This is a Sources Sought Notice under the Buy Indian Act for comprehensive fire alarm monitoring, periodic inspections, corrective maintenance, and life-safety remediation services at three Indian Health Service (IHS) healthcare facilities in Oklahoma operated by the Lawton Service Unit. The Indian Health Service is seeking to identify Indian Small Business Economic Enterprises (ISBEEs) capable of performing this requirement. Responses must be submitted via email to Contract Specialist Jarrod Prince at jarrod.prince@ihs.gov no later than 4:00 PM CST on November 25, 2026, with a maximum of 5 pages. The applicable NAICS code is 561621 (Security Systems Services) with a small business size standard of $25.0 million, and the Product Service Code is 6350. This is not a solicitation for proposals but rather a market research notice to identify potential contractors before formal solicitation.
The Performance Work Statement details a 5-year Blanket Purchase Agreement (BPA) requiring 24/7/365 UL-listed central station monitoring, compliance with NFPA codes (10, 13, 25, 72, 80, 96, 101), and Joint Commission accreditation standards. The contractor must maintain existing Notifier ONYX series fire alarm systems, water-based suppression systems, fire pumps, and 25 fire/smoke barrier doors at Lawton Indian Hospital, plus monitoring and extinguisher services at Anadarko and Carnegie health centers. Key responsibilities include semi-annual kitchen hood testing, quarterly waterflow and tamper testing, annual fire alarm and extinguisher certifications, emergency response within 2 hours for catastrophic failures, and facility engineer coordination with Joint Commission staff training. The contractor must furnish all tools, calibrated instruments, replacement parts, and specialized software; possess Oklahoma Department of Labor licenses for Commercial Fire Alarm, Fire Sprinkler, and Central Station Monitoring; and maintain Notifier factory certification. All personnel require HSPD-12 security verification, HIPAA compliance, and adherence to tobacco-free facility policies. Deliverables include itemized inspection reports within 5 business days and post-repair certifications confirming NFPA compliance.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SOURCES SOUGHT NOTICE — BUY INDIAN ACT
Lawton Indian Hospital · Notice ID IHS-SS-11182026
This is a Sources Sought notice. This is NOT a solicitation for proposals, proposal abstracts, or quotations.
Pursuant to 48 CFR Part 326, Subpart 326.603-3 and IHM 5.5-6, the Indian Health Service (IHS) must use the negotiation authority of the Buy Indian Act, 25 U.S.C. 47, to give preference to Indian Economic Enterprises (IEE) whenever the use of that authority is authorized and practicable.
The Government is seeking to identify Indian Small Business Economic Enterprises (ISBEEs) capable of performing the below Indian Health Service (IHS) requirement for Fire Alarm Monitoring, Periodic Inspections, Corrective Maintenance, and Life-Safety Remediation Services. Any vendor responding to this notice should submit their capability statement as well as the Buy Indian Act Indian Economic Enterprise Representation Form (attached).
Instructions for submission are outlined below.
Indian Small Business Economic Enterprises (ISBEEs) and other small business are highly encouraged to respond to this notice. However, firms should understand that generic capability statements are not sufficient for effective evaluation of their capacity and capability to perform the work required. Responses must directly demonstrate the company's capability, experience, and ability to provide uninterrupted fire detection, 24/7/365 central station monitoring, water-based fire suppression readiness, physical fire and smoke barrier containment, and emergency restoration capabilities are essential to safeguarding patients, healthcare personnel, and visitors.
All life-safety systems must maintain continuous accreditation with The Joint Commission (TJC) Environment of Care and Life Safety standards, as well as strict compliance with applicable National Fire Protection Association (NFPA) codes, including the Life Safety Code (NFPA 101). The places of performance are: Lawton Indian Hospital, 1515 NE Lawrie Tatum Rd, Lawton, OK 73507; Anadarko Indian Health Center, 201 E Parker McKenzie Dr., Anadarko, OK 73005; Carnegie Indian Health Center, 212 E 4th St, Carnegie, OK 73015.
Applicable NAICS Code: 561621 — Security Systems Services (except Locksmiths) (small business size standard: $25.0 million). Product Service Code (PSC): 6350.
The Government requests interested parties submit a written response to this notice, which includes:
a. Company Name.
b. Company socioeconomic status.
c. Company System for Award Management (SAM) Unique Entity Identifier (UEI) number.
d. Company point of contact, mailing address, telephone number(s), and website address.
e. Name, telephone number, and e-mail address of a company point of contact who has the authority and knowledge to clarify responses with Government representatives.
f. CAGE Code.
g. Tax ID.
h. Date submitted.
i. Applicable company GSA Schedule number or other available procurement vehicle.
j. Company's System for Award Management (SAM) registration status. All respondents must register in SAM at https://www.sam.gov/.
k. Buy Indian Act Indian Economic Enterprise Representation Form (attached).
Disclaimer and Important Notes. This notice does not obligate the Government to award a contract. Any information provided by industry to the Government as a result of this sources sought synopsis is strictly voluntary. Responses will not be returned. No entitlements to payment of direct or indirect costs or charges to the Government will arise as a result of contractor submission of responses, or the Government's use of such information or otherwise pay for the information provided in response. The Government reserves the right to use information provided by respondents for any purpose deemed necessary and legally appropriate. Any organization responding to this notice should ensure that its response is complete and sufficiently detailed to allow the Government to determine the organization's qualifications to perform the work. Respondents are advised that the Government is under no obligation to acknowledge receipt of the information received or provide feedback to respondents with respect to any information submitted. After a review of the responses received, a pre-solicitation synopsis and solicitation may be published on a Government Point of Entry (GPE). However, responses to this notice will not be considered adequate responses to a solicitation.
Confidentiality. No proprietary, classified, confidential, or sensitive information should be included in your response. The Government reserves the right to use any non-proprietary technical information in any resultant solicitation(s).
How to respond: Please include the notice IHS-SS-11182026 in the subject line. Responses must be submitted via email to the Contract Specialist, Jarrod Prince at jarrod.prince@ihs.gov no later than 4:00 PM CST on November 25, 2026.
Capability statements will not be returned and will not be accepted after the due date. The maximum number of pages for this submission is 5 pages.
Attachment:
1. Buy Indian Act Indian Economic Enterprise Representation Form
Department of Health and Human Services Indian Health Service
Performance Work Statement (PWS) Comprehensive Fire Alarm Monitoring, Periodic Inspections, Corrective Maintenance, and
Life-Safety Remediation Services 11/04/2026
1. Purpose and Background The Indian Health Service (IHS), an operating division within the Department of Health and Human Services (HHS), delivers comprehensive medical, clinical, and public health services to American Indians and Alaska Natives across 574 federally recognized Tribes. The Lawton Service Unit (LSU) operates three Joint Commission–accredited healthcare facilities in Oklahoma:
1. Lawton Indian Hospital (LIH): Main hospital campus, ambulatory clinics, outpatient surgical facilities, and administrative/support buildings located in Lawton, Oklahoma.
2. Anadarko Indian Health Center (AIHC): Ambulatory clinic, Public Health Nursing (PHN), Wellness Center, COVID Building, and support facilities in Anadarko, Oklahoma.
3. Carnegie Indian Health Center (CIHC): Ambulatory health clinic in Carnegie, Oklahoma.
Uninterrupted fire detection, 24/7/365 central station monitoring, water-based fire suppression readiness, physical fire and smoke barrier containment, and emergency restoration capabilities are essential to safeguarding patients, healthcare personnel, and visitors. All life-safety systems must maintain continuous accreditation with The Joint Commission (TJC) Environment of Care and Life Safety standards, as well as strict compliance with applicable National Fire Protection Association (NFPA) codes, including the Life Safety Code (NFPA 101).
The purpose of this Performance Work Statement (PWS) is to define the technical requirements for a contractor to provide scheduled baseline inspections, central station alarm monitoring, code-mandated certifications, on-demand corrective maintenance, physical life-safety remediation, mechanical interlock integrations, and 24/7 emergency diagnostic restoration across all Lawton Service Unit facilities.
2. Scope of Work and Existing Equipment Servicing Mandate
2.1 General Scope
The Contractor shall furnish all necessary licensed labor, supervision, specialized tools, calibrated test equipment, transportation, certified replacement parts, and materials to maintain all fire detection, alarm, suppression, and physical containment systems in full operating condition. The work comprises both scheduled routine compliance services and on-demand corrective remediation across all LSU facilities.
2.2 Existing Equipment Servicing Requirement (No Equipment Replacement) Existing life-safety equipment, fire alarm control panels, suppression infrastructure, and barrier assemblies will not be replaced by the Government. The Contractor must possess the verified technical capability, diagnostic software, licensing, programming keys, and specialized expertise required to service, inspect, maintain, troubleshoot, program, and remediate all currently installed equipment in place. Awardees must be capable of immediately assuming full service responsibility for existing installed systems (including, but not limited to, Notifier ONYX series intelligent panels and devices, water-based suppression systems, fire pumps, commercial kitchen hood suppression systems, and physical fire/smoke door assemblies) without requiring system change-outs or conversions.
2.3 Facility Scope Matrix
Facility Location Core Recurring Baseline Services Corrective & On-Demand Remediation Scope
Lawton Indian Hospital (LIH)
Lawton, OK
• 24/7/365 UL-Listed Central Station Monitoring
• Fire Alarm & Detection Testing
(NFPA 72)
• Sprinkler System Periodic Tests
(NFPA 25)
• Kitchen Hood Suppression Testing
(NFPA 96)
• Fire & Smoke Door Inspections
(NFPA 80/105)
• Portable Extinguisher Maintenance
(NFPA 10)
• Certified fire door gap remediation & field relabeling
• Flexible sprinkler drops & head relocations
• HVAC RTU/AHU smoke detector & shutdown interlocks
• Panel re-programming, addressing & CAD device mapping
• Electronic component replacement (Notifier modules/relays)
• Emergency restoration & diagnostic troubleshooting
Anadarko Indian Health Center (AIHC)
Anadarko, OK
• 24/7/365 UL-Listed Central Station Monitoring
• Fire Alarm & Initiating Device Testing (NFPA 72)
• Sprinkler System & Fire Pump Flow Testing (NFPA 25)
• Portable Extinguisher Maintenance
(NFPA 10)
• Fire pump minor repairs & flow adjustments
• Initiating device & module replacements
• Extinguisher cylinder recharging & hydro-testing
• Corrective sprinkler piping & valve maintenance
• Emergency restoration & diagnostic troubleshooting
Carnegie Indian Health Center
(CIHC)
Carnegie, OK
• Portable Fire Extinguisher Inspection, Maintenance & Certification (NFPA 10) (No alarm or sprinkler inspection required)
• Extinguisher 6-year teardown maintenance
• Hydrostatic cylinder pressure testing
• Direct replacement of unserviceable/expired cylinders
3. Contractor Technical Requirements and Operational Specifications
3.1 Part A: 24-Hour Central Station Alarm Monitoring
1. The Contractor shall provide continuous, uninterrupted Underwriters Laboratories (UL)-listed Central Station monitoring services 24 hours per day, 365 days per year, for all existing fire alarm control panels at LIH and AIHC.
2. The monitoring station shall receive and distinguish alarm, supervisory, waterflow, and trouble signals from the existing panel equipment.
3. Dispatch Protocols: Upon receipt of an alarm signal, the monitoring station shall immediately dispatch the appropriate municipal fire service:
o Lawton Indian Hospital Lawton Fire Department o Anadarko Indian Health Center Anadarko Fire Department
4. Facility Notification Hierarchy: Immediately following municipal fire department dispatch (or upon receipt of supervisory/trouble signals), the monitoring center shall notify facility personnel in accordance with the established priority lists:
Lawton Indian Hospital Call List:
First Contact: Lawton Nurse Supervisor – (580) 354-5423 Second Contact: Department Supervisor – (580) 354-5252 Third Contact: Facility Engineer – (580) 354-5251 Fourth Contact: Department Director – (580) 354-5581
Anadarko Indian Health Center Call List:
First Contact: Lawton Nurse Supervisor – (580) 354-5423 Second Contact: Primary AIHC Safety/Facilities Contact – (405) 535-8323 Third Contact: Secondary AIHC Safety/Facilities Contact – (405) 247-2458
3.2 Part B: Scheduled Inspections, Testing, and Certifications All periodic testing shall strictly conform to NFPA schedules, manufacturer specifications, and Joint Commission standards. The Contractor is responsible for inspecting 100% of applicable devices present on-site during inspection cycles, including any unlisted or excess devices discovered.
1. Fire Alarm & Detection Systems (NFPA 72): Semi-annual and annual functional testing of manual pull stations, photoelectric smoke detectors, thermal heat detectors, duct smoke detectors, waterflow switches, tamper switches, electromechanical door holders, visual strobes, and audible alarms across all installed panels. Smoke detector sensitivity testing in accordance with NFPA 72 intervals.
2. Water-Based Fire Suppression Systems (NFPA 25): Quarterly inspection of existing OS&Y control valves, waterflow switches, tamper switches, and Fire Department Connections (FDCs).
Annual main drain testing and annual backflow preventer certification. Annual fire pump flow performance testing (existing electric/diesel assembly at AIHC). Five-year internal piping inspections and obstruction flow testing (next due December 2030; last completed December 2025).
3. Portable Fire Extinguishers (NFPA 10): Annual inspection, maintenance tagging, external cleaning, 6-year internal teardown maintenance, and hydrostatic pressure testing per cylinder rating. Extinguisher cycle: LIH extinguishers serviced annually in September; AIHC and CIHC extinguishers serviced annually in December.
4. Commercial Kitchen Fire Suppression Systems (NFPA 96 / NFPA 17A): Semi-annual inspection (March and September) of dietary kitchen hoods at LIH, including fusible link replacements, microswitch interlock verifications, gas valve shutdown tests, and manual pull station actuation.
5. Fire and Smoke Barrier Doors (NFPA 80 / NFPA 105): Annual physical inspection of 19 fire-rated doors and 6 smoke barrier doors at LIH, including clearance gap measurements, positive latching, self-closing operation, coordinator sequencing, frame integrity, hinge wear, and physical certification labels. The Contractor shall conduct a Joint Commission staff competency briefing with designated LSU facility personnel during the inspection.
3.3 Part C: On-Demand Corrective Maintenance, Remediation, and Alterations When deficiencies are identified during periodic inspections, building modifications, or operational alerts, the Contractor shall execute corrective remediation on existing systems to restore compromised components to full code compliance upon authorization from the Government:
1. Fire and Smoke Door Remediation: Supply and install certified door gap kits (e.g., 90-minute UL-classified top, side, and bottom perimeter kits) to correct clearances exceeding NFPA 80 thresholds. Supply and install certified steel shims, continuous heavy-duty hinges, and fire-rated astragals. Adjust, repair, or replace self-closing devices, door coordinators, and electromagnetic hold-opens. Arrange and perform certified on-site field relabeling through an authorized Nationally Recognized Testing Laboratory (NRTL, such as Intertek/Warnock Hersey or UL) for doors/frames with painted, missing, or illegible labels.
2. Sprinkler System Corrective Works & Drop Reconfigurations: Supply and install flexible stainless-steel braided sprinkler drops, ceiling brackets, and transition fittings to adjust existing sprinkler heads to matching ceiling elevations following HVAC duct, mixing box, or ceiling tile modifications. Replace corroded, loaded, painted, damaged, or non-compliant sprinkler heads with code-compliant OEM equivalents. Replace missing, bent, or non-listed escutcheon plates and pipe ceiling sleeves.
3. HVAC / Mechanical Interlock Integration: Wire, interface, and program newly installed HVAC Roof Top Units (RTUs) and Air Handling Units (AHUs) directly into the existing Notifier fire alarm system. Install addressable duct smoke detector housings, properly sized sampling tubes, remote test stations, and control relay modules (Notifier FCM-1) to execute automatic fan shutdown during alarm states.
4. Fire Alarm System Programming, Addressing & Mapping: Perform addressable loop device re-labeling and software updates within existing Notifier panels to ensure panel alpha-numeric display descriptions accurately reflect physical room numbers. Maintain panel software database backups and furnish updated AutoCAD/PDF as-built device wiring maps and point-to-point cross-reference spreadsheets following any renovation or device addition.
5. Certified Replacement Components for Existing Systems: All replacement parts must integrate seamlessly with existing equipment without invalidating UL listings or system warranties. Furnish genuine OEM parts including Notifier monitor modules (FMM-101/FMM-1), control modules (FCM-1), intelligent smoke detector sensors, System Sensor heat detectors, notification appliances, power supply boards, and sealed lead-acid backup batteries. Provide direct replacement fire extinguishers (10-lb ABC multi-purpose dry chemical, Class K, and CO2) when existing units fail hydrostatic testing or exceed maximum service life.
3.4 Part D: Diagnostic Troubleshooting and Emergency Restoration Services
1. Routine Diagnostic Service Calls (Non-Emergency): For minor supervisory alerts, single-device trouble signals, or routine component swaps on existing systems, the Contractor shall provide an on-site licensed technician within twenty-four (24) to forty-eight (48) hours of notification.
2. Emergency Failure Service (24/7/365): In the event of a catastrophic system failure, main control panel outage, un-silenceable false alarms, continuous trouble condition, or compromised sprinkler suppression in an occupied healthcare area:
o Telephone Technical Triage: Within thirty (30) minutes of initial notification.
o On-Site Qualified Technician: Within two (2) hours of notification.
o The Contractor shall work continuously until the system is restored to full operational status or until an approved Interim Life Safety Measure (ILSM) and compensatory Fire Watch plan is coordinated with the LSU Safety Officer.
4. Period of Performance
4.1 The period of performance will be a 5-year BPA.
5. Place and Hours of Performance
5.1 Places of Performance
Work shall be performed on-site across three Lawton Service Unit healthcare campuses:
1. Lawton Indian Hospital (LIH): 1515 Lawrie Tatum Road, Lawton, OK 73507 (Main Hospital Bldg 421, OEH Bldg 425, Materials Management Bldg 423, Bldg 422, Dental Modular, Behavioral Health Modular, and Public Health Nursing).
2. Anadarko Indian Health Center (AIHC): 115 NW Coombs Road, Anadarko, OK 73005 (Main Clinic, PHN Building, Wellness Center, COVID Building, and Maintenance/Storage Facilities).
3. Carnegie Indian Health Center (CIHC): 402 S. Washington, Carnegie, OK 73015 (Ambulatory Clinic).
5.2 Hours of Performance and Scheduling
Standard Working Hours: Routine inspections, non-disruptive testing, and scheduled corrective repairs shall occur during standard business hours, Monday through Friday, 8:00 a.m.
to 4:30 p.m. (or 5:00 p.m. as coordinated with the Facility Engineer).
Federal Holidays: Scheduled routine work will not be performed on observed Federal Holidays unless explicitly authorized in advance by the Contracting Officer's Representative (COR).
Audible & Disruptive Testing Coordination: Audible alarm testing, waterflow alarm bell activations, suppression shutdowns, and work requiring ceiling-tile access in patient-care areas must be scheduled after standard clinic hours (evenings or weekends) or precisely coordinated with Facility Maintenance to prevent patient disruption.
Emergency Service Windows: Emergency triage and restoration services operate twenty-four
(24) hours per day, seven (7) days per week, 365 days per year (inclusive of weekends and Federal Holidays).
6. Government-Furnished Property, Services, and Information
6.1 Facilities and Utilities
The Government will provide the Contractor with reasonable access to facility spaces, equipment rooms, electrical power, and water supply required for performing testing (such as fire pump flow testing, main drain tests, and backflow testing).
6.2 Documentation and Access Credentials
The Government will provide available historical inspection reports, existing device riser layouts, system passwords, panel physical keys, and building access cards/visitor badges necessary for performing authorized work.
6.3 Points of Contact and Escorts
The Government will designate a Facility Maintenance liaison and Safety Officer contact to coordinate facility access, sign-offs, and Interim Life Safety Measure (ILSM) implementations.
Note: The Government will not furnish tools, specialized test equipment, safety consumables, diagnostic software, replacement modules, or transportation.
7. Contractor-Furnished Property, Equipment, and Materials Except for the access, utilities, and documentation specified in Section 6, the Contractor shall furnish everything required to perform the required outcomes, including but not limited to:
1. Specialized Tools & Calibrated Instruments: Calibrated water pressure gauges, pitot tubes, backflow test kits, sound pressure level (dB) meters, smoke sensitivity test equipment, calibrated door-gap feeler gauges, and latch-force spring scales.
2. Testing Consumables: Aerosol test smoke, heat gun testing units, replacement fusible links, test tags, certification collars, tamper seals, and calibration fluids.
3. Containment & Safety Gear: HEPA-filtered mobile containment carts, clean drop cloths, painter’s plastic, step ladders, personal protective equipment (PPE), and eye protection for working above acoustic ceilings in patient environments.
4. Certified Replacement Parts & Hardware: OEM Notifier addressable electronic modules, sensors, sealed batteries, flexible braided sprinkler drops, code-approved sprinkler heads, UL-classified door gap remediation kits, steel shims, continuous hinges, and replacement fire extinguishers.
5. Transportation & Communication: Service vehicles, transport, and a 24-hour dispatch phone number answered continuously for emergency calls.
8. Detailed Inspection Calendar
Month Lawton Indian Hospital (LIH) Anadarko Indian
Health Center
(AIHC)
Carnegie Indian Health Center (CIHC)
March
• Quarterly Tamper & Waterflow Testing
• Quarterly Supervisory Signal Verification
• Quarterly Off-Site Responder Dispatch Test
• Quarterly FDC Inspection
• Semi-Annual Kitchen Hood System
(NFPA 96)
• Quarterly Tamper & Waterflow Testing
• Quarterly Supervisory Signal Verification
• Quarterly Off-Site Responder Dispatch Test
• Quarterly FDC Inspection
May
• Annual Fire & Smoke Door Inspection (NFPA 80/105) & Competency Training
June
• Quarterly Tamper & Waterflow Testing
• Quarterly Supervisory Signal Verification
• Quarterly Off-Site Responder Dispatch Test
• Quarterly FDC Inspection
• Quarterly Tamper & Waterflow Testing
• Quarterly Supervisory Signal Verification
• Quarterly Off-Site Responder Dispatch Test
• Quarterly FDC Inspection
September
• Quarterly Tamper & Waterflow Testing
• Quarterly Supervisory Signal Verification
• Quarterly Off-Site Responder Dispatch Test
• Quarterly FDC Inspection
• Semi-Annual Kitchen Hood System
(NFPA 96)
• Annual Portable Fire Extinguisher Certification
• Quarterly Tamper & Waterflow Testing
• Quarterly Supervisory Signal Verification
• Quarterly Off-Site Responder Dispatch Test
• Quarterly FDC Inspection
December
• Quarterly Tamper & Waterflow Testing
• Quarterly Supervisory Signal Verification
• Quarterly Off-Site Responder Dispatch Test
• Quarterly FDC Inspection
• Annual NFPA 72 Fire Alarm Testing (Smoke, Heat, Pull Stations, Strobes/Horns, Duct Detectors, Door Releases, Fan Shutdowns, Rolling Shutters)
• Annual Main Drain & Backflow Tests
• 5-Year Flow Test (Next due 2030)
• Quarterly Tamper & Waterflow Testing
• Quarterly Supervisory Signal Verification
• Quarterly Off-Site Responder Dispatch Test
• Quarterly FDC Inspection
• Annual NFPA 72 Fire Alarm Testing
• Annual Fire Pump Performance Flow Test
• Annual Main Drain & Backflow Tests
• Annual Portable Fire Extinguisher Certification
• Annual Portable Fire Extinguisher Certification, Maintenance & Hydrostatic Testing
9. Baseline Equipment Inventory (Existing Equipment to be Maintained) Note: Device and component counts are approximate baseline figures. The Government will not replace these systems; the Contractor is responsible for inspecting, testing, and maintaining all installed devices present on site.
9.1 Lawton Indian Hospital Campus (LIH)
Main Hospital, CT Suite & Biomed (Building 421):
o Control Panel: Notifier NFS2-3030 intelligent panel, 3 remote annunciators, voice evacuation power boosters/file servers.
o Initiating/Notification: ~228 photoelectric smoke detectors, 16 heat detectors, 20 duct detectors, 32 manual pull stations, 200 horn/strobes and visual strobes, 9 magnetic door release holders.
o Sprinkler Riser: Backflow preventer, OS&Y control valves, 6 waterflow switches, 9 tamper switches.
o Doors: 19 fire doors, 6 smoke barrier doors.
Material Management, Finance, Diabetes & Shop (Building 423):
o Control Panel: Notifier NFS-320 addressable panel, remote annunciator, power extender/booster.
o Devices: 19 photoelectric smoke detectors, 2 duct detectors, 14 horn/strobes, 5 strobes.
o Sprinkler Riser: Backflow preventer, 2 tamper switches, 1 waterflow switch.
Office of Environmental Health (OEH Building 425):
o Control Panel: Notifier NFS-320 addressable panel.
o Devices: 10 photoelectric smoke detectors, 1 heat detector, 5 horn/strobes, 5 strobes.
o Sprinkler Riser: Backflow preventer, 2 tamper switches, 1 waterflow switch.
Modular Buildings (Dental, Behavioral Health, Public Health Nursing): Dedicated Notifier NFS-320 addressable panels, initiating and notification appliances, dedicated sprinkler risers, tamper switches, and backflow preventers.
Portable Fire Extinguishers: 120+ units distributed campus-wide.
9.2 Anadarko Indian Health Center Campus (AIHC)
Main Ambulatory Clinic Building:
o Control Panel: Notifier NFP-320 / NFS-320 addressable panel, annunciator, power booster.
o Devices: 26 smoke detectors, 2 heat detectors, 5 manual pull stations, 18 horn/strobes, 28 visual strobes, 13 monitor modules.
PHN Building, Wellness Center & COVID Building: All installed fire detection, audible/visual notification appliances, and sprinkler monitoring devices.
Water-Based System: Electric/diesel fire pump assembly, backflow preventer, main waterflow switch, and 4 supervisory tamper switches.
Portable Fire Extinguishers: 22 units distributed across campus (Main Clinic: 11; Wellness: 4;
PHN: 3; COVID: 2; Maintenance: 1; Storage: 1).
9.3 Carnegie Indian Health Center (CIHC)
Ambulatory Health Clinic: 5 portable fire extinguishers (inspection, maintenance, hydrostatic testing, and recharge only; no fire alarm or sprinkler scope).
10. Personnel Qualifications and System Capabilities
1. State Licensure Requirements:
o The Prime Contractor and any performing subcontractors must possess valid Oklahoma Department of Labor (ODOL) licenses for Commercial Fire Alarm, Fire Sprinkler, and Central Station Monitoring.
o Every on-site technician must carry individual Oklahoma licenses corresponding to their specialty trade (Commercial Fire Alarm or Fire Sprinkler).
2. Existing System Servicing Proficiency:
o Because existing systems will not be replaced, the Contractor must possess demonstrated direct technical proficiency, proprietary programming tools, software keys, and diagnostic equipment necessary to service and maintain existing Notifier ONYX series systems (NFS-320 and NFS2-3030) as well as the installed water-based suppression and fire pump infrastructure.
o Technicians performing programming, addressing, and database alterations on Notifier fire alarm control panels must be factory-trained and certified on Notifier ONYX series systems.
3. Fire Door Relabeling Authority: Personnel performing fire door field relabeling must be authorized field representatives of a Nationally Recognized Testing Laboratory (NRTL, such as Intertek/Warnock Hersey or UL).
11. Special Requirements, Security, and Facility Constraints
11.1 Security and Identity Verification (HSPD-12 / HHSAR 304.1300) In accordance with HHSAR 304.1300, contractor personnel requiring routine access to federal facilities must comply with Homeland Security Presidential Directive-12 (HSPD-12) identity verification policies.
All contractor personnel must report, present valid state/federal government-issued photo identification, log in with Hospital Security and Facilities Maintenance at the start of each workday, wear visible identification badges while on site, and sign out at the conclusion of each workday.
11.2 Information Security, HIPAA, and Non-Disclosure
Information Security: The Contractor is responsible for the security of all organizational information and shall comply with all federal information security rules applicable to the premises.
Confidentiality / Non-Disclosure: LSU facilities operate 24/7/365 providing direct patient care.
The Contractor shall maintain strict confidentiality regarding patient and facility operations in full compliance with the Health Insurance Portability and Accountability Act (HIPAA). The Contractor shall not disclose or disseminate any proprietary or patient information encountered during performance.
Official Information Requests: All media inquiries, public comments, or official information requests arising from performance shall be immediately referred to the CEO or Public Information Officer of the Lawton Service Unit.
11.3 Infection Control & Interim Life Safety Measures (ILSM)
Infection Control Risk Assessment (ICRA): The Contractor shall strictly adhere to LSU Safety and ICRA protocols. Technicians must use HEPA-filtered dust containment carts or drop cloths when working above ceiling tiles in clinical environments.
Interim Life Safety Measures (ILSM): Whenever a fire alarm or water-based suppression system is impaired or taken offline for more than four (4) hours in a 24-hour period, the Contractor must immediately notify the Safety Officer and Facility Engineer to coordinate an approved ILSM protocol and compensatory fire watch.
11.4 Tobacco-Free Federal Facility Policy
The Lawton Service Unit maintains a strictly enforced 100% tobacco-free and vapor-free environment.
No smoking, tobacco use, or electronic vapor devices are permitted anywhere inside buildings or on federal facility grounds.
11.5 Government Data and Software Ownership
All panel programming databases, system access passwords, software configuration files, and revised AutoCAD/PDF as-built drawings created or updated under this contract are the exclusive property of the Indian Health Service. The Contractor shall deliver copies to the Facility Engineer upon completion of any modification.
12. Deliverables and Reporting Standards
1. Itemized Inspection Reports:
o Delivered within five (5) business days following any inspection cycle.
o Every device must be explicitly located and itemized with a pass/fail determination (e.g., "Smoke Detector, Room 142 – NFS-320 Loop 1, Address 042 – PASS").
o Fire and smoke door reports must track each door by its unique LSU identifier, documenting latching force, clear opening width, top/bottom/side gap measurements, frame condition, and label status.
2. Corrective Repair Estimates: Written technical and cost estimates detailing parts, labor hours, and completion schedules, submitted within forty-eight (48) hours of deficiency identification (or within 4 hours for emergency repairs).
3. Post-Repair Certification Documentation: Following any corrective repair, flex-drop modification, RTU interlock wiring, or door gap correction, the Contractor shall provide a written certification letter and updated testing report confirming NFPA acceptance.
13. Quality Assurance Surveillance Plan (QASP)
# Performance Objective
Standard & Code Reference
Acceptable Quality Level (AQL)
Method of Surveillance
13.1 24/7 Alarm Monitoring
Continuous monitoring of all panels; immediate dispatch to fire departments and LSU call lists.
100% uptime; zero missed or delayed alarm transmissions.
Central station logs and quarterly call transmission test records.
13.2 Periodic Inspections & Testing
100% of listed and discoverable devices tested per NFPA 10, 13, 25, 72, 80, 96, and 105.
Zero missed devices;
complete itemized pass/fail reports within 5 business days.
Facility Engineer review of inspection reports against inventory.
13.3 Fire & Smoke Door Inspections & Remediation
Annual inspection of 25 doors (LIH); corrective gap/latch remediation completed per approved work orders.
100% inspected; all door gap kits and hardware adjustments meet NFPA 80 clearance tolerances.
Physical door inspection audit; post-repair feeler gauge measurements.
13.4 Extinguisher Service Lifecycle
Annual tagging, hydrostatic testing, and internal teardown maintenance.
100% of extinguishers tagged and compliant;
immediate replacement of unserviceable units.
Physical extinguisher tag inspection and maintenance log review.
13.5 Emergency Call-
Out Response
24/7/365 emergency response for outages, panel faults, or waterflow alarms.
Technician on-site within 2 hours of dispatch; fire watch coordinated within 4 hours if impaired.
Facility Security sign-in logs and work order timestamp records.
13.6 Routine Corrective Repairs & Integrations
Code-compliant execution of flex-drops, RTU fan shutdown wiring, and panel programming on existing equipment.
100% code compliance
(NFPA 13, 72, 90A);
zero leaks; zero addressing conflicts.
Joint commissioning test with LSU Maintenance and Facility Engineer.
13.7 Technician Licensure & Certification
All personnel hold active Oklahoma Department of Labor licenses and required factory certifications for existing installed systems.
100% compliance; zero uncertified or unlicensed labor permitted on site.
Verification of state licenses and Notifier/NRTL credentials prior to work.
Department Supervisor Signature Date
Clinical / Department Director Signature Date
Christopher G.
Anthony -S
Digitally signed by Christopher G.
Anthony -S Date: 2026.11.18 14:41:50 -06'00'
Christopher G.
Anthony -S
Digitally signed by Christopher G. Anthony -S Date: 2026.11.18 14:42:12 -06'00'
DEPARTMENT OF HEALTH & HUMAN SERVICES
Office of Management Services Division of Acquisition Policy (DAP)
5600 Fishers Lane Rockville, MD 20857
INDIAN HEALTH SERVICE
BUY INDIAN ACT
INDIAN ECONOMIC ENTERPRISE
REPRESENTATION FORM
SOLICITATION/SOURCES SOUGHT/RFI #: _________________________________________________
PROJECT TITLE: ________________________________________________________
DATE: ___________________________________________________________________
In accordance with 25 U.S.C. 47 the Buy Indian Act, the signature below constitutes self-certification that the Offeror meets the definition of an “Indian Economic Enterprise” (HHSAR 326.601) in response to this Sources Sought Notice, Request for Information (RFI) or Solicitation and resultant contract.
The enterprise must meet the definition of “Indian Economic Enterprise” throughout the following time periods:
(1) At the time an offer is made in response to this solicitation;
(2) At the time of contract award; and
(3) During the full term of the contract performance period. At any point during these periods, if the Contractor no longer meets the eligibility requirements, the contractor must provide immediate written notification to the Contracting Officer.
Individual Contracting Officers may require documentation of eligibility before awarding a set-aside or sole source contracts under the Buy Indian Act and awards may be subject to protest if the eligibility of the successful Offeror is in question. In addition to the self-certification requirements, successful Offerors must also be registered with the System of Award Management (SAM).
Any false or misleading information submitted by an enterprise when submitting an offer in consideration of an award set-aside under the authority of the Buy Indian Act is a violation of the law and punishable under 18 U.S.C. 1001.
False claims submitted as part of contract performance are subject to the penalties enumerated in 31 U.S.C. 3729 to 3731 and 18 U.S.C. 287.
REPRESENTATION
The Offeror represents as part of its offer that it does _____, does not _____ meet the definition of an “Indian Economic Enterprise” with “Indian Ownership” under the authority of the Buy Indian Act.
Name of the 51% owner of IEE Firm
Certifying Signature
Print Name
Name of Federally Recognized Tribal Entity
Business Name
UEI Number
Sources Sought Notice — Buy Indian Act
| SOLICITATION_NUMBER: IHS-SS-11182026 Fire Monitoring / Inspections / Servicing |
| PROJECT_TITLE: Fire Alarm Monitoring, Inspections, Maintenance,and Remediation Service |
| DATE: |
| Does: Off |
| DoesNot: 0 |
| NameOfTribalEntity: |
| BusinessName: |
| DUNSnumber: |
| OwnerName: |
| PrintName: |
File details come from the government source that posted it. Updated .