HSFEHQ-09-R-0021A

Table of Contents

SECTION A

A

A.1 SF 1449 SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL ITEMS

A

SECTION B - CONTINUATION BLOCK

B

B.1 PRICE/COST SCHEDULE

B-73

B.2 DELIVERY SCHEDULE

B-73

SECTION C - DESCRIPTION/SPECIFICATIONS/STATEMENT OF WORK ……………………..

C-1

SECTION D – PACKING AND MARKING ……………………………………………………………

D-1

SECTION E - INSPECTION AND ACCEPTANCE……………………………………………………...

E-1

SECTION F - DELIVERIES OR PERFORMANCE …………………………………………………….

F-1

SECTION G - CONTRACT ADMINISTRATION DATA ……………………………………………….

G-1

SECTION H - SPECIAL CONTRACT REQUIREMENTS ……………………………………………

H-1

SECTION I - CONTRACT CLAUSES

C

I.1 52.212-4 CONTRACT TERMS AND CONDITIONS--COMMERCIAL ITEMS (OCT 2008)

C-61 I.2 ADDENDUM to FAR 52.212-4 Contract Terms and Conditions-- Commercial Items C-4

I.3 52.217-8 OPTION TO EXTEND SERVICES (NOV 1999)

C-6

I.4 52.217-9 OPTION TO EXTEND THE TERM OF THE CONTRACT (MAR 2000)

C-6

I.5 52.228-5 INSURANCE - WORK ON A GOVERNMENT INSTALLATION (JAN 1997)

C-6

I.6 52.232-32 PERFORMANCE-BASED PAYMENTS (JAN 2008)

C-8

I.7 52.252-2 CLAUSES INCORPORATED BY REFERENCE (FEB 1998)

C-11 I.8 52.212-5 CONTRACT TERMS AND CONDITIONS REQUIRED TO IMPLEMENT STATUTES OR EXECUTIVE ORDERS--COMMERCIAL ITEMS (OCT 2008)

C-11

PART III – LIST OF DOCUMENTS, EXHIBITS, OR AND OTHER ATTACHMENTS ……………….

J-1

SECTION J – LIST OF ATTACHMENTS ……………………………………………………………………...

J-1

PART IV - REPRESENTATIONS AND INSTRUCTIONS………………………………………………………

K-1

K.1 SECTION K - REPRESENTATIONS, CERTIFICATIONS, AND OTHER STATEMENTS OF OFFERORS OR RESPONDENTS…………………………………………………………………………………………………….

K-1

SECTION L – INSTRUCTIONS, CONDITIONS, AND NOTICE TO OFFERORS-- OR RESPONDENTS …..

L-1

SECTION M. EVALUATION FACTORS FOR AWARD…………………………………………………………

M-1

A.2 PRICE/COST SCHEDULE

ITEM DESCRIPTION OF QTY UNIT UNIT AMOUNT

NO. SUPPLIES/SVCS PRICE

0001 0.00 ___________________ ____________________

Base Year Distribution Center (DC)

Atlanta

0001AA 0.00 Each___________________ ____________________

Generator sizes - 0 to 49kW

DC Atlanta

Welder Generator, 16 foot Utility Tag

Trailer and 20 foot Utility Tag Trailer

0001AB 0.00 Each___________________ ____________________

Generator sizes - 50 to 99kW

DC Atlanta

0001AC 0.00 Each___________________ ____________________

Generator sizes - 100 to 199kW

DC Atlanta

0001AD 0.00 Each___________________ ____________________

Generator sizes - 200 to 299kW

DC Atlanta

0001AE 0.00 Each___________________ ____________________

Generator sizes - 300 to 399kW

DC Atlanta

0001AF 0.00 Each___________________ ____________________

Generator sizes - 400 to 499kW

DC Atlanta

0001AG 0.00 Each___________________ ____________________

Generator sizes - 500 to 699kW

DC Atlanta

0001AH 0.00 Each___________________ ____________________

Generator sizes - 700 to 899kW

DC Atlanta

0001AI 0.00 Each___________________ ____________________

Generator sizes - 900kW

DC Atlanta

0001AJ 0.00 ___________________ ____________________

Grand Total from SUBCLIN 0001AA thru

0001AK

0001AK 0.00 ___________________ ____________________

Generator Maintenance Mechanic Proposed

Labor Rate - $_________

Parts and Materials (Cost Only) -

Miscellaneous Repair and Repairable -

Funding in support of Major Maintenance and repairs as defined in the

Performance Based Work Statement

(Attachment A), entitled, “National

On-Site Generator Maintenance” dated

December 2, 2008

This is a Cost only line item in support of Item 0001. No funding shall be expended without prior approval of the Contracting Officer Technical

Representative along with written

Concurrence via email from the

Contracting Officer.

0002 0.00 ___________________ ____________________

Distribution Center (DC) Frederick

0002AA 0.00 Each___________________ ____________________

Generator sizes - 0 TO 49kW

DC Frederick

0002AB 0.00 Each___________________ ____________________

Generator sizes - 50 to 99kW

DC Frederick

0002AC 0.00 Each___________________ ____________________

Generator sizes - 100 to 199kW

DC Frederick

0002AD 0.00 Each___________________ ____________________

Generator sizes - 200 to 299kW

DC Frederick

0002AE 0.00 Each___________________ ____________________

Generator sizes - 300 to 399kW

DC Frederick

0002AF 0.00 Each___________________ ____________________

Generator sizes - 400 to 499kW

DC - Frederick

0002AG 0.00 Each___________________ ____________________

Generator sizes - 500 to 699kW

DC - Frederick

0002AH 0.00 Each___________________ ____________________

Generator sizes - 700 to 899kW

DC - Frederick

0002AI 0.00 Each___________________ ____________________

Generator sizes - 900kW

DC - Frederick

0002AJ 0.00 ___________________ ____________________

Grand Total from SUBCLIN 0002AA thru

0002AK

0002AK 0.00 ___________________ ____________________

Generator Maintenance Mechanic Proposed

Labor Rate - $_________

Parts and Materials (Cost Only) -

Miscellaneous Repair and Repairable -

Funding in support of Major Maintenance and repairs as defined in the

Performance Based Work Statement

(Attachment A), entitled, “National

On-Site Generator Maintenance” dated

December 2, 2008

This is a Cost only line item in support of Item 0001. No funding shall be expended without prior approval of the Contracting Officer Technical

Representative along with written

Concurrence via email from the

Contracting Officer.

0003 0.00 ___________________ ____________________

Distribution Center (DC) Fort Worth

0003AA 0.00 Each___________________ ____________________

Generator sizes - 0 TO 49kW

DC Fort Worth

0003AB 0.00 Each___________________ ____________________

Generator sizes - 50 to 99kW

DC Fort Worth

0003AC 0.00 Each___________________ ____________________

Generator sizes - 100 to 199kW

DC Fort Worth

0003AD 0.00 Each___________________ ____________________

Generator sizes - 200 to 299kW

DC Fort Worth

0003AE 0.00 Each___________________ ____________________

Generator sizes - 300 to 399kW

DC Fort Worth

0003AF 0.00 Each___________________ ____________________

Generator sizes - 400 to 499kW

DC Fort Worth

0003AG 0.00 Each___________________ ____________________

Generator sizes - 500 to 699kW

DC Fort Worth

0003AH 0.00 Each___________________ ____________________

Generator sizes - 700 to 899kW

DC - Frederick

0003AI 0.00 Each___________________ ____________________

Generator sizes - 900kW

DC Fort Worth

0003AJ 0.00 ___________________ ____________________

Grand Total from SUBCLIN 0003AA thru

0003AK

0003AK 0.00 ___________________ ____________________

Generator Maintenance Mechanic Proposed

Labor Rate - $_________

Parts and Materials (Cost Only) -

Miscellaneous Repair and Repairable -

Funding in support of Major Maintenance and repairs as defined in the

Performance Based Work Statement

(Attachment A), entitled, “National

On-Site Generator Maintenance” dated

December 2, 2008

This is a Cost only line item in support of Item 0001. No funding shall be expended without prior approval of the Contracting Officer Technical

Representative along with written

Concurrence via email from the

Contracting Officer.

0004 0.00 ___________________ ____________________

Distribution Center (DC) Fort Worth

0004AA 0.00 Each___________________ ____________________

Generator sizes - 0 TO 49kW

DC Moffett

0004AB 0.00 Each___________________ ____________________

Generator sizes - 50 to 99kW

DC Moffett

0004AC 0.00 Each___________________ ____________________

Generator sizes - 100 to 199kW

DC Moffett

0004AD 0.00 Each___________________ ____________________

Generator sizes - 200 to 299kW

DC Moffett

0004AE 0.00 Each___________________ ____________________

Generator sizes - 300 to 399kW

DC Moffett

0004AF 0.00 Each___________________ ____________________

Generator sizes - 400 to 499kW

DC Moffett

0004AG 0.00 Each___________________ ____________________

Generator sizes - 500 to 699kW

DC Moffett

0004AH 0.00 Each___________________ ____________________

Generator sizes - 700 to 899kW

DC Moffett

0004AI 0.00 Each___________________ ____________________

Generator sizes - 900kW

DC Moffett

0004AJ 0.00 ___________________ ____________________

Grand Total from SUBCLIN 0004AA thru

0004AK

0004AK 0.00 ___________________ ____________________

Generator Maintenance Mechanic Proposed

Labor Rate - $_________

Parts and Materials (Cost Only) -

Miscellaneous Repair and Repairable -

Funding in support of Major Maintenance and repairs as defined in the

Performance Based Work Statement

(Attachment A), entitled, “National

On-Site Generator Maintenance” dated

December 2, 2008

This is a Cost only line item in support of Item 0001. No funding shall be expended without prior approval of the Contracting Officer Technical

Representative along with written

Concurrence via email from the

Contracting Officer.

0101 0.00 ___________________ ____________________

Option Year 1 - Distribution Center

(DC) Atlanta

0101AA 0.00 Each___________________ ____________________

Generator sizes - 0 to 49kW

DC Atlanta

Welder Generator, 16 foot Utility Tag

Trailer and 20 foot Utility Tag Trailer

0101AB 0.00 Each___________________ ____________________

Generator sizes - 50 to 99kW

DC Atlanta

0101AC 0.00 Each___________________ ____________________

Generator sizes - 100 to 199kW

DC Atlanta

0101AD 0.00 Each___________________ ____________________

Generator sizes - 200 to 299kW

DC Atlanta

0101AE 0.00 Each___________________ ____________________

Generator sizes - 300 to 399kW

DC Atlanta

0101AF 0.00 Each___________________ ____________________

Generator sizes - 400 to 499kW

DC Atlanta

0101AG 0.00 Each___________________ ____________________

Generator sizes - 500 to 699kW

DC Atlanta

0101AH 0.00 Each___________________ ____________________

Generator sizes - 700 to 899kW

DC Atlanta

0101AI 0.00 Each___________________ ____________________

Generator sizes - 900kW

DC Atlanta

0101AJ 0.00 ___________________ ____________________

Grand Total from SUBCLIN 0101AA thru

0101AK

0101AK 0.00 ___________________ ____________________

Generator Maintenance Mechanic Proposed

Labor Rate - $_________

Parts and Materials (Cost Only) -

Miscellaneous Repair and Repairable -

Funding in support of Major Maintenance and repairs as defined in the

Performance Based Work Statement

(Attachment A), entitled, “National

On-Site Generator Maintenance” dated

December 2, 2008

This is a Cost only line item in support of Item 0001. No funding shall be expended without prior approval of the Contracting Officer Technical

Representative along with written

Concurrence via email from the

Contracting Officer.

0102 0.00 ___________________ ____________________

Optiion Year 1 -Distribution Center

(DC) Frederick

0102AA 0.00 Each___________________ ____________________

Generator sizes - 0 TO 49kW

DC Frederick

0102AB 0.00 Each___________________ ____________________

Generator sizes - 50 to 99kW

DC Frederick

0102AC 0.00 Each___________________ ____________________

Generator sizes - 100 to 199kW

DC Frederick

0102AD 0.00 Each___________________ ____________________

Generator sizes - 200 to 299kW

DC Frederick

0102AE 0.00 Each___________________ ____________________

Generator sizes - 300 to 399kW

DC Frederick

0102AF 0.00 Each___________________ ____________________

Generator sizes - 400 to 499kW

DC - Frederick

0102AG 0.00 Each___________________ ____________________

Generator sizes - 500 to 699kW

DC - Frederick

0102AH 0.00 Each___________________ ____________________

Generator sizes - 700 to 899kW

DC - Frederick

0102AI 0.00 Each___________________ ____________________

Generator sizes - 900kW

DC - Frederick

0102AJ 0.00 ___________________ ____________________

Grand Total from SUBCLIN 0102AA thru

0102AK

0102AK 0.00 ___________________ ____________________

Generator Maintenance Mechanic Proposed

Labor Rate - $_________

Parts and Materials (Cost Only) -

Miscellaneous Repair and Repairable -

Funding in support of Major Maintenance and repairs as defined in the

Performance Based Work Statement

(Attachment A), entitled, “National

On-Site Generator Maintenance” dated

December 2, 2008

This is a Cost only line item in support of Item 0001. No funding shall be expended without prior approval of the Contracting Officer Technical

Representative along with written

Concurrence via email from the

Contracting Officer.

0103 0.00 ___________________ ____________________

Option Year 1 Distribution Center (DC)

Fort Worth

0103AA 0.00 Each___________________ ____________________

Generator sizes - 0 TO 49kW

DC Fort Worth

0103AB 0.00 Each___________________ ____________________

Generator sizes - 50 to 99kW

DC Fort Worth

0103AC 0.00 Each___________________ ____________________

Generator sizes - 100 to 199kW

DC Fort Worth

0103AD 0.00 Each___________________ ____________________

Generator sizes - 200 to 299kW

DC Fort Worth

0103AE 0.00 Each___________________ ____________________

Generator sizes - 300 to 399kW

DC Fort Worth

0103AF 0.00 Each___________________ ____________________

Generator sizes - 400 to 499kW

DC Fort Worth

0103AG 0.00 Each___________________ ____________________

Generator sizes - 500 to 699kW

DC Fort Worth

0103AH 0.00 Each___________________ ____________________

Generator sizes - 700 to 899kW

DC - Frederick

0103AI 0.00 Each___________________ ____________________

Generator sizes - 900kW

DC Fort Worth

0103AJ 0.00 ___________________ ____________________

Grand Total from SUBCLIN 0103AA thru

0103AK

0103AK 0.00 ___________________ ____________________

Generator Maintenance Mechanic Proposed

Labor Rate - $_________

Parts and Materials (Cost Only) -

Miscellaneous Repair and Repairable -

Funding in support of Major Maintenance and repairs as defined in the

Performance Based Work Statement

(Attachment A), entitled, “National

On-Site Generator Maintenance” dated

December 2, 2008

This is a Cost only line item in support of Item 0001. No funding shall be expended without prior approval of the Contracting Officer Technical

Representative along with written

Concurrence via email from the

Contracting Officer.

0104 0.00 ___________________ ____________________

Option Year 1 - Distribution Center

(DC) Moffett Field

0104AA 0.00 Each___________________ ____________________

Generator sizes - 0 TO 49kW

DC Moffett

0104AB 0.00 Each___________________ ____________________

Generator sizes - 50 to 99kW

DC Moffett

0104AC 0.00 Each___________________ ____________________

Generator sizes - 100 to 199kW

DC Moffett

0104AD 0.00 Each___________________ ____________________

Generator sizes - 200 to 299kW

DC Moffett

0104AE 0.00 Each___________________ ____________________

Generator sizes - 300 to 399kW

DC Moffett

0104AF 0.00 Each___________________ ____________________

Generator sizes - 400 to 499kW

DC Moffett

0104AG 0.00 Each___________________ ____________________

Generator sizes - 500 to 699kW

DC Moffett

0104AH 0.00 Each___________________ ____________________

Generator sizes - 700 to 899kW

DC Moffett

0104AI 0.00 Each___________________ ____________________

Generator sizes - 900kW

DC Moffett

0104AJ 0.00 ___________________ ____________________

Grand Total from SUBCLIN 0104AA thru

0104AK

0104AK 0.00 ___________________ ____________________

Generator Maintenance Mechanic Proposed

Labor Rate - $_________

Parts and Materials (Cost Only) -

Miscellaneous Repair and Repairable -

Funding in support of Major Maintenance and repairs as defined in the

Performance Based Work Statement

(Attachment A), entitled, “National

On-Site Generator Maintenance” dated

December 2, 2008

This is a Cost only line item in support of Item 0001. No funding shall be expended without prior approval of the Contracting Officer Technical

Representative along with written

Concurrence via email from the

Contracting Officer.

0201 0.00 ___________________ ____________________

Option Year 2 - Distribution Center

(DC) Atlanta

0201AA 0.00 Each___________________ ____________________

Generator sizes - 0 to 49kW

DC Atlanta

Welder Generator, 16 foot Utility Tag

Trailer and 20 foot Utility Tag Trailer

0201AB 0.00 Each___________________ ____________________

Generator sizes - 50 to 99kW

DC Atlanta

0201AC 0.00 Each___________________ ____________________

Generator sizes - 100 to 199kW

DC Atlanta

0201AD 0.00 Each___________________ ____________________

Generator sizes - 200 to 299kW

DC Atlanta

0201AE 0.00 Each___________________ ____________________

Generator sizes - 300 to 399kW

DC Atlanta

0201AF 0.00 Each___________________ ____________________

Generator sizes - 400 to 499kW

DC Atlanta

0201AG 0.00 Each___________________ ____________________

Generator sizes - 500 to 699kW

DC Atlanta

0201AH 0.00 Each___________________ ____________________

Generator sizes - 700 to 899kW

DC Atlanta

0201AI 0.00 Each___________________ ____________________

Generator sizes - 900kW

DC Atlanta

0201AJ 0.00 ___________________ ____________________

Grand Total from SUBCLIN 0201AA thru

0201AK

0201AK 0.00 ___________________ ____________________

Generator Maintenance Mechanic Proposed

Labor Rate - $_________

Parts and Materials (Cost Only) -

Miscellaneous Repair and Repairable -

Funding in support of Major Maintenance and repairs as defined in the

Performance Based Work Statement

(Attachment A), entitled, “National

On-Site Generator Maintenance” dated

December 2, 2008

This is a Cost only line item in support of Item 0001. No funding shall be expended without prior approval of the Contracting Officer Technical

Representative along with written

Concurrence via email from the

Contracting Officer.

0202 0.00 ___________________ ____________________

Option Year 2 - Distribution Center

(DC) Frederick

0202AA 0.00 Each___________________ ____________________

Generator sizes - 0 TO 49kW

DC Frederick

0202AB 0.00 Each___________________ ____________________

Generator sizes - 50 to 99kW

DC Frederick

0202AC 0.00 Each___________________ ____________________

Generator sizes - 100 to 199kW

DC Frederick

0202AD 0.00 Each___________________ ____________________

Generator sizes - 200 to 299kW

DC Frederick

0202AE 0.00 Each___________________ ____________________

Generator sizes - 300 to 399kW

DC Frederick

0202AF 0.00 Each___________________ ____________________

Generator sizes - 400 to 499kW

DC - Frederick

0202AG 0.00 Each___________________ ____________________

Generator sizes - 500 to 699kW

DC - Frederick

0202AH 0.00 Each___________________ ____________________

Generator sizes - 700 to 899kW

DC - Frederick

0202AI 0.00 Each___________________ ____________________

Generator sizes - 900kW

DC - Frederick

0202AJ 0.00 ___________________ ____________________

Grand Total from SUBCLIN 0202AA thru

0202AK

0202AK 0.00 ___________________ ____________________

Generator Maintenance Mechanic Proposed

Labor Rate - $_________

Parts and Materials (Cost Only) -

Miscellaneous Repair and Repairable -

Funding in support of Major Maintenance and repairs as defined in the

Performance Based Work Statement

(Attachment A), entitled, “National

On-Site Generator Maintenance” dated

December 2, 2008

This is a Cost only line item in support of Item 0001. No funding shall be expended without prior approval of the Contracting Officer Technical

Representative along with written

Concurrence via email from the

Contracting Officer.

0203 0.00 ___________________ ____________________

Option Year 2 - Distribution Center

(DC) Fort Worth

0203AA 0.00 Each___________________ ____________________

Generator sizes - 0 TO 49kW

DC Fort Worth

0203AB 0.00 Each___________________ ____________________

Generator sizes - 50 to 99kW

DC Fort Worth

0203AC 0.00 Each___________________ ____________________

Generator sizes - 100 to 199kW

DC Fort Worth

0203AD 0.00 Each___________________ ____________________

Generator sizes - 200 to 299kW

DC Fort Worth

0203AE 0.00 Each___________________ ____________________

Generator sizes - 300 to 399kW

DC Fort Worth

0203AF 0.00 Each___________________ ____________________

Generator sizes - 400 to 499kW

DC Fort Worth

0203AG 0.00 Each___________________ ____________________

Generator sizes - 500 to 699kW

DC Fort Worth

0203AH 0.00 Each___________________ ____________________

Generator sizes - 700 to 899kW

DC - Frederick

0203AI 0.00 Each___________________ ____________________

Generator sizes - 900kW

DC Fort Worth

0203AJ 0.00 ___________________ ____________________

Grand Total from SUBCLIN 0203AA thru

0203AK

0203AK 0.00 ___________________ ____________________

Generator Maintenance Mechanic Proposed

Labor Rate - $_________

Parts and Materials (Cost Only) -

Miscellaneous Repair and Repairable -

Funding in support of Major Maintenance and repairs as defined in the

Performance Based Work Statement

(Attachment A), entitled, “National

On-Site Generator Maintenance” dated

December 2, 2008

This is a Cost only line item in support of Item 0001. No funding shall be expended without prior approval of the Contracting Officer Technical

Representative along with written

Concurrence via email from the

Contracting Officer.

0204 0.00 ___________________ ____________________

Option Year 2 - Distribution Center

(DC) Moffett Field

0204AA 0.00 Each___________________ ____________________

Generator sizes - 0 TO 49kW

DC Moffett

0204AB 0.00 Each___________________ ____________________

Generator sizes - 50 to 99kW

DC Moffett

0204AC 0.00 Each___________________ ____________________

Generator sizes - 100 to 199kW

DC Moffett

0204AD 0.00 Each___________________ ____________________

Generator sizes - 200 to 299kW

DC Moffett

0204AE 0.00 Each___________________ ____________________

Generator sizes - 300 to 399kW

DC Moffett

0204AF 0.00 Each___________________ ____________________

Generator sizes - 400 to 499kW

DC Moffett

0204AG 0.00 Each___________________ ____________________

Generator sizes - 500 to 699kW

DC Moffett

0204AH 0.00 Each___________________ ____________________

Generator sizes - 700 to 899kW

DC Moffett

0204AI 0.00 Each___________________ ____________________

Generator sizes - 900kW

DC Moffett

0204AJ 0.00 ___________________ ____________________

Grand Total from SUBCLIN 0204AA thru

0204AK

0204AK 0.00 ___________________ ____________________

Generator Maintenance Mechanic Proposed

Labor Rate - $_________

Parts and Materials (Cost Only) -

Miscellaneous Repair and Repairable -

Funding in support of Major Maintenance and repairs as defined in the

Performance Based Work Statement

(Attachment A), entitled, “National

On-Site Generator Maintenance” dated

December 2, 2008

This is a Cost only line item in support of Item 0001. No funding shall be expended without prior approval of the Contracting Officer Technical

Representative along with written

Concurrence via email from the

Contracting Officer.

0301 0.00 ___________________ ____________________

Option Year 3- Distribution Center (DC)

Atlanta

0301AA 0.00 Each___________________ ____________________

Generator sizes - 0 to 49kW

DC Atlanta

Welder Generator, 16 foot Utility Tag

Trailer and 20 foot Utility Tag Trailer

0301AB 0.00 Each___________________ ____________________

Generator sizes - 50 to 99kW

DC Atlanta

0301AC 0.00 Each___________________ ____________________

Generator sizes - 100 to 199kW

DC Atlanta

0301AD 0.00 Each___________________ ____________________

Generator sizes - 200 to 299kW

DC Atlanta

0301AE 0.00 Each___________________ ____________________

Generator sizes - 300 to 399kW

DC Atlanta

0301AF 0.00 Each___________________ ____________________

Generator sizes - 400 to 499kW

DC Atlanta

0301AG 0.00 Each___________________ ____________________

Generator sizes - 500 to 699kW

DC Atlanta

0301AH 0.00 Each___________________ ____________________

Generator sizes - 700 to 899kW

DC Atlanta

0301AI 0.00 Each___________________ ____________________

Generator sizes - 900kW

DC Atlanta

0301AJ 0.00 ___________________ ____________________

Grand Total from SUBCLIN 0301AA thru

0301AK

0301AK 0.00 ___________________ ____________________

Generator Maintenance Mechanic Proposed

Labor Rate - $_________

Parts and Materials (Cost Only) -

Miscellaneous Repair and Repairable -

Funding in support of Major Maintenance and repairs as defined in the

Performance Based Work Statement

(Attachment A), entitled, “National

On-Site Generator Maintenance” dated

December 2, 2008

This is a Cost only line item in support of Item 0001. No funding shall be expended without prior approval of the Contracting Officer Technical

Representative along with written

Concurrence via email from the

Contracting Officer.

0302 0.00 ___________________ ____________________

Option Year 3 - Distribution Center

(DC) Frederick

0302AA 0.00 Each___________________ ____________________

Generator sizes - 0 TO 49kW

DC Frederick

0302AB 0.00 Each___________________ ____________________

Generator sizes - 50 to 99kW

DC Frederick

0302AC 0.00 Each___________________ ____________________

Generator sizes - 100 to 199kW

DC Frederick

0302AD 0.00 Each___________________ ____________________

Generator sizes - 200 to 299kW

DC Frederick

0302AE 0.00 Each___________________ ____________________

Generator sizes - 300 to 399kW

DC Frederick

0302AF 0.00 Each___________________ ____________________

Generator sizes - 400 to 499kW

DC - Frederick

0302AG 0.00 Each___________________ ____________________

Generator sizes - 500 to 699kW

DC - Frederick

0302AH 0.00 Each___________________ ____________________

Generator sizes - 700 to 899kW

DC - Frederick

0302AI 0.00 Each___________________ ____________________

Generator sizes - 900kW

DC - Frederick

0302AJ 0.00 ___________________ ____________________

Grand Total from SUBCLIN 0302AA thru

0302AK

0302AK 0.00 ___________________ ____________________

Generator Maintenance Mechanic Proposed

Labor Rate - $_________

Parts and Materials (Cost Only) -

Miscellaneous Repair and Repairable -

Funding in support of Major Maintenance and repairs as defined in the

Performance Based Work Statement

(Attachment A), entitled, “National

On-Site Generator Maintenance” dated

December 2, 2008

This is a Cost only line item in support of Item 0001. No funding shall be expended without prior approval of the Contracting Officer Technical

Representative along with written

Concurrence via email from the

Contracting Officer.

0303 0.00 ___________________ ____________________

Option Year 3 - Distribution Center

(DC) Fort Worth

0303AA 0.00 Each___________________ ____________________

Generator sizes - 0 TO 49kW

DC Fort Worth

0303AB 0.00 Each___________________ ____________________

Generator sizes - 50 to 99kW

DC Fort Worth

0303AC 0.00 Each___________________ ____________________

Generator sizes - 100 to 199kW

DC Fort Worth

0303AD 0.00 Each___________________ ____________________

Generator sizes - 200 to 299kW

DC Fort Worth

0303AE 0.00 Each___________________ ____________________

Generator sizes - 300 to 399kW

DC Fort Worth

0303AF 0.00 Each___________________ ____________________

Generator sizes - 400 to 499kW

DC Fort Worth

0303AG 0.00 Each___________________ ____________________

Generator sizes - 500 to 699kW

DC Fort Worth

0303AH 0.00 Each___________________ ____________________

Generator sizes - 700 to 899kW

DC - Frederick

0303AI 0.00 Each___________________ ____________________

Generator sizes - 900kW

DC Fort Worth

0303AJ 0.00 ___________________ ____________________

Grand Total from SUBCLIN 0303AA thru

0303AK

0303AK 0.00 ___________________ ____________________

Generator Maintenance Mechanic Proposed

Labor Rate - $_________

Parts and Materials (Cost Only) -

Miscellaneous Repair and Repairable -

Funding in support of Major Maintenance and repairs as defined in the

Performance Based Work Statement

(Attachment A), entitled, “National

On-Site Generator Maintenance” dated

December 2, 2008

This is a Cost only line item in support of Item 0001. No funding shall be expended without prior approval of the Contracting Officer Technical

Representative along with written

Concurrence via email from the

Contracting Officer.

0304 0.00 ___________________ ____________________

Option Year 3 - Distribution Center

(DC) Moffett Field

0304AA 0.00 Each___________________ ____________________

Generator sizes - 0 TO 49kW

DC Moffett

0304AB 0.00 Each___________________ ____________________

Generator sizes - 50 to 99kW

DC Moffett

0304AC 0.00 Each___________________ ____________________

Generator sizes - 100 to 199kW

DC Moffett

0304AD 0.00 Each___________________ ____________________

Generator sizes - 200 to 299kW

DC Moffett

0304AE 0.00 Each___________________ ____________________

Generator sizes - 300 to 399kW

DC Moffett

0304AF 0.00 Each___________________ ____________________

Generator sizes - 400 to 499kW

DC Moffett

0304AG 0.00 Each___________________ ____________________

Generator sizes - 500 to 699kW

DC Moffett

0304AH 0.00 Each___________________ ____________________

Generator sizes - 700 to 899kW

DC Moffett

0304AI 0.00 Each___________________ ____________________

Generator sizes - 900kW

DC Moffett

0304AJ 0.00 ___________________ ____________________

Grand Total from SUBCLIN 0304AA thru

0304AK

0304AK 0.00 ___________________ ____________________

Generator Maintenance Mechanic Proposed

Labor Rate - $_________

Parts and Materials (Cost Only) -

Miscellaneous Repair and Repairable -

Funding in support of Major Maintenance and repairs as defined in the

Performance Based Work Statement

(Attachment A), entitled, “National

On-Site Generator Maintenance” dated

December 2, 2008

This is a Cost only line item in support of Item 0001. No funding shall be expended without prior approval of the Contracting Officer Technical

Representative along with written

Concurrence via email from the

Contracting Officer.

0401 0.00 ___________________ ____________________

Option Year 4 - Distribution Center

(DC) Atlanta

0401AA 0.00 Each___________________ ____________________

Generator sizes - 0 to 49kW

DC Atlanta

Welder Generator, 16 foot Utility Tag

Trailer and 20 foot Utility Tag Trailer

0401AB 0.00 Each___________________ ____________________

Generator sizes - 50 to 99kW

DC Atlanta

0401AC 0.00 Each___________________ ____________________

Generator sizes - 100 to 199kW

DC Atlanta

0401AD 0.00 Each___________________ ____________________

Generator sizes - 200 to 299kW

DC Atlanta

0401AE 0.00 Each___________________ ____________________

Generator sizes - 300 to 399kW

DC Atlanta

0401AF 0.00 Each___________________ ____________________

Generator sizes - 400 to 499kW

DC Atlanta

0401AG 0.00 Each___________________ ____________________

Generator sizes - 500 to 699kW

DC Atlanta

0401AH 0.00 Each___________________ ____________________

Generator sizes - 700 to 899kW

DC Atlanta

0401AI 0.00 Each___________________ ____________________

Generator sizes - 900kW

DC Atlanta

0401AJ 0.00 ___________________ ____________________

Grand Total from SUBCLIN 0401AA thru

0401AK

0401AK 0.00 ___________________ ____________________

Generator Maintenance Mechanic Proposed

Labor Rate - $_________

Parts and Materials (Cost Only) -

Miscellaneous Repair and Repairable -

Funding in support of Major Maintenance and repairs as defined in the

Performance Based Work Statement

(Attachment A), entitled, “National

On-Site Generator Maintenance” dated

December 2, 2008

This is a Cost only line item in support of Item 0001. No funding shall be expended without prior approval of the Contracting Officer Technical

Representative along with written

Concurrence via email from the

Contracting Officer.

0402 0.00 ___________________ ____________________

Option Year 4 - Distribution Center

(DC) Frederick

0402AA 0.00 Each___________________ ____________________

Generator sizes - 0 TO 49kW

DC Frederick

0402AB 0.00 Each___________________ ____________________

Generator sizes - 50 to 99kW

DC Frederick

0402AC 0.00 Each___________________ ____________________

Generator sizes - 100 to 199kW

DC Frederick

0402AD 0.00 Each___________________ ____________________

Generator sizes - 200 to 299kW

DC Frederick

0402AE 0.00 Each___________________ ____________________

Generator sizes - 300 to 399kW

DC Frederick

0402AF 0.00 Each___________________ ____________________

Generator sizes - 400 to 499kW

DC - Frederick

0402AG 0.00 Each___________________ ____________________

Generator sizes - 500 to 699kW

DC - Frederick

0402AH 0.00 Each___________________ ____________________

Generator sizes - 700 to 899kW

DC - Frederick

0402AI 0.00 Each___________________ ____________________

Generator sizes - 900kW

DC - Frederick

0402AJ 0.00 ___________________ ____________________

Grand Total from SUBCLIN 0402AA thru

0402AK

0402AK 0.00 ___________________ ____________________

Generator Maintenance Mechanic Proposed

Labor Rate - $_________

Parts and Materials (Cost Only) -

Miscellaneous Repair and Repairable -

Funding in support of Major Maintenance and repairs as defined in the

Performance Based Work Statement

(Attachment A), entitled, “National

On-Site Generator Maintenance” dated

December 2, 2008

This is a Cost only line item in support of Item 0001. No funding shall be expended without prior approval of the Contracting Officer Technical

Representative along with written

Concurrence via email from the

Contracting Officer.

0403 0.00 ___________________ ____________________

Option Year 4 - Distribution Center

(DC) Fort Worth

0403AA 0.00 Each___________________ ____________________

Generator sizes - 0 TO 49kW

DC Fort Worth

0403AB 0.00 Each___________________ ____________________

Generator sizes - 50 to 99kW

DC Fort Worth

0403AC 0.00 Each___________________ ____________________

Generator sizes - 100 to 199kW

DC Fort Worth

0403AD 0.00 Each___________________ ____________________

Generator sizes - 200 to 299kW

DC Fort Worth

0403AE 0.00 Each___________________ ____________________

Generator sizes - 300 to 399kW

DC Fort Worth

0403AF 0.00 Each___________________ ____________________

Generator sizes - 400 to 499kW

DC Fort Worth

0403AG 0.00 Each___________________ ____________________

Generator sizes - 500 to 699kW

DC Fort Worth

0403AH 0.00 Each___________________ ____________________

Generator sizes - 700 to 899kW

DC - Forth Worth

0403AI 0.00 Each___________________ ____________________

Generator sizes - 900kW

DC Fort Worth

0403AJ 0.00 ___________________ ____________________

Grand Total from SUBCLIN 0403AA thru

0403AK

0403AK 0.00 ___________________ ____________________

Generator Maintenance Mechanic Proposed

Labor Rate - $_________

Parts and Materials (Cost Only) -

Miscellaneous Repair and Repairable -

Funding in support of Major Maintenance and repairs as defined in the

Performance Based Work Statement

(Attachment A), entitled, “National

On-Site Generator Maintenance” dated

December 2, 2008

This is a Cost only line item in support of Item 0001. No funding shall be expended without prior approval of the Contracting Officer Technical

Representative along with written

Concurrence via email from the

Contracting Officer.

0404 0.00 ___________________ ____________________

Option Year 4 - Distribution Center

(DC) Moffett Field

0404AA 0.00 Each___________________ ____________________

Generator sizes - 0 TO 49kW

DC Moffett

0404AB 0.00 Each___________________ ____________________

Generator sizes - 50 to 99kW

DC Moffett

0403AC 0.00 Each___________________ ____________________

Generator sizes - 100 to 199kW

DC Moffett Field

0404AD 0.00 Each___________________ ____________________

Generator sizes - 200 to 299kW

DC Moffett

0404AE 0.00 Each___________________ ____________________

Generator sizes - 300 to 399kW

DC Moffett

0404AF 0.00 Each___________________ ____________________

Generator sizes - 400 to 499kW

DC Moffett

0404AG 0.00 Each___________________ ____________________

Generator sizes - 500 to 699kW

DC Moffett

0404AH 0.00 Each___________________ ____________________

Generator sizes - 700 to 899kW

DC Moffett

0404AI 0.00 Each___________________ ____________________

Generator sizes - 900kW

DC Moffett

0404AJ 0.00 ___________________ ____________________

Grand Total from SUBCLIN 0404AA thru

0404AK

0404AK 0.00 ___________________ ____________________

Generator Maintenance Mechanic Proposed

Labor Rate - $_________

Parts and Materials (Cost Only) -

Miscellaneous Repair and Repairable -

Funding in support of Major Maintenance and repairs as defined in the

Performance Based Work Statement

(Attachment A), entitled, “National

On-Site Generator Maintenance” dated

December 2, 2008

This is a Cost only line item in support of Item 0001. No funding shall be expended without prior approval of the Contracting Officer Technical

Representative along with written

Concurrence via email from the

Contracting Officer.

GRAND TOTAL ---

A.3 DELIVERY SCHEDULE

ITEM NUMBER QUANTITY DATE OF DELIVERY

0001 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management Agency

Distribution Center - Atlanta

4532 North 2nd, Bldg 212B

Fort Gillem

GA

30297

USA

MARK FOR: Tureana Robinson

0001AA 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management Agency

Distribution Center - Atlanta

4532 North 2nd, Bldg 212B

Fort Gillem

GA

30297

USA

MARK FOR: Tureana Robinson

0001AB 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management Agency

Distribution Center - Atlanta

4532 North 2nd, Bldg 212B

Fort Gillem

GA

30297

USA

MARK FOR: Tureana Robinson

0001AC 0.00

SHIP TO : Federal Emergency Management Agency

Distribution Center - Atlanta

4532 North 2nd, Bldg 212B

Fort Gillem

GA

30297

USA

MARK FOR: Tureana Robinson

0001AD 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management Agency

Distribution Center - Atlanta

4532 North 2nd, Bldg 212B

Fort Gillem

GA

30297

USA

MARK FOR: Tureana Robinson

0001AE 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management Agency

Distribution Center - Atlanta

4532 North 2nd, Bldg 212B

Fort Gillem

GA

30297

USA

MARK FOR: Tureana Robinson

0001AF 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management Agency

Distribution Center - Atlanta

4532 North 2nd, Bldg 212B

Fort Gillem

GA

30297

USA

MARK FOR: Tureana Robinson

0001AG 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management Agency

Distribution Center - Atlanta

4532 North 2nd, Bldg 212B

Fort Gillem

GA

30297

USA

MARK FOR: Tureana Robinson

0001AH 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management Agency

Distribution Center - Atlanta

4532 North 2nd, Bldg 212B

Fort Gillem

GA

30297

USA

MARK FOR: Tureana Robinson

0001AI 0.00

SHIP TO : Federal Emergency Management Agency

Distribution Center - Atlanta

4532 North 2nd, Bldg 212B

Fort Gillem

GA

USA

MARK FOR: Turena Robinson

0001AJ 0.00

0001AK 0.00

0002 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management Agency

Distribution Center - Frederick

4420 Buckeystown Pike

Frederick

MD

21704

USA

MARK FOR: Tureana Robinson

0002AA 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management Agency

Distribution Center - Frederick

4420 Buckeystown Pike

Frederick

MD

21704

USA

MARK FOR: Tureana Robinson

0002AB 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management Agency

DC Frederick

4420 Buckeystown Pike

Frederick

MD

21704

USA

0002AC 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management Agency

DC Frederick

4420 Buckeystown Pike

Frederick

MD

21704

USA

0002AD 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management Agency

DC Frederick

4420 Buckeystown Pike

Frederick

MD

21704

USA

0002AE 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management Agency

DC Frederick

4420 Buckeystown Pike

Frederick

MD

21704

USA

0002AF 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management Agency

DC Frederick

4420 Buckeystown Pike

Frederick

MD

21704

USA

0002AG 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management Agency

DC Frederick

4420 Buckeystown Pike

Frederick

MD

21704

USA

0002AH 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management Agency

DC Frederick

4420 Buckeystown Pike

Frederick

MD

21704

USA

0002AI 0.00

SHIP TO : Federal Emergency Management Agency

DC Frederick

4420 Buckeystown Pike

Frederick

MD

21704

USA

0002AJ 0.00

0002AK 0.00

0003 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management agency

DC Fort Worth

501 W Felix Street, Bldg 12

Forth Worth

TX

76115

USA

0003AA 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management agency

DC Fort Worth

501 W Felix Street, Bldg 12

Forth Worth

TX

76115

USA

0003AB 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management agency

DC Fort Worth

501 W Felix Street, Bldg 12

Forth Worth

TX

76115

USA

0003AC 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management agency

DC Fort Worth

501 W Felix Street, Bldg 12

Forth Worth

TX

76115

USA

0003AD 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management agency

DC Fort Worth

501 W Felix Street, Bldg 12

Forth Worth

TX

76115

USA

0003AE 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management agency

DC Fort Worth

501 W Felix Street, Bldg 12

Forth Worth

TX

76115

USA

0003AF 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management agency

DC Fort Worth

501 W Felix Street, Bldg 12

Forth Worth

TX

76115

USA

0003AG 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management agency

DC Fort Worth

501 W Felix Street, Bldg 12

Forth Worth

TX

76115

USA

0003AH 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management agency

DC Fort Worth

501 W Felix Street, Bldg 12

Forth Worth

TX

76115

USA

0003AI 0.00

SHIP TO : Federal Emergency Management agency

DC Fort Worth

501 W Felix Street, Bldg 12

Forth Worth

TX

76115

USA

0003AJ 0.00

0003AK 0.00

0004 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management Agency

DC Moffett

NAS Ames Research Ctr., Bldg 144

Moffett Field

CA

94035

USA

0004AA 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management Agency

DC Moffett

NAS Ames Research Ctr., Bldg 144

Moffett Field

CA

94035

USA

0004AB 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management Agency

DC Moffett

NAS Ames Research Ctr., Bldg 144

Moffett Field

CA

94035

USA

0004AC 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management Agency

DC Moffett

NAS Ames Research Ctr., Bldg 144

Moffett Field

CA

94035

USA

0004AD 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management Agency

DC Moffett

NAS Ames Research Ctr., Bldg 144

Moffett Field

CA

94035

USA

0004AE 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management Agency

DC Moffett

NAS Ames Research Ctr., Bldg 144

Moffett Field

CA

94035

USA

0004AF 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management Agency

DC Moffett

NAS Ames Research Ctr., Bldg 144

Moffett Field

CA

94035

USA

0004AG 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management Agency

DC Moffett

NAS Ames Research Ctr., Bldg 144

Moffett Field

CA

94035

USA

0004AH 0.00 Not to exceed September 30, 2009

SHIP TO : Federal Emergency Management Agency

DC Moffett

NAS Ames Research Ctr., Bldg 144

Moffett Field

CA

94035

USA

0004AI 0.00

SHIP TO : Federal Emergency Management Agency

DC Moffett

NAS Ames Research Ctr., Bldg 144

Moffett Field

CA

94035

USA

0004AJ 0.00

0004AK 0.00

0101 0.00

SHIP TO : Federal Emergency Management Agency

Distribution Center - Atlanta

4532 North 2nd, Bldg 212B

Fort Gillem

GA

30297

USA

MARK FOR: Tureana Robinson

0101AA 0.00

SHIP TO : Federal Emergency Management Agency

Distribution Center - Atlanta

4532 North 2nd, Bldg 212B

Fort Gillem

GA

30297

USA

MARK FOR: Tureana Robinson

0101AB 0.00

SHIP TO : Federal Emergency Management Agency

Distribution Center - Atlanta

4532 North 2nd, Bldg 212B

Fort Gillem

GA

30297

USA

MARK FOR: Tureana Robinson

0101AC 0.00

SHIP TO : Federal Emergency Management Agency

Distribution Center - Atlanta

4532 North 2nd, Bldg 212B

Fort Gillem

GA

30297

USA

MARK FOR: Tureana Robinson

0101AD 0.00

SHIP TO : Federal Emergency Management Agency

Distribution Center - Atlanta

4532 North 2nd, Bldg 212B

Fort Gillem

GA

30297

USA

MARK FOR: Tureana Robinson

0101AE 0.00

SHIP TO : Federal Emergency Management Agency

Distribution Center - Atlanta

4532 North 2nd, Bldg 212B

Fort Gillem

GA

30297

USA

MARK FOR: Tureana Robinson

0101AF 0.00

SHIP TO : Federal Emergency Management Agency

Distribution Center - Atlanta

4532 North 2nd, Bldg 212B

Fort Gillem

GA

30297

USA

MARK FOR: Tureana Robinson

0101AG 0.00

SHIP TO : Federal Emergency Management Agency

Distribution Center - Atlanta

4532 North 2nd, Bldg 212B

Fort Gillem

GA

30297

USA

MARK FOR: Tureana Robinson

0101AH 0.00

SHIP TO : Federal Emergency Management Agency

Distribution Center - Atlanta

4532 North 2nd, Bldg 212B

Fort Gillem

GA

30297

USA

MARK FOR: Tureana Robinson

0101AI 0.00

SHIP TO : Federal Emergency Management Agency

Distribution Center - Atlanta

4532 North 2nd, Bldg 212B

Fort Gillem

GA

USA

MARK FOR: Turena Robinson

0101AJ 0.00

0101AK 0.00

0102 0.00

SHIP TO : Federal Emergency Management Agency

Distribution Center - Frederick

4420 Buckeystown Pike

Frederick

MD

21704

USA

MARK FOR: Tureana Robinson

0102AA 0.00

SHIP TO : Federal Emergency Management Agency

Distribution Center - Frederick

4420 Buckeystown Pike

Frederick

MD

21704

USA

MARK FOR: Tureana Robinson

0102AB 0.00

SHIP TO : Federal Emergency Management Agency

DC Frederick

4420 Buckeystown Pike

Frederick

MD

21704

USA

0102AC 0.00

SHIP TO : Federal Emergency Management Agency

DC Frederick

4420 Buckeystown Pike

Frederick

MD

21704

USA

0102AD 0.00

SHIP TO : Federal Emergency Management Agency

DC Frederick

4420 Buckeystown Pike

Frederick

MD

21704

USA

0102AE 0.00

SHIP TO : Federal Emergency Management Agency

DC Frederick

4420 Buckeystown Pike

Frederick

MD

21704

USA

0102AF 0.00

SHIP TO : Federal Emergency Management Agency

DC Frederick

4420 Buckeystown Pike

Frederick

MD

21704

USA

0102AG 0.00

SHIP TO : Federal Emergency Management Agency

DC Frederick

4420 Buckeystown Pike

Frederick

MD

21704

USA

0102AH 0.00

SHIP TO : Federal Emergency Management Agency

DC Frederick

4420 Buckeystown Pike

Frederick

MD

21704

USA

0102AI 0.00

SHIP TO : Federal Emergency Management Agency

DC Frederick

4420 Buckeystown Pike

Frederick

MD

21704

USA

0102AJ 0.00

0102AK 0.00

0103 0.00

SHIP TO : Federal Emergency Management agency

DC Fort Worth

501 W Felix Street, Bldg 12

Forth Worth

TX

76115

USA

0103AA 0.00

SHIP TO : Federal Emergency Management agency

DC Fort Worth

501 W Felix Street, Bldg 12

Forth Worth

TX

76115

USA

0103AB 0.00

SHIP TO : Federal Emergency Management agency

DC Fort Worth

501 W Felix Street, Bldg 12

Forth Worth

TX

76115

USA

0103AC 0.00

SHIP TO : Federal Emergency Management agency

DC Fort Worth

501 W Felix Street, Bldg 12

Forth Worth

TX

76115

USA

0103AD 0.00

SHIP TO : Federal Emergency Management agency

DC Fort Worth

501 W Felix Street, Bldg 12

Forth Worth

TX

76115

USA

0103AE 0.00

SHIP TO : Federal Emergency Management agency

DC Fort Worth

501 W Felix Street, Bldg 12

Forth Worth

TX

76115

USA

0103AF 0.00

SHIP TO : Federal Emergency Management agency

DC Fort Worth

501 W Felix Street, Bldg 12

Forth Worth

TX

76115

USA

0103AG 0.00

SHIP TO : Federal Emergency Management agency

DC Fort Worth

501 W Felix Street, Bldg 12

Forth Worth

TX

76115

USA

0103AH 0.00

SHIP TO : Federal Emergency Management agency

DC Fort Worth

501 W Felix Street, Bldg 12

Forth Worth

TX

76115

USA

0103AI 0.00

SHIP TO : Federal Emergency Management agency

DC Fort Worth

501 W Felix Street, Bldg 12

Forth Worth

TX

76115

USA

0103AJ 0.00

0103AK 0.00

0104 0.00

SHIP TO : Federal Emergency Management Agency

DC Moffett

NAS Ames Research Ctr., Bldg 144

Moffett Field

CA

94035

USA

0104AA 0.00

SHIP TO : Federal Emergency Management Agency

DC Moffett

NAS Ames Research Ctr., Bldg 144

Moffett Field

CA

94035

USA

0104AB 0.00

SHIP TO : Federal Emergency Management Agency

DC Moffett

NAS Ames Research Ctr., Bldg 144

Moffett Field

CA

94035

USA

0104AC 0.00

SHIP TO : Federal Emergency Management Agency

DC Moffett

NAS Ames Research Ctr., Bldg 144

Moffett Field

CA

94035

USA

0104AD 0.00

SHIP TO : Federal Emergency Management Agency

DC Moffett

NAS Ames Research Ctr., Bldg 144

Moffett Field

CA

94035

USA

0104AE 0.00 September 30, 2009- September 29, 2010

SHIP TO : Federal Emergency Management Agency

DC Moffett

NAS Ames Research Ctr., Bldg 144

Moffett Field

CA

94035

USA

0104AF 0.00

SHIP TO : Federal Emergency Management Agency

DC Moffett

NAS Ames Research Ctr., Bldg 144

Moffett Field

CA

94035

USA

0104AG 0.00

SHIP TO : Federal Emergency Management Agency

DC Moffett

NAS Ames Research Ctr., Bldg 144

Moffett Field

CA

94035

USA

0104AH 0.00

SHIP TO : Federal Emergency Management Agency

DC Moffett

NAS Ames Research Ctr., Bldg 144

Moffett Field

CA

94035

USA

0104AI 0.00

SHIP TO : Federal Emergency Management Agency

DC Moffett

NAS Ames Research Ctr., Bldg 144

Moffett Field

CA

94035

USA

0104AJ 0.00

0104AK 0.00

0201 0.00

SHIP TO : Federal Emergency Management Agency

Distribution Center - Atlanta

4532 North 2nd, Bldg 212B

Fort Gillem

GA

30297

USA

MARK FOR: Tureana Robinson

0201AA 0.00

SHIP TO : Federal Emergency Management Agency

Distribution Center - Atlanta

4532 North 2nd, Bldg 212B

Fort Gillem

GA

30297

USA

MARK FOR: Tureana Robinson

0201AB 0.00

SHIP TO : Federal Emergency Management Agency

Distribution Center - Atlanta

4532 North 2nd, Bldg 212B

Fort Gillem

GA

30297

USA

MARK FOR: Tureana Robinson

0201AC 0.00

SHIP TO : Federal Emergency Management Agency

Distribution Center - Atlanta

4532 North 2nd, Bldg 212B

Fort Gillem

GA

30297

USA

MARK FOR: Tureana Robinson

0201AD 0.00

SHIP TO : Federal Emergency Management Agency

Distribution Center - Atlanta

4532 North 2nd, Bldg 212B

Fort Gillem

GA

USA

MARK FOR: Turena Robinson

0201AE 0.00

SHIP TO : Federal Emergency Management Agency

Distribution Center - Atlanta

4532 North 2nd, Bldg 212B

Fort Gillem

GA

30297

USA

MARK FOR: Tureana Robinson

0201AF 0.00

SHIP TO : Federal Emergency Management Agency

Distribution Center - Atlanta

4532 North 2nd, Bldg 212B

Fort Gillem

GA

30297

USA

MARK FOR: Tureana Robinson

0201AG 0.00 September 30, 2010- September 29, 2011

SHIP TO : Federal Emergency Management Agency

Distribution Center - Atlanta

4532 North 2nd, Bldg 212B

Fort Gillem

GA

30297

USA

MARK FOR: Tureana Robinson

0201AH 0.00

SHIP TO : Federal Emergency Management Agency

Distribution Center - Atlanta

4532 North 2nd, Bldg 212B

Fort Gillem

GA

30297

USA

MARK FOR: Tureana Robinson

0201AI 0.00

SHIP TO : Federal Emergency Management Agency

Distribution Center - Atlanta

4532 North 2nd, Bldg 212B

Fort Gillem

GA

USA

MARK FOR: Turena Robinson

0201AJ 0.00

0201AK 0.00

0202 0.00

SHIP TO : Federal Emergency Management Agency

Distribution Center - Frederick

4420 Buckeystown Pike

Frederick

MD

21704

USA

MARK FOR: Tureana Robinson

0202AA 0.00

SHIP TO : Federal Emergency Management Agency

Distribution Center - Frederick

4420 Buckeystown Pike

Frederick

MD

21704

USA

MARK FOR: Tureana Robinson

0202AB 0.00

SHIP TO : Federal Emergency Management Agency

DC Frederick

4420 Buckeystown Pike

Frederick

MD

21704

USA

0202AC 0.00

SHIP TO : Federal Emergency Management Agency

DC Frederick

4420 Buckeystown Pike

Frederick

MD

21704

USA

0202AD 0.00

SHIP TO : Federal Emergency Management Agency

DC Frederick

4420 Buckeystown Pike

Frederick

MD

21704

USA

0202AE 0.00

SHIP TO : Federal Emergency Management Agency

DC Frederick

4420 Buckeystown Pike

Frederick

MD

21704

USA

0202AF 0.00

SHIP TO : Federal Emergency Management Agency

DC Frederick

4420 Buckeystown Pike

Frederick

MD

21704

USA

0202AG 0.00

SHIP TO : Federal Emergency Management Agency

DC Frederick

4420 Buckeystown Pike

Frederick

MD

21704

USA

0202AH 0.00

SHIP TO : Federal Emergency Management Agency

DC Frederick

4420 Buckeystown Pike

Frederick

MD

21704

USA

0202AI 0.00

SHIP TO : Federal Emergency Management Agency

DC Frederick

4420 Buckeystown Pike

Frederick

MD

21704

USA

0202AJ 0.00

0202AK 0.00

0203 0.00

SHIP TO : Federal Emergency Management agency

DC Fort Worth

501 W Felix Street, Bldg 12

Forth Worth

TX

76115

USA

0203AA 0.00

SHIP TO : Federal Emergency Management agency

DC Fort Worth

501 W Felix Street, Bldg 12

Forth Worth

TX

76115

USA

0203AB 0.00

SHIP TO : Federal Emergency Management agency

DC Fort…

This is the start of the file's text. The full file is on GovTribe.

Other files

File Type Posted
HSFEHQ-09-R-0021A 00006 .pdf PDF
HSFEHQ-09-R-0021A 00005.rtf RTF text file
Copy of GENERATOR MANIFEST LC-M2 —
HSFEHQ-09-R-0021A 00004.pdf PDF
SF 30 HSFEHQ-09-R-0021A_00003.pdf PDF
Attach C- DC Frederick Generator Inventory 2-18-09.xls XLS spreadsheet
Attach D DC FW.xls XLS spreadsheet
Attach B -DC Atlanta rev list.xls XLS spreadsheet
Attach E DC Moffett SNG.xls XLS spreadsheet
HSFEHQ-09-R-0021A_00002.pdf PDF
HSFEHQ-09-R-0021A_0001.pdf PDF
Attach A thru I.pdf PDF