Questions-Answers 03.docx
DOCX document 16 KB Posted
- Attached to
- Dockside Repairs of CGC CHASE (WHEC 718)
- Solicitation number
- HSCG85-10-R-P45CM7
About this file
Questions and Answers for Amendment A00003 to Dock-side Repairs of CGC CHASE.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| A00004 SF30.docx | DOCX document | |
| Questions-Answers 04.docx | DOCX document | |
| A00003 SF30.docx | DOCX document | |
| Questions-Answers 02.docx | DOCX document | |
| A00002 SF30.docx | DOCX document | |
| Questions-Answers 01.docx | DOCX document | |
| A00001 SF30.docx | DOCX document | |
| USCGC CHASE_Repair_August_2010_Rev 0.pdf | ||
| Solicitation 2 | — | |
| SF33 CHASE.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
| Request for Proposal | HSCG85-10-R-P45CM7 |
| DOCKSIDE REPAIRS OF CGC CHASE (WHEC-718) | Amendment 0003 |
A. Questions/Answers to Request for Clarification with regards to dockside repairs of CGC CHASE (WHEC - 718)
0001 Question: Work Item 14, Paragraph 3.4.6 and Paragraph 3.5.2: In the first paragraph (3.4.6) directs the use of Rydlyme Cleaning Solution yet in the second paragraph (3.5.2) directs the use of Sulfamic Acid. Please advice?
Answer: Rydlyme Cleaning Solution is acceptable.
0002 Question: Contractor cannot find any qualified circuit breaker tester for the breakers aboard the CGC CHASE. Please supply contractor with a qualified circuit breaker tester?
Answer: While the Coast Guard does not endorse any specific firm, in the past TECHNICAL SERVICES GROUP of Alameda, CA (510) 522-8326 has been used.
NOTES: B. ACKNOWLEDGE RECEIPT OF ALL AMENDMENTS IN PROPOSALS.
C. THE SOLICITATION PERIOD IS NOT EXTENDED.
D. ALL OTHER TERMS AND CONDITIONS CITED IN THE ORIGINAL SOLICITATION REMAIN THE SAME.