Vendor Questions and Responses.pdf
PDF 90 KB Posted
- Attached to
- Update/Replace Physical Access Control System (PACS) Federal contract opportunity
- Solicitation number
- HQ042322Q0060
- Issued by
- Defense Finance and Accounting Service
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Vendor Questions and Responses 2.pdf | ||
| Synopsis Solicitation Amendment.pdf | ||
| Synopsis Solicitation Instructions.pdf | ||
| Attachment 3 Technical Cert Form.docx | DOCX document | |
| Attachment 1 SOW.pdf | ||
| Attachment 2 Schedule of Items.docx | DOCX document | |
| Attachment 4 Clause Fill-Ins.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Questions & Responses Defense Finance and Accounting Service
Update/Replace Physical Access Control System (PACS) DFAS Texarkana Solicitation Number: HQ042322Q0060
RFQ Section, Pg Topic Question Response
SOW 1.1 Card Readers Fourteen (14) card readers. They are Innometriks Cheetah Core+Contact Reader part #’s INN-CHTA-CT and INN-CHTA- CTO. - Do the 14 card readers identified in the SOW have corresponding Request-to-Exit Devices that are fully functional?
If so, what type of REX devices are existing (REX PIR, Push-button, crash-bar, latch-bolt,etc.)
All REX devices are PIR and in good working order https://www.kantech.com/products /exit_trex.aspx There are two newer PIR REX devices on the communications room doors, brand unk.
SOW 2 FISCAM
Capability
Does the Customer intend to actually connect to a FISCAM-rated database during everyday operational use or just to be “FISCAM-capable”?
At this time all components must be installed to support full FISCAM compliance; however at this time the system will operate as a standalone system with no external connectivity.
SOW 3.8 Battery location System shall include a minimum of 8-hour battery backup, with batteries located outside of the system IAW DFAS 5200.8-I (9). - Please clarify what is meant by “located outside of the system”.
Does the customer have a specific location identified where the batteries are to be installed?
The back-up batteries and related equipment are mounted on the same wall as the PACS equipment in the 2nd floor communications room