SPECIFICATIONS AND/OR FEEDER SCHEDULES FOR
WIRE SIZES. PANELBOARD AND CIRCUIT DESIGNATIONS
ARE INDICATED.
HOMERUN CONSISTING OF ONE THREE-PHASE CIRCUITS:
SEE SPECIFICATIONS AND/OR FEEDER SCHEDULES FOR
WIRE SIZES. PANELBOARD AND CIRCUIT DESIGNATIONS
ARE INDICATED.
HOMERUN CONSISTING OF ONE SINGLE-PHASE, 2-P0LE
CIRCUIT: SEE SPECIFICATIONS AND/OR FEEDER
SCHEDULES FOR WIRE SIZES. PANELBOARD AND
CIRCUIT DESIGNATIONS ARE INDICATED.
HOMERUN CONSISTING OF TWO SINGLE-PHASE CIRCUITS:
SEE SPECIFICATIONS AND/OR FEEDER SCHEDULES FOR
WIRE SIZES. PANELBOARD AND CIRCUIT DESIGNATION ARE
INDICATED.
SCALE: DETAIL TITLE REFERENCE
DETAIL NUMBER
SHEET NUMBER WHERE DETAIL IS REFERENCED
ADDITIONAL SHEET REFERENCES
DETAIL NUMBER
SHEET NUMBER TO WHERE DETAIL IS REFERENCED
XX.XX
XX
WP
WP
EWC
C
QUAD RECEPTACLE, GROUND FAULT
C
POWER POLE
J
J
PB
C
ST
DB
G
ALUMINUMAL
PD
PP
T
SPD SURGE PROTECTION DEVICE, SEE SPECIFICATIONS.
SPD SURGE PROTECTION DEVICE
ECB
MMS
ENCLOSED CIRCUIT BREAKER
MANUAL MOTOR STARTER SWITCH
NOTIFICATION APPLIANCE CIRCUITNAC
SWITCH, 1 POLE, LETTER INDICATES SWITCHLEG
CONTROLLED.
SWITCH, KEYSWITCH
P
SWITCH
a
SWITCH, 2 POLE
SWITCH, 3-WAY
SWITCH, 4-WAY
K
SWITCH - PILOT LIGHT
M MOTOR RATED SWITCH
SWITCH, 3-WAY, LETTER INDICATES SWITCHLEG
CONTROLLED
SWITCH, KEYSWITCH, 3-WAY
NIGHT LIGHT, UNSWITCHEDNL
SWITCHES
SWITCH - LINE VOLTAGE TIMER, 120/277 VAC.
WATTSTOPPER TS-400 OR EQUAL.
SWITCH, EXPLOSION PROOF
QUAD RECEPTACLE FOR COMPUTER WORKSTATION
C
3a
3K
EXP
LB
VARIABLE FREQUENCY DRIVEVFD
SWITCH, LOW VOLTAGE MOMENTARYL
SWITCH, WEATHERPROOF
1. ALL ELECTRICAL WORK AND MATERIALS SHALL BE IN COMPLIANCE WITH ALL
GOVERNING CODES AND STANDARDS. THIS SHALL INCLUDE BUT NOT BE LIMITED
TO THE FOLLOWING:
A. NFPA 70 NATIONAL ELECTRICAL CODE (2020 EDITION)
B. FLORIDA BUILDING CODE (EIGHTH EDITION 2023)
C. NFPA 101 LIFE SAFETY CODE (2021EDITION)
D. NFPA 72 NATIONAL FIRE CODE (2019 EDITION)
E. FLORIDA FIRE PREVENTION CODE (EIGHTH EDITION 2023)
F. LOCAL REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION.
G. NFPA 1 NATIONAL FIRE CODE (2018 EDITION)
2. ANY CONSTRUCTION WORK DURING SCHOOL HOURS OF OPERATION MUST BE
SEQUENCED IN SUCH A WAY THAT IT WILL NOT INTERFERE WITH DAILY SCHOOL
ACTIVITIES. IF WORK IS CONDUCTED DURING SCHOOL HOURS OF OPERATIONS
THE CONTRACTOR MUST COORDINATE THE WORK WITH THE PM, A/E AND SCHOOL
REPRESENTATIVE.
3. THE CONTRACTOR RESPONSIBLE FOR THE EXECUTION OF THIS WORK SHALL
BECOME THOROUGHLY FAMILIAR WITH THE PROJECT SPECIFICATIONS BEFORE
COMMENCING ANY WORK. THE PROJECT SPECIFICATIONS AND DRAWINGS FORM
THE BASIS OF THIS CONTRACT REQUIREMENTS AND INCLUDE THE TYPE AND
GRADE OF MATERIALS TO BE INSTALLED, EQUIPMENT TO BE FURNISHED, THE
MANNER BY WHICH TO BE INSTALLED AND WHERE TO BE LOCATED. IN THE EVENT
OF A CONFLICT BETWEEN THE PROJECT SPECIFICATIONS AND DRAWINGS,
ASSUME THE MOST STRINGENT AND/OR COSTLY REQUIREMENT APPLIES.
4. THE CONTRACTOR SHALL CONSULT ALL TRADES FURNISHING EQUIPMENT AND
OBTAIN FROM THEM ALL DATA PERTAINING TO FURNISHED EQUIPMENT. THE
CONTRACTOR SHALL PROVIDE ALL CONDUIT, WIRING, DISCONNECT SWITCHES,
AND ASSOCIATED HARDWARE AS REQUIRED FOR COMPLETE AND OPERATING
SYSTEMS. COORDINATE AND INSTALL CONDUIT AND BOXES TO CLEAR EMBEDDED
DUCTS, OPENINGS AND OTHER STRUCTURAL FEATURES.
5. WHERE THE CONTRACTOR DETERMINES THAT HIS SYSTEM WILL REQUIRE
ADDITIONAL 120VAC POWER SUPPLIES IN LOCATIONS OTHER THAT AT THE FIRE
ALARM CONTROL PANEL, HE SHALL COORDINATE THESE REQUIREMENTS FOR
ADDITIONAL POWER AND ALL COSTS FOR NEW BREAKERS, CONDUIT, WIRE,
SURGE SUPPRESSORS AND ANY OTHER REQUIREMENTS SHALL BE INCLUDED IN
THIS CONTRACTORS BID.
6. EQUIPMENT LABELS AND INSTRUCTIONS REGARDING THE APPLICATION AND
INSTALLATION OF THE LISTED EQUIPMENT SHALL BE FOLLOWED TO INSURE THAT
THE EQUIPMENT IS BEING INSTALLED IN ACCORDANCE WITH THE
MANUFACTURER'S LISTING INSTRUCTIONS. THE TEMPERATURE RATING OF THE
EQUIPMENT TERMINATIONS MUST BE CAREFULLY CORRELATED WITH THE
CONDUCTOR AMPACITY TO PREVENT OVERHEATING AND PREMATURE FAILURE.
7. THE BUSINESS OPERATION OF THE BUILDING SHALL NOT BE DISRUPTED DURING
THE EXECUTION OF THIS WORK WITHOUT PRIOR NOTIFICATION AND APPROVAL BY
THE OWNER.
8. ALL EXISTING ITEMS DESIGNATED TO REMAIN, SUCH AS LIGHTING FIXTURES,
OUTLETS, SWITCHES, FIRE ALARM DEVICES, ETC. THAT ARE IN CONFLICT WITH
NEW CEILING OR WALLS, SHOULD BE RELOCATED AND LEFT IN OPERATION.
CONTRACTOR TO WALK THE SITE AND BECOME FAMILIAR WITH RELOCATION OF
EXISTING DEVICES PRIOR TO CONSTRUCTION.
9. WHERE CIRCUITS ARE INDICATED TO BE INSTALLED IN EXISTING PANELS, VERIFY
ACTUAL SPARES OR SPACES IN SAID PANELBOARDS AND USE THE SPARE
DEVICES OR FURNISH NEW CIRCUIT BREAKERS AS INDICATED ON THE DRAWINGS.
10. UNLESS SPECIFICALLY INDICATED AS EXISTING, ALL EQUIPMENT, CONDUIT, WIRE
AND ALL ACCESSORIES, REQUIRED AS PART OF THE INSTALLATION, AND USE OF
STATED EQUIPMENT, SHALL BE PROVIDED BY THE CONTRACTOR AS A PART OF
THIS PROJECT.
11. WHERE THE CONTRACTOR PROPOSES ALTERNATE SOLUTIONS, DIFFERENT
ROUTINGS OF CONDUIT, DIFFERENT LOCATIONS OF EQUIPMENT, ETC., THE
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OF THE RAMIFICATIONS OF THE
PROPOSED CHANGE THAT ARE NOT INCLUDED IN HIS PROPOSAL, BUT BECOME
APPARENT AT A LATER DATE, AND SHALL BEAR THE CONSEQUENCES OF
CORRECTING ANY AND ALL CONFLICTS, DEFICIENCIES OR OTHER PROBLEMS AT
NO INCREASE IN COST OR INCREASE IN CONSTRUCTION TIME ALLOTTED.
12. THE CONTRACTOR SHALL INCLUDE IN HIS SCOPE; (1) THE LABOR AND MATERIALS
REQUIRED FOR CREATING OPENINGS FOR CONDUIT PENETRATIONS THROUGH
WALLS, SLABS AND ROOF STRUCTURES; AS WELL AS THE SEALING OF THESE
PENETRATIONS; (2) THE ROUTING OF CONDUITS AROUND INPENETRATABLE
OBSTACLES, SUCH AS POURED-IN-PLACE BEAMS, COLUMNS, LINTELS AND
SIMILAR OBSTRUCTIONS AND; (3) THE SEALING OF PENETRATIONS OF CONDUITS
INTO WHICH NEW WIRE IS PULLED AS A PART OF THIS PROJECT, TO INCLUDE
FIREPROOFING WHERE NECESSARY.
13. IF THE INTENT OF THE ENGINEER WITH REGARD TO ANY DETAIL IS NOT CLEAR,
OR IS CAPABLE OF MORE THAN ONE INTERPRETATION, SUCH MATTERS SHALL BE
BROUGHT TO THE ENGINEER IN WRITING BEFORE THE SUBMISSION OF BIDS, AND
THE ENGINEER SHALL ISSUE CORRECTION OR CLARIFICATION IN WRITING.
OTHERWISE, NO EXTRA COSTS OR EXTENSIONS OF TIME WILL BE BE ALLOWED
FOR THE WORK OR MATERIAL THAT THE A/E WILL REQUIRE, PROVIDED THAT IT
COMES WITHIN A REASONABLE INTERPRETATION OF THE DRAWINGS AND
SPECIFICATIONS.
14. NO WIRING SHALL BE DONE PRIOR TO THE CONTRACTOR'S REVIEW OF THE
PROJECT EQUIPMENT SHOP DRAWINGS AND COORDINATION WITH THE DESIGN
DOCUMENTS. ANY DISCREPANCIES SHALL BE BROUGHT TO THE
ARCHITECT/ENGINEER ATTENTION FOR FINAL RESOLUTION. WORK THAT HAS TO
BE REPLACED DUE TO LACK OF PROPER SHOP DRAWINGS CO-ORDINATION SHALL
BE DONE AT CONTRACTORS EXPENSE
15. EXISTING SYSTEMS SHOWN ARE BASED ON VISUAL INSPECTION AND EXISTING
DRAWINGS, BUT THEY MAY NOT REFLECT THE ACTUAL CONDITIONS IN EVERY
CASE. THE CONTRACTOR SHALL INSPECT THE SITE AND EXAMINE THE WORK
BEFORE SUBMITTING HIS PROPOSAL. THE CONTRACTOR SHALL NOTE THE
LOCATION OF EXISTING FACILITIES, THE EXTENT OF HIS WORK, AND
INTERFERENCE BY OTHER TRADES WITH HIS WORK. ANY DISCREPANCIES
SHOULD BE DISCUSSED WITH THE ENGINEER. SUBMISSION OF A PROPOSAL WILL
BE CONSTRUED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN MADE AND
LATER CLAIMS FOR LABOR, EQUIPMENT OR MATERIALS REQUIRED BECAUSE OF
DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED.
16. FURNISH AND INSTALL EQUIPMENT DISCONNECT SWITCHES IN STRICT
COMPLIANCE WITH APPLICABLE CODE REQUIREMENTS.
17. FIRESTOP ALL PENETRATIONS (MADE BY THIS CONTRACTOR) THROUGH
FIRE-RATED WALLS, FLOORS AND CEILINGS. THIS CONTRACTOR SHALL BE
RESPONSIBLE FOR ALL CUTTING AND PATCHING RELATED TO THIS
CONTRACTOR'S WORK. PATCH ALL UNUSED OPENINGS (CREATED BY THIS
CONTRACTOR) TO MATCH SURROUNDING CONDITIONS.
18. ABSOLUTELY NO SPLICES WILL BE ALLOWED IN ANY SYSTEMS WIRES. PROVIDE
FULL LENGTH WIRING BETWEEN DEVICES AND TERMINALS.
19. HEIGHTS REQUIRED BY EQUIPMENT SUPPLIERS TAKE PRECEDENCE OVER ALL
OTHER DIMENSIONS.
20. ITEMS IN TILE SURFACES SHALL BE INSTALLED AS CLOSE AS POSSIBLE TO THE
DIMENSION GIVEN AND SHALL BE HORIZONTALLY AND VERTICALLY CENTERED
AND ALIGNED WITH THE TILE JOINTS.
21. ALL FEEDERS ARE TO HAVE LESS THAN 2% TOTAL VOLTAGE DROP AND ALL
BRANCH CIRCUITS SHALL HAVE LESS THAN 3% VOLTAGE DROP. WIRING TO
RECEPTACLES SHALL BE #12 THWN MINIMUM.
22. EXCEPT WHERE SPECIFICALLY NOTED OTHERWISE, THE CONTRACTOR SHALL
PROVIDE NEW CONDUIT FOR ALL CONDUCTORS THAT ARE INSTALLED AS A PART
OF THIS PROJECT. INSULATED PLASTIC BUSHINGS ARE TO BE PROVIDED ON ALL
CONDUIT STUB-OUTS AND STUB-UPS.
23. THE INSTALLATION OF ALL DEVICES, INCLUDING MOUNTING HEIGHTS, SHALL BE
FULLY ADA AND NFPA COMPLIANT.
24. THE CONTRACTOR SHALL VERIFY THE EXACT DIRECTION OF ALL DOOR SWINGS
PRIOR TO ROUGH-IN OF BOXES MOUNTED IN WALLS.
25. THE CONTRACTOR SHALL THOROUGHLY CLEAN ALL EQUIPMENT TO BE
COMPLETELY FREE OF INTERNAL DEBRIS AND EXTERIOR PAINT, MARKS, DIRT
AND ALL SCRATCHES SHALL BE TOUCHED UP.
26. ALL EMPTY/SPARE CONDUITS SHALL HAVE PULL STRINGS WITH LABELING TAGS
AT EACH END.
27. ALL RACEWAYS SHALL HAVE A GREEN INSULATED COPPER
EQUIPMENT-GROUNDING CONDUCTOR.
28. EXPANSION FITTINGS SHALL BE PROVIDED IN EXPOSED CONDUIT RUNS OVER 100
FEET, AT BUILDING EXPANSION JOINTS AND IN CONDUIT RUNS BETWEEN
BUILDINGS.
29. MOTOR SIZES AND LOCATIONS SHOWN ON THE DRAWINGS ARE BASED ON
INFORMATION OBTAINED DURING DESIGN. VERIFY THE ACTUAL LOCATIONS AND
PROVIDE WIRING AND PROTECTION OF PROPER SIZES AS REQUIRED. WIRE
MOTORS FOR PROPER DIRECTION OF ROTATION AND CHECK ROTATION AT
START-UP.
30. ALL BRANCH CIRCUITS AND FEEDERS SHALL BE PROVIDE WITH SEPARATE
GROUNDING CONDUCTORS.
31. AIR HANDLERS - AHU'S MUST BE INTERFACE WITH EMS AND FIRE ALARM. ALL NEW
AND EXISTING AIR HANDLERS AND FANS SHALL SHUTDOWN UPON ACTIVATION OF
THE FIRE ALARM SYSTEM. COMPLY WITH NFPA 90A.
32. WITHIN 30 DAYS OF ACCEPTANCE OF PROJECT, COMPLETION RECORD DRAWINGS,
OPERATION AND MAINTENANCE MANUALS SHALL BE PROVIDED BY THE
CONTRACTOR TO THE OWNER IN ACCORDANCE WITH FBC C405.7.4.
33. VERIFY AND CONFIRM ALL WORKING CLEARANCES ARE MAINTAINED FOR ALL
NEW, RENOVATED AND RELOCATED ELECTRICAL EQUIPMENT IN COMPLIANCE
WITH NEC TABLE 110.26(A).
34. CONTRACTOR SHALL REPLACE LIGHTING FIXTURES DAMAGED. IT SHALL ALSO
RELOCATE ANY EXISTING LIGHT FIXTURE THAT IS IN THE WAY OF PROPOSED NEW
DUCT WORK.
35. CONTRACTOR TO NOTIFY OWNER PRIOR TO DISCONNECT ANY ALARM DEVICE.
36. PROVIDE TYPED PANEL DIRECTORIES FOR ALL PANELBOARDS AFFECTED BY
DEMOLITION OR NEW WORK. DIRECTORIES SHALL REFLECT TRUE PROJECT
AS-BUILT CONDITIONS FOR ALL BRANCH CIRCUITS. DIRECTORIES SHALL INCLUDE
WHERE EACH PANEL IS FED FROM, AND EACH BRANCH CIRCUIT LOAD
DESCRIPTION SHALL INCLUDE THE ROOM NUMBERS FOR EACH LOAD SERVED.
ROOM NUMBERS SHALL BE BASED ON ACTUAL ROOM SIGNAGE INSTALLED IN
FIELD. BREAKERS IN EXISTING PANELS NO LONGER USE SHALL BE LABELED
“SPARE” AND TURNED OFF.
37. PROVIDE DEMO/ REMOVAL OF ALL ABANDONED CONDUIT, BOXES, DEVICES,
CABINETS, AND THE REPAIR OF ALL HOLES IN WALLS TO MAINTAIN FIRE RATINGS
INCLUDING PAINTING TO MATCH EXISTING CONDITIONS..
38. WHERE EXISTING WIRING IS CALLED TO BE REUSED, THE FEEDER AND
GROUNDING SYSTEM SHALL BE TESTED FOR PROPER OPERATION AND
PERFORMANCE.
39. PRIOR TO ENERGIZING ANY NEW ELECTRICAL EQUIPMENT, AN INDEPENDENT
TESTING FIRM SHALL PERFORM VISUAL AND MECHANICAL INSPECTIONS AND
ELECTRICAL TESTS ON ALL NEWLY INSTALLED EQUIPMENT SUPPLIED WITHIN THIS
CONTRACT. THE CONTRACTOR SHALL PROVIDE A COMPLETE TORQUE REPORT
FOR ALL WIRE TERMINATIONS TO NEWLY INSTALLED OR RELOCATED EQUIPMENT.
ALL INSPECTIONS AND TEST SHALL BE COMPLETED BY AN INDEPENDENT TESTING
ORGANIZATION CERTIFIED BY THE INTERNATIONAL ELECTRICAL TESTING
ASSOCIATION (NETA) OR (NICET).
GENERAL NOTES
ELECTRICAL SCOPE OF WORK
1. PROVIDE RENOVATED POWER INFRASTRUCTURE AND
CONNECTIONS TO EXISTING ELEVATORS AND ASSOCIATED
EQUIPMENT. THIS IS NOT ALL INCLUSIVE OF THE SCOPE OF
WORK. REFER TO CONTRACT DOCUMENTS FOR FURTHER
CLARIFICATION.
E200
TITLE
E200
135° HEAT DETECTOR
SMOKE DETECTOR
FIRE ALARM SYSTEM
FIRE ALARM CONTROL PANEL "FACP"
CONTROL MODULE RELAY
VAPORTIGHT, LED, WET LOCATION,
GENERAL PURPOSE WALL MOUNTED
LITHONIA
OLVTWM-4000K-MVOLT 120/277V 48W LEDA
DESIGN SELECTION VOLTS LAMPS/FIXTURE
LIGHTING FIXTURE SCHEDULE
TYPE DESCRIPTION
LIGHTING FIXTURE NOTES:
a. FINAL FIXTURE FINISHES SHALL BE
SELECTED DURING SUBMITTAL
PROCESS BY ARCHITECT FROM
EXTENDED STANDARD COLOR
CHART FOR EACH FIXTURE.
b. ALL FIXTURES, WHETHER STANDARD
OR NOT, REQUIRE LISTING BY A
NATIONALLY RECOGNIZED TESTING
LABORATORY.
c. ALL FIXTURE NOTED AS
EMERGENCY FIXTURES SHALL
SUPPLY A MINIMUM OF 90MIN
BACK-UP BATTERY POWER.
d. WHEN FIXTURE MODEL DIFFERS
FROM FIXTURE DESCRIPTION, THEN
THE FIXTURE DESCRIPTION SHALL
GOVERN.
LIGHTING FIXTURES
CEILING MOUNTED RECESSED, DOWN LIGHT
SURFACE MOUNTED LIGHTING FIXTURE
CEILING MOUNTED RECESSED, EMERGENCY DOWN LIGHT
WALL MOUNTED SCONCE FIXTURE, BATTERY/EMERGENCY
SINGLE FACE EXIT LIGHT FIXTURE ARROW
INDICATES DIRECTION OF EGRESS
DOUBLE FACE EXIT LIGHT FIXTURE ARROW
INDICATES DIRECTION OF EGRESS
4' FLUORESCENT STRIP FIXTURE
4' FLUORESCENT STRIP FIXTURE, BATTERY/EMERGENCY
4' FLUORESCENT STRIP FIXTURE, WALL MOUNTED
4' FLUORESCENT STRIP FIXTURE, WALL MOUNTED,
BATTERY/EMERGENCY
NOTES
VAPORTIGHT, LED, WET LOCATION,
1X4 PENDANT MOUNTED
LITHONIA
CSVT-4000LM-MVOLT-40K-80
CRI
120/277V 48W LEDBE ON EMERGENCY
CIRCUIT
KISSIMMEE CITY HALL
ELEVATOR
REPLACEMENTS
N
C H
U R
C H
S T
R E
E T
K
IS
S
IM
M E
E
F L O
R
ID
A
5301 WATERFORD DISTRICT DR.
SUITE 750
MIAMI, FL 33126
TEL: 954-421-1944
FAX: 954-421-1924
CA-00006208
WWW.SGMENGINEERING.COM
COPYRIGHT © 2024 SGM ENGINEERING, INC.
JA
JA
OFFICE
ELEVATOR
EQUIP.ROOM
FIRE PUMP
OPEN OFFICE
TOHOPOKELIGA
CONFERENCE ROOM
MEN
WOMEN
VIDEO EDIT
JANITOR
PERMITTING
CONFERENCE
OFFICE
LOBBYADMIN
1L1-91,93,95
ELEVATOR
#2
ELEVATOR
#1
ELEVATOR
#1 & #2 CAB
LIGHTING
1HE1-5
1HM1-56:58:60
1HE1-7:9:11
1LE1-15,173
GENERAL NOTES:
a. REFER TO SYMBOL LEGEND ON SHEET E001.
b. REFER TO SPECIFICATIONS.
c. REFER TO EQUIPMENT SCHEDULES FOR DISCONNECT, CONDUIT AND WIRE SIZES.
d. ALL FEEDERS ARE TO HAVE LESS THAN 2% TOTAL
VOLTAGE DROP AND ALL BRANCH CIRCUITS SHALL HAVE
LESS THAN 3% VOLTAGE DROP.
e. EXISTING EQUIPMENT AND SYSTEMS SHOWN ARE BASED
ON VISUAL INSPECTION AND EXISTING DRAWINGS. THE
CONTRACTOR SHALL INSPECT THE SITE AND EXAMINE
THE SYSTEMS BEFORE PERFORMING ANY WORK.
SOURCES OF VARIOUS BRANCH CIRCUITS COULD NOT BE
CONFIRMED BY VISUAL INSPECTION. THE CONTRACTOR
SHALL FIELD VERIFY (TRACE) "EXISTING TO REMAIN"
BRANCH CIRCUITS AND FEEDERS (CONDUIT AND WIRE)
TO MAKE SAFE (LOCKOUT-TAGOUT) BEFORE ANY
DEMOLITION OR NEW WORK.
f. ALL SYMBOLS SHOWN IN " LIGHT" COLOR INDICATE
EXISTING TO REMAIN. SYMBOLS SHOWN "DARK"
INDICATES EQUIPMENT BEING MODIFIED, OR NEW.
g. ENSURE PROPER WORKING CLEARANCE FOR ALL
ELECTRICAL DEVICES AND EQUIPMENT.
h. ALL POWER AND CONTROL CONDUITS OUTSIDE OF THE
MACHINE ROOM AND ELEVATOR PIT SHALL BE
CONCEALED.
i. CONTRACTOR TO PROVIDE TRACING SERVICES PRIOR
TO ANY WORK TO CONFIRM EXISTING CIRCUITS.
g. EXISTING FIRE ALARM SYSTEM SHALL BE TESTED PRIOR
COMMENCEMENT OF WORK. CONTRACTOR TO NOTIFY
THE OWNER AND A/E OF ANY EXISTING ALARM,
SUPERVISORY OR TROUBLE CONDITION IN THE ALARM
PANEL PRIOR TO COMMENCING WORK ON THE FIRE
ALARM SYSTEM. ALARM PANEL SHALL BE CLEARED OF
ALL TROUBLES BEFORE COMMENCING WORK.
i. PROVIDE, INSTALL AND TERMINATE ALL FIRE ALARM
EQUIPMENT INCLUDING, BUT NOT LIMITED TO
RACEWAYS, WIRE CABLE, MODULES, RELAYS, ETC. MAKE
FINAL CONNECTIONS FOR A FULLY FUNCTIONAL SYSTEM.
PLAN KEY NOTES:
1. DISCONNECT AND REMOVE EXISTING LIGHT FIXTURE
AND ASSOCIATED LIGHTING SWITCH IN ELEVATOR PIT.
CONTRACTOR TO PROTECT THE EXISTING CIRCUIT,
FOR USE IN RENOVATION.
2. EXISTING WEATHER PROOF RECEPTACLE TO BE
REPLACED WITH NEW. CONTRACTOR TO PROTECT THE
EXISTING CIRCUIT, FOR USE IN RENOVATION.
3. EXISTING FIRE ALARM DEVICES TO BE REPLACED WITH
NEW.
4. EXISTING ELEVATOR MOTOR TO BE REPLACED WITH
NEW LIKE AND KIND ELEVATOR MOTOR. CONTRACTOR
TO DISCONNECT EXISTING FEEDER AND PROTECT
WHILE OLD EQUIPMENT IS REPLACED.
5. EXISTING CAB LIGHTING DISCONNECTs TO BE
REPLACED WITH NEW IN-KIND. CONTRACTOR TO
PROTECT EXISTING CIRCUIT AND COMPONENTS.
6. EXISTING ELEVATOR CONTROL MODULE AND RECALL
CONNECTIONS TO BE TEMPORARILY DISCONNECTED
WHILE NEW WORK IS BEING CONDUCTED.
CONTRACTOR TO PROTECT ALL COMPONENTS FOR
USE IN NEW ELEVATOR MOTORS.
7. EXISTING PENDANT MOUNT LIGHT FIXTURES TO BE
REPLACED WITH NEW IN SAME LOCATION.
CODE ENFORCEMENT
COMMUNICATION
ELECTRICAL
PNL
HC1
PNL
1HQ1
PNL
1HE1
PNL
EDP
PNL
1H1
PNL
MDP
PNL
1HM1
PNL
1LE1
PNL
1LC1
FACP
FATC-1
PNL
1L1 (3 SECTIONS)
KISSIMMEE CITY HALL
ELEVATOR
REPLACEMENTS
N
C H
U R
C H
S T
R E
E T
K
IS
S
IM
M E
E
F L O
R
ID
A
5301 WATERFORD DISTRICT DR.
SUITE 750
MIAMI, FL 33126
TEL: 954-421-1944
FAX: 954-421-1924
CA-00006208
WWW.SGMENGINEERING.COM
COPYRIGHT © 2024 SGM ENGINEERING, INC.
ELECTRICAL FIRST LEVEL DEMO PARTIAL FLOOR PLAN
ENLARGED ELECTRICAL RM. 106
JA
GENERAL NOTES:
a. REFER TO SYMBOL LEGEND ON SHEET E001.
b. REFER TO SPECIFICATIONS.
c. REFER TO EQUIPMENT SCHEDULES FOR DISCONNECT, CONDUIT AND WIRE SIZES.
d. ALL FEEDERS ARE TO HAVE LESS THAN 2% TOTAL
VOLTAGE DROP AND ALL BRANCH CIRCUITS SHALL HAVE
LESS THAN 3% VOLTAGE DROP.
e. EXISTING EQUIPMENT AND SYSTEMS SHOWN ARE BASED
ON VISUAL INSPECTION AND EXISTING DRAWINGS. THE
CONTRACTOR SHALL INSPECT THE SITE AND EXAMINE
THE SYSTEMS BEFORE PERFORMING ANY WORK.
SOURCES OF VARIOUS BRANCH CIRCUITS COULD NOT BE
CONFIRMED BY VISUAL INSPECTION. THE CONTRACTOR
SHALL FIELD VERIFY (TRACE) "EXISTING TO REMAIN"
BRANCH CIRCUITS AND FEEDERS (CONDUIT AND WIRE)
TO MAKE SAFE (LOCKOUT-TAGOUT) BEFORE ANY
DEMOLITION OR NEW WORK.
f. ALL SYMBOLS SHOWN IN " LIGHT" COLOR INDICATE
EXISTING TO REMAIN. SYMBOLS SHOWN "DARK"
INDICATES EQUIPMENT BEING MODIFIED, OR NEW.
g. ENSURE PROPER WORKING CLEARANCE FOR ALL
ELECTRICAL DEVICES AND EQUIPMENT.
h. ALL POWER AND CONTROL CONDUITS OUTSIDE OF THE
MACHINE ROOM AND ELEVATOR PIT SHALL BE
CONCEALED.
i. CONTRACTOR TO PROVIDE TRACING SERVICES PRIOR
TO ANY WORK TO CONFIRM EXISTING CIRCUITS.
g. EXISTING FIRE ALARM SYSTEM SHALL BE TESTED PRIOR
COMMENCEMENT OF WORK. CONTRACTOR TO NOTIFY
THE OWNER AND A/E OF ANY EXISTING ALARM,
SUPERVISORY OR TROUBLE CONDITION IN THE ALARM
PANEL PRIOR TO COMMENCING WORK ON THE FIRE
ALARM SYSTEM. ALARM PANEL SHALL BE CLEARED OF
ALL TROUBLES BEFORE COMMENCING WORK.
i. PROVIDE, INSTALL AND TERMINATE ALL FIRE ALARM
EQUIPMENT INCLUDING, BUT NOT LIMITED TO
RACEWAYS, WIRE CABLE, MODULES, RELAYS, ETC. MAKE
FINAL CONNECTIONS FOR A FULLY FUNCTIONAL SYSTEM.
PLAN KEY NOTES:
1. PROVIDE CONNECTION TO NEW LIGHT FIXTURES AND
SWITCHES. PROVIDE SWITCH IN LOCATION THAT IS
ACCESSIBLE THROUGH PIT. COORDINATE EXACT
LOCATION OF ALL FIXTURES WITH ELEVATOR INSTALLER.
2. PROVIDE NEW 30A DISCONNECT SWITCH AND RE-USE
EXISTING CONDUCTORS AND CONDUIT TO RE-CONNECT
ELEVATOR CAB LIGHTS.
3. PROVIDE NEW DISCONNECT SWITCH FOR ELEVATOR
EQUIPMENT. PROVIDE NEW ENCLOSED CIRCUIT
BREAKER. REFER TO EQUIPMENT FEEDER SCHEDULE
AND COORDINATE WITH ELEVATOR MANUFACTURER.
4. PROVIDE NEW GFI WEATHER PROOF RECEPTACLE.
RE-USE EXISTING BRANCH CIRCUIT AND PROVIDE NEW
BACK BOX, CONDUIT AND WIRE AS REQUIRED.
5. CONTROL MODULES TO BE RE-CONNECTED TO NEW
ELEVATOR CONTROLLERS AND MOTORS.
6. PROVIDE NEW HEAT AND SMOKE DETECTORS IN
ELEVATOR SHAFT AND NEW SMOKE DETECTORS IN
ELEVATOR MACHINE ROOM AND ELEVATOR LOBBIES.
PROVIDE NEW J-BOX ROUGHED IN WALL INCLUDING ALL
WIRING, CONDUIT AND CONNECTIONS AND CONNECT TO
EXISTING FIRE ALARM SYSTEM..
7. PROVIDE NEW DESIGNATED AND ALTERNATE LEVEL
RECALL RELAYS FOR BUILDING ELEVATOR RECALL.
8. ELEVATOR EQUIPMENT TO BE PROVIDED WITH
BATTERIES. POWER TRANSFER TO BATTERIES WILL
OCCUR WITHIN 60 SECONDS OF LOSS OF NORMAL
POWER.
9. PROVIDE NEW FEED FROM DISCONNECT SWITCH TO
ELEVATOR UNIT.
10. PROVIDE NEW FEEDER CONNECTION (CONDUIT AND
WIRE) TO NEW MECHANICAL EQUIPMENT IN NEW
LOCATION.
11. PROVIDE FIRE FIGHTER EMERGENCY OPERATION FOR
PHASE I ELEVATOR RECALL AS REQUIRED BY NFPA
101-9.4.3.2.
12. NEW SUMP PUMP TO BE PROVIDED, WITH NEW FEEDER
(CONDUIT AND WIRE) THEN CONNECTED TO EXISTING
SUMP PUMP CONTROLS AND EMERGENCY POWER.CODE ENFORCEMENT
COMMUNICATION
ELECTRICAL
106PNL
HC1
PNL
1HQ1
PNL
1HE1
PNL
EDP
PNL
1L1 (3 SECTIONS)
PNL
1H1
PNL
MDP
PNL
1HM1
PNL
1LE1
PNL
1LC1
FACP
FATC-1
PERMITTING
CONFERENCE
OFFICE
LOBBYADMIN
1L1-91,93,95
K
A
A
A
A
SP-1
1HE1-16:18
OFFICE
ELEVATOR
EQUIP.ROOM
FIRE PUMP
VIDEO EDIT
CHILLER
YARD
ELEVATOR
#2
ELEVATOR
#1
ELEVATOR
#1 & #2 CAB
LIGHTING
1HE1-5
1HM1-56:58:60
1HE1-7:9:11
1LE1-15,17
3 8
DX-1-1
CU-1-1
BE
BE
1HE1-8:10
1L1-274
1HE1-12:14
KISSIMMEE CITY HALL
ELEVATOR
REPLACEMENTS
N
C H
U R
C H
S T
R E
E T
K
IS
S
IM
M E
E
F L O
R
ID
A
5301 WATERFORD DISTRICT DR.
SUITE 750
MIAMI, FL 33126
TEL: 954-421-1944
FAX: 954-421-1924
CA-00006208
WWW.SGMENGINEERING.COM
COPYRIGHT © 2024 SGM ENGINEERING, INC.
ENLARGED ELECTRICAL RM. 106
ENLARGED ELEVATOR SHAFTS
ENLARGED ELEVATOR EQUIPMENT RM.
JA
REPLACEMENTS
N
C H
U R
C H
S T
R E
E T
K
IS
S
IM
M E
E
F L O
R
ID
A
5301 WATERFORD DISTRICT DR.
SUITE 750
MIAMI, FL 33126
TEL: 954-421-1944
FAX: 954-421-1924
CA-00006208
WWW.SGMENGINEERING.COM
COPYRIGHT © 2024 SGM ENGINEERING, INC.
G
480/277V, 3Ø, 4W
500KVA GENERATOR
ST
BOND NEUTRAL TO GROUND
AT GENERATOR
FIRE PUMP
CONTROLLER
ATS-C
150A, 4P
GENERAL NOTES:
a. REFER TO SYMBOL LEGEND AND NOTES ON SHEET E-001.
b. REFER TO BOOK SPECIFICATIONS.
c. REFER TO PANEL FEEDER SCHEDULE ON THIS SHEET FOR
PANEL FEEDER CONDUIT AND WIRE SIZES.
d. REFER TO EQUIPMENT SCHEDULES ON THIS SHEET FOR
DISCONNECT, CONDUIT AND WIRE SIZES.
e. ALL FEEDERS ARE TO HAVE LESS THAN 2% TOTAL
VOLTAGE DROP AND ALL BRANCH CIRCUITS SHALL HAVE
LESS THAN 3% VOLTAGE DROP.
f. ALL SYMBOLS SHOWN IN "LIGHT" COLOR INDICATE
EXISTING TO REMAIN; NO WORK REQUIRED UNLESS NOTED
OTHERWISE.
g. ALL SYMBOLS SHOWN IN "DARK" COLOR INDICATE EXISTING
EQUIPMENT TO BE MODIFIED, UNLESS NOTED OTHERWISE.
h. FIELD VERIFY EXISTING CONDITIONS PRIOR TO
DEMOLITION.
i. COORDINATE WORK WITH ALL OTHER TRADES BEFORE
ANY ROUGH-INS.
PLAN KEY NOTES: #
1. PROVIDE NEW CIRCUIT BREAKER TO PANEL SHOWN.
REFER TO PANEL SCHEDULE ON SHEETS E701 FOR MORE
DETAILS.
2. REFER TO EQUIPMENT FEEDER SCHEDULE FOR MORE
INFORMATION ON NEW FEEDER SIZES FOR ELEVATOR.
1 1 1 1 1
ELECTRICAL PARTIAL ONE-LINE DIAGRAM
JA
JA
JA
JA
REPLACEMENTS
N
C H
U R
C H
S T
R E
E T
K
IS
S
IM
M E
E
F L O
R
ID
A
5301 WATERFORD DISTRICT DR.
SUITE 750
MIAMI, FL 33126
TEL: 954-421-1944
FAX: 954-421-1924
CA-00006208
WWW.SGMENGINEERING.COM
COPYRIGHT © 2024 SGM ENGINEERING, INC.
JA
JA
JA
JA
REPLACEMENTS
N
C H
U R
C H
S T
R E
E T
K
IS
S
IM
M E
E
F L O
R
ID
A
5301 WATERFORD DISTRICT DR.
SUITE 750
MIAMI, FL 33126
TEL: 954-421-1944
FAX: 954-421-1924
CA-00006208
WWW.SGMENGINEERING.COM
COPYRIGHT © 2024 SGM ENGINEERING, INC.
18"
46" 46"
3" DUPLEX
RECEPTACLE FIRE ALARM
PULL BOX
TYPICAL
DOOR
CABINET- SEE
ARCH. PLANS
FOR SIZE
DUPLEX
RECEPTACLE
FAN
SWITCH
LIGHT
SWITCHCOMPUTER
DATA OUTLET
6"
18"
LIGHT
SWITCH
SEALANT
PENETRATION WITH
SEAL OUTSIDE OF PYRO-PAC MODEL FS.
(ACCESSIBLE FROM ONLY
LINK-SEAL TYPE
WALL SLEEVE.
MODEL-WS.
ONE SIDE)
SEAL OUTSIDE OF
SEALANT
JOINT WITH MASTIC
INTERIOR FACE OF CONCRETE
LINK-SEAL TYPE
WALL PENETRATION.
SEAL MODEL-LS.
WATER STOP AND
ANCHOR COLLAR
FOUNDATION WALL
PIPE SLEEVE
CONCRETE
FLOOR SLAB
RISER CLAMP
CONDUIT
UL APPROVED
FIRE-STOPPING SYSTEM.
1/4" CONCRETE ANCHOR & 1/4" BOLT (UP TO 1 - 1/2" EMT)
3/8" CONCRETE ANCHOR & 3/8" BOLT (2" - 4" EMT)
1/4" ROD FOR 3/4" TO 1 - 1/2" EMT CONDUIT
3/8" ROD FOR 2" TO 4" EMT CONDUIT
CONDUIT CLAMP
12 GA. GALV. STEEL
ELECTRICAL METAL TUBING (EMT)
46"
FIRE
PULL DOWN
FIRE ALARM
A/C SUPPLY
OR RETURN
DIFFUSER
CEILING
MANUAL
PULL
STATION
FIRE
PHONE
JACK
FINISHED FLOOR
NFPA 72 AUDIBLE ONLY
APPLIANCE 6" MIN BELOW
FINISHED CEILINGFIREFIRE
NO
LE
SS
TH
AN
" A
ND
NO
GR
EA
TE
R T
HA
N 9 6" A
.F.F
OR
6"
BE
LO
W
CE
ILIN
G, WH
ICH
EV
ER
IS L
OW
ER
, TO
BO
TT
OM
OF
VIS
UA
L L
EN
S
AUDIBLE/VISUAL &
VISUAL ONLY
APPLIANCES.
SYNCHRONIZE MORE
THAN TWO APPLIANCES
N ANY FIELD OF VIEW.
" A
.F .F
. T O
TO
P
OF
B
OX
" T
O
TO
P
OF
B
AC
K
BO
X
AU
DI
BL
E
ON
LY
D
EV
IC
ES
" M
I.
AB
OV
E
FI
NI
SH
ED
F
LO
OR
FOR CEILING HEIGHTS
LESS THAN 86" THE VISUAL
LENS MOUNTING HEIGHT SHALL
BE WITHIN 6" OF THE CEILING.
NFPA 72 AUDIBLE ONLY APPLIANCE
6" MIN BELOW FINISHED CEILING 5' MIN.
SMOKE/HEAT
DETECTORS NEVER HERE
CEILING MOUNTED
SMOKE/HEAT DETECTORS
WALL MOUNTED
SMOKE/HEAT DETECTORS
FINISHED WALL
4"
4"
" M
AX
5' MAX. TO EXIT DOOR
MAGNETIC
DOOR
HOLDER
DOOR
WIDTH
LESS 3"
5"
ANNUNCIATOR PANEL
ELEVATOR CONTROL
GAS
SOLENOID
VALVE
NOTIFICATION DEVICE
SLC
CONTROL
MODULE
AHU
SHUTDOWN
RELAY
FIRE ALARM
TERMINAL
CABINET/
NAC PANEL
TYPICAL
#6 COPPER TO LOCAL SYSTEMS
GROUND BUSBAR IN IDF
120V POWER FOR NFPA-72
(PROVIDE SURGE PROTECTION
AT EACH 120V INPUT) (TYPICAL)
DETAIL NOTES:
ALL FIRE ALARM WIRING SHALL BE
RUN IN 3/4" CONDUIT MINIMUM
TO NEXT
DEVICE
TO NEXT
DEVICE
INITIATING DEVICE
TO NEXT
DEVICE
SEALANT
PENETRATION WITH
SEAL OUTSIDE OF PYRO-PAC MODEL FS.
(ACCESSIBLE FROM ONLY
LINK-SEAL TYPE
WALL SLEEVE.
MODEL-WS.
ONE SIDE)
SEAL OUTSIDE OF
SEALANT
JOINT WITH MASTIC
INTERIOR FACE OF CONCRETE
LINK-SEAL TYPE
WALL PENETRATION.
SEAL MODEL-LS.
WATER STOP AND
ANCHOR COLLAR
FOUNDATION WALL
2" 2"
USE TWO (2) INTERMEDIATE HANGER RODS FOR HANGERS OVER 37"
USE ONE (1) INTERMEDIATE HANGER ROD FOR HANGERS 25" TO 36"
12 GA. GALV. STEEL
CHANNEL CONDUIT CLAMP
3/8" ROD
CONDUIT HANGER
1 1/2" X 1 1/2" 12 GA. GALV. STEEL CHANNEL
REFER TO CONDUIT SPACING SCHEDULE
ELECTRICAL METAL TUBING (EMT
FOR EMT SPACING REQUIRMENTS
(TYPICAL)
OR
HANG FROM BEAM CLAMP OR ROOF JOIST AS REQUIRED.
JA
REPLACEMENTS
N
C H
U R
C H
S T
R E
E T
K
IS
S
IM
M E
E
F L O
R
ID
A
5301 WATERFORD DISTRICT DR.
SUITE 750
MIAMI, FL 33126
TEL: 954-421-1944
FAX: 954-421-1924
CA-00006208
WWW.SGMENGINEERING.COM
COPYRIGHT © 2024 SGM ENGINEERING, INC.
* NOTE
THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS
FROM THE 2004 EDITION OF THE UL FIRE RESISTANCE DIRECTORY.
System No.W-L-1001 June 15, 2005
F Ratings - 1, 2, 3 and 4 Hr (See Items 2 and 3) T Ratings - 0, 1, 2, 3, and 4 Hr (See Item 3) L Rating At Ambient - less than 1 CFM/sq ft L Rating At 400 F - less than 1 CFM/sq ft
1. Wall Assembly - The 1, 2, 3 or 4 hr fire-rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner described in the individual U300 or U400 Series Wall or Partition Designs in the UL Fire Resistance Directory and shall include the following construction features:
A. Studs - Wall framing may consist of either wood studs (max 2 hr fire rated assemblies) or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102
mm) lumber spaced 16 in. (406 mm) OC with nom 2 by 4 in. (51 by 102 mm) lumber end plates and cross braces. Steel studs to be min 3-5/8 in. (92 mm) wide by 1-3/8 in. (35
mm) deep channels spaced max 24 in. (610 mm) OC.
B. Gypsum Board* - Nom 1/2 or 5/8 in. (13 or 16 mm) thick, 4 ft. (122 cm) wide with square or tapered edges. The gypsum wallboard type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 26 in. (660 mm).
2. Through Penetrant - One metallic pipe, conduit or tubing installed either concentrically or eccentrically within the firestop system. The annular space between pipe, conduit or tubing and periphery of opening shall be min of 0 in. (0 mm) (point contact) to max 2 in.
(51 mm). Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly.
The following types and sizes of metallic pipes, conduits or tubing may be used:
A. Steel Pipe - Nom 24 in. (610 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe - Nom 24 in. (610 mm) diam (or smaller) service weight (or heavier) cast iron soil pipe, nom 12 in. (305 mm) diam (or smaller) or Class 50 (or heavier) ductile iron pressure pipe.
C. Conduit - Nom 6 in. (152 mm) diam (or smaller) steel conduit or nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing D. Copper Tubing - Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing E. Copper Pipe - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe.
F. Through Penetrating Product* - Flexible Metal Piping - The following types of steel flexible metal gas piping may be used:
1. Nom 2 in. (51 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both sides of floor or wall assembly.
OMEGA FLEX INC
2. Nom 1 in. (25 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both sides of floor or wall assembly.
TITEFLEX CORP
A BUNDY CO
3. Nom 1 in. (25 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both sides of floor or wall assembly.
WARD MFG INC
3. Fill,Void or Cavity Material* - Caulk or Sealant - Min 5/8. 1-1/4,1-7/8 and 2-1/2 in. (16, 32, 48 and 64 mm) thickness of caulk for 1, 2, 3 and 4 hr rated assemblies, respectively, applied within annulus, flush with both surfaces of wall. Min 1/4 in. (6 mm) diam bead of caulk applied to gypsum board/penetrant interface at point contact location on both sides of wall.
The hourly F Rating of the firestop system is dependent upon the hourly fire rating of the wall assembly in which it is installed, as shown in the following table.
The hourly T Rating of the firestop system is dependent upon the type or size of the pipe or conduit and the hourly fire rating of the wall assembly in which it is installed, as tabulated below:
+When copper pipe is used, T Rating is 0 hr.
3M COMPANY - CP 25WB+ caulk or FB-3000 WT sealant, *Bearing the UL Classification Marking
SECTION A-A
1A
1BA
Max Pipe or Conduit Diam in.
(mm) F Rating Hr T Rating Hr
1 (25) 1 or 2 0+, 1 or 2 1 (25) 3 or 4 3 or 4 4 (102) 1 or 2 0 6 (152) 3 or 4 0
12 (305) 1 or 2 0
A
SECTION A-A
A
A
System No. C-AJ-1044 June 15, 2005
F Ratings - 2, 3, and 4 Hr (See Items 2A and 4) T Rating - 0 Hr
L Rating At Ambient - 2 CFM/sq ft L Rating At 400 F - less than 1 CFM/sq ft
W Rating - Class I (See Item 4)
1. Floor or Wall Assembly - Lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Except as noted in table under Item 4, min thickness of solid concrete floor or wall assembly is 4-1/2 in. (114 mm). Floor may also be constructed of any min 6 in. (152 mm) thick UL Classified hollow core Precast Concrete Units*. When floor is constructed of hollow core precast concrete units, packing material (Item 3) and caulk fill material (Item 4) to be installed symmetrically on both sides of floor, flush with floor surface. Wall assembly may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is in solid lightweight or normal weight concrete. Floor is 32 in. (813 mm). Max diam of opening in floor constructed of hollow-core precast concrete units is 7 in. (178 mm).
See Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for names of manufacturers.
1A. Steel Sleeve (Optional, not shown) - Max 15 in. (381 mm) ID (or smaller) Schedule 10 (or heavier) steel sleeve cast or grouted into floor or wall assembly. Sleeve may extend a max of 2 in. (51 mm) above top of floor or beyond either surface of wall. Max 16 in. (406 mm) ID (or smaller) min 0.028 (0.71 mm) wall thickness (or heavier) galvanized steel sleeve cast or grouted into floor or wall assembly. Sleeve may extend a max of 1/2 in. (13 mm) beyond either surface of floor or wall.
2. Through Penetrants - One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. Max annular space between pipe, conduit or tubing and edge of through opening or sleeve is dependent on the parameters shown in Item 4. Min annular space between pipe or conduit and edge of through opening is 0 in. (0 mm) (point contact). Pipe conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used:
A. Steel Pipe - Nom 30 in. (762 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe - Nom 30 in. (762 mm) diam (or smaller) cast or ductile iron pipe.
C. Conduit - Nom 6 in. (152 mm) diam (or smaller) rigid steel conduit.
D. Conduit - Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing.
E. Copper - Tubing Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tube.
F. Copper Pipe - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe.
3. Packing Material - Polyethylene backer rod or nom 1 in. (25 mm) thickness of tightly-packed mineral wool batt or glass fiber insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of caulk fill material (Item 4).
4. Fill,Void or Cavity Material* - Caulk or Sealant - Applied to fill the annular space flush with top surface of floor. In wall assemblies, required caulk thickness to be installed symmetrically on both sides of wall, flush with wall surface. At point contact location between penetrant and sleeve or between penetrant and concrete, a min 1/4
in. (6 mm) diam bead of caulk shall be applied at top surface of floor and at both surfaces of wall. The hourly F Ratings and the min required caulk thicknesses are dependent upon a number of parameters, as shown in the following table:
(a)Min 2 in. (51 mm) thickness of mineral wool batt insulation required in annular space.
(b)Min 1 in. (25 mm) thickness of mineral wool batt insulation required in annular space on both sides of floor or wall assembly. Min 1 in. (25 mm) thickness of caulk to be installed flush with each surface of floor or wall assembly.
3M COMPANY - CP 25WB+ caulk or FB-3000 WT sealant. (Note: W Rating applies only when FB-3000 WT sealant is used.)
*Bearing the UL Classification Marking
Min Floor or Wall Thkns In. (mm)
Nom Pipe Tube or Conduit Diam in. (mm)
Max Annular Space in. (mm)
Min Caulk Thkns in. (mm)
F Rating Hr
2-1/2 (64) 1/2-12 (13-305) 1-3/8 (35) 1/2 (13) 2 2-1/2 (64) 1/2-12 (13-305) 3-1/4 (83) 1 (25) 2 4-1/2 (114) 1/2-6 (13-152) 1-3/8 (35) 1/4 (6) (a) 2 4-1/2 (114) 1/2-12 (13-305) 1-1/4 (32) 1/2 (13) 3 4-1/2 (114) 1/2-20 (13-508) 2 (51) 1 (25) 3 4-1/2 (114) 1/2-20 (13-508) 2 (51) 1 (25) 3 4-1/2 (114) 1/2-12 (13-305) 3-1/4 (83) 1 (25) 3 4-1/2 (114) 22-30 (558-762) 2 (51) 2 (51) 3 5-1/2 (140) 1/2-6 (13-152) 1-3/8 (35) 1 (25) (b) 4
* NOTE
THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS
FROM THE 2004 EDITION OF THE UL FIRE RESISTANCE DIRECTORY.
System No. C-AJ-1275 August 26, 2004 F Rating - 2 Hr T Rating - 0 Hr
1. Floor or Wall Assembly - Min 4-1/2 in. thick reinforced lightweight or normal weight (100-150 pcf) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 8 in.
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.
2. Through Penetrant - One metallic pipe, conduit or tubing installed either concentrically or eccentrically within the firestop system. The annular space between pipe, conduit or tubing and periphery of opening shall be min 0 in. (point contact) to max 1-7/8 in. Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly.
The following types and sizes of metallic pipes, conduits or tubing may be used:
A. Steel Pipe - Nom 6 in. diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe - Nom 6 in. diam (or smaller) service weight (or heavier) cast iron soil pipe, nom 6 in diam (or smaller) or Class 50 (or heavier) ductile iron pressure pipe.
C. Conduit - Nom 6 in. diam (or smaller) steel conduit or nom 4 in. diam (or smaller) steel electrical metallic tubing.
D. Copper Tubing - Nom 6 in. diam (or smaller) Type L (or heavier) copper tubing.
E. Copper Pipe - Nom 6 in. diam (or smaller) Regular (or heavier) copper pipe.
3. Firestop System - The details of the firestop system shall be as follows:
A. Packing Material - Min 4-1/2 in. thickness of min 4 pcf mineral wool batt insulation firmly packed into opening as a permanent form. Packing material to be flush with top surface of floor or from both surfaces of wall.
B. Fill,Void or Cavity Materials* - Min 1/16 in. dry (1/8 in. wet) thickness of fill material sprayed or brushed into annular space on top surface of floor or both surfaces of wall to completely cover mineral wool and overlap a min of 1 in. onto penetrant and top surface of floor or both surfaces of wall.
3M COMPANY - FireDam™ Spray 100
*Bearing the UL Classification Mark
3A
3B
3A
3B 1
SECTION A-A
A
A
SECTION
A-A
1 44
A
A
1. Floor or Wall Assembly — Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening ) is 27-1/4 in. (692 mm).
See Concrete Block (CAZT) category in the Fire Resistance Directory for names of manufacturers.
1A. Steel Sleeve — (Optional, Not Shown) - Nom 28 in. (711 mm) diam (or smaller) Schedule 10 (or heavier) steel sleeve cast or grouted into floor or wall assembly. As an alternate, nom 28 in. (711 mm) diam (or smaller) sleeve fabricated from nom 0.028 in. (0.71 mm) thick galv steel cast or grouted into floor or wall assembly flush with floor or wall surfaces.
2. Through-Penetrant — One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. An annular space of min 0 in. (point contact) to max 3-1/4 in. (83 mm) is required within the firestop system . When optional steel sleeve is used, min annular space shall be 1/2 in. (13 mm). Pipe, conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used:
A. Steel Pipe — Nom 24 in. (610 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. When Type FB-1000 NS or FB-1003 SL sealant (see Item 4) is used, pipe diam shall not exceed nom 8 in. (203 mm).
B. Conduit — Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing or nom 6 in. (152 mm) diam (or smaller) steel conduit.
C. Copper Tubing — Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing. When Type FB-1000 NS or FB-1003 SL sealant (see Item 4) is used, tubing diam shall not exceed nom 4 in.
(102 mm).
D. Copper Pipe — Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe. When Type FB-1000 NS or FB-1003 SL sealant (see Item 4) is used, pipe diam shall not exceed nom 4 in. (102 mm).
E. Iron Pipe — Nom 24 in. (610 mm) diam (or smaller) cast or ductile iron pipe. When Type FB-1000 NS or FB-1003 SL sealant (see Item 4) is used, pipe diam shall not exceed nom 8 in. (203 mm).
3. Packing Material — Min 3 in. (76 mm) thickness of min 4 pcf (64 kg/m3) mineral wool batt insulation firmly packed into opening as a permanent form.
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .