ITB_26-XX_Statement_of_Work_-_Health_Dept_HVAC_Graphics_&_Control_System.docx

DOCX document 283 KB Posted

Attached to
26-27 Health Department HVAC Graphics & Control System
Solicitation number
26-27
Issued by
Bay County, Florida

About this file

This is a Statement of Work issued by the Bay County Board of County Commissioners in Florida for the installation of a new web-based HVAC Graphics and Controls System at the Bay County Health Department located at 597 West 11th Street, Panama City, Florida. The project encompasses the provision and installation of a new workstation computer with Windows 11 Pro, a network-compliant Building Supervisor Controller package, space temperature sensors, duct probes, thermostats, electrical cabling, and network wiring. The contractor must develop a custom web-based graphics interface with 3D/2D graphical screens, real-time data displays, alarm status monitoring, historical trends, and equipment location diagrams integrated with existing HVAC equipment including Air Handlers, Exhaust Fans, FCUs, Chillers, and Boilers. Additional requirements include system integration, point-to-point testing, air/water flow balancing, cybersecurity hardening, comprehensive documentation, and a minimum of eight hours of on-site training for facilities maintenance staff. Sealed submissions must be received by 2:30 PM on Tuesday, April 14, 2026, with the bid opening occurring immediately thereafter. A mandatory pre-bid meeting and optional site visit are required prior to submission. The project is estimated for completion within 90 days of contract award.

Contractors must be Florida-licensed Mechanical/Class A Air Conditioning Contractors, with all subcontractors appropriately licensed in their respective trades. The estimated project cost is $225,000, with liquidated damages assessed at $250 per day for non-compliance with the 90-day completion schedule. The contractor must provide a one-year workmanship warranty and a five-year software maintenance plan covering future upgrades and security patches. All software licenses, administrative passwords, and engineering programming tools must be registered to the Bay County Board of County Commissioners. The contractor is responsible for obtaining all required permits and inspections, ensuring compliance with manufacturer specifications and current Florida building codes, providing onsite supervision, and disposing of job debris. Contractor contacts are listed for three major control system vendors: Daikin Applied (Brandon Crump, 850-572-8383), JCI (Zane Eubanks, 850-324-8931), and Trane (Scott Nunn, 850-266-4234).

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ITB 26-xx Health Department HVAC Graphics & Control System

SUMMARY:

The Bay County Board of County Commissioners (County) seeks bids from qualified, licensed Contractors to provide all necessary labor, engineering, programming, design, installation, supervision, equipment, and supplies to install a new web-based HVAC Graphics and Controls System at the Bay County Health Department which is located at 597 W 11th St. Panama City, Florida, 32401.

QUALIFICATIONS:

Contractors shall be a HVAC Florida licensed Mechanical/Class A Air Conditioning Contractor. All Sub-Contractors shall be Florida licensed in their particular trade.

Bids may be deemed nonresponsive if not accompanied by proof of appropriate State of Florida Mechanical/Class A Air Conditioning License.

SCOPE OF WORK:

Installation & Hardware/Software

· Provide and install a new workstation computer (minimum Intel Core i7 Processor, 32 GB RAM) with Windows 11 Pro operating system.

· Disconnect and remove existing controller.

· Install a new network compliant Building Supervisor Controller package (e.g., JCI Metasys, Trane Tracer SC+, Tridium Niagara.)

· Web browser internet access (Remote internet outside IP address required.)

· Provide and install as necessary new space temperature sensors, duct probes, duct static transmitter, duct sensors, thermostats and associated wiring, new communication wire, and velocity pressure probes for full functionality and programmable controllers.

· Provide and install as necessary electrical cabling, conduit, and network wiring.

Graphics & Programming

· Develop and design a user-friendly custom web-based graphics interface for all updated HVAC equipment integrating the existing Air Handlers, Exhaust Fans, FCUs, Chillers and Boilers, creating a 3D/2D graphical screens for each piece of HVAC equipment.

· Graphics shall include real-time data, setpoints, alarm status, temperatures, pressures, valve positions and damper status and historical trends for temperature, humidity, and fan speed and diagrams of the HVAC equipment.

· Graphics shall include a visual of each piece of equipment and its location within a floorplan representative of the Health Department.

· Graphics must allow users to change setpoints, adjust schedules, and facilities management to override equipment.

· Create programming for optimal start/stop, occupancy schedules, and holiday schedules.

· Develop, document, and test a new Sequence of Operations for all equipment.

Security

· Contractor to provide cybersecurity hardening (SSL certificates, secure passwords) and coordinate with IT.

· Web browser internet access (Remote internet outside IP address required.

System Integration

· Ensure all data points are properly mapped and trended.

System Commissioning

· Perform point-to-point testing to verify all sensors and devices are communicating correctly.

· Validate that new graphics accurately reflect physical equipment status.

· Balance system air/water flows as required by new controllers’ configurations.

Documentation

· Provide as-built drawings/wiring diagrams, software details (license/logins, user manuals, and serial and model numbers, and the commissioning/startup report showing the system was tested, calibrated and operating correctly.

License Ownership

· All software licenses, admin passwords, and engineering programming tools (e.g., Controller) are to be registered to the Bay County Board County of Commissioners.

Training

· Provide a minimum of 8 hours of on-site training for the facilities maintenance staff.

GENERAL CONDITIONS

· Provide all permitting and inspections for above stated work.

· All work to be done as per manufacturer specifications and to current Florida building codes.

· Provide onsite supervision.

· Contractor responsible for the disposal of job debris.

WARRANTY:

· One (1) year workmanship warranty and (5) year software maintenance plan/ pack for future upgrades and security patches.

*Notes for Purchasing:

· Mandatory pre-bid and optional site visit after pre-bid for this project.

· Estimated cost is $ 225,000

· 90 days for completion

· Liquidated Damages - $250.00 per day

· Please contact:

· Daikin Applied, Brandon Crump: 850-572-8383

· JCI, Zane Eubanks: 850-324-8931

· Trane, Scott Nunn: 850-266-4234 image1.png