jefferson parish event 145.pdf

PDF 3 MB Posted

Attached to
Modernization of Two (2) Hydraulic Elevators at the Jefferson Parish Juvenile Court
Solicitation number
145
Issued by
Jefferson Parish, Louisiana

About this file

This is a Scope of Work and Technical Specifications document issued by the Jefferson Parish Purchasing Department for Bid Event No. 145, concerning the modernization of two hydraulic passenger elevators at the Jefferson Parish Juvenile Court located at 1546 Gretna Blvd., Harvey, Louisiana. The project encompasses complete modernization of two passenger elevators (Car #1 with glass back and Car #2), including all labor, materials, equipment, transportation, and incidentals necessary for a turnkey installation. Both elevators are 3,000 lbs and 2,500 lbs capacity respectively, operating at 100 feet per minute with two-button selective collective controls serving two floors. Prospective bidders may schedule site visits with the Department of General Services between 8:00 a.m. and 3:00 p.m., Monday through Friday, by contacting Robbie Brouillette at 504-364-2675. Bids are due September 29, 2026 at 2:00 p.m. through the eProcurement system at www.jeffparishbids.net. The successful bidder must attend a Start of Work Conference before commencing work and receive written Notice to Proceed from the Department of General Services.

Bidders must possess a Louisiana State Contractor's License in Limited Specialty Services, Louisiana State Fire Marshal's Office Conveyance Device Mechanic certification, and National Association of Elevator Contractors or National Elevator Industry Education Program Certified Elevator Technician (CET) certification. An electronic bid bond equal to 5% of the total bid must accompany submissions through Central Bidding, with performance and payment bonds of 50% of contract price required upon execution. The apparent low bidder must provide proof of all required licenses and certifications within 10 days of bid opening or face rejection. Work must be performed during regular hours of 7:00 a.m. to 5:00 p.m., Monday through Friday, with the bidder permitted to work outside these hours at no additional cost. Liquidated damages of $300 per day apply commencing 180 days after Notice to Proceed until substantial completion. All materials and workmanship carry a minimum one-year warranty from the contractor, with specific compliance required to ASME A17.1, A17.2, A17.5, A17.6, NFPA 70 and 101, ADA standards, and National Electrical Code provisions. Approved principal elevator manufacturers include Vantage, MEI – Total Elevator Solutions, and Vantage Elevator Solutions, with specific component manufacturers approved for controllers, hydraulic machines, jack assemblies, door equipment, cab interiors, and communication devices.

View the file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Bid Event No. 145

Labor, Materials, Equipment, Transportation and All Other Incidentals Necessary to Provide a Complete Modernization of Two

(2) Hydraulic Elevators at the Jefferson Parish Juvenile Court

BID DUE: September 29, 2026 AT 2:00 PM

ATTENTION VENDORS!!!

Please review all pages and respond accordingly, complying with all provisions in the technical specifications and Jefferson Parish Instructions for Bidders and

General Terms and Conditions. All bids must be received on the Purchasing Department’s eProcurement site, www.jeffparishbids.net, by the bid due date and time. Late bids will not be accepted.

Jefferson Parish Purchasing Department

200 Derbigny Street General Government Building, Suite 4400

Gretna, LA 70053 Purchasing Specialist: Sean Dumas Email: Sean.Dumas@jeffparish.gov

Phone: 504-364-2808

Bid Bond

An Electronic Bid Bond must be submitted with this bid, through one of the respective clearing houses at https://www.centralbidding.com/bid-bonds/ To access the bonding companies on Central Bidding, hover over the “Central Bidding” link at the top of the page and select the “Bid Bonds” link.

The electronic bid bond number is to be placed in the required section listed on the standard envelope. Scanned copies of bid bonds will not be accepted with your submission.

Juvenile Court Elevator Modernization

Section 1.0 – Site Visit:

All prospective bidders can schedule a site visit with Robbie Brouillette from the Department of General Services between 8:00 a.m. and 3:00 p.m., Monday through Friday. Mr. Brouillette can be reached at 504-364-2675.

Section 2.0 – Scope:

We extend this proposal to provide labor, materials, equipment, transportation, and all other incidentals necessary to modernize Two (2) hydraulic elevators at Jefferson Parish Juvenile Court located at 1546 Gretna Blvd., Harvey, LA.

• One (1) passenger elevator, Cars #1 (Glass back).

• One (1) passenger elevator, Cars #2.

Section 3.0 – License and Certification Requirements:

The following licenses issued by the Louisiana State Licensing Board for Contractors will be required for this bid. The license number must be placed in the appropriate field on the electronic bid envelope. Failure to do so will result in your bid’s rejection in accordance with the law.

A Louisiana State Contractor’s License in the class listed below will be required in accordance with La. R.S. 38:2212(B)(2) and 37:2150 et. seq., and such license number must be entered in the appropriate field in the electronic procurement system. Failure to do so will result in your bid being rejected and not read aloud in accordance with the law.

3.1 License(s) issued by the Louisiana State Licensing Board for Contractors:

• Limited Specialty Services

The apparent low bidder shall be required to provide sufficient proof of the following licenses and certifications within 10 days of bid opening. Failure to provide this documentation or sufficient documentation in the Parish’s discretion within 10 days of bid opening will result in your rejection and the Parish moving on to the next lowest bidder. Submit documents to the Department of General Services.

3.2 License/certifications issued by the Louisiana State Fire Marshal's Office:

• Conveyance Device Mechanic

3.3 Certifications issued by the National Association of Elevator Contractors or by the National Elevator Industry Education Program (NEIEP):

• Certified Elevator Technician (CET)

Bid Event #145

SP - Page 1 of 28

Section 3.0 – License and Certification Requirements: continued

3.4 - Compliance with Regulatory Agencies and Codes Upon request, the apparent low bidder shall be required to provide sufficient proof of their capacity to be compliant with the following regulatory agencies and codes:

• ASME A17.1, 2, 5,

• National Electrical Code, NFPA 70 and 101

• Americans with Disabilities Act, ADA

• Local Fire Authority

Section 4.0 – Bonds:

• Surety Bond: An Electronic bid bond in the amount of 5% of the total bid will be required with bid submission. The vendor shall indicate the electronic bid bond number in the location specified on the electronic bid envelope. No scanned paper copies of any bid bond will be accepted as part of the electronic bid submission.

• Performance Bond: A Performance Bond in the amount of 50% of the total contract price will be required. The performance bond shall be produced upon contract execution.

• Payment Bond: A payment bond of 50% of the total contract price will be required. The payment bond shall be produced upon contract execution.

Section 5.0 – Submittals:

If the bidder intends to provide materials equal to or better than owner-specified materials, the following shall be supplied upon request.

• Manufacturer's catalog data

• Detail sheets

• Specifications of the product

• Warranty information

Section 6.0 – Quantities/Inspection:

Bidders must inspect the sites and perform their measurements to determine the proper quantity of materials and equipment required to complete this project. All measurements given in these specifications are for informational purposes only.

SP - Page 2 of 28

Section 7.0 Bid Specifications:

• Provide labor, materials, equipment, tools, construction equipment, machinery, incidentals, and other facilities and services necessary for proper execution and completion of required work.

• Furnish and install equipment utilizing existing and modified hoistways and machine rooms.

• All materials for this project shall be bidder-supplied new unless specified.

• No more than one elevator shall be out of service in a group of elevators (not including a second car out of service for more than sixty minutes for regular preventive maintenance during non-peak traffic periods).

• No Interruptions or changes in regular group automatic operation during normal business hours.

• Firefighter’s Emergency Operation Phase I or II is not activated during regular business hours.

• No activation of Standby Power Operation during regular business hours.

• No large equipment shall be transported through public or tenant spaces during regular business hours.

• Bidder shall verify that the specified materials and equipment will fit into the designated spaces and that, when installed per the manufacturers’ guidelines, they will ensure a

• complete, coordinated, satisfactory, and properly operating system.

• Equipment shall be installed so it may be easily removed for maintenance and repair.

• All equipment shall have maximum accessibility, safety, and continuity of operation.

• This project is a significant elevator modernization in an existing building open for public business and will continue to operate throughout all phases of required work.

• It is essential that the bidder give special attention and priority to all matters concerning project safety, protection from dust and loose materials, reduction of noise level, protection from water and air infiltration into the building, and maintenance of neat, sightly conditions in and around work areas inside and outside of the building.

• All packaging, scrap materials, and demolition debris shall be removed daily from the building and site.

• Provide visible warning and direction signs, barricades, temporary lighting, overhead protection, and hazard-free walking surfaces throughout public areas.

• Mechanical and electrical equipment shall have identification plates with the Manufacturer’s name, address, model number, rating, and any other information required by governing codes.

SP - Page 3 of 28

Section 7.0 Bid Specifications: continued

• Within 30 days of final acceptance, provide three sets of neatly bound written information necessary for proper maintenance and adjustment of equipment. Include the following as minimums.

Straight-line wiring diagrams of “as-installed” elevator circuits with an index of the location and function of components. Provide one set reproducible wiring diagrams.

Mount one set of wiring diagrams on panels, racked or similarly protected, in the elevator machine room. Provide the remaining set rolled and in a protective drawing tube.

The written maintenance control program (MCP) is specifically designed for the equipment included in this contract. Include any unique or product-specific procedures or methods required to inspect or test the equipment. In addition, identify weekly, bi-weekly, monthly, quarterly, and annual maintenance procedures, including statutory and other equipment needed tests

All necessary interface cards for equipment maintenance, code-mandated testing, and troubleshooting.

Instructions, including recommended grade of lubricants Catalogs for all replaceable parts, including ordering forms and instructions Four (4) sets of keys per elevator for all switches and control features are appropriately tagged and marked.

Bound instructions explaining all operating features, including all apparatus in the car and lobby control panels.

Bound maintenance and adjustment instructions explaining areas to be addressed, methods and procedures to be used, and specified tolerances for all equipment.

Non-Proprietary Equipment Design:

Provide three sets of neatly bound written information necessary for proper maintenance and adjustment of equipment within 30 days following final acceptance. Final retention will be withheld until the purchaser receives the Data and the Consultant reviews it. Include the following as minimums.

Provide Straight-line wiring diagrams of “as-installed” elevator circuits with an index of the location and function of components. Mount one set of wiring diagrams on panels, racked or similarly protected, in the elevator machine room. Provide the remaining set rolled and in a protective drawing tube. Maintain all drawing sets in addition to all subsequent changes. These diagrams are the Purchaser’s property. A legend sheet shall be furnished with each set of drawings to provide the following information:

1. Name and symbol of each relay, switch, or apparatus.

2. Location on drawings, drawing sheet number and area, and location of all contacts.

3. Location of apparatus, whether on the controller or the car.

SP - Page 4 of 28

Non-Proprietary Equipment Design:

Provide a written Maintenance Control Program (MCP) specifically designed for the equipment included under this contract. Include any unique or product-specific procedures or methods required to inspect or test the equipment. In addition, identify weekly, bi-weekly, monthly, quarterly, and annual maintenance procedures, including statutory and other equipment needed tests.

Provide printed instructions explaining all operating features.

Provide complete software documentation for all installed equipment.

Provide catalogs listing all replaceable parts, including the Contractor’s identifying numbers and ordering instructions.

Provide diagnostic test devices with all supporting information necessary for interpreting test data, troubleshooting the elevator system, and performing routine safety tests.

The elevator installation shall be designed to be maintained by any licensed elevator maintenance company employing journeymen mechanics without purchasing or leasing additional diagnostic devices or special tools.

Provide onsite capability to diagnose faults to the level of individual circuit boards and individual discrete components for the solid-state elevator controller.

If the fault diagnosis equipment is not entirely self-contained within the controller, the Department of General Services must be provided with a separate, detachable device as required per the building listed in these specifications as part of this installation. Such device shall be in the Department of General Services' possession and become its property.

• Provide all upgrades and revisions of software during the progress of the work and warranty period.

• Provide a QEI inspection before turnover for use by the general public. the owner shall receive an inspection report.

General Summary

• Section includes modernization of hydraulic elevators as follows:

• One (1) passenger elevator, Cars #1 (Glass back).

• One (1) passenger elevator, Cars #2.

• Products Installed but Not Furnished Under This Section:

• Emergency Voice/Alarm Communication System Provisions (as required).

• CCTV camera provisions (as required).

• Elevator security devices, control unit, mounting brackets, wiring materials, logic circuits, security system interface terminals, boxes, and relays. Elevator #2 – 1st floor hall call button.

• Car interior finishes (as required).

• Car flooring (as required).

SP - Page 5 of 28

Definitions

• Technical terms used are defined in the latest edition of the Safety Code for Elevators and Escalators, ASME A17.1, or in this section.

• ELEVATOR CONSULTANT or CONSULTANT refers to Lerch Bates Inc. (Lerch Bates).

• PROVIDE means “furnish and install.”

• MANUFACTURER means either the Original Equipment Manufacturer (OEM) or the principal manufacturer of a component or system.

• RETAIN means, unless otherwise specified, the existing equipment is to be left in place with no alterations and no change in the original manufacturer’s designed performance or functionality. Items that are “retained” shall be thoroughly cleaned in place and adjusted to achieve the originally designed function.

• REFURBISH means, unless otherwise specified, the existing equipment is to be cleaned, repainted, repaired, and parts replaced to put the equipment into a condition to provide the same appearance, performance, and functionality as the equipment provided when it was originally installed. Unless otherwise specified, the scope of replacement of components is limited to those items currently available for purchase as replacement parts from the manufacturer or after-market suppliers approved by the manufacturer.

• REUSE means that the Contractor shall carefully remove equipment from the existing installation, avoiding any damage or additional wear. Store in a safe location to maintain the equipment in its pre-removal condition. Reinstall and incorporate into the modernized elevator installation using the same procedures and recommendations provided by the manufacturer of the equipment.

• CALL BACK means a request from the Owner to the Contractor to provide a technician on site to evaluate an elevator that is out of service or not functioning properly, rectify the root cause of the malfunction, and place the unit back into normal service.

• INCLUDES or INCLUDING means including the items specified, but not limited solely to those items, if additional work or components are required to achieve the specified outcome.

• Words in the singular shall include the plural whenever applicable or context so indicates.

Work Included:

• Provide all labor, engineering, tools, transportation, services, supervision, materials, and equipment necessary for and incidental to satisfactory completion of required work as indicated in Contract Documents. This is a turnkey project. All necessary work necessary for a code-compliant project is to be included by the Elevator Contractor.

This includes all electrical, fire alarm, shunt trip, receptacles, etc.

• Provide all required staging, hoisting, and movement of new equipment, reused equipment, or removal of existing equipment.

• Applicable conditions of Owner’s General, Special, and Supplemental Conditions.

• Scope of work includes, but is not limited to, the following:

SP - Page 6 of 28

Work Included:

• Coordination, scheduling, and management of the work of component suppliers and subcontractors.

• Furnish and install equipment as specified, utilizing existing and/or modified hoistways and machine rooms.

• Containment, storage, transport, and disposal of all used hydraulic oil and jack hole clean out spoils and debris removed from the existing jack hole at no extra cost to the Owner.

Related work coordination:

• Coordinate the following requirements with other trades.

• Miscellaneous Steel:

• Pit ladders

• Electric:

• Electrical service, outlets, lights, switches in elevator machine rooms and pits.

• Finishes:

• Cab interiors, hoistway entrances, fixtures.

• Elevator Cab Flooring:

• Material and finish to be specified in other applicable section.

• Flooring installation must be coordinated to ensure the car saddle is installed at the proper height (even with the finished floor).

Security Equipment:

• Coordinate location(s) in elevator machine rooms and cabs where cables, conduit, components, etc., for CCTV and/or secure access interface equipment must be installed.

Action And Informational Submittals:

• Within thirty Calendar days after award of contract and before beginning equipment fabrication, submit field-verified existing installation information for review.

• Hydraulic Car Information:

• Existing Total Car Weight:

• Documented on the crosshead data tag, all cars.

• Field Verified: weigh single cars and one car per group of each identical duty type.

• Estimated Gross Load on Jack

• Power Confirmation Information: Field-verified existing conditions at each elevator main disconnect:

• Actual maximum available voltage and current.

• Verify true earth ground value.

• Within thirty Calendar days after award of contract and before beginning equipment fabrication, submit planned modernization design information, shop drawings, and required material samples for review. Allow thirty calendar days for response to initial submittal.

• Indicate equipment lists, reactions, and design information on layouts, including:

SP - Page 7 of 28

Car:

• Total car weight to be included on the new crosshead data tag.

• Written confirmation that the designed modernization total combined weight of the car and the rated load:

• Does not vary by more than 5% from that of the original installation.

• Verify buffer capacity via data tags or known manufacturing data.

• Power Confirmation Information: Design for existing conditions.

• Motor horsepower and code letter designation.

• Motor starter in-rush current, full load running current, and demand factor.

• Engineered power consumption based on hydraulic elevator with [HYDRAULIC UP

STARTS] upstarts per hour full load.

• Written confirmation that existing electrical provisions are adequate for post modernization installation equipment requirements.

• Written confirmation that total planned modernization reactions on the building structure do not exceed originally designed reactions by more than 5%. If the installation has been altered previously and the original car-top data tag is missing, confirm that the new reactions will not exceed the existing reactions.

Reaction calculations shall include:

• Gross Load on Jack.

• Traveling Cables.

• Total Car Weight.

• Car Capacity.

Product Data, Including:

• Capacities, sizes, performances, operation, control, signal systems operations, safety features, finishes, and similar information.

• Product data for car enclosures and hoistway entrances.

• Product data for signal fixtures, lights, graphics, tactile marking plates, and details of mounting.

• Full details of ascending car protection means and installation.

• Two-way conversation devices.

• Post-modernization machine room heat emissions in BTU.

• Shop Drawings:

• Fully Dimensioned Fixture Drawings:

• Car operating panels.

• Car floor indicators.

• Hall stations.

• Destination/landing input stations.

• Position indicators.

• Hall lanterns.

• Access key switch.

• Remote panels.

SP - Page 8 of 28

Product Data, Including:

• Samples for Verification:

• For exposed car, hoistway door and frame, and signal equipment finishes.

• Samples of Sheet Materials: 3" (75 mm) square.

• Running Trim Members: 4" (100 mm) lengths.

• Include full component samples, if requested:

• Signal fixtures.

• Lighting.

• Graphics.

• Braille Plates.

The Written Maintenance Control Program (MCP) is specifically designed for the equipment included under this contract.

• Include any unique or product-specific procedures or methods required to inspect or test the equipment.

• Identify weekly, bi-weekly, monthly, quarterly, and annual maintenance procedures, including statutory and other required equipment tests.

Submittal review shall not be construed as an indication that the submittal is correct or suitable or that the work represented by the submittal complies with the Contract Documents. Compliance with Contract Documents, Code requirements, dimensions, fit, and interface with other work is the Contractor’s responsibility.

• Acknowledge and/or respond to review comments within fourteen calendar days of return.

• Promptly incorporate required changes due to inaccurate data or incomplete definitions so that delivery and installation schedules are not affected.

• Identify and cloud drawing revisions, including Contractor elective revisions on each resubmittal.

• Contractor’s revision response time is not a justification for equipment delivery or installation delay.

Closeout Submittals Manufacturer’s Warranty:

• Provide documentation of Manufacturer’s Warranty in compliance with Contract Documents.

Owner’s Information:

• Provide electronic copies (flash drive or Consultant-approved equivalent) of written information necessary for proper maintenance and adjustment of equipment within 30 days following final acceptance. Final retention will be withheld until the Consultant receives and reviews the data.

SP - Page 9 of 28

Include the following as minimums:

• Straight-line wiring diagrams of “as-installed” elevator circuits with an index of location and function of components. Provide one set of reproducible masters. Mount one set of wiring diagrams on panels, racked, or similarly protected, in the elevator machine room.

Provide the remaining set rolled and in a protective drawing tube. Maintain all drawing sets, including all subsequent changes. These diagrams are the Owner’s property.

• Written Maintenance Control Program (MCP) specifically designed for the equipment included under this contract. Include any unique or product-specific procedures or methods required to inspect or test the equipment. In addition, identify weekly, bi-weekly, monthly, quarterly, and annual maintenance procedures, including statutory and other required equipment tests.

• Lubrication instructions, including recommended grade of lubricants.

• Parts catalogs for all replaceable parts, including ordering forms and instructions.

• Instructions explaining all operating features, including all apparatus in the car and lobby control panels.

• Maintenance Control Program documentation for all equipment.

Provide the Owner with the following:

• Any interface cards required for equipment maintenance, code-mandated testing, and troubleshooting.

• Four sets of keys for all switches and control features properly tagged and marked.

• Diagnostic equipment complete with access codes, adjusters’ manuals, and set-up manuals for adjustment, diagnosis, and troubleshooting of the elevator system, and performance of routine safety tests.

Permits, Tests, And Certificates Permits:

• Secure and pay for all permits required for Work to be performed, including but not limited to:

• Municipal and State permits.

• Device or equipment removal permits.

• Hot works permits.

• Post, maintain, and renew all permits in compliance with local governmental requirements.

• Obtain final close-out of all required permits.

• Tests and Inspections: Schedule with the AHJ and perform tests required by the

Governing Authority in accordance with the procedure described in ASME A17.2 Guide for Inspection of Elevators, Escalators, and Moving Walks in the presence of an

• Authorized Representative of the AHJ. QEI Inspection to be provided upon completion of modernization.

• Certificates: Obtain, pay for, and deliver to purchaser with all temporary and final inspection certificates provided by the proper governing authorities.

• Violations: Resolve any outstanding violations on record with the AHJ on devices being removed prior to final acceptance by the purchaser.

SP - Page 10 of 28

Permits:

• QUALITY ASSURANCE

• Compliance with Regulatory Agencies: Comply with the most stringent applicable provisions of currently enforced codes, laws, and/or authorities, including revisions and changes in effect, including, but not limited to:

• An inspection by a Qualified Elevator Inspector (QEI) will be provided prior to the closeout of this project.

• American Society of Mechanical Engineers:

• ASME A17.1, Safety Code for Elevators, Escalators, and Moving Walks.

• ASME A17.2, Guide for Inspection of Elevators, Escalators, and Moving Walks.

• ASME A17.5, Elevator and Escalator Electrical Equipment.

• ASME A17.6, Standard for Elevator Suspension, Compensation, and Governor Systems.

• ASME A17.7, Performance-Based Safety Code for Elevators, Escalators, and Moving

Walks.

• National Fire Protection Association (NFPA):

• NFPA 70, National Electric Code.

• NFPA 80, Fire Doors and Windows.

• NFPA 101, Life Safety Code.

• International Building Code (IBC).

• Accessibility:

• American National Standard Institute (ANSI): A117.1, Accessible and Usable Buildings and Facilities.

• Uniform Federal Accessibility Standards (UFAS).

• ADAAG, Americans with Disabilities Act Accessibility Guidelines.

• Inspections: Provide access to areas where work is being performed for the consultant at any time throughout the project.

Maintenance Interim Maintenance:

• Furnish preventive maintenance service on elevators described herein for a period from mobilization, verbal or written, until each unit is removed from building service for modernization. In addition, provide interim preventive maintenance for completed units until the modernization of each group of elevators is complete and one-year warranty maintenance, as defined below, commences. Perform interim maintenance based upon terms and conditions of Owner’s existing maintenance agreement.

• Prior to the removal of any car from service, the consolidated callback service for all cars in the specific group shall be no more than three calls per month. Contractor will be responsible for providing preventative maintenance to achieve this requirement.

• If callback activity exceeds three callbacks per unit per month at any time when cars are off-line, all maintenance must be completed on OT until callback rate is less than three/unit/month.

• Use competent personnel, acceptable to Owner, employed and supervised by the Elevator Contractor.

SP - Page 11 of 28

Delivery And Storage

• The protection of all equipment and exposed finishes shall be the responsibility of the Elevator Contractor during delivery, handling, and installation until completion of project.

• The Elevator Contractor shall replace damaged materials with new at no additional cost for material and labor to Owner.

• Manufacturers’ original packing must adequately protect materials during delivery.

• Deliver materials to the site ready for use in the accepted manufacturer’s original and unopened containers and packaging, bearing labels as to type of material, brand name, and manufacturer’s name. Delivered materials shall be identical to accepted samples.

• Store materials in original protective packaging under cover in a dry and clean location off the ground. Remove delivered materials that are damaged or otherwise not suitable for installation from the job site and replace with acceptable materials.

• It is the responsibility of the Contractor to properly store and protect all materials in space provided or designated by the Owner against damage, stains, scratches, corrosion, weather, construction debris, and environmental conditions.

Products Manufacturers And Products:

• Approved Elevator Systems:

• Approved subject to compliance with the requirements of the contract, provide products by one or more of the following Principal Manufacturers. Where specific product models are referenced below only those specific product models or types are approved.

• Vantage

• MEI – Total Elevator Solutions.

• Vantage Elevator Solutions

• Approved Elevator Components In addition to products manufactured by the Principal

Manufacturers specified above, the following Manufacturers are approved for the specific components listed below, subject to the requirements of the contract:

Controllers:

• GAL (Vantage)

• MCE (Nidec)

• Smart Rise.

• Alpha (Lykos Controller).

Hydraulic Machines (Power Units):

• EECO.

• Maxton.

• IMO.

• Bore-Max (Vantage)

SP - Page 12 of 28

Hydraulic Jack Assemblies:

• EECO.

• D.L. Martin.

• Nidec (Canton).

Passenger Elevator Door Equipment (Operators, Tracks, Hangers, and Closers):

• GAL.

• Wittur.

Cab Interior Finishes (Standard/Pre-Engineered/Cab Systems):

• FabACab.

• Cab Works.

• SnapCab.

Car and Hall Signal Fixtures:

• Innovation.

• MAD Fixtures.

Two-Way Audio Communication Device:

• Janus/Rath.

• Wurtec.

Two-Way Video/Non-Verbal Communication Devices:

• Janus/Rath.

• Wurtec.

Door Edge Detector with Approaching Object Detection:

• CEDES.

• Janus.

Materials Steel:

• Sheet Steel (Furniture Steel for Exposed Work): Stretcher-leveled, cold-rolled, commercial quality carbon steel, complying with ASTM A366, matte finish.

• Sheet Steel (for Unexposed Work): Hot-rolled, commercial quality carbon steel, pickled and oiled, complying with ASTM A568/A568M-03.

• Structural Steel Shapes and Plates: ASTM A36.

Stainless Steel: Type 302 complying with ASTM A240, with standard tempers and hardness required for fabrication, strength, and durability. Apply mechanical finish on fabricated work in the locations shown or specified, Federal Standard and NAAMM nomenclature, with texture and reflectivity required to match Architect’s sample. Protect with adhesive paper covering.

• No. 4 Satin: Directional polish finish. Graining directions as shown or, if not shown, in

[DIRECTION] dimension.

• No. 8 Mirror: Reflective polish finish with no visible graining.

SP - Page 13 of 28

• Textured: 5WL as manufactured by Rigidized Metals or Windsor pattern as manufactured by Rimex Metals or approved equal with .050" mean pattern depth with bright directional polish (satin finish).

• Burnished: Non-directional, random abrasion pattern.

Bronze: Stretcher-leveled, re-squared sheets composed of 60% copper and 40% zinc similar to Muntz Metal, Alloy Group 2, with standard temper and hardness required for fabrication, strength, and durability. Clean and treat bronze surfaces before mechanical finish. After completion of the final mechanical finish on the fabricated work, use a chemical cleaner to produce finish, Federal Standard, and NAAMM nomenclature, matching Architect’s sample:

• No. 4 Satin: Directional polish finish, fine-satin, clear-coated with clear-organic coating recommended by Fabricator. Provide graining direction as shown or, if not shown, in vertical dimension.

• No. 8 Mirror: Reflective polish finish with no visible graining, bright-polished, clear-coated finish with clear-organic lacquer coating recommended by Fabricator.

• Acid-Etched Pattern: Provide a No. 8 mirror reflective-polished background with selectively acid-etched, matte-textured, custom pattern as shown. Acid selection and dilution, if required, as recommended by Fabricator. After final finishing, coat bronze with clear-organic lacquer coating recommended by Fabricator.

Aluminum: Extrusions per ASTM B221; sheet and plate per ASTM B209.

Plastic Laminate: ASTM E84 Class A and NEMA LD3.1, Fire-Rated Grade (GP-50), Type 7, 0.050" ±.005" thick, color and texture as follows:

• Exposed Surfaces: Color and texture selected by owner.

• Concealed Surfaces: Contractor’s standard color and finish.

• Fire-Retardant Treated Particle Board Panels: Minimum 3/4" thick backup for natural finished wood and plastic laminate veneered panels, edged and faced as shown, provided with suitable anti-warp backing; meet ASTM E84 Class “I” rating with a flame-spread rating of 25 or less, registered with Local Authorities for elevator finish materials.

• Natural Finish Wood Veneer: Standard thickness, 1/40" thoroughly dried conforming to ASME/HPMA HP-1983, Premium Grade. Place veneer, tapeless spliced with grain running in direction shown, belt and polish sanded, book-matched. Species and finish designated and approved by Architect.

• Paint: Clean exposed metal parts and assemblies of oil, grease, scale, and other foreign matter and factory paint one shop coat of standard rust-resistant primer. After erection, provide one finish coat of industrial enamel paint. Galvanized metal need not be painted.

• Prime Finish: Clean all metal surfaces receiving a baked enamel paint finish of oil, grease, and scale. Apply one coat of rust-resistant primer followed by a filler coat over uneven surfaces. Sand smooth and apply final coat of primer.

• Baked Enamel Finish: Prime finish per above. Unless specified “prime finish” only, apply and bake three additional coats of enamel in the selected solid color.

SP - Page 14 of 28

Entrance Field Paint:

• Clean all surfaces to remove dirt and grease.

• Sand and finish surfaces as necessary to remove pits and scratches and prepare the surface for painting.

• Apply filler to ensure a smooth surface; sand and apply one coat of electrostatic enamel in the selected solid color.

• Refinishing of natural metals: Remove existing protective finish. Buff as necessary to remove scratches. Regrain or finish as specified and protect as indicated for the particular metal type.

• Entrance Support Equipment within Hoistway: Include strut angles, headers, sill support angles, fascia, hanger covers, etc.

• Clean, remove, and check for corrosive activity. Replace components that exhibit severe deterioration.

• Tighten all fastenings.

Performance and Operation

• Car Speed: Allowable variance from contract speed of no more than +/- 10% in the up direction and +/-10% in the down direction under any loading condition.

• Car Capacity: Safely lower, stop, and hold the rated load.

• Car Stopping Zone: ±3/8" under any loading condition.

• Door Times: Seconds from start to fully open or fully closed:

• Cars #1 and #2: Door Open: 2.1 seconds. Door Close: 4.1 seconds.

• Car Floor-to-Floor Performance Time: Seconds from the start of doors closing until doors are 3/4 open for center-opening doors or 1/2 open for side-opening doors, and the car is level and stopped at the next successive floor under any loading condition or travel direction:

• Cars #1 and #2: 17.3 seconds (= or – 10%). Floor Height: 13’-5” between floors 1 and 2.

Noise and Vibration Control:

• Airborne Noise:

• The measured noise level of elevator equipment and its operation shall not exceed 60 dBA inside the car under any condition, including door operation and car ventilation exhaust blower on its highest speed.

• Limit noise level in the machine room and control space relating to elevator equipment and its operation to no more than 80 dBA.

• All dBA readings to be taken 3'-0" off the floor and 3'-0" from the equipment using the “A” weighted scale.

• Vibration Control: Mechanically isolate all new elevator equipment from the building structure and other components. Minimize objectionable noise and vibration transmission to occupied areas of the building.

SP - Page 15 of 28

Elevator Operation Requirements

• General:

• Cars automatically slow down and stop level at floors in response to car and landing calls, with stops made in sequence in the established direction of travel, regardless of order in which buttons are pressed.

• Landing calls are canceled when the assigned car arrives at the landing.

• Automatic Dispatch Failure: Provide auxiliary dispatch system to automatically dispatch elevators in the event of failure of the primary control system.

• Hall Call Button Failure: Should failure of hall call button system occur, initiate operation providing predetermined service to all landings; elevators respond normally to car calls.

• Automatic Leveling:

• When arriving at a floor cars level to within 1/8” above or below the landing sill prior to opening doors, without travelling past the landing during leveling

• Maintain leveling accuracy regardless of carload, direction of travel, rope slippage, or stretch.

Door Operation:

Passenger Elevators:

• Automatically open doors when car arrives at a floor.

• Stop and reopen doors or hold doors in open position upon activation of “door open” button.

• At expiration of normal dwell time, or upon activation of “door close” button, close doors:

• Prevent doors from closing and reverse doors at normal opening speed if door reopening device beams are obstructed while doors are closing, except during nudging operation.

• In event of door reopening device failure, provide for automatic shutdown of car at floor level with doors open

• Close cycle does not begin upon activation of “door close” button until normal door dwell time for a car or hall call has expired, except firefighters’ operation.

• Nudging Operation:

• After beams of door reopening device are obstructed for a predetermined time interval (minimum 20.0-25.0 seconds), sound warning signal, and attempt to close doors with maximum of 2.5 foot-pounds kinetic energy.

• Activation of the door open button overrides nudging operation and reopens doors.

• Interrupted Beam Time:

• When beams are interrupted during initial door opening, hold door open a minimum of 3.0 seconds.

SP - Page 16 of 28

• When beams are interrupted after the initial 3.0 second hold open time, reduce time doors remain open to an adjustable time of approximately 1.0 1.5 seconds after beams are reestablished.

• Differential Door Time:

• Field adjustable time that doors remain open after stopping in response to calls.

• Car Call: Hold open time adjustable between 3.0 and 5.0 seconds.

• Hall Call: Hold open time adjustable between 5.0 and 8.0 seconds.

• Use hall call time when car responds to coincidental calls.

• Reopen doors when car is designated for loading.

• Independent Service.

• When feature is activated from within the car allow control of car only from buttons and controls inside the car.

• Close doors by constant pressure on desired destination floor button or door close button.

• Selective Collective Operation, Single Cars, Car(s) #1 and #2:

• Elevators operate via momentary pressure buttons to:

• Place hall call by selecting direction of travel at each hall landing (up and down buttons at each intermediate landing, single buttons at each terminal landing).

• Place car call by selecting destination floor from inside the car (individual buttons for each floor served).

• Hall calls, other than calls placed at the landing at which car is standing, start car, and cause the car to stop at first landing for which a call is registered in the direction of travel.

• Stops are made in order in which landings are reached, irrespective of sequence in which calls are registered.

• Parked Car (No Demand):

• When feature is enabled, elevator remains at landing of last assignment (if no further demand) with doors closed, for a predetermined amount of time (programmable for any amount of time). Upon expiration of time, the elevator returns to the main egress landing with the doors closed.

• If feature is disabled, if no further demand, the elevator remains at landing of last assignment with the doors closed until a hall call is registered.

• Car and Hall Lanterns:

• Lanterns provide audio and visual signal upon each stop, regardless of responding to car or hall call.

• Visual signal remains active from commencement of door opening until doors are completely closed.

• Standby or Emergency Power Operation, Cars #1 and #2:

• The terms Standby Power and Emergency Power are both referred to as

Emergency Power in this Section. Elevator operation is the same when either is provided.

SP - Page 17 of 28

• Where emergency power is provided to the elevator main disconnects and required by the Building Code the elevator installation shall comply with the Emergency Power Operation requirements of ASME A17.1 as modified by any superseding Building Code requirements.

• Where emergency power is not provided, all elevator controller software and sequencing capabilities to allow future emergency power operation shall be included in the elevator control systems based on the applicable code requirements for new buildings in effect at the time of project permit application.

• Operation is activated by a signal from an Automatic Transfer Switch (ATS) to elevator controls indicating the Emergency power source is operational.

• Start and run all elevators simultaneously and any single car simultaneously at contract car speed and capacity.

• Illuminate “ELEVATOR EMERGENCY POWER” signals.

• Restoration of Normal Power:

• At least 20 seconds prior to transfer from emergency power to normal power at the ATS, a pre-transfer signal is supplied to the elevator control system from the ATS.

• Elevators operating on emergency power stop at the next available landing and remain there until normal power is restored.

Battery Backup Operation for Emergency Lighting, Communication, and Alarm:

• Car mounted battery unit with solid-state charger to operate alarm bell, car emergency lighting, and voice communication system.

• Car lighting and communication shall be provided with a minimum of 4 hours of operation on back-up power during a loss of normal power, and a minimum of 1 hour of operation for car-mounted alarm, and any remote alarm mounted at the designated floor level.

• Battery to be rechargeable with minimum five-year life expectancy.

• Provide constant pressure test button in service compartment of car operating panel.

• Provide lighting integral with portion of normal car lighting system.

• Emergency Car Communication System Operation:

• Comply with all requirements of ASME A17.1 2019, or later editions if adopted by the AHJ.

• Hands-Free Communication System:

• In Car System:

• Hands-free two-way audio communication system in each elevator car.

• Automatic dialer to include automatic rollover capability if call is not answered with minimum two numbers.

• Intercom type systems shall be capable of auto dialing out of the building to any active telephone number selected by Owner if intercom call is not answered.

SP - Page 18 of 28

• Means to identify building and car for Authorized Personnel and Emergency

Personnel on demand.

• Activated by button in car identified with “PHONE” symbol or by external telephone call.

• Adjacent light jewel illuminates and flashes when call is acknowledged.

Authorized Personnel Communication:

• Communication system allows authorized personnel, via phone or intercom system, inside the building or at an outside location, to establish verbal communications with each elevator individually.

Communication for Deaf, Hard of Hearing and Speech Impaired:

• Means for non-verbal communication between passengers inside the elevator car and Authorized Personnel and Emergency Personnel inside or outside of the building.

• System allows for in car video display of custom or preselected text messages generated by Authorized Personnel or Emergency Personnel.

• Passengers inside the elevator car respond to text messages via “Yes” and “No” buttons that generate a visible indication at the location monitored by the Authorized/Emergency Personnel.

Elevator Alterations

Hydraulic PASSENGER Elevators:

ALTERATION SUMMARY

CAR #1: EXISTING INSTALLATION MODERNIZED INSTALLATION

Capacity: 3000 lbs. No Change lbs.

Class of Loading: Class A No Change Duty Type: Passenger No Change Contract Speed: 100 fpm No Change Hydraulic Jack Type: In Ground No Change Machine Type: Submersible Power Unit Submersible Power Unit Machine Location: Remote at floor 1 Remote at floor 1 Operation Control: Two-Button Selective Collective Two-Button Selective Collective

Floors Served: 1, 2 Front No Change

Total Entrances:

2 Front No Change

Car Entrance Type:

Single Speed Side Opening (SSS0) Front

SP - Page 19 of 28

CAR #1: EXISTING INSTALLATION MODERNIZED INSTALLATION

Hoistway Entrance Type:

Entrance Size: 42" Wide x 84" (7'-0") High (Field Verify)

Minimum Clear to Underside of Canopy: 96” High (Field Verify) No Change

CAR #2: EXISTING INSTALLATION MODERNIZED INSTALLATION

Capacity: 2500 lbs. No Change lbs.

Class of Loading: Class A No Change Duty Type: Passenger No Change Contract Speed: 100 fpm 100 fpm Hydraulic Jack Type: In Ground No Change Machine Type: Submersible Power Unit Submersible Power Unit Machine Location: Remote at floor 1 Remote at floor 1 Operation Control: Two-Button Selective Collective Two-Button Selective Collective

Floors Served: 1, 2 Front No Change

Total Entrances:

2 Front

Car Entrance Type:

Hoistway Entrance Type:

Entrance Size: 42" Wide x 84" (7'-0") High (Field Verify)

Minimum Clear to Underside of Canopy: 96” High (Field Verify) No Change

SP - Page 20 of 28

Machine Room Equipment

• Provide and arrange equipment in existing machine room spaces.

• Identification: Permanently identify (painted on or securely attached) machine room equipment with minimum 3" characters corresponding to elevator identification.

• Driving machine (Power Unit).

• Transformer, choke/filter.

• Controller.

• Main line disconnect switch.

• Elevator hoistway pit equipment.

Hydraulic Machine (Power Unit):

New:

• Assembled unit mounted on isolating pads consisting of:

• Dry or submersible type positive displacement pump and induction motor.

• Dry type only with motors exceeding 50 hp.

• Master-type control valves combining:

• Safety features.

• Holding, direction, bypass, stopping, manual lowering functions.

• Shut off valve.

• Oil reservoir with protected vent opening.

• Oil level gauge.

• Outlet strainer.

• Drip pan.

• Muffler.

Tank Heater:

• Oil tank heater with adjustable thermostat to keep the oil tank temperature within the hydraulic control valve manufacturer’s recommended operating range.

• Enclose dry type units below oil reservoir with removable sheet steel panels lined with sound-absorbing material for applications with motors exceeding 40 hp.

• Motor Starter:

• Soft start type unit including:

• Integral electronic overload protection.

• Integral bypass.

• Muffler:

• In discharge oil line near pump unit.

• Design shall dampen and absorb pulsation and noise in the flow of hydraulic fluid.

• Piping and Oil:

SP - Page 21 of 28

• All piping, connections and oil required for the elevator system.

• Buried piping shall be secondarily contained with watertight Schedule 80 PVC sleeves between elevator machine room and pit.

• A minimum of two sound isolation couplings shall be provided between the pump unit and oil line and the oil line and jack unit.

• Provide 2-90°joints to reduce vibration and create wave diffraction.

• Provide isolated pipe stands or hangers.

• Shut-Off Valve:

• Oil line shut off valve in the machine room or accessible from outside the hoistway.

• Second valve in pit adjacent to jack unit.

• Controller: UL/CSA labeled:

• Compartment:

• Securely mount all assemblies, power supplies, chassis switches, relays, etc., on a substantial, self-supporting steel frame.

• Completely enclose equipment with covers. Provide means to prevent overheating.

Relay Design:

• Magnet operated with contacts of design and material to insure maximum conductivity, long life, and reliable operation without overheating or excessive wear.

• Provide wiping action and means to prevent sticking due to fusion.

• Contacts carrying high inductive currents shall be provided with arc deflectors or suppressors.

• Microprocessor-Related Hardware:

• Provide built-in noise suppression devices providing a high level of noise immunity on all solid-state hardware and devices.

• Provide power supplies with noise suppression devices.

• Isolate inputs from external devices (such as pushbuttons) with opto-isolation modules.

• Design control circuits with one leg of power supply grounded.

• Safety circuits are not to be affected by accidental grounding of any part of the system.

• System automatically restarts when power is restored.

• System memory is retained in the event of power failure or disturbance.

• Equipment is provided with Electro Magnetic Interference (EMI) shielding within

FCC guidelines.

• Wiring:

• CSA labeled copper for factory wiring.

• Neatly route all wiring interconnections and securely attach wiring connections to studs or terminals.

SP - Page 22 of 28

• Permanently mark components (relays, fuses, PC boards, etc.) with symbols shown on wiring diagrams.

• Auxiliary disconnect: Provide controller or power unit mounted auxiliary, lockable “open,” disconnect if mainline disconnect is not in sight of controller and/or machine.

Hoistway And Pit Equipment

• Provide and arrange equipment in existing hoistway and pit spaces.

• Hydraulic Jack Assembly:

• Retain.

• Change hydraulic jack packing.

• Jack Support:

• Retain.

• Clean and Paint.

Shut-Off Valves:

New:

• Manual on/off valves in oil lines adjacent to pump unit and jack units in pit.

Guide Rails:

Retain:

• Clean rails and brackets.

• Remove rust.

• Repaint non-machined surfaces.

• Check and tighten all rail and bracket fastenings.

Buffers, Car:

Retain:

• Remove rust and repaint non-machined surfaces.

Pit Flood Devices:

Car Equipment

• Frame: Retain

• Platform: Retain

• Platform Guard: New

• Car Rail Guide Roller or Shoe Assemblies: Retain

• Top of Car Guardrail: New

Car Top Control Station:

• Mount to provide safe access and utilization while standing on car top.

• Operating device with Up and Down direction buttons, a Run button, an

Inspection/Automatic switch and Emergency Stop switch.

• Operating device provides an audible and visible indicator that fire recall has been initiated.

• Fix station to the car crosshead or provide portable station provided the extension cord and housing is permanently attached to the car crosshead.

SP - Page 23 of 28

• The car will be operated by constant pressure on the appropriate directional button and the Run button simultaneously.

• Normal operating devices will be inoperative while this device is in use.

Car Top Emergency Audible Signal:

• Provide on top of each elevator.

• Activation of Alarm Button or Emergency Stop switch will cause Emergency

Audible Signal.

• Provide auxiliary power supply to provide 1-hr. power in the event of loss of normal power.

• Work Light and Duplex Plug Receptacle:

• Work light on top and bottom of car.

• Car top light mounted to provide illumination of all car top equipment.

• GFCI protected duplex outlet. one (1) at top and one (1) at bottom of car.

• Include on/off switch and lamp guard.

CAR OPERATING PANEL: NEW

Communication

Car Communication System :

Hands Free Two-Way Communication Instrument In Car:

• Mounted behind car…

This is the start of the file's text. The full file is on GovTribe.