This document is a DFAS Cleveland Safety Office Industrial Hygiene Report dated March 23, 2018, documenting environmental testing results for indoor air quality (IAQ) at the DFAS facility in Cleveland, Ohio.

The report presents comprehensive IAQ screening data collected on February 27 and March 1, 2018, across multiple floors and the sub-basement training room. Testing parameters included temperature, relative humidity, carbon dioxide (CO2), carbon monoxide (CO), airborne particulate matter, airborne fibers, and microbial spore sampling. Results indicate temperature readings ranged from 72.1 to 77.6 degrees Fahrenheit, relative humidity from 24.2 to 26.1 percent, CO2 from 610 to 950 ppm (below the 1,000 ppm industry standard), and CO from 0.0 to 2.1 ppm (well below EPA guidelines). Airborne particulate concentrations indoors ranged from 380 to 2,400 particles per cubic centimeter, significantly lower than outdoor readings. Airborne fiber sampling showed levels below the asbestos standard of 0.01 fibers per cubic centimeter. Microbial air sampling detected total spore counts lower indoors than outdoors, with identified species including Ascospores, Aspergillus/Penicillium, Basidiospores, and Cladosporium. Visual inspection detected no musty odors, moisture staining, or mold growth. The report concludes that no actions are recommended for carbon dioxide, carbon monoxide, ambient particulate, fibers, or microbial IAQ parameters, with minor recommendations regarding relative humidity adjustment during winter months at the facility's discretion.

View the file

Other files for this federal contract opportunity

Other files attached to Industrial Hygiene Testing and Survey, newest first.
File Type Posted
Questions and Answers Amendment 002 Final.pdf PDF
Questions and Answers.pdf PDF
QA -Attach 2 Chemical List.pdf PDF
Attach 4 - Wage Determination.pdf PDF
Instructions to Offeror.pdf PDF
Attach 3 - HQ042326QE044 Clauses.pdf PDF
Attach 1 Industrial Hygiene PWS.pdf PDF
Attach 2- SOI.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MEMORANDUM FOR: DFAS Cleveland Personnel

SUBJECT: DFAS Cleveland Safety Office Industrial Hygiene Report: March 23, 2018 – Floors

Attached please find the latest environmental tests conducted for DFAS here at the . For the CONCLUSIONS and RECOMMENDATIONS, please see pages 9 through 12 of this report.

Please direct any questions to the Safety Office @

DFAS Safety Office

File details come from the government source that posted it. Updated .