Request For Information (RFI) 1

IFBP02131100001

Replace Roof Project

FCI Schuylkill

1. Who is responsible for removing razor wire as needed for roof work? If contractor, does it need to be re-installed each night?

ANSWER:

THE REMOVAL AND RE-INSTALLATION OF THE EXISTING

LIGHTNING PROTECTION AND/OR RAZOR RIBBON IS THE

CONTRACTOR RESPONSIBILITY AS REQUIRED. YES RAZOR WIRE

WILL BE RE-INSTALLED EACH NIGHT.

2. Who is responsible for removing and re-installing lightning protection? If contractor, does this have to be done by certified lightning protection company and be re-certified?

ANSWER:

THE REMOVAL AND REINSTALLATION OF THE EXISTING

LIGHTNING PROTECTION AND/OR RAZOR RIBBON IS THE

CONTRACTOR RESPONSIBILITY AS REQUIRED. NO IT DOES NOT

HAVE TO BE RE-INSTALLED BY A CERTIFIED LIGHTNING

PROTECTION COMPANY NOR RE-CERTIFIED.

3. What gauge metal for edging is required?

ANSWER:

A. Sheet metal:

1. Clad steel, min 0.6 mm 24 GA galvanized Z275G90.

(1) Smooth.

2. ASTM-A653/A653M.

3. Coated on each face with 0.025 mm 1 mil fluorocarbon coating, 70 percent Kynar/Hylar.

B. Sheet metal:

1. Galvanized steel, ASTM-A653/A653M.

2. Minimum 0.75 mm 22 GA.

C. Sheet metal:

1. Stainless steel, ASTM-A167 or ASTM-A176.

2. Minimum 0.6 mm 24 GA, soft annealed.

4. In the Statement of Work – Please verify what type of cover board system you want to use (Part 2 Products, 2.02).

ANSWER:

AS PER MANUFACTURES SPECIFICATIONS NOT TO VOID

WARRANTY, MINIMUM 7/16" PLYWOOD OR OSB