Request For Information (RFI) 1
IFBP02131100001
Replace Roof Project
FCI Schuylkill
1. Who is responsible for removing razor wire as needed for roof work? If contractor, does it need to be re-installed each night?
ANSWER:
THE REMOVAL AND RE-INSTALLATION OF THE EXISTING
LIGHTNING PROTECTION AND/OR RAZOR RIBBON IS THE
CONTRACTOR RESPONSIBILITY AS REQUIRED. YES RAZOR WIRE
WILL BE RE-INSTALLED EACH NIGHT.
2. Who is responsible for removing and re-installing lightning protection? If contractor, does this have to be done by certified lightning protection company and be re-certified?
ANSWER:
THE REMOVAL AND REINSTALLATION OF THE EXISTING
LIGHTNING PROTECTION AND/OR RAZOR RIBBON IS THE
CONTRACTOR RESPONSIBILITY AS REQUIRED. NO IT DOES NOT
HAVE TO BE RE-INSTALLED BY A CERTIFIED LIGHTNING
PROTECTION COMPANY NOR RE-CERTIFIED.
3. What gauge metal for edging is required?
ANSWER:
A. Sheet metal:
1. Clad steel, min 0.6 mm 24 GA galvanized Z275G90.
(1) Smooth.
2. ASTM-A653/A653M.
3. Coated on each face with 0.025 mm 1 mil fluorocarbon coating, 70 percent Kynar/Hylar.
B. Sheet metal:
1. Galvanized steel, ASTM-A653/A653M.
2. Minimum 0.75 mm 22 GA.
C. Sheet metal:
1. Stainless steel, ASTM-A167 or ASTM-A176.
2. Minimum 0.6 mm 24 GA, soft annealed.
4. In the Statement of Work – Please verify what type of cover board system you want to use (Part 2 Products, 2.02).
ANSWER:
AS PER MANUFACTURES SPECIFICATIONS NOT TO VOID
WARRANTY, MINIMUM 7/16" PLYWOOD OR OSB
File details come from the government source that posted it. Updated .