AF1250 Air Flow Panel

CS - 8556

ASM

innovations in access flooring

ASM Modular Systems Inc.

9500 Industrial Center Dr. Ladson, SC, 29456 Tel: 843-534-1110 Fax: 843-534-1111 (www.asmproducts.com)

4/21 no damper

0.08

0.20 0.18 0.16 0.14 0.12 0.10

0.05 0.06

0.04

Static Pressure (In. H O) with open

3320.02 237 closed

1/2 open

Damper Adjusts From Top With

Hex Key HD Galv.

Damper

BOTTOM VIEW

Epoxy Paint Finish Inside & Out

Full-Hard CRS Top Sheet

Draw Quality Steel Bottom Pan

BOTTOM VIEW WITH DAMPER

SPECIFICATIONS

GENERAL INFORMATION

• 25% open area

• 24 inches square all steel construction.

• Concentrated load rating to 1250 lbf. (4.45 kN)

• Available with or without galv. slide damper.

• Protected from corrosion by epoxy paint finish.

• Fire rating of bare panel:

Class A Flame Spread Non-Combustible Materials

FINISH OPTIONS

• HPL tile (116")

- Static dissipative

- Static conductive

• Vinyl tile:

VPT - Static conductive VPT - Static dissipative

• Bare surface

UNDERSTRUCTURE OPTIONS

• Rigid Grid bolted stringers:

2' x 2' system 2' x 4' system 4' x 4' Basketweave system

VOLUME OF AIR FLOW (C.F.M.)

AutoCAD SHX Text

R

R scott

Polygon

Line

Typewritten Text

Formica Stone Grafix

Air Flow Panel for Panel Type 1 Area

Sheets and Views

Model

FS200D Enviro-Panel

PARTIAL BOTTOM VIEW

BARE CORNER-LOCK PANEL

TILE COVERED PANEL

PHYSICAL DATA

PERFORMANCE DATA

FINISH OPTIONS

FEATURES

▪ Weight of Bare Panel: 33.5 lb

▪ Height of Bare Panel: 1.33”

▪ Fire Rating of Bare Panel:

- Class A Flame Spread

- Non-Combustible Materials

▪ Concentrated Load Rating:

▪ Uniform Load Rating:

▪ Ultimate Load Rating:

- Safety Factor:

▪ Impact Load Rating:

▪ Rolling Load Rating:

- CISCA Wheel A (10 Pass):

- CISCA Wheel B (10K Pass):

▪ HPL Tile (1⁄16” or ⅛”)

- Integral Trim

▪ Vinyl Tile:

- Conductive

- Static Dissipative

- Custom

▪ Rubber Tile:

▪ Bare Surface

▪ Bare Corner-Lock

▪ Contact ASM for other tile options such as Bamboo, Cork, Ceramic, Wood, Stone, etc.

▪ Free Standing - Stringerless

▪ Corner-Lock

▪ Rigid Grid Bolted Stringers

- 2’ x 2’ System

- 2’ x 4’ System

- 4’ x 4’ Basketweave Systems

▪ Available in 24” size

▪ E-Coat Finish

▪ Welded Steel Construction

▪ Full-Hard Steel Top Sheet

▪ Full-Strength, Deep Drawn Corners

▪ Light Weight Cementitious Fill Recycled

NOTE: DATA SHEET DRAWING AND INFORMATION ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE.

ASM Modular Systems, Inc.® 9500 Industrial Center Dr. Ladson, SC 29456 ▪ TEL: 843-534-1110 ▪ FAX: 843-534-1111 ▪ www.asmproducts.com ACS - 18513

24”

½”

Varies with Tile

Corner-Lock Screw with Positive Grounding Feature

1.25”

1.33”

(8/2020)

600 psf (2929.4 kg/m²)

2-to-1 Min.

150 lb (68 kg)

1,125 lbf (5.00 kN) 875 lbf (3.89 kN)

1,250 lbf (5.56 kN)

MADE IN USA

Formica - Stone Grafix

Line

For Panel Type 1 Area

New Quick Corner™ Leveler

Adapts Easily and Quickly

Delivers 7’ Cold Air Plume

Lowers Server Inlet Temps

High Density Cooling Closer to the Rack 66% High Volume Air Flow

MAX-AIR delivers 15% more cool air volume than Infinity AIRSTREAM and weighs under 28 LBS making it one of the lightest, easiest panels to manage in the data center. MAX-AIR’s enhanced slot design allows for greater air volume transfer and maximum cooling effective-ness closer to the rack. Optimal supply air temperatures to Lo-Mid-Hi server inlets improves energy efficiency and overall equipment reliability.

Infinity® Air Grate, by Opstock, Inc www.infinityairgrate.com

High Density CoolingHigh Density Cooling

MAX-AIR™

Steel Panel (epoxy finish)

Understructure (wood/steel)

Panel Weight

Design Load

Safety Factor

Ultimate

Rolling

CFM

(.10” H²O)

MAX-AIR™ ANY 6.75 lbs /ft² 1250 lbs >3 4000 lbs 850 lbs 1300

AIRSTREAM™ ANY 7.0 lbs /ft² 1500 lbs >3 5000 lbs 1000 lbs 1100

Open Area*

66%

55%

* percentage of available open area ** Load performance tests are in accordance with CISCA’s recommended test procedures

Infinity® Performance Characteristics ** U.S. Patents: No. 7,823,340 No. 8,099,912 No. D561,327

AIRFLOW CONTROL ACCESSORIES

Quad Damper Kit (control range 10 CFM– 1950 CFM) FLEX-AIR Intake Hood (restore positive airflow to servers)

For Sales and Information, contact:

Computer Floors, Inc 19 Richmond Street, Clifton, New Jersey 07011

(973) 340-3666 (888) 564-4998 www.computerfloors.us

Highlight

Highlight

Air Flow Panel for Panel Type 2 Area

ConCore 1250-24"

With HPL

CORNER DETAIL

Welded assembly at domes and perimeter

Cementitious core material

TOP VIEW

Full hard cold rolled steel top sheet

Painted finish

Draw quality steel bottom pan with structural dome design

Protected from corrosion by an epoxy paint finish.

All steel welded construction filled internally with a

Non-combustible material.

Class A flame spread rating.

cementitious core material.

Panel weight : 8.6 lbs./ft² (with tile).

General information

SPECIFICATIONS

System Performance Criteria (Tested on Actual Understructure)

Panel Understructure

SYSTEM

WEIGHT

System Type

Design

Loads

STATIC LOADS

10 Passes 10,000 Passes

ROLLING LOADS

IMPACT

LOADS

Tate Access Floors, Inc.

7510 Montevideo Road

Jessup, MD 20794

Tel (410) 799-4200 Fax (410) 799-4207

1/16" Conductive HPL__________(Color)____________

1/16" HPL_______________(Color)________________

Tile factory laminated with integral trim edge

4' Bolted Stringer

COVERING OPTIONS

© 2008 Tate Access Floors, Inc.

R 8/30/21

Laminated Panel With Integral Trim

1-3/8" deep at corners

1-5/8" deep

Ultimate Loads Safety Factor

1. System Design Load is based on permanent set ≤ 0.010" and is verified by loading panels in accordance with the CISCA concentrated load method but with panels installed on actual understructure instead of steel blocks. (Testing on blocks does not represent performance of an actual installation.) Ultimate, Rolling, and Impact Load tests are performed using CISCA test procedures.

2. Safety Factor is Ultimate Load divided by Design Load.

Bolted Stringer

49.3 kg / m²

10.1 lbs / ft²

567 kg

1250 lbs

68 kg

150 lbs

454 kg

1000 lbs 800 lbs

363 kg

Min. 2

Min. 2500lbs

Min. 1134kg

ConCore 1250 Panel-24" With

High Pressure Laminate (HPL) x

Formica Stone Grafix

For Panel Type 2 Area