IQ_GST_Tank_Information.pdf

PDF 138 KB Posted

Attached to
Reclaimed Water Ground Storage Tank Cleaning and Inspection
Solicitation number
QQ-2025-014
Issued by
Collier County, Florida

About this file

This document is a comprehensive Ground Storage Tank (GST) information table for Collier County Irrigation Quality (IQ) water storage facilities, detailing seven water storage tanks located across different addresses in the county. The tanks range in storage capacity from 0.500 MG to 2.500 MG, with varying dimensions between 17 and 24 feet, and are situated at locations including Santa Barbara Boulevard, Radio Road, Palm Drive, Warren Street, and Watergate Way. The table provides critical technical specifications for each tank, including overflow levels, high-high/float shut-off levels, high levels, operational shutoff levels, floor elevations, tank top areas, circumferences, and wall areas. Each tank's most recent painting year is also documented, ranging from 2019 to 2024.

The document includes a notable annotation that all tanks will trigger an alarm 0.5 feet over the Operational Shutoff Level, with a specific callout that Ground Storage Tanks 2 and 3 (GST 2 & 3) lack the redundancy of shutting down via float and can only be stopped via a motor-operated valve (MOV). The tanks are part of Collier County's infrastructure supporting their Irrigation Quality water system, which serves over 50,000 residential, commercial, and governmental customers. The tank information appears to support the upcoming contract opportunity for tank cleaning and inspection, providing potential vendors with detailed technical specifications necessary for understanding the scope and requirements of the maintenance project.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Site Dimensions Storage Capacity

Tank Elevations

Year Painted

Overflow 24.000 Area of top of tank High-High / Float Shut off Level 23.000 5,153 ft2

Countryside 0.925 MG High level 22.500 Circumference 4701 Santa Barbara BLVD Operation Shutoff Level 22.000 255 ft

Floor 0.000 Area of Walls 6,120 ft2

Overflow 19.000 Area of top of tank High-High / Float Shut off Level 18.000 8,012 ft2

Foxfire 1.1 MG High level 17.500 Circumference 5500 Radio RD Operation Shutoff Level 17.000 318 ft

Floor 0.000 Area of Walls 6,042 ft2

Overflow 18.500 Area of top of tank High-High / Float Shut off Level 17.500 14,103 ft2

Glades 2.000 MG High level 17.000 Circumference 105 Palm DR Operation Shutoff Level 16.500 421 ft

Floor 0.000 Area of Walls 6,947 ft2

Overflow 23.000 Area of top of tank High-High / Float Shut off Level 22.000 8,012 ft2

Royal Palm 1.3 MG High level 21.500 Circumference 5630 Warren ST Operation Shutoff Level 21.000 318 ft

Floor 0.000 Area of Walls 7,314 ft2

Overflow 20.000 Area of top of tank High-High / Float Shut off Level 19.000 16,742 ft2

P-Bay Gst - 1 20.5' 2.500 MG High level 18.500 Circumference 6200 Watergate WAY Operation Shutoff Level 18.000 459 ft

Floor 0.000 Area of Walls 9,410 ft2

Overflow 17.000 Area of top of tank High-High / Float Shut off Level 16.000 3,849 ft2

P-Bay Gst - 2 17' 0.500 MG High level 15.500 Circumference 6200 Watergate WAY Operation Shutoff Level 15.000 220 ft

Floor 0.000 Area of Walls 3,740 ft2

Overflow 17.000 Area of top of tank High-High / Float Shut off Level 16.000 3,849 ft2

P-Bay Gst - 3 17' 0.500 MG High level 15.500 Circumference 6200 Watergate WAY Operation Shutoff Level 15.000 220 ft

Floor 0.000 Area of Walls 3,740 ft2

Note: All tanks will Alarm .5 feet over Operational Shutoff Level GST 2 & 3 do not have the redundancy of shutting down via float-only via MOV

24' 81'

19'

16.5'

23'

101'

146'

70'

70'

GST Information

File details come from the government source that posted it. Updated .