This document outlines the details for ITB 25001, a state contract opportunity issued by the Alaska Energy Authority for the replacement of Generator #2 at the Tuluksak Power Plant. The contract requires the installation of a new 210 kW generator and related mechanical and electrical system modifications. A non-mandatory pre-bid meeting is scheduled for August 8, 2024 and bids will be due on August 20, 2024. The contract will be awarded to a single bidder who can furnish all required labor, equipment, and materials.

The contract is funded through a State of Alaska appropriation. Bidders are invited to submit a single lump-sum bid for the full scope of work. No site visit is required prior to bidding. The contract documents include detailed design drawings and specifications that bidders should review carefully to understand the full extent of the work required.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

P.O. 111405, Anchorage, AK 99511 (907)349-0100

ALASKA ENERGY AUTHORITY

INSTALL NEW

POWER

CONDUCTORS

ENGINE &

GENERATOR

PREVIOUSLY

REMOVED

400A.F./350A.T.250A.F./250A.T.

150KW

226 FLA

150KW

226 FLA

INSTALL

NEW

BREAKER

400:5

INSTALL

NEW CT's

INSTALL

NEW

CONTACTOR

400A

INSTALL NEW

GENERATOR #2

210KW, 315FLA

NOTES:

1) RED TEXT THIS SHEET SHOWS THE INTENDED

REVISIONS FOR REPLACENT OF GENSET #2.

AS BUILT CONFIRMATION WAS NOT PROVIDED.

FIELD VERIFY ACTUAL WIRING AND DEVICES PRIOR

TO WORKING ON SYSTEM.

2) SEE ELECTRICAL EQUIPMENT SCHEDULE SHEET E1

FOR MAKE AND MODEL OF ALL NEW COMPONENTS.

3) SEE SPECIFICATIONS FOR ADDITIONAL DETAIL.

LEAVE MPU

WIRING AS IS

CONNECT FAP TO 26,

27, & 28 ON NEW LSM

REMOVE ALL

OF THIS

CONNECT 24VDC TO

15 & 16 ON NEW LSM

DISCONNECT 8290 & REMOVE

OR ABANDON IN PLACE

xxxxx xxxx xxxxxxxxx xxxxxxxxx

REMOVE EXISTING LSM &

INSTALL NEW WOODWARD LSM 9907-252

RECONNECT EXISTING WIRING EXCEPT AS NOTED

SEE ATTACHED WOODWARD CONNECTION DETAIL

NOTE: THIS DRAWING SHOWS THE INTENDED

REVISIONS FOR CONVERSION OF NEW GENSETS

#1 & #3. AS BUILT CONFIRMATION WAS NOT

PROVIDED. FIELD VERIFY ACTUAL WIRING AND

DEVICES PRIOR TO WORKING ON SYSTEM. GENERATOR 2

GENERATOR 2

210 KW

315 FLA

INPUT NEW 400:5

CT SETTINGS

IN GEN #2 LOAD

SHARE MODULE

INPUT NEW 400:5

CT SETTINGS IN

GEN #2 POWER

METER

400:5

400:5, TYP(3)

400A

NOTES:

1) GEN #2 WAS PREVIOUSLY MODIFIED FOR INTEGRATION OF AN ELECTRONICALLY

GOVERNED ENGINE. ALL GREYSCALE TEXT AND LINE WORK THIS SHEET INDICATES THE ASSUMED

PRESENT ASBUILT CONFIGURATION OF THE GENERATOR #2 SWITCHGEAR ENCLOSURE.

AS BUILT CONFIRMATION WAS NOT PROVIDED. FIELD VERIFY ACTUAL WIRING AND DEVICES PRIOR

TO WORKING ON SYSTEM

2) ALL RED LINEWORK AND TEXT REPRESENTS NEW WORK TO BE ACCOMPLISHED THIS PROJECT.

3) REPLACE EXISTING BREAKER, CONTACTOR AND CT'S AS INDICATED. SEE ELECTRICAL

EQUIPMENT SCHEDULE SHEET E1 FOR MAKE AND MODEL OF NEW COMPONENTS. SEE SPECIFICATIONS

FOR ADDITIONAL DETAIL

5) SEE SHEET E3 FOR NEW SWITCHGEAR / GENERATOR INTERCONNECT WIRING TERMINATIONS.

400AF

350AT

REPLACE EXISTING COMPONENTS SHOWN IN REVCLOUDS WITH NEW AS INDICATED, TYP. SEE NOTE 3.

NOTE: THIS DRAWING SHOWS THE

ORIGINAL SWITCHGEAR WIRING

AND IS PROVIDED FOR REFERENCE

ONLY. FIELD VERIFY ACTUAL

WIRING AND DEVICES PRIOR TO

WORKING ON SYSTEM.

24VDC POWER

REMOVE

INVERTER

AND INSTALL

JUMPER

Mechanical
Electrical
Switchgear Modifications Redlines