J-1a Drawings.pdf

PDF 13 MB Posted

Attached to
OMA ATCT - Roof and Fall Protection Upgrade
Solicitation number
697DCK-22-R-00403
Issued by

About this file

This solicitation is for roof and fall protection upgrades at the Air Traffic Control Tower on Eppley Airfield in Omaha, Nebraska. Interested vendors must attend a mandatory site visit on June 29, 2022 and submit any questions to the contact by July 05. Proposals are due by July 22, 2022. To be eligible, vendors must be registered in SAM and submit a proposal in accordance with the solicitation instructions. The work will be awarded by the Department of Transportation Federal Aviation Administration Southwestern Region.

View the file

Other files

File Type Posted
697DCK-22-R-00403-0002.pdf PDF
697DCK-22-R-00403 - 0001.pdf PDF
QuestionsandAnswers.docx DOCX document
697DCK-22-R-00403Final.pdf PDF
J-3 Past Performance Questionnaire.pdf PDF
J-1 Specifications.pdf PDF
J-2 Wage Determination.txt TXT text file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Pat Johnston Text Box Roof and Fall Protection Upgrade at

OMA ATCT

on Eppley Airfield Omaha, Nebraska

SHOWN IN CLOUDS

CONTRACTOR SHALL PERFORM ALL WORK

CONTRACT SPECIFICATION.

AND FLASHING AND PREPARE FOR NEW ROOF SYSTEM IN ACCORDANCE WITH THE

REMOVE EXISTING ROOF SYSTEM INCLUDING MEMBRANE, INSULATION, DRAINS, BOOTS

ENGINEERING SERVICES

TERMINAL

ATCT

DEMOLITION

6TH FLOOR ROOF DETAILS

NEEPPLEY AIRFIELDOMAHA

PROJECT ENGINEER MGR: ENGINEERING - KANSAS CITY

01/10/2022 1701903

OMA-D-ATCT-D016

o m a -d -a tc t-d .d g n

DRAWING PRODUCED ON ACE RO MICROSTATION SYSTEM

ATO - TECHNICAL OPERATIONS CENTRAL SERVICE AREA

C O

N S

T R

U C

T

IO

N o m a -d -a tc t-d .d g n

/1

/2

:0

:5

P

M P lo tt e d b y S

R V

C -C

A E

G -E

D M

S -C

O O

R D

A

B

C

D

E

F

G

H

8 7 6 5 4 3 2 1

H

G

F

E

D

C

12345678

REVDRAWING NO

DATE JCN

APPROVED BY

ISSUED BY

CHECKED

DRAWN

DESIGNED

SUBMITTED BY

REVIEWED BY

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV

DATE

APPROVED

DESCRIPTION JCN

DATE

REDLINE

APVD

A

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

E D

M

IS

S

U E

D F

O R

(DO NOT DISTURB)

ANTENNA MOUNT RACEWAY ASSEMBLY

ON NEW RACEWAY.)

(REMOVE AND RETAIN FOR INSTALLATION

TO BE REMOVED BY FAA.)

(ANTENNAS AND ASSOCIATED CABLES

WORK SHOWN IN CLOUDS

CONTRACTOR SHALL PERFORM ALL

WORK COMMENCEMENT.

ON-SITE REPRESENTATIVE PRIOR TO

SYSTEM. FULLY COORDINATE WITH THE

FOR NEW FALL PROTECTION/RACEWAY

MOUNT RACEWAY IN PREPARATION

REMOVE THE EXISTING ANTENNA

W/ DWG. A5A AND CONTRACT SPECIFICATION.

REMOVE ROOF HATCH IN ACCORDANCE

DEMOLITION

CONTROL CAB PLANS

OMA-D-ATCT-D017

a -d -a tc t-d .d g n

DRAWING PRODUCED ON ACE RO MICROSTATION SYSTEM

ATO - TECHNICAL OPERATIONS CENTRAL SERVICE AREA

A S -B

U

IL

T

N

N N

N

N

TO WORK COMMENCEMENT.

FULLY COORDINATE WITH THE ON-SITE REPRESENTATIVE PRIOR

AND COORDINATE WITH NEW FALL PROTECTION/RACEWAY SYSTEM.

ROOF SYSTEM IN ACCORDANCE WITH CONTRACT SPECIFICATION

INSULATION AND FLASHING IN PREPARATION FOR NEW

REMOVE EXISTING ROOF SYSTEM INCLUDING MEMBRANE,

o m a -d -a tc t-d .d g n

/1

/2

:0

:5

P

M P lo tt e d b y S

R V

C -C

A E

G -E

D M

S -C

O O

R D

A

B

C

D

E

F

G

H

8 7 6 5 4 3 2 1

H

G

F

E

D

C

12345678

REVDRAWING NO

DATE JCN

APPROVED BY

ISSUED BY

CHECKED

DRAWN

DESIGNED

SUBMITTED BY

REVIEWED BY

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV

DATE

APPROVED

DESCRIPTION JCN

DATE

REDLINE

APVD

A

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

E D

M

IS

S

U E

D F

O

AND PREPARE FOR NEW ROOF SYSTEM.

REMOVE COMPLETE EXISTING ROOF SYSTEM

WALL

PENTHOUSE

MEMBRANE

BAR FOR EPDM

STEEL TERMINATION

SHOWN IN CLOUDS

CONTRACTOR TO PERFORM ALL WORK

AND TAPERED

A C

C E

S S O

P E

N

IN

G

DEMO DRAWING

CIC CAB (AIR-A-PLANE)

ROOFING DETAILS

OMA-D-ATCT-D018

a -d -a tc t-d .d g n

N S

T R

U C

T

IO

N

1' 2'01'

SCALE: 1" = 1'-0"

SCALE: 3" = 1'-0"

9"6"3"3" 0

SCALE: 1-1/2" = 1'-0"

3"6"9"1' 0 1'

JUST BEFORE ENTRANCE TO CONDUIT. TYP. 2 PLACES.

DOWN CONDUCTOR FASTENED AND BONDED TO PARAPET

TYP. 2 PLACES.

1" PVC WITH DOWN CONDUCTOR, FASTENED EVERY 3' TO TRIM.

RACEWAY SYSTEM

PREPARATION FOR CONNECTION TO THE NEW CAB ANTENNA MOUNT/

REMOVE EXISTING DOWN CONDUCTOR AND PORTION OF CONDUIT IN

o m a -d -a tc t-d .d g n

/1

/2

:0

:3

P

M P lo tt e d b y S

R V

C -C

A E

G -E

D M

S -C

O O

R D

A

B

C

D

E

F

G

H

8 7 6 5 4 3 2 1

H

G

F

E

D

C

12345678

REVDRAWING NO

DATE JCN

APPROVED BY

ISSUED BY

CHECKED

DRAWN

DESIGNED

SUBMITTED BY

REVIEWED BY

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV

DATE

APPROVED

DESCRIPTION JCN

DATE

REDLINE

APVD

A

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

E D

M

IS

S

U E

D F

O

Text Box SKETCH - Third Level Roof Fall Protection

1701903ROOF AND FALL PROTECTION UPGRADE01/10/2022F

SIXTH FLOOR AND ROOF PLANS

James L. BlairMark Benne

JBP

06/25/1998

F

PSJ07/07/2008314806AS BUILT INTERIOR MODERNIZATION CCD #04/26/2009E

PSJ 314806INTERIOR MODERNIZATION04/19/2007D

AM06/01/1999314806ANNUAL BASELINE UPDATE CCD #2581809/29/2004C

c e o m a a a s rf .d g n

DRAWING PRODUCED ON ACE RO MICROSTATION SYSTEM

ATO - TECHNICAL OPERATIONS CENTRAL SERVICE AREA

CE-D-OMA-7252-A4A

C O

N S

T R

U C

T

IO

N c e o m a a a s rf .d g n

/1

/2

:0

:3

P

M P lo tt e d b y S

R V

C -C

A E

G -E

D M

S -C

O O

R D

A

B

C

D

E

F

G

H

8 7 6 5 4 3 2 1

H

G

F

E

D

C

12345678

REVDRAWING NO

DATE JCN

APPROVED BY

ISSUED BY

CHECKED

DRAWN

DESIGNED

SUBMITTED BY

REVIEWED BY

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV

DATE

APPROVED

DESCRIPTION JCN

DATE

REDLINE

APVD

A

38'-3"

3'-5" 4'-10 1/2" 12'-0" 6'-2"

11 1/2"9'-10 1/2"

14'-3"

11 1/2"

1'-6 1/2"

18'-2"

9"

8"

18'-2"

9 @ 9 1/2"=7'-1 1/2"5'-2 1/2" 3'-8"

1'-2"

2'-0"

18'-2"11 1/2"

5'-0" 3'-0"8"

18'-2" 11 1/2"

38'-3"

14'-3"

6'-8"

3'-9"

38'-3"

9'-0"

24'-0"

9'-0"

INTEGRITY RELIABILITY

C O

N F

IG

U R

A T

IO

N M A

N A

G E

M E

N T

S

NOITAREPO LACI

N

HC

E T

CHANGES REQUIRE AN AUTHORIZING CCD.

THIS FACILITY IS UNDER CONFIGURATION CONTROL.

CM MANAGER DATE

N O I

T A

R T

SI

NIMDA NOIT

AI

V

A

L

A R

E D

E F

D

M

IS

S

U

R

MARILYN TOMKO 8-11-2009

P

LETTERING

"B" LABEL

ROOM NAME N E S

3'-0"x7'-0"x1 3/4" B 3 6TH FLOOR 3

3'-0"x7'-0"x1 3/4" A 3 7

3'-0"x7'-0"x1 3/4" A 6 7

3'-0"x7'-0"x1 3/4" A 9 7

3'-0"x7'-0"x1 3/4" A 5 MECH. ROOM 7

A 10 - 3 "B" LABEL

A 7 4

2'-6"x7'-0'x1 3/4" A 1 4

3'-0"x7'-0"x1 3/4" A 3 1

W

W

STAIR 'A'

P P P

P

BREAK ROOM

P P P P

P P P P

MECH. ROOM

P P P P

P P P P

P P P P

2HR RATING

P

E C

W

E

W

C

W

W

E C

COAT RACK

BRONZE ANODIZED STORM-PROOF LOUVER

W.G. DIFFERENTIAL PRESSURE, STAIR

TO ELEVATOR LOBBY. ROOF HATCH

E C

W

1'O"x4'0"x4" DEEP

DOWN 10 R

S T

A

IR

B

E C

W

1.

2.

3.

SEE NOTES SHEET A1

W

W

E C

P

P P P P

P

REMOVE AND DISPOSE:

ILS MONITOR ANTENNA

SUPPORT PER

DETAIL ON DWG.

CONDUCTOR

IN INSET OF CORNER

SEE "TYPICAL ROOF EDGE

DETAIL", DWG. CE-D-7252-A4-1,

SHEET 1.

WAVE GUIDE ROOF ENTRANCE

ASSEMBLY PER DRAWING

CE-D-7385-2A.

WAVE GUIDE SUPPORT

TO PERIMETER CABLE

ALONG RACEWAY ON CAB ROOF

TOWER CAB

SEE SHT. A4-1 AT CAB BASE

1 1/4" GALV. PIPE

HANDRAIL. SEE

DETAIL THIS SHEET

SEE STRUCTURAL DRAW-

INGS FOR LOCATION.

4" DIA. TML

ANTENNA

TML ANTENNA MOUNTING

ASSEMBLY PER DWG.

CE-D-7385-2.

ROOF REPLACED IN 1999

W/ FIRESTONE ADHERED

EPDM MEMBRANE.

EPDM FIREST0NE WALKPADS.

PADS ARE SPACED 1" TO 3"

BETWEEN PADS. CUT 3"-6"

WIDE CHANNEL IN PADS TO

ALLOW RUNOFF FLOW TO

DRAINS IN SWALE OF ROOF.

ILS MONITOR ANTENNA

SUPPORT PER DETAILS ON

DWG. CE-D-7252-A4-1.

DOWN CONDUCTOR

IN INSET OF CORNER

TO COUNTERPOISE

SEE DWG. CE-D-7252-A4-1 FOR EDGE AND

FLASHING DETAILS.

SCALE: 1/4" = 1'

FIELD-FABRICATED PIPE BOOT

LAPPED MIN. 3" & OUT 3" FROM

EDGE OF PIPE ONTO MEMBRANE

20 GA. GALV. SHEET METAL

HIGH W/ 2" LAP AT PIPE

SEALED AT TOP W/CAULKING.

METAL HAS FLAT BLACK FINISH.

LIGHT-WEIGHT

CONCRETE FILL INSULATION

METAL DECK

BOLT TO BEAM

4"x6"x1/4" WELDED

ANCHOR PLATE

THIS DRAWING REPLACES CE-D-7252-A4

DWG. CE-D-7252-A21

4.

5.

W

E C

W

E C

W

E C

SCALE:

HANDRAIL DETAIL AT ROOF

A43" = 1'-0" A4

A9A1

A9A1

A9A1

7A9A1

S2A4

A1

A

A

A

A4

3A

A

A

A

7'-10 1/2"

CONCRETE FILL

1" FIBERBOARD

SUBSTRATE OVER

INSULATION

60 MIL ADHERED

EPDM MEMBRANE

ROOF PLAN

5'-0" x 6'-0" x 4"

DEEP WEATHERPROOF

MECHANICAL

BREAK ROOM

D

1 1/4" STD. GALV. PIPE RAILING

2 RAIL, 3'-6" ABOVE ROOF SURFACE

HANDRAIL, FLAT BLACK6.

ROOF WITH 80 MIL ADHERED TPO

SINGLE-PLY MEMBRANE OVER 1/2" COVERBOARD

POLYISOCYANURATE BOARDS AND CONCRETE FILL INSULATION.

TO OBTAIN WARRANTY AND POSITIVE DRAINAGE.

ACCORDING TO MANUFACTURERS' RECOMANDATIONS

TAPERED CRICKET AROUND FAN SHROUD

N

M

L

1.311.11

L

N

EXHAUST FAN

DOWN CONDUCTOR

4" VENT

RIDGE

3" VENT STACK

DOWN

WOOD BLOCK, TYP

EVERY 3'-0"

DOWN CONDUCTOR

TO COUNTERPOISE

PRECAST PANEL BELOW

RADIO ANTENNA SUPPORT

PER DETAIL ON DRAWING

CE-D-7552-A4-1.

PER DWG. CE-D-7385-2A.

SEE DWG. CE-D-7385-2

FOR ROOFING & FLASHING

AROUND TML EQUIPMENT.

RIDGE

FLASHING DETAIL FOR TYPICAL

FLASHING DETAIL.

RIDGE

ROOF

HATCH

SEE

SPEC

3" R.D.

RIDGE

3" R.D.

3" R.D.

PRECAST PANEL

BELOW

3" VENT STACK

3" R.D.

2'-6" X 3'-0"

1.11 1.17

DOOR

SIZE TYPE

HDW

SET

NO.

SIGN

ON DOOR

DET.

NO.

ON.

SHT.

A-B

REMARKS

DOOR SCHEDULE

ROOM

NO. FLOOR

WALLS

ROOM FINISH SCHEDULE

6-1

STAIR

6-2

TRAINING

6-3 STAIR

6-4 E.P.D.O.

6-5

6-6 PR 3'-0"x6'-8"x1 3/4"

6-7 2'-6"x7'-0"x1 1/34" TOILET

6-8 CLOSET

6-9 HALL

"B" LABEL DOOR & LABELED FRAME.

600 CONC CMU CMU CMU CMU &

STRUC

601 GWB GWB GWB GWB

602 E.P.D.O. GWB GWB GWB GWB

603 GWB

CMU

CMU

GWB GWB GWB

CMU CMU CMU

CMU CMU CMU

604 CABLE CHASE GRATING

605 ELEVATOR

606 TOILET

CER. CMU CMU CMU CMU

607 CLOSET

CMU CMU CMU CMU

608 LOBBY GWB GWB GWB GWB

609 HALL GWB GWB GWB GWB

SUSP.

GYP. BD.

CEILING

STRUCT.

ACOUSTIC

PANEL

605 600

6-6

6-3

6-2

6-5

6-9

6-4

6-1

6-8

6-7

ACCESS PNL.

11 - 12"x12"x60"

DOUBLE TIER LOCKERS

& MOTORIZED DAMPER CONTROLLED BY

PRESSURE SWITCH SET TO OPEN AT .15"

FIREPROOF ACCESS PANEL

TO FIREDAMPER

2 HR. CEILING

ACCESS PANEL

4"x4" CONC. CURB

TO FACP

TO FACP

TO FACP

EDGE OF CEILING DROP

2'-6"

FLOOR

HATCH

COVER

2'-6" x 4'-0" x 4" DEEP

WEATHERPROOF TYPE LOUVER

W/BIRD SCREEN

WEATHGERPROOF

TYPE LOUVER

W/BIRD SCREEN

U P

FIN. FL. EL. 137'-9"

ALL CEILING HEIGHTS ARE 9'-0" EXCEPT

TOILET, CLOSET & E.P.D.O. ARE 8'-0".

NOT USED

USED VINYL BASE AT VAT FLOORING.

SCALE: 1/4" = 1'

6TH FLOOR BLDG. AREA - 1288.125 S.F.

ROOM

ELECTRIC STRIKE

VISION PANEL

TILE PT-4 PT-4 PT-4 PT-4

GWB

PT-4

GWB

2HR. GWB

2HR. CEILING IN HALL 609 & CAB

STAIRWAY. SEE DWG. A-11

FOR KITCHEN UNIT LAYOUT, SEE

P.H.

TOWEL

AND

WASTEMIRROR

SCREEN

F .H .C

TO FACP

FLOOR GRATING

SEE SECTION

1'-0"

A10

A13

2HR. CEILING IN HALL 609 & CAB

REFER TO DWG. CE-D-7252-A5A FOR LEGEND

7'-3"

6TH FLOOR PLAN

NOTES:

TYPE LOUVER

W/BIRD SCREEN

TOILET CLOSET

ELEVATOR

LOBBY

HALL

CABLE CHASE

"A"

STAIR

MECHANCIAL ROOM

E.P.D.O. (FUT.)

COLUMN & BLDG. LINE

EPOXY FLOOR COATING

TENNANT ECO-PT 250 & ECO-HTS 100

ACT-1

ACT-1

VCT-1

VCT-1

NOTE 6

W/EPOXY

CONC.

VCT-1

VCT-1

VCT-1

RT-1

1.31

OVER LADDER

TO ROOF

SHAFT

NO.

F

REPLACEMENT.

PROTECTION SYSTEM AS REQUIRED FOR THE ROOF

INFORMATION. REMOVE AND REINSTALL THE LIGHTNING

CONTRACT DRAWINGS AND SPECIFICATION FOR MORE

THE EAST HALF OF THE ROOF AREA. REFER TO THE

THE WEST HALF AND A FALL RESTRAINT SYSTEM ON

SYSTEM WHICH INCLUDES A GUARDRAIL SYSTEM ON

SUPPLY AND INSTALL OSHA COMPLIANT FALL PROTECTION

MEMBRANE COVER BOARDS, INSULATION AND FLASHING.

INSTALL A FULL EPDM ROOF SYSTEM INCLUDING

REMOVE: EXISTING EPDM ROOF SYSTEM. SUPPLY AND

CONTRACTOR SHALL PERFORM ALL WORK

SHOWN IN CLOUDS

F

F

STACK

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

E D

M

IS

S

U E

D F

O R

REMOVE AND DISPOSE:

F

REMOVE AND DISPOSE:

SYSTEM

NEW COMPLETE INSULATED

AND CURB. REPLACE WITH

REMOVE: ROOF HATCH LID

BY THE FAN MANUFACTURER.

MAINTAIN CRICKET AND FLASHING AS REQUIRED

REMOVE AND REPLACE EXHAUST FAN AND CURB.

CE-D-7252-A4-1

1701903ROOF AND FALL PROTECTION UPGRADE01/10/2022J

CONTROL CAB PLANS

James L. BeselMark Benne

JBP

05/25/1998

J

PLJ02/14/2012500666AS BUILT CAB MODERNIZATION09/13/2012H

PLJ07/07/2008500666AS BUILT INTERIOR MODERNIZATION CCD #04/26/2009G

PLJ 314806INTERIOR MODERNIZATION04/03/2007F

c e o m a a a s rj .d g n

DRAWING PRODUCED ON ACE RO MICROSTATION SYSTEM

ATO - TECHNICAL OPERATIONS CENTRAL SERVICE AREA

CE-D-OMA-7252-A5A

C O

N S

T R

U C

T

IO

N c e o m a a a s rj .d g n

/1

/2

:0

:4

P

M P lo tt e d b y S

R V

C -C

A E

G -E

D M

S -C

O O

R D

A

B

C

D

E

F

G

H

8 7 6 5 4 3 2 1

H

G

F

E

D

C

12345678

REVDRAWING NO

DATE JCN

APPROVED BY

ISSUED BY

CHECKED

DRAWN

DESIGNED

SUBMITTED BY

REVIEWED BY

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV

DATE

APPROVED

DESCRIPTION JCN

DATE

REDLINE

APVD

A

E D

M

IS

S

U

R

FLUORESCENT

12"x12"

CONTROL CAB CONSOLES SHOWN ABOVE AND DETAILED ON DWGS. CE-D-7252-A14 THRU A17.

4" HOLE THRU CEILING

1/

1'-5 11/16"

" 7'-6 13/16"

4'-4 9/16"

7" RAISED FLOOR SYSTEM

(SEE DETAIL ABOVE)

METAL CEILING HATCH

NOTE 3

MONTE CARLO 4C028 COLONY II, 4-BLADE CEILING FAN. BLACK IN COLOR.

LIGHTOLIER BLACK MATTE EYEBALL CAN LIGHT FIXTURE LOL1062 LV W/6497BK MR16 FRAMING PROJECTOR & 1000LV FRAME.

SUPERVISOR'S CONSOLE PER DWG. CE-D-OMA-7252-A16.

CONVENIENCE UNIT, SEE DWG. CE-D-OMA-7252-A17.

STAIR SHELF, CORIAN BRAND; COLOR IS PLATINUM, SIZE 30"x50" W/4" BACK SPLASH.

9. HEADSET/BINDER STORAGE UNIT PER DWG. CE-D-OMA-7252-A15.

1.

2.

3.

4.

5.

6.

7.

8.

ATC

NOT TO SCALE

FLOOR

CEILING

CEILING TILE & GRID

(a) PLASTIC LAMINATE

CONSOLES

STAIRS

& WALLS

(a) PLASTIC LAMINATE

(b) PAINT

BLACK #205

ITEM COLOR MANUFACTURER

S.R.P. = SIGNAL REFERENCE PLANE

NOTES:

LEGEND:

CAB ROOM FINISH AND COLOR LEGEND

GALILEO #4070 JULIE INDUSTRIES

TOP OF GLASS PANELS

EDGE OF ROOF

SCALE: 1/4" = 1'-0"

SCALE: 1/4" = 1'-0"

LIGHTNING AIR TERMINAL ACCESS HOLE (5 PLACES)

ANTENNA MOUNT

LIGHTNING AIR TERMINAL SUPPORT

MASTS AND AIR TERMINALS. SEE

DWG. CE-D-7252-E10 FOR

FABRICATION AND INSTALLATION

MOUNT/RACEWAY SYSTEM.

RELOCATED TO NEW ANTENNA

DETAILS (TYP 5 PLACES) TO BE

DRAIN (3 PLACES)

SUPPLY AND INSTALL: NEW ROOFTOP

ANTENNA MOUNT/CABLE RACEWAY

SLOPE1/2" TO 5/8" (TYP.)

HATCH

PENTHOUSE

PER DETAIL ON DWG.

HVAC VENT HOODS

CE-D-7252-A5-1

OBSTRUCTION LIGHT

(5 PLACES)

CEILING

HATCH

ROOF NOTICE STICKER TO

INSIDE OF HATCH COVER

ZONE SENSOR

(TYP 2 PLACES)

SMOKE DETECTOR

LIGHT FIXTURE

(12 PLACES)

CLOSURE

PANEL

REMOTE

DETECTOR

FOR

PENTHOUSE

CEILING GRID

AND PANELS

CEILING CLOSURE

PANEL AND EXHAUST

AIR SLOT

WINDOW SHADE

POCKET

CHAIN HOIST HOOK

RECESS

CEILING PANEL

(5 PLACES)

REFLECTED CEILING PLAN ROOF PLAN

FROST CLIMAPLUS #414-205, 8 PIECES / CARTON

USG INTERIORS, INC. SHADOW LINE EDGE

1595-60 BLACK

1595-60 BLACK

ESD CARPET W/CONDUCTIVE RESEALABLE

ADHESIVE OVER 1/2" PLYWOOD WHICH IS OVER

COPPER EQUIPOTENTIAL PLANE (EPP) (CPT-4)

REF. DWG. CE-D-7252-E11.

2' X 2' X 3/4" ACOUSTICAL LAY-IN

(b) ESD PLASTIC LAMINATE

(c) PAINT (POWDER COAT)

(c) SOLID SURFACE TRIM WORK

SDG S60074T-BLACK

BLACK

VARIOUS

PLATINUM

WILSONART

NEVAMAR

WILSONART

VARIOUS

CORIAN BRAND

SCALE: 1/4" = 1'-0"

FLOOR PLAN

SCALE: 1/4" = 1'-0"

FLOOR PLAN-CONSOLE LAYOUT

FLOOR PLAN-STRUCTURE

NOTE 9

NOTE 5

SUPERVISOR'S CONSOLE

NOTE 4

SHELF

NOTE 8

CONVENIENCE UNIT

NOTE 7

7" RAISED FLOOR

NOTE 5

2'x2' ACOUSTICAL TILE CEILING AND

GRID PER FINISHED SCHEDULE THIS

DETAIL

SHEET, SEE METAL CEILING HATCH

(2 PLACES)

ABANDON IN PLACE

LIGHT GUN BOX

CEILING FAN

(2 PLACES)

NOTE 2

SLATWALL CONSOLE SYSTEM

BY EVANS CONSOLES

FAA MODEL C-1c STANDARD ATCT CAB

REFER DETAILS ON DWG. CE-D-OMA-7252-A15

OPEN TO FLOOR BELOW

SLATWALL CONSOLE SYSTEM

BY EVANS CONSOLES

INSTALLED IN SPRING 2012

TATE CONCOR CC1250 ALL STEEL 24"x24" RAISED FLOOR SYSTEM @ 7" TALL.

CONSOLE FINISHES BELOW AND DWG. CE-D-OMA-7252-A15.

(NOTE 5)

INSTALLED SPRING 2012

LIGHT FIXTURE (TYP. 3 PLACES)

CONTROL

GROUND

FLIGHT

DATA

CONTROL

LOCAL

NOTE: THIS DRAWING REPLACES CE-D-7252-A5.

CONTRACT SPECIFICATION.

WITH THE MANUFACTURER'S RECOMMENDATIONS AND THE

INSULATION, MEMBRANE, DRAINS AND FLASHING IN ACCORDANCE

80 MIL SLOPE EDPM ROOF SYSTEM COMPLETE WITH R-30

SUPPLY AND INSTALL:

REPLACE THE PENTHOUSE

LID INCLUDING INSULATED

HATCH AND SEALS IN

ACCORDANCE WITH

CONTRACT SPECIFICATION

ROOF

SUPPLY AND INSTALL PENTHOUSE

STEP SYSTEM PER CONTRACT

SPECIFICATION AND DETAIL 'E'

ON DWG. OMA-D-ATCT-A019

SYSTEM IN ACCORDANCE WITH THE

CONTRACT SPECIFICATION AND

DWG. OMA-D-ATCT-A018 AND A019

RE-INSTALL LIGHTNING PROTECTION

SYSTEM ON NEW ROOFTOP

ANTENNA MOUNT/RACEWAY

NOT BEING USED, SEE DWG. CE-D-7252-E2.

ALL WORK SHOWN IN CLOUDS

CONTRACTOR SHALL PERFORM

J

J

INTEGRITY RELIABILITY

C O

N F

IG

U R

A T

IO

N M A

N A

G E

M E

N T

CHANGES REQUIRE AN AUTHORIZING CCD.

THIS FACILITY IS UNDER CONFIGURATION CONTROL.

CM MANAGER DATE

SPECIFICATION

WITH NEW PER CONTRACT

PULL-DOWN LADDER AND REPLACE

REMOVE EXISTING CAB CEILING

J

J

N

N

N

N

N

X

X0

X

X001

X

X

SCALE: 1/4" = 1'-0"

4' 8'04'

J

J

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

E D

M

IS

S

U E

D F

O R

Rectangle

1701903ROOF AND FALL PROTECTION UPGRADE01/10/2022E

TYPICAL WINDOW AND WALL DETAILS

LLOYD O. HOLMRALPH C. KENNEDY

RHT

JRC

ACD

PROJECT ENGINEER MGR: ENGINEERING - KANSAS CITY

01/30/1974

E

RCM 1403420REPLACE ALL WINDOWS IN OMA ATCT FUNCT04/04/2016D

RCM AS-BUILT01/21/19893

JSL SMPS63INSTALL NEW ROOF MEMBRANE04/28/19882

c e o m a a s re .d g n

DRAWING PRODUCED ON ACE RO MICROSTATION SYSTEM

ATO - TECHNICAL OPERATIONS CENTRAL SERVICE AREA

CE-D-OMA-7252-A13

C O

N S

T R

U C

T

IO

N c e o m a a s re .d g n

/1

/2

:0

:0

P

M P lo tt e d b y S

R V

C -C

A E

G -E

D M

S -C

O O

R D

A

B

C

D

E

F

G

H

8 7 6 5 4 3 2 1

H

G

F

E

D

C

12345678

REVDRAWING NO

DATE JCN

APPROVED BY

ISSUED BY

CHECKED

DRAWN

DESIGNED

SUBMITTED BY

REVIEWED BY

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV

DATE

APPROVED

DESCRIPTION JCN

DATE

REDLINE

APVD

A

A3 A13 SCALE: 1 1/2" = 1'-0"

1A

A13 SCALE: 1 1/2" = 1'-0"

A1 A13

A4 A13

A13

SECTION PRECAST AT ROOF

SCALE: 3/4" = 1'-0"

A13

SECTION

SECTION

SCALE: 3/4" = 1'-0"

SECTION

WALL SECTION AT

CONCOURSE RAMP

A6 A13

SCALE: 3/4" = 1'-0"

3-A

TYPICAL WINDOW SECTION

TYPICAL EXTERIOR

MASONRY WALL REINF

DETAIL OF PRE-CAST

ANCHOR AT FLOOR

NOT TO SCALE

NOT TO SCALE

WELD

CONCRETE. EACH END OF

SEALANT

WALL ANCHORS

FOR LEDGER AND

SEE SECTION

GROUT IN WALL

NO.4 AT 4'-0" OC

3/16" WIRE

2 - 3/8" DIA x 6" LG STUDS

ANGLE-2 1/2"x2 1/2"x3/8"x0'-5"

1/4

ANGLE-2 1/2"X2 1/2"X3/8"X0'-3"

4 - 1/2" DIA ANCHORS

4 PER 7'-4" PANEL

ANCHORS-2 PER 3' PANEL

4" NOMINAL

FACE BRICK

EXISTING

SLAB

L

X

IS

T

G

N C

O U

R S

E

VAPOR BARRIER

W16

SECOND FLOOR ELEV 88'-0"

SUSPENDED CEILING

FIREPROOFING SPRAY-ON

W16

THIRD FLOOR ELEV 101'-9"

METAL STUDS & 1/2" GWB

FOURTH FLOOR ELEV 113'-9"

W16

FIREPROOFING SPRAY-ON

SUSPENDED CEILING

AND 1/2" GWB (PAINT)

METAL FURRING CHANNELS

FIREPROOFING SPRAY-ON

W16

FIFTH FLOOR ELEV 125'-9"

TERMINATION

AND MEMBRANE

FOR EDGE FLASHING

DWG CE-D-7252-A4-1

SEE DETAILS ON

3 1/2" BATT INSULATION

AND 1/2" GWB (PAINT)

METAL FURRING CHANNELS

FIREPROOFING SPRAY-ON

W16

(SPRAY-ON)

FIREPROOFING

W10 (VARIES, SEE DWG S4)

INSULATED CONCRETE FILL

SOLDIER COURSE

COPING

18 GA GALV

PRECAST

ANCHOR AT 16" OC

TWISTED GALVANIZED

TO BM

AT 3'-0" OC WELD

PLATE ANCHORS

5/16"x2" BENT

COPING

18 GA GALVANIZED

CONT

BOND BEAM 2-NO.4

TOP OF STEEL EL 149'-11"

DRAINS

7 1/2" MAXIMUM, 4" AT

1/2" GWB

METAL STUDS AND

SIXTH FLOOR EL 137'-9"

WITH POLYETHELENE VAPOR

T

L

8"

A13S2

INSULATION

1" RIGID

BLOCK

LIGHTWEIGHT

SPRAY-ON

FIREPROOFING

8" METAL STUDS AND 1/2" GWB

EL 76'-0"

FIRST FLOOR

INSULATION

2" PERIMETER

FILL

4" GRANULAR

5"x5"x1/2" PLATE WITH

VERTICAL REINFORCING

1/4"x2" TWISTED STRAP

INSERT IN PRECAST

ANCHOR 1/2" BOLT TO

PANEL AT HEAD AND SILL

HEAD FLASHING

EXIST. PRECAST CONC PANEL

EXIST. FOAM BOARD INSUL.

EXIST. 4" NOM. CMU BEYOND

EXIST. 5/8" GYPSUM BEYOND

SEALANT

BRICK BEYOND

P

R E

C A

S T

P

R E

C A

S T

CIP CONCRETE

SEALANT

WITH VAPOR BARRIER

EXIST. FIBERGLAS BATT INSUL

EXISTING VENETIAN BLINDS

LINE OF GYP WALL BEYOND

INSULATED ALUMINUM WINDOW

VINYL TILE

EXISTING CARPET TILE OR

STRAIGHT AT CARPET

VINYL BASE COVED AT TILE

SEALANT

SEALANT

WITH BULLNOSE

SOLID SURFACING MATERIAL SILL

EXIST. FOAM BOARD INSULATION

EXISTING BRICK BEYOND

PAN FLASHING SET IN

SEALANT WITH END DAMS

EXIST. METAL STUDS

STEEL BEAM

PROTECTION ON

EXIST. CEMENT FIRE

CIP CONCRETE

SCALE: 1 1/2" = 1'-0"

10 3/8"

3 5/8" STUD CONT.

7/8" FURRING CHANNEL

1/2" GYPSUM BOARD

RIDGID INSULATION

1 1/2" STUDS

SPANDREL PANEL

EXISTING PRECAST CONC.

2-NO. 4

POLYETHELENE VAPOR BARROR

(2nd & 3rd FLOORS)

FIN TUBE RADIATOR

3 1/4" LIGHT WT. CONC.

1 1/2" STEEL DECK

LOCATION SEE 2/A13

GYPSUM BOARD - VARIES BY

EXISTING ACOUSTICAL TILE OR

A13

A6 A13

WALLCOVERING

WITH PAINTED FINISH OR

GYPSUM WALLBOARD PRIMED

A9A9

4x4-3/ GALV. W.W.M.

5 1/2" +/-

NOTES:

1) GLASS MAY BE INSTALLED IN FRAMES AT SHOP AND

PLACED IN OPENINGS FROM BUILDING INTERIOR. FINAL

SEALING OF WINDOW FRAME TO SUBSTRATE MUST BE

PERFORMED FROM THE EXTERIOR.

A13A13

4x4-3/GALV. W.W.M.

2-#4

GALVANIZED HORIZONTAL JOINT

REINFORCING AT 16" O.C.

2) DO NOT USE WOOD SHIMS OR BLOCKS TO SUPPORT

OR BRACE WINDOW FRAMES.

FINISHED EXTERIOR WALLS

BARRIER TYPICAL ALL

1A

A13A13

BEYOND

EXIST. 3 5/8" MTL STUDS

A13A13

HEAD DETAIL

SCALE: 3" = 1'-0"

A13A13

A13A13

SILL DETAIL

SCALE: 3" = 1'-0"

A13

TPO MEMBRANE

80 MIL ADHERED

1/2" COVERBOARD

POSITIVE DRAINAGE AND R-30.

INSULATION NEED TO PROVIDE

RIGID INSULATION AND TAPERED

E

REMOVE EXISTING EPDM ROOF

SYSTEM. SUPPLY AND INSTALL

GUARDRAIL SYSTEM AND NEW EPDM

ROOF SYSTEM IN ACCORDANCE

WITH CONTRACT SPECIFICATION

E

CONTRACTOR SHALL PERFORM ALL WORK

SHOWN IN CLOUDS

E

SCALE: 3" = 1'-0"

9"6"3"3" 0

SCALE: 3/4" = 1'-0"

3'2'1'01'

SCALE: 1 1/2" = 1'-0"

3"6"9"1' 0 1'

E

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

E D

M

IS

S

U E

D F

O

ACCORDANCE WITH THE CONTRACT SPECIFICATION.

DRAINS, INSULATION, BOOTS, MEMBRANE AND FLASHING IN

SUPPLY AND INSTALL NEW EPDM ROOF SYSTEM INCLUDING

CONTRACTOR SHALL PERFORM ALL WORK SHOWN IN CLOUDS

ACCORDANCE WITH THE CONTRACT SPECIFICATION.

HALF OF THE SHAFT ROOF PERIMETER ON BUILDING EXTERIOR FACE IN

DESIGN, SUPPLY AND INSTALL GUARDRAIL SYSTEM AROUND THE WEST

REPLACE VENT FAN

ACCORDANCE WITH THE CONTRACT SPECIFICATION.

DRAINS, INSULATION, BOOTS, MEMBRANE AND FLASHING IN

SUPPLY AND INSTALL NEW EPDM ROOF SYSTEM INCLUDING

ACCORDANCE WITH THE CONTRACT SPECIFICATION.

DRAINS, INSULATION, BOOTS, MEMBRANE AND FLASHING IN

SUPPLY AND INSTALL NEW EPDM ROOF SYSTEM INCLUDING

REROOF AND FALL PROTECTION

6TH FLOOR ROOF DETAILS

OMA-D-ATCT-A016

a -d -a tc t-a .d g n

N S

T R

U C

T

IO

N

VENT FAN DETAIL

NOT TO SCALE ROOF DRAIN DETAIL

NOT TO SCALE

ROOF SCHUTTLE DETAIL

NOT TO SCALE

VENT FAN DETAIL

NOT TO SCALE

DETAIL AT PRECAST PANELS

NOT TO SCALE

TYPICAL ROOF EDGE DETAIL

NOT TO SCALE

o m a -d -a tc t-a .d g n

/1

/2

:0

:1

P

M P lo tt e d b y S

R V

C -C

A E

G -E

D M

S -C

O O

R D

A

B

C

D

E

F

G

H

8 7 6 5 4 3 2 1

H

G

F

E

D

C

12345678

REVDRAWING NO

DATE JCN

APPROVED BY

ISSUED BY

CHECKED

DRAWN

DESIGNED

SUBMITTED BY

REVIEWED BY

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV

DATE

APPROVED

DESCRIPTION JCN

DATE

REDLINE

APVD

A

DRAWING CE-D-7252-A4-1-S1, REVISION D, DATED 07/13/99

DRAWING OMA-D-ATCT-A016, DATED 06/10/21, SUPERSEDES

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

E D

M

IS

S

U E

D F

O

ROOF AND FALL PROTECTION

6TH FLOOR DETAILS

OMA-D-ATCT-A017

a -d -a tc t-a .d g n

N S

T R

U C

T

IO

N

CONTRACT SPECIFICATION.

ROOF SYSTEM IN ACCORDANCE WITH THE

SYSTEM (LID/CURB) WITH COMPLETE INSULATED

REMOVE AND REPLACE COMPLETE ROOF HATCH

CONTRACT SPECIFICATION.

NEW MEMBRANE ROOF SYSTEM IN ACCORDANCE WITH

MEMBRANE, BOOTS AND INSULATION. SUPPLY AND INSTALL

REMOVE EXISTING ROOF SYSTEM INCLUDING FLASHING,

SPECIFICATION.

ACCORDANCE WITH CONTRACT

NEW GUARD RAILING SYSTEM IN

PREPARE AREA, SUPPLY AND INSTALL

PER NOTE 2, SHEET 1

EPDM MEMBRANE

NOTE 1, SHEET 1

SUBSTRATE, PER

WOOD FIBERBOARD

CONCRETE FILL

EXISTING INSULATED

CONTRACTOR TO PERFORM ALL WORK

PRIOR TO INSTALLATION OF NEW ROOF SYSTEM

REMOVE AND DISPOSE OF ANTENNA MOUNT

o m a -d -a tc t-a .d g n

/1

/2

:0

:3

P

M P lo tt e d b y S

R V

C -C

A E

G -E

D M

S -C

O O

R D

A

B

C

D

E

F

G

H

8 7 6 5 4 3 2 1

H

G

F

E

D

C

12345678

REVDRAWING NO

DATE JCN

APPROVED BY

ISSUED BY

CHECKED

DRAWN

DESIGNED

SUBMITTED BY

REVIEWED BY

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV

DATE

APPROVED

DESCRIPTION JCN

DATE

REDLINE

APVD

A

DRAWING CE-D-7252-A4-1-S2, REVISION 2, DATED 7/13/99

DRAWING OMA-D-ATCT-A017, DATED 06/10/21, SUPERSEDES

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

E D

M

IS

S

U E

D F

O R

SCALE: 3" = 1'-0"

9"6"3"3" 0

SCALE: 6" = 1'-0"

18"12"6"6" 0

CONTRACTOR SHALL PERFORM ALL WORK

PENTHOUSE WALL

REQUIRED DETAILS

EPDM FLASHING PER MANUFACTURER'S

FOR FLASHING AND MEMBRANE

STEEL TERMINATION BARS

TAPERED INSULATION PER NOTE 1

ROOF DECK

REQUIRED DETAILS

EPDM FLASHING PER MANUFACTURER'S

PARAPET WALL

WOOD BLOCKING

MEMBRANE PER NOTE 2

0.060" THICK EPDM

ACCESS OPENING

-3 /4

C E

N T

E R C

O L

U M

N C

A V

IT

Y

" O

P E

N

IN

G

IN

T O

2 3/4"

ROOF PANEL ASSEMBLY

SUPPLY AND INSTALL NEW EPDM ROOF

SYSTEM COMPLETE WITH DRAINS,

INSTALLATION, BOOTS, MEMBRANE

AND FLASHINGS IN ACCORDANCE

WITH THE CONTRACT SPECIFICATION.

6"

U N

IT

B

45 1/2"

/2

U N

IT

A

13"

/2

"7"

/2

/8

REROOF AND FALL PROTECTION

CIC CAB (AIR-A-PLANE)

ROOFING DETAILS

OMA-D-ATCT-A018

a -d -a tc t-a .d g n

N S

T R

U C

T

IO

N

BELOW.

OF BOARD ARE STAGGERED FROM THE JOINTS OF INSULATION

AND TAPERED INSULATION INTO STEEL ROOF DECK. JOINTS

INSULATION W/TAPDEK MECHANICAL FASTENERS THRU BOARD

3. 1/2" THICK LAYER OF WOOD FIBERBOARD OVER TAPERED

(FIRESTONE RUBBER MANUFACTURER).

2. 60 MIL THICKNESS FULLY ADHERED EPDM MEMBRANE

REQUIREMENTS OF THE MEMBRANE MANUFACTURER.

INSULATION WAS MECHANICALLY ATTACHED IN PLACE PER

POSITIVE DRAINAGE WILL BE ATTAINED TO THE ROOF DRAINS.

INSULATION WITH NECESSARY CRICKETS AND SLOPES SO

1-3/8" THICKNESS AT DRAINS AND ROOF EDGES. INSTALL

SPEC. HH-1-1972 WITH 1/4" PER FOOT MINIMUM AND A MIN.

1. TAPERED POLYISOCYANURATE INSULATION MEETING FEDERAL

NOTES:

GENERAL CROSS SECTION

NOT TO SCALE

o m a -d -a tc t-a .d g n

/1

/2

:0

:2

P

M P lo tt e d b y S

R V

C -C

A E

G -E

D M

S -C

O O

R D

A

B

C

D

E

F

G

H

8 7 6 5 4 3 2 1

H

G

F

E

D

C

12345678

REVDRAWING NO

DATE JCN

APPROVED BY

ISSUED BY

CHECKED

DRAWN

DESIGNED

SUBMITTED BY

REVIEWED BY

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV

DATE

APPROVED

DESCRIPTION JCN

DATE

REDLINE

APVD

A

SCALE: 3" = 1'-0"

9"6"3"3" 0DETAIL AT ROOF DRAIN

SCALE: 3"=1'-0"

DETAIL AT PARAPET

SCALE: 3"=1'-0"

EPDM MEMBRANE, PER NOTE 2

TAPERED INSULATION, PER NOTE 1

WOOD FIBERBOARD SUBSTRATE, PER NOTE 3

IN ACCORDANCE WITH THE CONTRACT SPECIFICATION.

INSTALLATION, BOOTS, MEMBRANE AND FLASHINGS

ROOF SYSTEM COMPLETE WITH DRAINS,

SUPPLY AND INSTALL NEW EPDM

2 PLACES

GASKET, NEOPRENE SHEET, .060" THICK

JOINT CAP, SEE AX959-0157C

NO. 14 X 1/2 CRES WITH SEAL WASHER

HEX HEAD SCREW, TYPE "Z"

CONDUIT (TYP. 2 PLACES)

TO PARAPET JUSTBEFORE ENTRANCE TO

DOWN CONDUCTOR FASTENED AND BONDED

EVERY 3' TO TRIM (TYP. 2 PLACES)

1" PVC WITH DOWN CONDUCTOR, FASTENED

MOUNT/RACEWAY SYSTEM

NEW CAB ROOF ANTENNA

PROTECTION SYSTEM TO

REINSTALL LIGHTNING

ROOF DRAIN

2" DRAIN TUBE

SCALE: 1-1/2" = 1'-0"

3"6"9"1' 0 1'

DETAIL AT PENTHOUSE WALL

SCALE: 1-1/2"=1'-0"

TERMINATOR BAR FOR EPDM FLASHING

SUBSTRATE PER NOTE 3

WOOD FIBERBOARD

PER NOTE 2

EPDM MEMBRANE

PER NOTE 1

TAPERED INSULATION

1' 2'01'

SCALE: 1" = 1'-0"

FRONT ELEVATION SIDE ELEVATION

CAB PENTHOUSE

INTAKE HOOD ON EMERGENCY VENT LOUVERS

DEATAIL

SCALE: 1" = 1'-0"

OF CAULKING

SET BED IN HOOD

WITH NO. 6 SHEET METAL SCREWS

FASTENED ON 6" CENTERS

1-1/2" FLANGE (TYP.)

UNIT B, 20GA GALV.

UNIT A, 20GA GALV.

DRAWING CE-D-7252-A5-1, REVISION 3, DATED 3/22/93

DRAWING OMA-A-ATCT-A018, DATED 06/10/21, SUPERSEDES

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

E D

M

IS

S

U E

D F

O

TYP.

3/16

PRIOR TO WORK COMMENCEMENT.

WELD TO PIPE WITH WEATHER-TIGHT WELDS

CAP PLATE x 1/4 LESS THAN PIPE I.D.

PIPE SCH. 40 (3" I.D.) WITH CAB

10'-0" LONG BY 3" DIA. FIBERGLASS

WITH STD. NUT AND WASHER, TYP.

3/8" DIA STAINLESS STEEL

BOLTED CONNECTION USING

PLATE 1/2" WITH 2-1/2" DIA. HOLE TYP.

SCH. 40 PIPE (2.88" O.D.)

PROVIDE CLOSURE PLATE

SCH. 40 PIPE (2.88" O.D.)

2-1/2" 6061-T6 ALUMINUM

CAB ROOF GUARDRAIL SYSTEM

OMA-D-ATCT-A019

a -d -a tc t-a .d g n

N S

T R

U C

T

IO

N o m a -d -a tc t-a .d g n

/1

/2

:0

:2

P

M P lo tt e d b y S

R V

C -C

A E

G -E

D M

S -C

O O

R D

A

B

C

D

E

F

G

H

8 7 6 5 4 3 2 1

H

G

F

E

D

C

12345678

REVDRAWING NO

DATE JCN

APPROVED BY

ISSUED BY

CHECKED

DRAWN

DESIGNED

SUBMITTED BY

REVIEWED BY

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV

DATE

APPROVED

DESCRIPTION JCN

DATE

REDLINE

APVD

A

PENTHOUSE STEP SYSTEM

NOT TO SCALE

E A5A

A

SCALE: 3" = 1'-0"

9"6"3"3" 0

1' 2'01'

SCALE: 1" = 1'-0"

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

E D

M

IS

S

U E

D F

O

01 - Cover Page - Roof and Fall Protection Upgrade - OMA ATCT
02 - oma-d-atct-d016
oma-d-atct-d016
03 - oma-d-atct-d017
oma-d-atct-d017
04 - oma-d-atct-d018
oma-d-atct-d018
05 - Sketch - Third Level Roof Fall Protection
06 - ce_oma_7252_a4a_s0_rf
ce_oma_7252_a4a_s0_rf
07 - ce_oma_7252_a5a_s0_rj
ce_oma_7252_a5a_s0_rj
08 - ce_oma_7252_a13_s0_re
ce_oma_7252_a13_s0_re
09 - oma-d-atct-a016
oma-d-atct-a016
10 - oma-d-atct-a017
oma-d-atct-a017
11 - oma-d-atct-a018
oma-d-atct-a018
12 - oma-d-atct-a019
oma-d-atct-a019

13 - ce-d-7252-s-3

File details come from the government source that posted it. Updated .