J150200007 NLON Inventory.pdf

PDF 200 KB Posted

Attached to
Boiler Maintenance & Repair
Solicitation number
ACQR6146079
Issued by

About this file

This is a boiler and related equipment inventory document for facility J-1502000-09. The facility operates six boilers with varying specifications and capacities. Boilers #1, #2, and #3 are Babcock and Wilcox units built between 1960 and 1965, each with a capacity of 76,500 pounds per hour (pph) and design pressures of 775 psi. Boiler #1S and Boiler #4 are Cleaver Brooks firetube models built in 2011, each rated at 1200 BHP with 150 psi design pressure. Boiler #6 is an Energy Resources Inc. heat recovery steam generator with a maximum steam capacity of 50,000 pph and 200 psi average allowable working pressure, featuring 17,882 square feet of heating surface.

The facility also contains two deaerators manufactured by Chicago Heater Company (built 1990 and 1993) with identical capacities of 350,000 pph at 50 psig and steel construction. Supporting infrastructure includes a hot water production system with piping sizes ranging from 2 to 14 inches and approximately 8 linear miles of steam distribution piping. The steam distribution system utilizes multiple pressure levels (600 psig, 200 psig, 125 psig, and 5 psig) with piping sizes from 1 to 8 inches. This inventory represents a comprehensive steam generation and distribution system suitable for large-scale industrial or institutional operations.

View the file

Other files

File Type Posted
J150200006 BLDG 29 Boiler Specifications.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

J-1502000-09

Boiler and Related Equipment Inventory

Boiler #1 Boiler #1S

Babcock and Wilcox Cleaver Brooks

National Board # 20583 National Board #17317

Built 1960 Built 2011

Capacity 76,500 pph Design Pressure 150 psi

Design Pressure 775 psi Rating 1200 BHP

Steam Temp 500ᵒF Type: Firetube

Heating Surface 7895 ft2 Model # CBL-200X-1200-150ST

Economizer heating surface

3030ft2

Economizer pressure 825 psi

Boiler #2 Boiler #3

Babcock and Wilcox Babcock and Wilcox

National Board # 20582 National Board # 21838

Built 1960 Built 1965

Capacity 76,500 pph Capacity 76,500 pph

Design Pressure 775 psi Design Pressure 775 psi

Steam Temp 500ᵒF Steam Temp SAT

Heating Surface 7895 ft2 Heating Surface 6934 ft2

Economizer heating surface

3030ft2 Economizer heating surface 3030ft2

Economizer pressure 825 psi Economizer pressure 825 psi

Boiler #4 Boiler #6

Cleaver Brooks Energy Resources Inc.

National Board #17454 Heat recovery Steam Generator

Built 2011 Model# S3-2616

Design Pressure 150 psi National Board # 3225

Rating 1200 BHP Average AWP 200 psi

Type: Firetube Heating Surface 17,882 ft2

Model # CBL-200X-1200-150ST Maximum Steam Capacity 50,000 pph

Deaerator #1 Deaerator #2

Chicago Heater CO. Chicago Heater CO.

Built: 1990 Built: 1993

Diameter: 7’5” Height 8’ Diameter: 7’8” Height 6’4”

Capacity: 350,000 PPH 50 psig Capacity: 350,000 PPH 50 psig

Steel Construction Steel Construction

Hot Water Production System Steam Distribution

Piping Sizes Vary From 2” TO

14”

Approximately 8 linear miles of piping

Piping sizes range from 1” to 8”

Nominal steam piping pressures are

600 psig, 200 psig, 125 psig, and 5 psig.

File details come from the government source that posted it. Updated .