REPLACE BOATHOUSE ELECTRICAL WORK ORDER 5935865
SECTION 26 20 00 Page 1
SECTION 26 20 00
INTERIOR DISTRIBUTION SYSTEM
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM B 1 (2001; R 2007) Standard Specification for Hard-Drawn
Copper Wire
ASTM B 8 (2004) Standard Specification for Concentric-Lay- Stranded Copper Conductors, Hard, Medium-Hard, or Soft
ASTM D 709 (2001; R 2007) Laminated Thermosetting Materials
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE C2 (2014) National Electrical Safety Code
IEEE Std 100 (2000) The Authoritative Dictionary of IEEE Standards
Terms
INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)
NETA ATS (2003) Acceptance Testing Specifications
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA 250 (2003) Enclosures for Electrical Equipment (1000 Volts Maximum)
NEMA BU 1.1 (2005) General Instructions for Proper Handling, Installation, Operation, and Maintenance of Busway Rated 600 Volts or Less
NEMA C80.1 (2005) Standard for Electrical Rigid Steel Conduit
(ERSC)
SECTION 26 20 00 Page 2
NEMA C80.3 (2005) Standard for Electrical Metallic
NEMA RN 1 (2005) Standard for Polyvinyl Chloride (PVC) Externally Coated Galvanized Rigid Steel Conduit and Intermediate Metal Conduit
NEMA ST 20 (1992; R 1997) Standard for Dry-Type Transformers for
General Applications
NEMA TP 1 (2002) Guide for Determining Energy Efficiency for Distribution Transformers
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2014) National Electrical Code
NFPA 70E (2014) Electrical Safety in the Workplace
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
29 CFR 1910.147 Control of Hazardous Energy (Lock Out/Tag Out)
UNDERWRITERS LABORATORIES (UL)
UL 1561 (1999; Rev thru Sep 2005) Dry-Type General Purpose and Power Transformers
UL 44 (2005; Rev thru Nov 2005) Thermoset-Insulated Wires and Cables
UL 467 (2007) Standard for Grounding and Bonding Equipment
UL 486A-486B (2003; Rev thru Aug 2006) Standard for Wire
Connectors
UL 489 (2002; Rev thru Jun 2006) Standard for Molded-Case Circuit Breakers, Molded-Case Switches and Circuit- Breaker Enclosures
UL 50 (2007) Standard for Enclosures for Electrical Equipment
UL 510 (2005; Rev thru Aug 2005) Polyvinyl Chloride, Polyethylene, and Rubber Insulating Tape
UL 514B (2004; Rev thru Aug 2007) Standard for Conduit, Tubing and Cable Fittings
SECTION 26 20 00 Page 3
UL 6 (2004) Standard for Electrical Rigid Metal Conduit-
Steel
UL 67 (1993; Rev thru Apr 2006) Standard for Panelboards
UL 797 (2004) Standard for Electrical Metallic Tubing -- Steel
UL 83 (2003; Rev thru Apr 2006) Standard for Thermoplastic- Insulated Wires and Cables
UL 870 (1995; Rev thru Jul 2003) Standard for Wireways, Auxiliary Gutters, and Associated Fittings
UL 943 (2006) Ground-Fault Circuit-Interrupters
1.2 DEFINITIONS
Unless otherwise specified or indicated, electrical and electronics terms used in these specifications, and on the drawings, shall be as defined in IEEE Std 100.
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation. The following shall be submitted in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Panelboards; G
Transformers; G
Wireways; G
SD-03 Product Data
Circuit breakers; G
Transformers; G
Submittals shall include performance and characteristic curves.
SD-06 Test Reports
600-volt wiring test; G
SECTION 26 20 00 Page 4
Grounding system test; G
Transformer tests; G
Ground-fault receptacle test; G
SD-09 Manufacturer's Field Reports
Transformer factory tests
1.4 QUALITY ASSURANCE
1.4.1 Material and Equipment Manufacturing Date
Products manufactured more than 2 years prior to date of delivery to site shall not be used, unless specified otherwise.
PART 2 PRODUCTS
2.1 MATERIALS AND EQUIPMENT
Materials, equipment, and devices shall, as a minimum, meet requirements of UL, where UL standards are established for those items, and requirements of NFPA 70.
2.2 CONDUIT AND FITTINGS (INDOORS ONLY; REFER TO SPEC SECTION 26 10 00
FOR OUTDOOR CONDUIT REQUIREMENTS)
Shall conform to the following:
2.2.1 Rigid Metallic Conduit
2.2.1.1 Rigid, Threaded Zinc-Coated Steel Conduit
NEMA C80.1, UL 6.
2.2.2 Electrical, Zinc-Coated Steel Metallic Tubing (EMT)
UL 797, NEMA C80.3.
2.2.3 Plastic-Coated Rigid Steel Conduit
NEMA RN 1, Type 40(40 mils thick)
2.2.4 Fittings for Metal Conduit, EMT, and Flexible Metal Conduit
UL 514B. Ferrous fittings shall be cadmium- or zinc-coated in accordance with UL 514B.
SECTION 26 20 00 Page 5
2.3 OUTLET BOXES AND COVERS
UL 514A, cadmium- or zinc-coated, if ferrous metal. UL 514C, if nonmetallic.
2.4 CABINETS, JUNCTION BOXES, AND PULL BOXES
Volume greater than 100 cubic inches, UL 50, hot-dip, zinc-coated, if sheet steel.
2.5 WIRES AND CABLES
Wires and cables shall meet applicable requirements of NFPA 70 and UL for type of insulation, jacket, and conductor specified or indicated. Wires and cables manufactured more than 12 months prior to date of delivery to site shall not be used.
2.5.1 Conductors
Conductors No. 8 AWG and larger diameter shall be stranded. Conductors No. 10 AWG and smaller diameter shall be solid, except that conductors for remote control, alarm, and signal circuits, classes 1, 2, and 3, shall be stranded unless specifically indicated otherwise.
Conductor sizes and ampacities shown are based on copper. All conductors shall be copper.
2.5.1.1 Minimum Conductor Sizes
Minimum size for branch circuits shall be No. 12 AWG; for Class 1 remote-control and signal circuits, No. 14 AWG; for Class 2 low-energy, remote-control and signal circuits, No. 16 AWG; and for Class 3 low-energy, remote-control, alarm and signal circuits, No. 22 AWG.
2.5.2 Color Coding
Provide for service, feeder, branch, control, and signaling circuit conductors. Color shall be green for grounding conductors and white for neutrals; except where neutrals of more than one system are installed in same raceway or box, other neutrals shall be white with a different colored (not green) stripe for each. Color of ungrounded conductors in different voltage systems shall be as follows:
a. 208/120 volt, three-phase
(1) Phase A - black
(2) Phase B - red
(3) Phase C - blue
b. 480/277 volt, three-phase
SECTION 26 20 00 Page 6
(1) Phase A - brown
(2) Phase B - orange
(3) Phase C - yellow
2.5.3 Insulation
Unless specified or indicated otherwise or required by NFPA 70, power and lighting wires shall be 600-volt, Type THWN/THHN conforming to UL 83 or Type XHHW conforming to
UL 44.
2.5.4 Bonding Conductors
ASTM B 1, solid bare copper wire for sizes No. 8 AWG and smaller diameter; ASTM B 8, Class B, stranded bare copper wire for sizes No. 6 AWG and larger diameter.
2.6 SPLICES AND TERMINATION COMPONENTS
SPLICE NOT AUTHORIZED
2.7 PANELBOARDS
UL 67 and UL 50 having a short-circuit current rating as indicated of 10,000 amperes symmetrical minimum. Panelboards shall be circuit breaker-equipped. Design shall be such that individual breakers can be removed without disturbing adjacent units or without loosening or removing supplemental insulation supplied as means of obtaining clearances as required by UL. "Specific breaker placement" is required in panelboards to match the breaker placement indicated in the panelboard schedule on the drawings. Use of "Subfeed Breakers" is not acceptable unless specifically indicated otherwise. Main breaker shall be "separately" mounted "above" or "below" branch breakers. Where "space only" is indicated, make provisions for future installation of breakers. Directories shall indicate load served by each circuit in panelboard. Directories shall also indicate source of service to panelboard (e.g., Panel PA served from Panel MDP). Provide new directories for existing panels modified by this project as indicated. Type directories and mount in holder behind transparent protective covering. Panelboards shall be listed and labeled for their intended use.
2.7.1 Enclosure
Enclosures shall meet the requirements of UL 50. All cabinets shall be fabricated from sheet steel of not less than No. 10 gauge if flush-mounted or mounted outdoors, and not less than No. 12 gauge if surface-mounted indoors, with full seam-welded box ends. Front edges of cabinets shall be form-flanged or fitted with structural shapes welded or riveted to the sheet steel, for supporting the panelboard front. All cabinets shall be so fabricated that no part of any surface on the finished cabinet shall deviate from a true plane by more than 1/8 inch.
Holes shall be provided in the back of indoor surface-mounted cabinets, with outside spacers
SECTION 26 20 00 Page 7 and inside stiffeners, for mounting the cabinets with a 1/2 inch clear space between the back of the cabinet and the wall surface. Flush doors shall be mounted on hinges that expose only the hinge roll to view when the door is closed. Each door shall be fitted with a combined catch and lock, except that doors over 24 inches long shall be provided with a three-point latch having a knob with a T-handle, and a cylinder lock. Two keys shall be provided with each lock, and all locks shall be keyed alike. Finished-head cap screws shall be provided for mounting the panelboard fronts on the cabinets.
2.7.2 Panelboard Buses
Support bus bars on bases independent of circuit breakers. Main buses and back pans shall be designed so that breakers may be changed without machining, drilling, or tapping. Provide isolated neutral bus in each panel for connection of circuit neutral conductors. Provide separate ground bus identified as equipment grounding bus per UL 67 for connecting grounding conductors; bond to steel cabinet.
2.7.3 Circuit Breakers
UL 489, thermal magnetic-type having a minimum short-circuit current rating equal to the short-circuit current rating of the panelboard in which the circuit breaker shall be mounted.
Breaker terminals shall be UL listed as suitable for type of conductor provided. Series rated circuit breakers and plug-in circuit breakers are unacceptable.
2.7.3.1 Multipole Breakers
Provide common trip-type with single operating handle. Breaker design shall be such that overload in one pole automatically causes all poles to open. Maintain phase sequence throughout each panel so that any three adjacent breaker poles are connected to Phases A, B, and C, respectively.
2.7.3.2 Circuit Breaker With GFCI
UL 943 and NFPA 70
2.8 TRANSFORMER (45-KVA, 480-120V/208Y, 3-PHASE, INDOOR ONLY)
NEMA ST 20, general purpose, dry-type, self-cooled, ventilated. Provide transformers in NEMA 3R enclosure. Provide 45KVA, 480VAC primary, 120V/208Y secondary, 3-phase, 60-Hz distribution transformer. Transformer shall have 220 degrees C insulation system for transformers 15 kVA and greater, with temperature rise not exceeding 150 degrees C under full-rated load in maximum ambient of 40 degrees C. Transformer shall be quiet type with maximum sound level at least 3 decibels less than NEMA standard level for transformer ratings indicated. Transformer shall be sized for the existing concrete foundation.
2.8.1 Specified Transformer Efficiency
SECTION 26 20 00 Page 8
Transformers, indicated and specified with: 480V primary, 80 degrees C or 115 degrees C temperature rise, kVA ratings of 37.5 to 100 for single phase or 30 to 500 for three phase, shall be energy efficient type. Minimum efficiency, based on factory test results, shall not be less than NEMA Class 1 efficiency as defined by NEMA TP 1.
2.9 GROUNDING AND BONDING EQUIPMENT
2.9.1 Ground Rods
UL 467.
2.10 WIREWAYS
UL 870. Material shall be steel epoxy painted galvanized 16 gauge for heights and depths up to 6 by 6 inches, and 14 gauge for heights and depths up to 12 by 12 inches. Provide in length required for the application with hinged or screw cover NEMA 3R enclosure per NEMA ICS 6.
2.11 FACTORY APPLIED FINISH
Electrical equipment shall have factory-applied painting systems which shall, as a minimum, meet the requirements of NEMA 250 corrosion-resistance test.
2.12 SOURCE QUALITY CONTROL
2.12.1 Transformer Factory Tests
Submittal shall include routine NEMA ST 20 transformer test results on each transformer and also contain the results of NEMA "design" and "prototype" tests that were made on transformers electrically and mechanically equal to those specified.
PART 3 EXECUTION
3.1 INSTALLATION
Electrical installations, including weatherproof and hazardous locations and ducts, plenums and other air-handling spaces, shall conform to requirements of NFPA 70 and IEEE C2 and to requirements specified herein.
3.1.1 Labels
Wherever work results in service entrance disconnect devices in more than one enclosure, as permitted by NFPA 70, each enclosure, new and existing, shall be labeled as one of several enclosures containing service entrance disconnect devices. Label, at minimum, shall indicate number of service disconnect devices housed by enclosure and shall indicate total number of enclosures that contain service disconnect devices. Provide laminated plastic labels. Use
SECTION 26 20 00 Page 9 lettering of at least 0.25 inch in height, and engrave on black-on-white matte finish. Service entrance disconnect devices in more than one enclosure, shall be provided only as permitted by NFPA 70.
3.1.2 Wiring Methods
Provide insulated conductors installed in specified conduit or specified otherwise or required by NFPA 70 to be installed otherwise. Grounding conductor shall be separate from electrical system neutral conductor. Provide insulated green equipment grounding conductor for circuit(s) installed in conduit and raceways. Shared neutral, or multi-wire branch circuits, are not permitted with arc-fault circuit interrupters. Minimum conduit size shall be 1/2 inch in diameter for low voltage lighting and
3.1.3 Mounting Heights
Mount panelboard so height of operating handle at its highest position is maximum 78 inches above floor.
3.1.4 Conductor Identification
Provide conductor identification within each enclosure where tap, splice, or termination is made. For conductors No. 6 AWG and smaller diameter, color coding shall be by factory-applied, color-impregnated insulation. For conductors No. 4 AWG and larger diameter, color coding shall be by plastic-coated, self-sticking markers; colored nylon cable ties and plates; or heat shrink-type sleeves.
3.1.5 Splices
SPLICES ARE NOT AUTHROIZED. ALL CIRCUITS SHALL BE PULLED SPLICE-
FREE.
3.1.6 Grounding and Bonding
Provide In accordance with NFPA 70.
3.1.7 Repair of Existing Work
Repair of existing work, demolition, and modification of existing electrical distribution systems] shall be performed as follows:
3.1.7.1 Workmanship
Lay out work in advance. Exercise care where cutting, channeling, chasing, or drilling of floors, walls, partitions, ceilings, or other surfaces is necessary for proper installation, support, or anchorage of conduit, raceways, or other electrical work. Repair damage to buildings, piping, and equipment using skilled craftsmen of trades involved.
SECTION 26 20 00 Page 10
3.1.7.2 Existing Concealed Wiring to be Removed
Existing concealed wiring to be removed shall be disconnected from its source. Remove conductors; cut conduit flush with floor, underside of floor, and through walls; and seal openings.
3.1.7.3 Continuation of Service
Maintain continuity of existing circuits of equipment to remain. Existing circuits of equipment shall remain energized. Circuits which are to remain but were disturbed during demolition shall have circuits wiring and power restored back to original condition.
3.2 WARNING SIGN MOUNTING
Provide the number of signs required to be readable from each accessible side. Space the signs in accordance with NFPA 70E.
3.3 FIELD QUALITY CONTROL
Furnish test equipment and personnel and submit written copies of test results. Give Contracting Officer 5 working days notice prior to testS.
3.3.1 Devices Subject to Manual Operation
Each device subject to manual operation shall be operated at least five times, demonstrating satisfactory operation each time.
3.3.2 600-Volt Wiring Test
Test wiring rated 600 volt and less to verify that no short circuits or accidental grounds exist.
Perform insulation resistance tests on wiring No. 6 AWG and larger diameter using instrument which applies voltage of approximately 500 volts to provide direct reading of resistance.
Minimum resistance shall be 250,000 ohms.
3.3.3 Transformer Tests
Perform the standard, not optional, tests in accordance with the Inspection and Test Procedures for transformers, dry type, air-cooled, 600 volt and below; as specified in NETA ATS.
Measure primary and secondary voltages for proper tap settings. Tests need not be performed by a recognized independent testing firm or independent electrical consulting firm.
3.3.4 Ground-Fault Receptacle Test
Test ground-fault receptacles with a "load" (such as a plug in light) to verify that the "line" and "load" leads are not reversed.
SECTION 26 20 00 Page 11
3.3.5 Grounding System Test
Test grounding system to ensure continuity, and that resistance to ground is not excessive.
Test each ground rod for resistance to ground before making connections to rod; tie grounding system together and test for resistance to ground. Make resistance measurements in dry weather, not earlier than 48 hours after rainfall. Submit written results of each test to Contracting Officer, and indicate location of rods as well as resistance and soil conditions at time measurements were made.