The document is a comprehensive 2,000,000 Gallon Fluted Column Tank Inspection Report prepared by TankRehab, LLC for Sarasota County Utilities, located at 1850 Wendall Kent Rd in Sarasota, Florida. The inspection was conducted on June 20, 2023, by Tom Donovan and covers a water storage tower manufactured by Pitt-Des Moines, Inc. in 1997, with a contract number 56174. The report provides a detailed assessment of the tank's exterior and interior coating conditions, safety features, sanitation, and structural integrity, highlighting various areas requiring maintenance and potential corrective actions.
The inspection reveals that the tank is currently in fair condition, with several recommendations for improvement. Key findings include isolated coating failures on the exterior roof and interior surfaces, corrosion around vent openings, and the need for safety upgrades such as replacing ladders, installing safety climbing devices, and addressing roof vents and access hatches. The estimated budgetary considerations for these improvements total approximately $339,000, covering spot repairs, ladder replacements, safety climb installations, and roof vent replacements. The report suggests that the tank should be inspected every year for corrosion control maintenance and that the sludge and sediment build-up should be removed from the tank every two years.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 242547TEG_Project_Documents.pdf | ||
| DRAWINGS_FOR_CONSTRUCTION_OF_ELEVATED_WATER_STORAGE.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2030 E. Adams St.
Jacksonville, Florida 32202
(904)551-9293 contact@tankrehab.com
2,000,000 Gallon Fluted Column Tank Inspection Report
North Tower #56124
Prepared For:
Sarasota County Utilities 1850 Wendall Kent Rd Sarasota, FL
Prepared By:
Tom Donovan June 2023
ATTACHMENT A - INSPECTION REPORT
2,000,000 Gallon Fluted Column Tank Inspection Report 1 Sarasota, Florida
General Information
INTRODUCTION:
On June 20, 2023, Tom Donovan of TankRehab.com, LLC, performed a washout and inspection on a 2,000,000-gallon Elevated Water Storage Tank as required by FAC 62-555.350. This report fulfills the requirements of FAC 62-555.350 for the water storage tank located at 1850 Wendall Kent Rd, Sarasota, FL. The inspection was completed to determine the condition of the coatings, safety, sanitation and structural.
TANK DETAILS
CAPACITY: 2,000,000 Gallons DESIGN: Elevated
INSPECTION
DATE:
June, 2023 INSPECTOR: Tom Donovan
CONSTRUCTION
STYLE:
Welded CONSTRUCTION
DATE:
BUILDER: Pitt-Des Moines, INC Contract #56124
HEIGHT/
DIMENSION:
115 ft High B.C.L.
/100 ft Dia
EXTERIOR
COATING:
Acrylic Polyurethane EXTERIOR
LEAD PRESENCE:
unknown
INTERIOR
COATING:
Epoxy INTERIOR
LEAD PRESENCE:
unknown
2,000,000 Gallon Fluted Column Tank Inspection Report 2
Exterior Coating Conditions
TANK ROOF
The exterior coating system is in fair condition. The exterior coating system was noted for isolated coating failure and should be corrected as soon as scheduling permits.
Protective coating system thickness range: 15.2 to 31.1 mils; Average of 22.54 mils
TANK BOWL
The coating system on the tank bowl is in good condition.
Protective coating system thickness range: 15.2 to 31.1 mils; Average of 22.54 mils
TANK SIDEWALLS
The exterior coating system on the tank sidewalls good condition.
Protective coating system thickness range: 15.2 to 31.1 mils; Average of 22.54 mils
RECOMMENDATIONS
The exterior coating is in good condition. It is recommended to spot repair the isolated coating failures to prevent costly metal loss.
2,000,000 Gallon Fluted Column Tank Inspection Report 3
Interior Coating Conditions
ROOF AND AREA ABOVE HIGH WATER LEVEL
The interior coating system on the roof and the area above the highwater level is in fair condition. Isolated areas of coating failure and corrosion were noted on the roof of the tank at the connection points and angles.
Protective coating system thickness range: 13.6 to 32.7 mils; Average of 22.10 mils.
SIDEWALLS
The interior coating system on the tank sidewalls is in fair condition. The interior epoxy coating system is currently protecting the sidewall.
Protective coating system thickness range: 13.6 to 32.7 mils; Average of 22.10 mils.
BOWL
The interior coating system on the tank bowl is in fair condition. The interior epoxy coating system was noted for having small blisters along random areas of the tank bowl.
Protective coating system thickness range: 13.6 to 32.7 mils; Average of 22.10 mils.
RECOMMENDATIONS
The interior coating system was noted for isolated coating failure and should be corrected as soon as scheduling permits.
SSPC-7 surface prep to identify failed protective coatings followed by a spot and full finish coat will prolong the interior protective coating.
2,000,000 Gallon Fluted Column Tank Inspection Report 4
DRY
FLUTED COLUMN
The interior coating system is in fair condition. Corrosion occurring around the vent openings.
Protective coating system thickness range: 5.1 to 13.6 mils; Average of 9.84 mils.
BOWL
The interior coating system on the bowl is in good condition. The interior epoxy coating system is currently protecting the bowl of the tank.
Protective coating system thickness range: 5.1 to 13.6 mils; Average of 9.84 mils.
DRY RISER
The interior coating system on the dry riser is in good condition. The interior epoxy coating system is currently protecting the dry riser of the tank.
Protective coating system thickness range: 5.1 to 13.6 mils; Average of 9.84 mils.
RECOMMENDATIONS
dry for isolated coating failure and should be corrected as soon as scheduling permits.
2,000,000 Gallon Fluted Column Tank Inspection Report 5
Safety, Sanitation, and Structural Conditions
SAFETY
Ladders
The interior wet ladder and safety climb is in need of replacement.
The column ladders need fall prevention safety cable climbs.
Balcony, Balcony Railing
The balcony and balcony railing are in good condition.
Aviation Warning Lights
This tower is equipped with aviation warning lights. Operation was not confirmed during this inspection.
Tank Access Hatch
The tank access hatch is a manway. The access hatch is in need of repair or replacement. The access hatch was not locked at the time of the inspection.
Secondary Access Hatch
This tower is equipped with a secondary access hatch.
2,000,000 Gallon Fluted Column Tank Inspection Report 6
SANITATION
Roof Hatch
The 30 roof hatch should be repaired/replaced during the next renovation with a minimum of 30 inches and that it should be fitted with a solid watertight cover which overlaps the framed opening and extends down around the frame a minimum of two inches to prevent contaminated rainwater from entering the tank.
Roof Vent
The two roof vents need replacement.
Overflow
The overflow pipe needs screen installed.
STRUCTURAL
Foundations
The concrete foundation was found to be in good condition.
Bowl
Steel thickness range: .516 to .517 inch.
Anchor Bolts
The anchor bolts appear to be tight and in good condition.
2,000,000 Gallon Fluted Column Tank Inspection Report 7
SECURITY
Security Fence
This tank site contains a locked security fence.
Ladder Gate
The access contains a lockable door to prevent unauthorized access into the column.
Locked Roof Hatch
The roof hatch was not locked at the time of our inspection.
2,000,000 Gallon Fluted Column Tank Inspection Report 8
SUMMARY AND RECOMMENDATIONS
SUMMARY
Overall this water storage tower is in good structural condition. The exterior coating system should be spot repaired as soon as scheduling permits. The interior coating system should be spot repaired as soon as scheduling permits. Active corrosion on the exterior roof and should be stopped to prevent costly steel replacement.
RECOMMENDATIONS
Spot coating repair interior and safety climb.
Spot coating repair exterior roof.
Replace roof vents and overflow screens.
BUDGETARY CONSIDERATION
$275,000.00 to spot repair and full finish coat $18,500.00 to replace ladder .
$13,000.00 to spot repair exterior roof.
$16,000.00 to supply/install ladder safety climbs on
$20,000.00 to replace (2) roof vents and overflow screen.
$6 hatch.
2,000,000 Gallon Fluted Column Tank Inspection Report 9
2,000,000 Gallon Fluted Column Tank North Tower
2,000,000 Gallon Fluted Column Tank Inspection Report 10
Photo #1 Support column at ground level corrosion.
Photo #2 No screen on overflow.
2,000,000 Gallon Fluted Column Tank Inspection Report 11
Photo #3 Mildew around bottom of column.
Photo #4 Protective coating failure.
2,000,000 Gallon Fluted Column Tank Inspection Report 12
Photo #5 Grounded tank/corrosion.
Photo #6 Exterior protective coating system.
2,000,000 Gallon Fluted Column Tank Inspection Report 13
Photo #7 Exterior protective coating system on tank roof.
Photo #8 Minor delamination/corrosion on tank roof.
2,000,000 Gallon Fluted Column Tank Inspection Report 14
Photo #9 Minimal protective coating failure on roof.
Photo #10 Corrosion causing metal loss.
2,000,000 Gallon Fluted Column Tank Inspection Report 15
Photo #11 Roof vents in need of replacement.
Photo #12 Roof vents in need of replacement.
2,000,000 Gallon Fluted Column Tank Inspection Report 16
Photo #13 30 in need of replacement.
Photo #14
2,000,000 Gallon Fluted Column Tank Inspection Report 17
Photo #15 Protective coating failure on angles and cathodic hand holes in roof.
Photo #16 Protective coating failure in roof.
2,000,000 Gallon Fluted Column Tank Inspection Report 18
Photo #17 Before washout.
Photo #18 After washout.
2,000,000 Gallon Fluted Column Tank Inspection Report 19
Photo #19 distribution
Photo #20
2,000,000 Gallon Fluted Column Tank Inspection Report 20
Photo #21 Cathodic protection in tank was not confirmed operational.
Photo #22 Obstruction lights off. Roof hatches shut before exiting roof.
2,000,000 Gallon Fluted Column Tank Inspection Report 21
Photo #23 View of
Photo #24
2,000,000 Gallon Fluted Column Tank Inspection Report 22
Photo #25 View of Bowl of tank.
Photo #26 Condensate blanket in good condition.
2,000,000 Gallon Fluted Column Tank Inspection Report 23
Photo #27 Anchor bolts are tight.
Photo #28 Ladders need safety climbing device.
2,000,000 Gallon Fluted Column Tank Inspection Report 24
Photo #29 Access to tank locked.
Photo #30 Access to tank site locked.