This document is an Addendum 1 for KEYS Bid 20-25, issued by Keys Energy Services, a municipal electric utility in Key West, Florida, for substation lattice structure repairs and restoration. The project involves comprehensive repair work across six substations, targeting 67 steel lattice structures comprising 244 total legs and their corresponding concrete foundations. Bidders are required to submit electronic proposals by 10:00 a.m. on Tuesday, August 19, 2025, with a tentative project timeline from contract award in September 2025 to project completion by February 2026. Site visits are available by appointment with Sam Gaccione, and bidders are encouraged to inspect the substations to understand the fabrication work required. The steel repairs will involve materials ranging from 1.5 x 1.5 inch to 8 x 8 inch angled steel, with thicknesses between .20 and .60 inches.
The contract is structured as a not-to-exceed pricing arrangement, with contractors expected to provide detailed labor and material costs for each substation location. No union requirements exist, and no estimated project value has been disclosed. Bidders must submit a bid bond or certified check for 5% of their total proposal and demonstrate compliance with comprehensive insurance requirements. The awarded contractor will be responsible for procuring materials, performing site inspections, and taking precise measurements before ordering replacement components. Keys Energy Services reserves the right to reject any or all proposals and waive irregularities, indicating flexibility in the procurement process. The project emphasizes structural steel restoration, thorough cleaning, weatherproof coating application, and potential structural repairs or replacements across the specified substations.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
KEYS BID 20-25 SPECIFICATIONS FOR SUBSTATION LATTICE STRUCTURE
REPAIRS AND RESTORATION
Addendum 1
Questions and Answers:
1. Steel specifications and associated drawings for all parts that need to be fabricated or procured for replacement The steel to be used in the repairs should be Structural steel – ASTM A572 Grade 50 or an alternative of equal strength, and weather resistance. Drawings for each individual part that needs to be fabricated are not available.
• Steel grade / type Structural steel – ASTM A572 Grade 50 or an alternative of equal strength, and weather resistance.
• Galvanizing requirements
ASTM A123 (No quench)
• Part number specific detail drawings
We do not have individual drawings for each part to be replaced or fabricated.
The vendor is expected to inspect the structures and fabricate the parts as needed.
• Bolt / washer sizes and qty’s We do not have this information. Awarded contractor is expected to perform a site inspection to determine this information.
• Substation temporary supports
Need load specs that temporary supports need to be rated for and connection specs for connecting to existing structure.
• We do not have this information.
2. I’m trying to obtain an electronic copy of the plans/specs for this project, is it available?
The plans and specifications are included in the bid specification document, specifically on pages 8 through 63.
• What is the start date for construction?
Please refer to the schedule provided in the bid specification.
• What is the estimated value for this project?
No estimated value can be provided. KEYS Energy Services is soliciting competitive bids.
• Are there union requirements for this project?
No.
3. Regarding the request for proposal below, is it your expectations that the winning bidder will procure the replacement steel or is this an owner procured material? If contractor procured, can you provide more information regarding the sizes of the steel that must be replaced?
The awarded contractor is expected to procure the materials to be used in the repairs. The steel in need of replacement and/or repair ranges from 1.5 x 1.5 inch angled steel to potentially 8 x 8 inch angled steel. The thicknesses range from .20 inch to .60 inch. The awarded contractor is expected to perform a site inspection at each substation to take
KEYS BID 20-25 SPECIFICATIONS FOR SUBSTATION LATTICE STRUCTURE
REPAIRS AND RESTORATION
measurements of the structures prior to ordering materials. Bidders may perform site visits upon request. Attached are the available drawings sorted by substation.
4. It appears from the scope documents that all lattice structures are of the same type. Will KES please confirm?
The lattice structures are not all the same type. They vary in height, base width, and dimensions of the materials used. The steel in need of replacement and/or repair ranges from 1.5 x 1.5 inch angled steel to potentially 8 x 8 inch angled steel. The thicknesses range from .20 inch to .60 inch.
The awarded contractor is expected to perform a site inspection at each substation to take measurements of the structures prior to ordering materials. Bidders may perform site visits upon request. Attached are the available drawings sorted by substation.
5. Will KES please provide As-Built drawings for the lattice structures that will be repaired?
Attached are the available drawings sorted by substation.
6. Are we able to get escorted into the various substations to inspect ahead of bid submittal so we know what fabrication work will be required?
Yes. Please request appointment by contacting Sam Gaccione at Samuel.Gaccione@KeysEnergy.com.
Attachment:
Drawings mailto:Samuel.Gaccione@KeysEnergy.com
Big Coppit Substation
Big Pine Substation
Kennedy Dr. Substation Photos and Drawings
69 kV Switchyard and SI DVAR
Jaret Lane Cross-Out
Jaret Lane Cross-Out
I
" 2
ii. ' f
1N/ t-- a•,, <o· 1-r'
I I I
��·-o·
�!� "1-
,UTUN/T �2 -�{���---====:
� \�:��� L_ rib
// / / ,-:i
GE.N.PLANT /
UNIT NQ.J
1/
�4·.o·
L'\. _ _,., �u
P L O T r I I I
I I I I I
P L A N
I I I I
I
I I
I I
I t I I
1/ p'· r
E..Xl�..,..,NG,.
S.1--\0�i.:. 1....11'.IE,.
LEGEND
REFERENCE DRAWINGS
IIS5· G-101 PLANT C.001;:?:DINA,"'l"E. � Tlc.'!;:.TWE:.LLL0CAT10N
\IS�•G,-l!:.01 UNIT "JOI G�OUN08..001<!. G,l!,1,J��AI...
A<;t;RA•·-HO,e;.MENT
11'::,'5-G -\02,. POWCR. P''-""-NT P'"-OT PL,O,.N
GRAPHIC SCALE
R. W. BECK and ASSOCIATES
Soo!tle,Wo,�1n;ton 0,1onOo,F1o"do Oon,or,Colo•Uo
UTILITY BOARO OF THE CITY OF KEY WEST
KEY WEST, FLOF!IOA
o.,s.T.a-a-..,& "•'• ,so•• 1156-E-IOl.2 C••t"f ,c � f,1,FC-5801-SMlMO
US1 Substation
TYPE 1 TYPE 1 TYPE 2 TYPE 2
TYPE 3
X BRACING ON 2
OPP. SIDES + 1
ANCHOR EACH LEG
X BRACING ON 2
OPP. SIDES + 1
ANCHOR EACH LEG
X
BRACING
ON 2
OPP.
SIDES +
ANCHOR
EACH
LEGADDL. BRACE TYPE 2 TYPE 1
TYPE 4
X BRACING ON ALL
4 SIDES + 4
ANCHOR
SUPPORTS ON
EACH LEG
SINGLE BRACE ON
ALL 4 FACES + 2
ANCHOR
SUPPORTS ON
EACH LEG
TYPE 4TYPE 4
| Lattice Repair Pictures and Drawings_Big_Pine.pdf |
| Blank Page |
| Lattice Repair Pictures and Drawings_Kennedy_Drive.pdf |
| Lattice Repair Pictures and Drawings_Part4_Part2 |
| Blank Page |
| Lattice Repair Pictures and Drawings_Part5 |
| Blank Page |
| Blank Page |
| Blank Page |
| Blank Page |
| Lattice Repair Pictures and Drawings_US1.pdf |
| image002 |
| image003 |
| Lattice Repair Pictures and Drawings.pdf |
File details come from the government source that posted it. Updated .