Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

(a) By completing items 8 and 15, and returning or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment your desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE

2. AMENDMENT/MODIFICATION NO. 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQ. NO. 5. PROJECT NO. (If applicable)

7. ADMINISTERED BY (If other than Item 6) CODE

STANDARD FORM 30 (REV. 10-83)

Prescribed by GSA FAR (48 CFR) 53.243

FACILITY CODE

9A. AMENDMENT OF SOLICITATION

NO.

9B. DATED (SEE ITEM 11)

10A. MODIFICATION OF CONTRACT/ORDER NO.

10B. DATED (SEE ITEM 13)

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended, is not extended.

12. ACCOUNTING AND APPROPRIATION DATA (If required) copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

13. THIS ITEM ONLY APPLIES TO MODIFICATION OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO.

IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15C. DATE SIGNED

15A. NAME AND TITLE OF SIGNER (Type or print)

16C. DATE SIGNED

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

PAGE OF PAGES

6. ISSUED BY CODE

8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code) (X)

CODE

15B. CONTRACTOR/OFFEROR

(Signature of person authorized to sign)

16B. UNITED STATES OF AMERICA

(Signature of Contracting Officer)

NSN 7540-01-152-8070

Previous edition unusable

HSCG80-16-Q-P45258

SSDG & SHORE TIE CIRCUIT BREAKERS UPGRADE

AMENDMENT A00001

Response to Requests for Clarification:

1) Question: Per the solicitation paragraph 3.2.6 calls for the new circuit breakers to have the following salient features ie…Shunt trips/shunt close/Charging motor: 24-30VDC however the provided references 618 WMEC 311-001 Rev. P for the A Class, 627 311-001 Rev. K for the B Class & 618 WMEC 324-003 Rev G all show the charging Motors and closing coils to be 120VAC and only the shunt trip coil utilizing

24VDC.

Is this a type error or were these breakers changed at some point to a 24VDC control circuit?

Answer: The breakers may have been changed and the drawings may not have been updated. The contractor needs to do a ship check to verify the breaker and breaker information.

2) Question: In paragraph 3.3 of the solicitation Electrical Isolation Plan states both the Coast Guard and the Contractor shall be jointly responsible for securing electrical equipment and providing electrical service to vital loads.

Due to the configuration and location of the effected circuit breakers being replaced shore power will have to be secured for a period of time resulting in a complete loss of electrical power to the main switchboard. Will the emergency generator be use to provide power to the emergency lighting and loads during this power outage and if so how long of a period could be expected? Also is there any loads from the main switchboard that would require temporarily providing power that is not already supported by the emergency switchboards like generator space heaters etc… and if so would these circuits be allowed to temporarily be sourced from spare circuits if available?

Answer: The contractor will need to communicate with the cutter to determine that information and to come up with a game plan.

3) Question: Further in paragraph 3.3 of solicitation it states that it may be necessary for the contractor to perform the installation with no power to the vessel. In this instance, the contractor shall be responsible for providing a portable generator, portable lights and string lights to ensure at a minimum the work area and main passage way are safely illuminated. This is no problem however will it be intended to have a full crew living and working aboard? Also will the portable generator be allowed to be put on deck to minimize voltage drops to loads?

Answer: The crew will be onboard during working hours and the duty section will be onboard after hours. The contractor needs to work with the crew to determine a plan for power isolation and for providing power to vital equipment.

4) Question: This is a request for clarification regarding one item in the specification (210 WMEC Ship Service and Shore Tie Circuit Breakers). Section 3.2.6 references the installation of two emergency circuit breakers. I would like to confirm that the requirement is for the installation and commissioning of three 800A circuit breakers per vessel.

Answer: Should say three (3) 800A circuit breakers per vessel instead of two emergency circuit breakers.

topmostSubform[0]:
Page1[0]:
AmendmentNo[0]: A00001
Code[0]:
Code[1]:
AccountingData[0]:
A13[0]:
C13[0]:
D13[0]:
NameandTitleSigner[0]:
NameandTitleOfficer[0]:

MABLE L. LEE

Description[0]: SHIP SERVICE DIESEL GENERATOR (SSDG) AND SHORE TIE CIRCUIT BREAKERS UPGRADE

210' MEDIUM ENDURANCE CUTTERS

1. This amendment is issued to provide answers and clarification to submitted questions. Date for submission of quotes remains 13 Jan 2016.

2. All other terms and conditions remain unchanged.

FacilityCode[0]:
Code[2]:
IssuedBy[0]: Commander (MECPL)

Surface Forces Logistics Center 300 East Main Street, Suite 550 Norfolk, VA 23510-9111 NameandAddress[0]:

All Prospective Bidders AdministeredBy[0]: Same as Block 6 POC: Mable Lee/Contract Specialist

(757) 628-4820 E-mail: mable.l.lee@uscg.mil

ContractIDCode[0]:
ReqNumber[0]: 2116806P45258
AmendmentNo[1]: HSCG80-16-Q-P45258
ModificationNo[0]:
ProjectNo[0]:
Page[0]: 1
Pages[0]: 2
EffectiveDate[0]: 12/31/2015
Dated9B[0]: 12/04/2015
Dated10B[0]:
CheckBox9[0]: Off
CheckBox10[0]: Off
CheckBox11[0]: 1
CheckBox13A[0]: Off
CheckBox13B[0]: Off
CheckBox13C[0]: Off
CheckBox13D[0]: Off
IsNot[0]: Off
Is[0]: Off
Extended[0]: Off
NotExtended[0]: 1
DateSigned[0]:
DateSigned[1]:
Copies[0]:
CopiesReturned[0]:

File details come from the government source that posted it. Updated .