Hydac Filter Specifications.pdf
PDF 378 KB Posted
- Attached to
- 4410--Filter Boiler Reheat System
- Solicitation number
- 36C24625Q0426
About this file
This document contains technical specifications and configuration details for the Schroeder Industries AutoFilt RF3-2.5 Backflushing Filter system. The specifications outline a filter system with a flow range of 1760-2640 gpm (6670-10,000 L/min), working pressure of 150 psi (10 bar), and maximum working temperature of 194°F (90°C).
The document provides detailed dimensional drawings, installation configurations, and a model number selection guide for ordering. Key specifications include a 10" ANSI flange size, filter area of 1940 in², 6 filter elements, and backflush volume options of 17 gallons per cycle for Electric-Pneumatic Controls or 85 gallons per cycle for All Electric Controls. The system weighs 990 lbs empty and has a housing volume of 50 gallons. The specifications include pressure drop flow curves and multiple configuration options for housing materials, control types, and element sets ranging from 25 micron to 3000 micron filtration ratings.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Supply eCMS Line Item Template.xlsx | XLSX spreadsheet | |
| 36C24625Q0426.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SCHROEDER INDUSTRIES | PROCESS FILTRATION20
1760-2640 gpm
6670-10,000 L/min
150 psi 10 bar
RF3-2.5 Backflushing Filter AutoFilt® RF3
Specifications
Pressure Drop
Information Based on Flow Rate and Viscosity
NOTES:
1. Metric di men sions in ( ).
2. Drawings may change without notice. Contact factory for certified drawings.
57.11
69.31
47.11
6.7
.22
.70
69.31
SNOITARUGIFNOC EGNALF TELTUO
TELNI
.54
00.6
.32
.79
.01 43
8.7
8.7
35.7
°94
17.
SECALP )3(
Flange Size: 10"ANSI
Flow Range: 1760-2640 gpm (6670-10,000 L/min)
Working Pressure: 150 psi (10 bar)
Max. Working Temperature: 194°F (90°C)
Empty Weight: 990 lbs. (450 kg)
Housing Volume: 50 gallons (190 L)
Filter Area: 1940 in.2 (12,500 cm2)
No. of Filter Elements 6
Backflush Flange Size: 2"ANSI
Backflush Volume: 17 gallons (65 L/cycle) Electric-Pneumatic Controls (EPT) 85 gallons (325 L/cycle) All Electric Controls (EU) sevruC wolF 3FR
5.2-3FR
00001
000001
55.445.335.225.115.00 )disp( pord erusserP
Fl ow
R at e (g pm
= )ylppa snoitidnoc( etar wolf xam
:etoN sgnitar noitartlif mµ0003 - mµ001 rof era sevruc esehT rof %03 yb sesaercni pord erusserp ehT .snoitidnoc naelc rednu roF .8 hguorht 0-3FR sezis gnisu nehw noitartlif mµ05 - mµ52 .sgnitar noitartlif lla ot seilppa nwohs evruc eht ,C-3FR
RF3-C
RF3-0
RF3-1
RF3-2
RF3-2.5
RF3-3
RF3-4
RF3-5
RF3-6
RF3-7
RF3-8
RF5
RF7
RF10
RF4
RF4-1
RF4-2
RF12
BTU
ATF
PLF1
PVD
SCHROEDER INDUSTRIES | PROCESS FILTRATION
Filter Model Number Selection
Backflushing Filter AutoFilt® RF3
RF3-2.5
RF3-2.5
EPT = Electric pneumatic cycle control, ∆p dependent
EU = Electric control, ∆p dependent
PT = Pneumatic cyclic control, ∆p dependent
PTZ = Pneumatic cyclic timed control
7 = 3X415V/N/PE 60Hz
8 = 3X460V/X/PE 60Hz
B = 3X575V/X/PE 60Hz
E = 1X230V/N/PE 60Hz
F = 1X110V/N/PE 60Hz
BOX 1 BOX 2 BOX 3 BOX 4 BOX 5 BOX 6 BOX 7 BOX 8 BOX 9 BOX 10 BOX 11
Vessel Certification
Omit = Standard Version
ASME = ASME Version
Size of Element Set
2.5
Modification Number
2 = Latest version supplied by factory
Shut-Off Valve Material
N = Standard Steel
E = Stainless Steel
Housing Material and Coating
N = Standard Steel 1.0038, outside primed
NM = Standard Steel 1.0038, outside primed, inside metallogal painted
NG =Standard Steel 1.0038, outside primed, inside rubber coated
E = Stainless Steel 1.4571
A = With ANSI-flanged, add. A at the end
Drive Control / Connecting Voltage
Filter Series
Filter Size
RF3 2.5
How to Build a Valid Model Number for a RF3:
Example: NOTE: One option per box
BOX 1 BOX 2 BOX 3 BOX 4 BOX 5
BOX 6 BOX 7 BOX 8 BOX 9
Flange Position
1 = Filter outlet opposite filter inlet (standard)
2 = Filter outlet offset 90˚ clockwise to standard
3 = Filter outlet offset by 180˚ clockwise to standard
4 = Filter outlet offset by 270˚ clockwise to standard
BOX 10 BOX 11
RF3 ASME2.5KS1000235NNGEPT82.5 = RF3-2.5-EPT8-NG-N-5-3-2
/KS1000-2.5-ASME
Element Set
KD25 = Conical SuperMesh™
KD40 = Conical SuperMesh™
KS50 = Conical Slotted Tubes
KS100 = Conical Slotted Tubes
KS200 = Conical Slotted Tubes
KS300 = Conical Slotted Tubes
KS400 = Conical Slotted Tubes
KS500 = Conical Slotted Tubes
KS1000 = Conical Slotted Tubes
KS1500 = Conical Slotted Tubes
KS2000 = Conical Slotted Tubes
KS2500 = Conical Slotted Tubes
KS3000 = Conical Slotted Tubes
NOTES:
Box 3. Needs to have control type and voltage selected
ex. EPT8.
Box 4. can contain two options ex. NMA.
| note. | If | ANSI | flanges | ||
| are | not | specified |
DIN style will be provided.
Differential Pressure Gauge
1 = Pressure Chamber, Aluminum 3.258302
2 = Pressure Chamber, Stainless Steel 1.4305
3 = With Chemical Seal Stainless Steel 316TI
5 = HDA 4700
Stainless Steel
6 = HDA 4300 Duplex Stainless Steel
BOX 1 BOX 2 BOX 3 BOX 4 BOX 5 BOX 6 BOX 7 BOX 8 BOX 9 BOX 10 BOX 11
RF3 2.5