HDESD Manzanita Entry Canopy_100CD-Permit_Drawings_26-1030 (1).pdf
PDF 2 MB Posted
- Attached to
- Manzanita Entry Canopy
- Solicitation number
- S-P09003-00018339
- Issued by
- Deschutes County, Oregon
About this file
This document is a 100% Construction Documents/Permit set of architectural and engineering drawings prepared by BBT Architects for the High Desert Education Service District (HDESD) Manzanita Entry Canopy project located at 1212 NE 5th Street, Redmond, Oregon 97756. The project involves the construction of a new exterior canopy entry addition to an existing HDESD building in the City of Redmond's M1 Light Industrial zone. The scope of work includes demolition of existing sidewalk and ramp, construction of new concrete sidewalks, ramps, and railings, new parking striping, and a structural steel canopy with metal roofing and soffit systems. The project includes an add alternate for providing additional sidewalk, curb, and metal railings as indicated on drawing A2.02. The drawings are dated October 30, 2026 and prepared by a project team including BBT Architects (Nathan Leigh, Principal contact), Walker Structural Engineering (Jon Walker), and Colebreit Engineering (Nick Evano for electrical systems). The existing site contains 28 parking spaces, with the proposed work reducing this to 27 spaces due to removal of one space; existing parking remains at 27 spaces with modifications to compact space sizing.
The project meets City of Redmond code exemptions under Municipal Code Chapter 8.3010 for site and design review (exemption #5 as canopy addition is less than 1,000 square feet) and under Oregon Structural Specialty Code Chapter 34 exemption #4 for alterations increasing accessibility of the existing building. The construction will utilize non-combustible materials and must comply with 2025 Oregon Structural Specialty Code, 2017 ICC A117.1 accessibility standards, and City of Redmond Municipal Code requirements. The project includes coordination with existing building systems, including an existing automatic fire sprinkler and alarm system, and requires verification of underground utility locations including existing electrical service, power, and telecommunication lines that will remain in place.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
0 GRID BUBBLE
KEYNOTE TAG
EXTERIOR/INTERIOR
ELEVATION TAG
ELEVATION HEIGHT TAG
SYMBOLS
DETAIL TAG
A1.01
A101
SIM
SECTION TAG
REVISION TAG1
A8.10 s w S im p so n
A v e
S u it e
B e n d
O re g o n t .3
.5 f
.3
.8
C O
P Y
R
IG
H T
B
B T
A R
C H
IT
E C
TS
Date
Project Number
/3
/2
:2 :5
P
M
G0.00
COVER SHEET
HDESD MANZANITA
ENTRY CANOPY
1212 NE 5th Street, Redmond OR
10/30/2026
100% CD/PERMIT
PROJECT DESCRIPTION
VICINITY MAP
ENTRY CANOPY
ABV
ACT
ADA
ADR
AFF
AFP
AL /ALUM
ANSI
APPROX
ASTM
ATTM
ARCH
AWC
AWI
AWP
BD
BLDG
CB
CG
CJ
CMU
COL
CON
CONT
COORD
CPT
CT
DBA
DEG
DIA OR Ø
DIM
DN
DR
DS
DTL
(E)
EL / ELEV
EMT
EFP
EOS
EQ
ER
EXP JT
EXT
FC
FD
FE
FEC
FF
FFHB
FOM
FOS
FOW
FRL
FRP
FT
FSD
GA
GALV
GRC
GWB
GWS
HB
HDWR
HM
HS
HORIZ
HT
IN
INSUL
INT
ABBREVIATIONS
ABOVE
ACOUSTICAL CEILING TILE
AMERICANS WITH DISABILITIES ACT
ART DISPLAY RAIL
ABOVE FINISH FLOOR
ACOUSTICAL FIBERBOARD PANEL
ALUMINUM
AMERICAN NATIONAL STANDARDS INSTITUTE
APPROXIMATELY
AMERICAN SOCIETY FOR TESTING MATERIALS
ATTACHMENT
ARCHITECTURAL
AT
ACOUSTIC WALL COVERING
ACOUSTIC WALL INSULATION
ACOUSTIC WALL PANEL
BOARD
BUILDING
CATCH BASIN
CORNER GUARD
CONTROL JOINT
CONCRETE MASONRY UNIT
COLUMN
CONCRETE
CONTINUOUS
COORDINATE
CARPET TILE
CERAMIC TILE
CENTER LINE
DEFORMED BAR ANCHOR
DEGREE
DIAMETER
DIMENSION
DOWN
DOOR
DOWNSPOUT
DETAIL
EXISTING
ELEVATION
ELECTRICAL METAL TUBING
EPOXY FLOOR PAINT
EDGE OF SLAB
EQUAL
EPOXY RESIN
EXPANSION JOINT
EXTERIOR
FIBER CEMENT
FLOOR DRAIN
FIRE EXTINGUISHER
FIRE EXTINGUISHER IN CABINET
FACTORY FINISH
FROST FREE HOSE BIB
FACE OF MASONRY
FACE OF STUD
FACE OF FINISH WALL
FIBER REINFORCED LAMINATE
FIBERGLASS-REINFORCED PLASTIC
FOOT, FEET
FIRE SMOKE DAMPER
GAUGE
GALVANIZED
GLASSFIBER REINFORCED CONCRETE
GYPSUM WALL BOARD
GLASS WRITING SURFACE
HOSE BIBB
HARDWARE
HOLLOW METAL
HOLLOW STEEL
HORIZONTAL
HEIGHT
INCH, INCHES
INSULATION
INTERIOR
JT
LAM
LVT
MAX
MDF
MECH
MFG
MFR
MIN
MTL
MP
NA
NIC
NO
NTS
OC
OD
OFCI
OFOI
OH
OPH
OPP
ORD
OSSC
OTA
P
PB
PL
PLAM
PLYWD
PS
PR
PT
PVC
RAF
RB
RC
RD
REF
REQD
RF
RM
RO
RR
RST
SAM
SAMF
SC
SDT
SECT
SF
SFRM
SHT
SIM
SM
SS
SSF
SSM
STD
STF
STL
STRUCT
STV
TB
TBD
TEMP
TO
TP
TS
TWS
TYP
UL
UNO
JOINT
LAMINATED
LUXURY VINYL TILE
MAXIMUM
MEDIUM-DENSITY FIBERBOARD
MECHANICAL
MANUFACTURING
MANUFACTURER
MINIMUM
METAL
METAL PANEL
NOT APPLICABLE
NOT IN CONTRACT
NUMBER
NOT TO SCALE
ON CENTER
OUTSIDE DIAMETER
OWNER FURNISHED CONTRACTOR INSTALLED
OWNER FURNISHED OWNER INSTALLED
OVERHEAD
OPPOSITE HAND
OPPOSITE
OVERFLOW ROOF DRAIN
OREGON STRUCTURAL SPECIALTY CODE
OPEN TO ABOVE
PAINT
PUSH BUTTON
PLASTIC LAMINATE
PLASTIC LAMINATE
PLYWOOD
PAINT SYSTEM
PAIR
PRESSURE TREATED
POLYVINYL CHLORIDE
RUBBER ATHLETIC FLOORING
RUBBER BASE
RESILIENT CHANNEL
ROOF DRAIN
REFERENCE
REQUIRED
RUBBER FLOORING
ROOM
ROUGH OPENING
RESTROOM
RUBBER STAIR TREAD AND RISER
SELF-ADHERING MEMBRANE
SELF-ADHERING MEMBRANE FLASHING
SEALED CONCRETE
STATIC DISSIPATIVE TILE
SECTION
SQUARE FEET
SPRAYED FIRE-RESISTIVE MATERIAL
SHEET
SIMILAR
SHEET METAL
STAINLESS STEEL
SPRUNG STAGE FLOORING
SOLID SURFACE MATERIAL
STANDARD
SEAMLESS TROWELED FLOORING
STEEL
STRUCTURAL
SMART TV
TACK BOARD
TO BE DETERMINED
TEMPERED
TOP OF
TOILET PARTITION
TUBE STEEL
TACKABLE WALL SURFACE
TYPICAL
UNDERWRITERS LABORATORY
UNLESS NOTED OTHERWISE
VCT
VERT
VIF
W/
WD
WAF
WOM
WP
WRB
VINYL COMPOSITION TILE
VERTICAL
VERIFY IN FIELD
WITH
WOOD
WOOD ATHLETIC FLOORING
WALK OFF MAT
WALL PROTECTION
WEATHER RESISTIVE BARRIER
OWNER:
HIGH DESERT EDUCATION SERVICE DISTRICT
1212 NE 5th St.
Redmond, OR 97756
Phone: 541.948.3853
Contact: Nick Viggiano
Email: nick.viggiano@hdesd.org
ARCHITECT:
BBT ARCHITECTS
1140 SW Simpson Ave, Suite 200
Bend, Oregon 97702
Phone: 541.382.5535
Contact: Nathan Leigh
Email: nleigh@bbtarchitects.com
STRUCTURAL ENGINEER:
WALKER STRUCTURAL ENGINEERING
40 NW Greenwood Ave, Suite 200
Bend, OR 97703
Phone: 541.330.6869
Contact: Jon Walker
Email: jwalker@walkerse.com
ELECTRICAL ENGINEER:
COLEBREIT ENGINEERING
721 SW Industrial Way, Suite 110
Bend, OR 97702
Phone: 541.262.4326
Contact: Nick Evano
Email: nick.evano@colebreit.com
PROJECT TEAMDRAWING INDEX
GENERAL
G0.00 COVER SHEET
ARCHITECTURAL
A1.01 SITE PLAN
A2.01 FLOOR PLANS - EXISTING/DEMO AND FLOOR PLAN - NEW
A2.02 FLOOR PLANS - ADD ALTERNATE 1
A3.01 ELEVATIONS - EXISTING/DEMO AND ELEVATIONS - NEW
A4.01 SECTIONS & DETAILS
A6.01 REFLECTED CEILING PLAN
STRUCTURAL
S0.1 GENERAL STRUCTURAL NOTES, SPECIAL INSPECTION TABLES & DRAWING INDEX
S2.1 STRUCTURAL FOUNDATION & FRAMING PLANS
S5.1 STRUCTURAL FOUNDATION & FRAMING DETAILS
ELECTRICAL
E0.01 ELECTRICAL LEGEND
E2.01 CANOPY ELECTRICAL
HDESD MANZANITA
BID ALTERNATES
A NEW EXTERIOR CANOPY OUTSIDE OF AN EXISTING BUILDING.
DEMOLITION OF EXISTING SIDEWALK AND RAMP, NEW
CONCRETE SIDEWALKS, RAMPS AND RAILINGS, AND NEW
PARKING STRIPING
ADD ALTERNATES:
1. PROVIDE ADDITIONAL SIDEWALK, CURB, AND METAL RAILINGS AS
INDICATED ON DRAWINGS, SEE A2.02.
PROJECT
LOCATION
N
No. Description Date
C
C
M H
C
C
P
SIT
E P
LA
N
;E
XIS
TIN
G N
ATIV
E
LA
NDSCAPE
;N
EW
'X
5'
CO
NC
LA
NDIN
G
;2 8' -9
/2
SITE PLAN LEGEND
EXISTING BUILDING
(NO WORK)
PROPERTY LINE
SET BACK
SITE PLAN KEYNOTES#
A2.01
EXISTING BUILDING
(NO WORK)
EX
IS
TI
N G
P A
RKI
N G
(1
SP
A C
ES
E X
IS
TI
N G
P A
R K
IN
G
(5 S
P A
C E S
N E 5th STREET
N E
KIN
G
W O
O D A
V E
2 2 33
EXISTIN
G
PA
RKIN
G
(4 SPA
C
ES)
A. NO CHANGES PROPOSED TO EXISTING IMPERVIOUS AREA
B. SEE CODE ANALYSIS FOR ADDITIONAL PARKING INFORMATION
GENERAL NOTES - SITE
GENERAL PROJECT INFORMATION
ADDRESS: 1212 NE 5TH STREET, REDMOND, OREGON 97756
AUTHORITY HAVING JURISDICTION (AHJ): CITY OF REDMOND
ZONE: M1 - LIGHT INDUSTRIAL
OCCUPANCY CLASSIFICATION: (EXISTING, NO CHANGE) MIXED USE: B BUSINESS, E EDUCATION (CHILD CARE), AND S-1
MODERATE-HAZARD STORAGE
OCCUPANCY SEPARATION: (EXISTING, NO CHANGE) NON-SEPARATED
CONSTRUCTION TYPE: (EXISTING, NO CHANGE) TYPE V-B (NON-RATED). CANOPY ADDITION WILL BE
CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS
FIRE PROTECTION: (EXISTING, NO CHANGE) AUTOMATIC FIRE SPRINKLER AND ALARM ARE
INSTALLED
STRUCTURAL DESIGN CRITERIA: SEE STRUCTURAL
APPLICABLE CODES
2025 OREGON STRUCTURAL SPECIALTY CODE (OSSC)
2017 ICC A117.1 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES
CITY OF REDMOND MUNICIPAL CODE
CITY OF REDMOND MUNICIPAL CODE
8.500 OFF-STREET PARKING
LAND USE: CHILD CARE
PARKING REQUIRED: 1 SPACE PER EMPLOYEE, DESIGNATED PICK-UP AREA REQUIRED (20 EMPLOYEES = 20 SPACES)
EXISTING PARKING: 28 SPACES, INCLUDING 2 ACCESSIBLE AND 4 DESIGNATED 'DROP OFF ONLY'
PROPOSED PARKING: 27 SPACES (REMOVAL OF 1 SPACE)
8.3010 SITE AND DESIGN REVIEW
PROJECT MEETS EXEMPTION #5. CANOPY ADDITION IS LESS THAN 1,000 SQUARE FEET.
OSSC CHAPTER 34
3403.6.7.1 ALTERATIONS AFFECTING AN AREA CONTAINING A PRIMARY FUNCTION
PROJECT MEETS EXEMPTION #4. ALTERATIONS TO EXISTING SIDEWALK AND NEW CANOPY ADDITION ARE FOR THE PURPOSE OF INCREASING
ACCESSIBILITY OF THE EXISTING BUILDING.
CODE ANALYSIS
s w S im p so n
A v e
S u it e
B e n d
O re g o n t .3
.5 f
.3
.8
C O
P Y
R
IG
H T
B
B T
A R
C H
IT
E C
TS
Date
Project Number
/3
/2
:2 :5
P
M
A1.01
SITE PLAN
HDESD MANZANITA
ENTRY CANOPY
1212 NE 5th Street, Redmond OR
10/30/2026
100% CD/PERMIT
2 EXISTING STRIPED ACCESS AISLE TO REMAIN
3 EXISTING ACCESSIBLE PARKING TO REMAIN
5 PROVIDE ALLOWANCE FOR CONCRETE SIDEWALK REPAIRS, APPROX 555 SQ.FT.
6 EXISTING PARKING SPACES TO BE CHANGED TO 9' x 18' COMPACT SPACES.
PROVIDE 4" PARKING STRIPING, TWO COATS MINIMUM
7 LOCATION OF (1) EXISTING PARKING SPACE TO BE REMOVED. SEE EXISTING/DEMO
PLAN A2.01
PROJECT
NORTH
N
SCALE: 1" = 20'-0"A1.01
1 SITE PLAN
A3.01
UPUP
UP
10 10
COMPACT COMPACT COMPACT COMPACT
A4.01
A4.01
2 3
1 4
A A
B B
C C
A4.01
A4.01
A3.01
A3.013
14' - 6" 10' - 0" 11' - 0"
1' - 0" 8' - 0" RAMP 1' - 0"
35' - 6"
M
IN
6 11
(1:12 MAX)
7' - 0" +/- RAMP RUN 5' - 0" MIN
M
IN
/- 12
1' - 4"1' - 4"
1' - 0"1' - 0"
UP
UP
NEW CONCRETE SIDEWALK
60' - 6" VIF MATCH EXISTING
TY
P
IC
A L
2' +/-9' - 0" TYPICAL MATCH OPPOSITE
/2
LA
N
D
IN
G
(1 :1
M
A X
R
A M
P R
U N
/2
"M
A
TC
H E
X
IS
TI
N
G
V
IF
EQ EQ
R 2' - 2 1/4"
A. SEE A4.01 FOR CURB AND SIDEWALK INFORMATION
PROPOSED FLOOR PLAN NOTES
PROPOSED FLOOR PLAN KEYNOTES#
A. VERIFY LOCATION OF EXISTING UTILITIES, NOTIFY ARCHITECT OF
CONFLICTS WITH NEW WORK.
B. CUT AND PATCH EXISTING ASPHALT AS NECESSARY FOR NEW
WORK
EXISTING/DEMO FLOOR PLAN NOTES
EXISTING/DEMO FLOOR PLAN KEYNOTES#
s w S im p so n
A v e
S u it e
B e n d
O re g o n t .3
.5 f
.3
.8
C O
P Y
R
IG
H T
B
B T
A R
C H
IT
E C
TS
Date
Project Number
/3
/2
:2 :5
P
M
A2.01
FLOOR PLANS -
EXISTING/DEMO AND
FLOOR PLAN - NEW
HDESD MANZANITA
ENTRY CANOPY
1212 NE 5th Street, Redmond OR
10/30/2026
100% CD/PERMIT
1 NEW STRUCTURAL COLUMN, TYPICAL
3 NEW CONTINUOUS STEEL RAILINGS, RETURN EXTENSIONS TO POST, SEE ELEVATIONS
4 NEW CONCRETE RAMP
5 NEW CONCRETE CURB
6 EXISTING SIDEWALK AND CURB TO REMAIN
7 EXISTING STOREFRONT DOORS TO REMAIN
8 REPAIR EXISTING CONCRETE SIDEWALK, SEE SITE PLAN FOR ADDITIONAL
INFORMATION
9 NEW CONCRETE LANDING LEVEL WITH EXISTING ASPHALT
10 JOG CURB AT COLUMNS/LANDING
11 PROVIDE 6" WIDE SIDEWALK TRENCH DRAIN WITH TRENCH PAN, COVER GRATE, CURB
OPENING, AND DOWNSPOUT BOOT WITH CLEANOUT; INSTALL PER MANUFACTURER'
WRITTEN INSTRUCTIONS; TRIM EXISTING DOWNSPOUT AS NECESSARY; GRATE AND
CURB OPENING TO BE COATED CAST IRON; SUBMIT MANUFACTURER'S PRODUCT
INFORMATION AND DETAILS FOR ARCHITECT'S REVIEW; FINISHES SELECTED BY
ARCHITECT FROM MANUFACTURER'S STANDARD COATINGS AND COLORS
12 PROVIDE CURB - LOCATE FACE CLEAR OF (E) ELECTRICAL EQUIPMENT
13 PROVIDE PAINTED 'COMPACT' MARKING AT MODIFIED SPACES, TYPICAL
14 LINE OF ROOF OVERHEAD
15 COORDINATE FOOTING WITH UG UTILITY LINES
16 PROVIDE CIRCULAR ISOLATION JOINT AT SINGLE HSS COLUMNS, TYPICAL
17 PROVIDE RADIUSED ISOLATION JOINT AT DOUBLE HSS COLUMNS, TYPICAL
18 REVIEW CONCRETE CONTROL JOINT LAYOUT WITH ARCHITECT
19 PAINT CURB YELLOW AT RAMP RUN AND LANDING
PROJECT
NORTH
N
SCALE: 1/4" = 1'-0"A2.01
1 FLOOR PLAN - EXISTING/DEMO
SCALE: 1/4" = 1'-0"A2.01
2 FLOOR PLAN - NEW
1 DEMOLISH EXISTING SIDEWALK AND CURB, TYPICAL
2 DEMOLISH EXISTING RAMP AND CURBS
3 REMOVE EXISTING STRIPING, TYPICAL
4 REMOVE EXISTING BOLLARDS
5 REMOVE EXISTING SIGNAGE AND POSTS. SALVAGE SIGNAGE FOR RE-USE
6 EXISTING ELECTRICAL SERVICE AND EQUIMPMENT TO REMAIN
7 EXISTING ACCESSIBLE PARKING, ACCESS AISLE, LANDING, CURBS AND
SIDEWALK TO REMAIN
8 DEMO AND SALVAGE EXISTING WHEELSTOPS FOR RE-USE
9 EXISTING UNDERGROUND POWER AND TELECOM TO REMAIN
10 REMOVE EXISTING SIGN POST, SALVAGE SIGN FOR REINSTALLATION
11 (4) EXISTING BOLLARDS TO REMAIN
PROJECT
NORTH
N
A4.01
A4.01
2 3
1 4
A A
B B
C C
A4.01
A4.01
COMPACT COMPACT COMPACT COMPACT
A3.013
12' - 0"15' - 6"
ADD ALTERNATE #1:
EXTEND CURB AND SIDEWALK AS SHOWN
ADD ALTERNATE #1:
EXTEND CURB AND SIDEWALK AS SHOWN
ADD ALTERNATE #1:
MODIFY STEEL RAILINGS AS SHOWN
SIM
SIM
SIM
R 9 3/4"
/2 s w S im p so n
A v e
S u it e
B e n d
O re g o n t .3
.5 f
.3
.8
C O
P Y
R
IG
H T
B
B T
A R
C H
IT
E C
TS
Date
Project Number
/3
/2
:2 :5
P
M
A2.02
FLOOR PLANS - ADD
ALTERNATE 1
HDESD MANZANITA
ENTRY CANOPY
1212 NE 5th Street, Redmond OR
10/30/2026
100% CD/PERMIT
SCALE: 1/4" = 1'-0"A2.02
1 FLOOR PLAN - ADD ALTERNATE 1
Level 1 0' - 0"
6 7
16 16
Level 1 0' - 0"
A4.01
A4.01
22" DIA. CONCRETE PEDESTALS,
PIGMENTED CONCRETE FINISH
A4.01
1' - 0"EQ.EQ.EQ.2' - 3 3/4"2' - 3 3/4"4' - 6"4' - 6"4' - 6"1' - 0"
TY
P
STEEL RAILING
16' - 9 3/4"
STEEL RAILING
13' - 3 3/4"
14 15
ABC
A4.01
A4.01
1' - 4" EQ. EQ. EQ.
A. PATCH HOLES IN EXISTING METAL WALL PANEL AT LOCATIONS OF REMOVED
ELEMENTS, PREPARE SURFACE AND PROVIDE TOUCH-UP PAINT TO MATCH
EXISTING USING COMPATIBLE PAINT SYSTEM PER SPECIFICATIONS
B. PAINT STEEL STRUCTURE AND RAILINGS
EXTERIOR GENERAL NOTES
EXTERIOR KEYNOTES#
s w S im p so n
A v e
S u it e
B e n d
O re g o n t .3
.5 f
.3
.8
C O
P Y
R
IG
H T
B
B T
A R
C H
IT
E C
TS
Date
Project Number
/3
/2
:3 :0
P
M
A3.01
ELEVATIONS -
EXISTING/DEMO AND
ELEVATIONS - NEW
HDESD MANZANITA
ENTRY CANOPY
1212 NE 5th Street, Redmond OR
10/30/2026
100% CD/PERMIT
SCALE: 1/4" = 1'-0"A3.01
1 ELEVATION - EXISTING/DEMO
SCALE: 1/4" = 1'-0"A3.01
2 ELEVATION - NEW
SCALE: 1/4" = 1'-0"A3.01
3 ELEVATION -SIDE
1 REMOVE AND SALVAGE EXISTING SECURITY CAMERA
2 REMOVE EXISTING LIGHT FIXTURE
3 REMOVE EXISTING SIGNAGE AND SALVAGE FOR FUTURE INSTALLATION BY OWNER
4 REMOVE EXISTING SIGNAGE AND SALVAGE FOR REINSTALLATION
5 EXISTING ACCESS CONTROL TO REMAIN
6 DEMOLISH EXISTING BOLLARDS, TYPICAL
7 APPROXIMATE LOCATION OF EXISTING ELECTRIC SERVICE EQUIPMENT TO REMAIN
9 EXISTING DOWNSPOUT TO REMAIN. MODIFY TERMINATION INTO NEW TRENCH DRAIN
10 EXISTING DOWNSPOUT TO REMAIN
11 STEEL TRUSS SEE STRUCTURAL DRAWINGS, PROVIDE BIRD WIRE ALONG TOP OF BOTTOM
CHORD
13 EXISTING KNOX BOX AND CARD READER TO REMAIN
14 REINSTALL EXISTING DROP OFF SIGN ON NEW GALVANIZED STEEL POST
15 REINSTALL EXISTING DROP OFF SIGN ON NEW STEEL COLUMN
16 EXISTING LIGHTING FIXTURE TO REMAIN
2 3
METAL ROOFING
METAL SOFFIT
STEEL BEAMS, PAINTED
STEEL COLUMNS, PAINTED
STEEL RAILINGS, PAINTED
CONCRETE RAMP
10' - 0"
TY
P
A4.01
RIDGE CAP AND VALLEY
FLASHINGS BY MFR.
PROVIDE 1/8" STEEL SHEET INFILL
PANELS AT GABLE END, FASTEN TO
METAL STUDS AND HSS, PAINT PANELS
AND FASTENERS
AB
STEEL COLUMNS
AND BEAMS,
PAINTED, TYPICAL
EXISTING
METAL
BUILDING
5' - 6" 8"
A4.01
A4.01
A4.01
METAL ROOFING
(E) PEMB
CONTINUOUS CLOSED CELL
FOAM CLOSURE STRIP SET
IN SEALANT
PREFINISHED METAL CAP
ATTACHED TO PEMB PANELS
CONTINUOUS CLOSED
CELL FOAM CLOSURE STRIP
SET IN SEALANT
FF PEMB
8"
CONDUIT PER ELECTRICAL,
DROP TO LIGHTING AT HIGH
FLUTES
GRID
STEEL ANGLE FASCIA
SUPPORT PER
STRUCTURAL, PAINTED
STEEL BEAM PER
STRUCTURAL,
PAINTED
METAL SOFFIT C CLOSURES
BY SOFFIT MFR, TYP
PREFINISHED SHEET METAL
CLEAT TO MATCH FASCIA
PREFINISHED SHEET
METAL FASCIA WITH DRIP
DRIP FLASHING TO
MATCH FASCIA
PREFINISHED METAL
SOFFIT PANELS
METAL ROOF DECK
PER STRUCTURAL
METAL ROOF PANELS
METAL ROOF DECK
1' - 4"
1/4" FURRING TO
CONCEAL ANGLE
GRID
STEEL ANGLE FASCIA
SUPPORT PER STRUCTURAL,
SHOP DRILL HOLES AT 16"
OC FOR LVL ATTACHMENT
STEEL BEAM PER
STRUCTURAL,
PAINTED
METAL SOFFIT C CLOSURES
BY SOFFIT MFR, TYP
PREFINISHED SHEET
METAL CLEAT TO
MATCH FASCIA
PREFINISHED SHEET
METAL DRIP FLASHING
TO MATCH FASCIA
PREFINISHED METAL
SOFFIT PANELS, TYP
METAL ROOF DECK
PER STRUCTURAL
METAL ROOF PANELS
RAKE CLOSURE
BY METAL ROOF
PREFINISHED SHEET
METAL WITH DRIP
OVER LVL FASCIA
1/4" FURRING TO
CONCEAL ANGLE
METAL ROOF DECK
1' - 0"
GRID
1 3/4" X 7 1/4" LVL
FASCIA
PROVIDE METAL FURRING AT SPACING
REQUIRED MY MANUFACTURER FOR
METAL ROOFING AND SOFFIT
INSTALLATIONS
STEEL PIPE RAILING WHERE OCCURS:
CORE DRILL INTO CONCRETE CURB
AND SET WITH NON-SHRINK EPOXY
GROUT, SEE ELEVATIONS FOR POST
SPACING
PROVIDE ISOLATION JOINTS AT
CURB AND EXISTING BUILDING
CONCRETE CURB, PROFILE
AND RADIUSED CORNERS
TO MATCH EXISTING M
A
X
8 3/4"
6"
4" CONCRETE SIDEWALK
4" BASE ROCK
COMPACTED SUBGRADE
2" BASE ROCK
COMPACTED SUBGRADE
EXISTING ASPHALT
PAVING, PATCH AS
NECSSARY, SEAL JOINT
EXISTING BASE ROCK
2% SLOPE MAX
LINE OF EXISTING BUILDING
WALL/FOOTING
MATCH EXISTING UNO
V A
R
IE
S
NOTES:
1. CURB EXPANSION JOINTS TO BE PROVIDED:
A. AT EACH POINT OF TANGENCY OF THE CURB.
B. AT EACH COLD JOINT.
C. AT EACH SIDE OF INLET STRUCTURES.
D. AT LOCATIONS NECESSARY TO LIMIT SPACING TO 45 FEET.
E. MATERIAL TO BE PRE-MOLDED, ASPHALT IMPREGNATED, NON EXTRUDING, WITH A THICKNESS OF 1/2
INCH
2. CURB CONTRACTION JOINTS
A. SPACING TO BE NOT MORE THAN 15 FEET
B. THE DEPTH OF THE JOINT SHALL BE AT LEAST 1-1/2 INCHES
3. SIDEWALK EXPANSION TO BE PROVIDED AT:
A. AT DOWNSPOUT TRENCH
B. AT RAMPS
C. AND AT SPACING NOT TO EXCEED 45 FEET
D. SEAL JOINT
4. FINISH WITH BROOM AND EDGE ALL JOINTS.
5. BASE ROCK: 3/4-INCH MINUS, <8% PASSING #200 SIEVE COMPACTED TO 92% MAX DENSITY (ASTM D155)
6. COMPACTED SUBGRADE: SCARIFY AND COMPACT TO MIN 92% MAX DENSITY
7. PROVIDE EXPANSION CAPS AND DOWELS AT LOCATIONS WHERE NEW AND EXISTING CONCRETE CURB
AND SIDEWALK MEET; 18-INCH LONG #4 SMOOTH BARS AT 3'-0" OC AT MID DEPTH OF CONCRETE s w S im p so n
A v e
S u it e
B e n d
O re g o n t .3
.5 f
.3
.8
C O
P Y
R
IG
H T
B
B T
A R
C H
IT
E C
TS
Date
Project Number
/3
/2
:3 :0
P
M
A4.01
SECTIONS & DETAILS
HDESD MANZANITA
ENTRY CANOPY
1212 NE 5th Street, Redmond OR
10/30/2026
100% CD/PERMIT
SCALE: 1/2" = 1'-0"A4.01
1 CROSS SECTION @ GABLE
SCALE: 1/2" = 1'-0"A4.01
2 CROSS SECTION @ BUILDING
SCALE: 3" = 1'-0"A4.01
3 TYPICAL CANOPY HIGH EAVE @ PEMB
SCALE: 3" = 1'-0"A4.01
4 TYPICAL FASCIA AT LOW EAVE
SCALE: 3" = 1'-0"A4.01
5 TYPICAL FASCIA AT RAKE
SCALE: 1 1/2" = 1'-0"A4.01
7 CURB AND SIDEWALK SECTION
A4.01
A4.01
2 3
1 4
A A
B B
C C
A4.01
A4.01
LIGHTING AND SECURITY CAMERA
PER ELECTRICAL DRAWINGS,
COORDINATE FINAL LOCATIONS
WITH ARCHITECT AND ENGINEER
s w S im p so n
A v e
S u it e
B e n d
O re g o n t .3
.5 f
.3
.8
C O
P Y
R
IG
H T
B
B T
A R
C H
IT
E C
TS
Date
Project Number
/3
/2
:3 :0
P
M
A6.01
REFLECTED CEILING
PLAN
HDESD MANZANITA
ENTRY CANOPY
1212 NE 5th Street, Redmond OR
10/30/2026
100% CD/PERMIT
PROJECT
NORTH
N
SCALE: 1/4" = 1'-0"A6.01
1 RCP - NEW
GENERAL NOTES:
1. ALL CONSTRUCTION AND DESIGN SHALL CONFORM TO THE 2024 INTERNATIONAL BUILDING CODE AS AMENDED BY THE STATE OF OREGON
(2025 OSSC).
2. THE STRUCTURAL DRAWINGS SHALL BE UTILIZED IN CONJUNCTION WITH OTHER DESIGN CONSULTANT'S DRAWINGS (ARCHITECTURAL, MECHANICAL, ETC.). IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE THE REQUIREMENTS OF THE DRAWINGS INTO THEIR
SHOP DRAWINGS AND CONSTRUCTION.
3. THE GENERAL STRUCTURAL NOTES ARE INTENDED FOR USE IN CONJUNCTION WITH THE PROJECT SPECIFICATIONS. IN THE EVENT OF A
CONFLICT BETWEEN THE TWO, THE GENERAL STRUCTURAL NOTES SHALL SUPERSEDE THE PROJECT SPECIFICATIONS. ANY DISCREPANCY
SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT AND ENGINEER.
4. CONSTRUCTION SEQUENCE AND METHODS:
A. THE STRUCTURAL DRAWINGS ARE INTENDED FOR THE STRUCTURE TO ACT AS A WHOLE ONCE CONSTRUCTION IS COMPLETE. IT IS
THE RESPONSIBILITY OF THE CONTRACTOR TO ENSURE SAFETY AND STABILITY (I.E. TEMPORARY BRACING IF REQUIRED) DURING
CONSTRUCTION AS A RESULT OF CONSTRUCTION METHODS AND SEQUENCES.
B. THE CONTRACTOR SHALL TAKE INTO ACCOUNT COLD WEATHER CONSTRUCTION AND THE EFFECTS OF THERMAL MOVEMENT
DURING THE CONSTRUCTION SCHEDULE.
C. NON-CANTILEVERED OR RESTRAINED RETAINING WALLS SHALL NOT BE BACKFILLED UNTIL THE WALL HAS BEEN TIED INTO THE
LOWER AND UPPER SLAB SUPPORTS UNLESS ADEQUATE ENGINEERED BRACING HAS BEEN APPROVED.
5. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. THE ARCHITECT AND/OR ENGINEER SHALL BE NOTIFIED OF ANY
DISCREPANCY BETWEEN THE EXISTING CONDITIONS AND CONSTRUCTION DOCUMENTS.
6. SUBMITTALS:
A. SUBMITTALS OF SHOP DRAWINGS, MILL TEST REPORTS, PRODUCT DATA FOR ITEMS AND BIDDER DESIGN ITEMS SHALL BE MADE TO
THE ARCHITECT/ ENGINEER PRIOR TO FABRICATION AND CONSTRUCTION. BEFORE SUBMISSION TO THE ARCHITECT/ ENGINEER, THE
CONTRACTOR SHALL REVIEW THE SUBMITTALS FOR COMPLETENESS. VERIFICATION OF DIMENSIONS AND QUANTITIES IS THE SOLE
RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTOR SHALL MARK THE SHOP DRAWING WITH ALL NECESSARY COMMENTS AND
DETAILER REQUESTED INFO BEFORE FORWARDING TO THE ARCHITECT/ ENGINEER. SUBMITTALS SHALL BE MADE IN TIME TO
PROVIDE A MINIMUM OF TWO WEEKS FOR REVIEW BY THE ARCHITECT/ ENGINEER.
B. SHOP DRAWINGS FOR ALL STRUCTURAL ITEMS SHALL BE SUBMITTED TO THE ARCHITECT/ ENGINEER PRIOR TO FABRICATION AND
CONSTRUCTION. SUCH ITEMS INCLUDE:
CONCRETE MIX DESIGNS, CONCRETE AND MASONRY REINFORCEMENT (INCLUDING MILL TEST REPORTS), EMBEDDED STEEL ITEMS, STRUCTURAL STEEL (INCLUDING MILL TEST REPORTS), STEEL DECK, STEEL STUDS, AND COLD FORMED STEEL FRAMING.
SHOP DRAWINGS OR CONTRACTOR ENGINEERED DETAILS SHALL BEAR THE SEAL AND SIGNATURE OF A REGISTERED STRUCTURAL ENGINEER
IN THE STATE OF OREGON IF IT DIFFERS FROM THE DESIGN OF THE STRUCTURAL DRAWINGS. ANY REVISION FROM THE STRUCTURAL
DRAWINGS SHALL BE SUBMITTED ALONG WITH SUPPORTING CALCULATIONS BEARING THE SEAL AND SIGNATURE OF A REGISTERED
STRUCTURAL ENGINEER IN THE STATE OF OREGON TO THE ARCHITECT/ ENGINEER FOR REVIEW AND ACCEPTANCE.
C. CALCULATIONS, DESIGN DRAWINGS, AND SHOP DRAWINGS FOR THE DESIGN, FABRICATION AND CONSTRUCTION OF THE BIDDER
DESIGN ITEMS SHALL BEAR THE SEAL AND SIGNATURE OF A REGISTERED STRUCTURAL ENGINEER IN THE STATE OF OREGON AND
SHALL BE SUBMITTED TO THE ARCHITECT/ ENGINEER PRIOR TO FABRICATION. BIDDER DESIGN ITEMS FOR THIS PROJECT INCLUDE:
PRECAST CONCRETE, STAIRS, SUNSHADES/ PREMANUFACTURED AWNINGS, SKYLIGHTS, WINDOW WALLS, AND ALL OTHER GLAZING
SYSTEMS.
CALCULATIONS AND BIDDER DESIGN DRAWINGS SHALL INCLUDE THE DESIGN, CONNECTION TO THE STRUCTURE, AND ACCOUNTING OF ANY
LOCALIZED EFFECTS THE CONNECTIONS OR SYSTEMS MAY INDUCE ON THE STRUCTURE. ALL SUCH BIDDER DESIGNED ITEMS SHALL BE BASED
ON THE DESIGN REQUIREMENTS AS SPECIFIED IN THE GENERAL STRUCTURAL NOTES.
7. DESIGN CRITERIA:
A. CODE: 2024 INTERNATIONAL BUILDING CODE AS AMENDED BY THE STATE OF OREGON (2025 OSSC) .
B. LOADS AND DESIGN CRITERIA: THE FOLLOWING LIVE LOADS AND CRITERIA WERE USED IN ADDITION TO THE DEAD LOAD OF THE STRUCTURE.
LIVE LOADS:
ROOF
GROUND SNOW LOAD.................................................. 38 PSF
SNOW EXPOSURE FACTOR............................................ Ce= 1.0
SNOW IMPORTANCE FACTOR....................................... Is= 1.0
THERMAL FACTOR........................................................ Ct = 1.1
ROOF SNOW LOAD (SLOPES < 1:12).............................. 25 PSF (PLUS ADDED SNOW DRIFT IF SHOWN ON PLANS)
SOIL CRITERIA: (NO REPORT USE ASSUMED VALUES)
FOOTING (FROST) DEPTH................................................... ..... 1'-6" MIN. BELOW GRADE
ALLOWABLE SOIL BEARING VALUES
ON ENGINEERED FILL OR NATIVE SOILS........................ 1500 PSF (W/ 1/3 INCREASE FOR SHORT TERM LATERAL LOADS)
RETAINING WALLS
ACTIVE - UNRESTRAINED........................................................ 35 PCF (LEVEL BACKFILL)
ACTIVE - RESTRAINED.................................................... 50 PCF (LEVEL BACKFILL)
PASSIVE.......................................................................... 250 PSF/FT. BELOW NATURAL GRADE (ENGINEERED FILL OR NATIVE SOILS)
FRICTION COEFFICIENT............................................................ 0.35 (ENGINEERED FILL OR NATIVE SOILS)
LATERAL CRITERIA:
RISK CATEGORY........................................................................ II
WIND (DIRECTIONAL DESIGN PROCEDURE PER 2025 OSSC)
ULT. DESIGN WIND SPEED, Vult (3-SEC GUST)................... 99 MPH
WIND EXPOSURE............................................................. C
INTERNAL PRESSURE COEFFICIENT................................. ± 0.18
COMPONENTS AND CLADDING DESIGN
PRESSURE NOTES:
1. LOADS APPLIED IN EITHER DIRECTION
NORMAL TO SURFACE
2. REFER TO FIGURE 30.4-1 ASCE 7-16
FOR ZONES
3. GABLE, HT.=30', EXP. ADJ.=0.713
SEISMIC (EQUIVALENT LATERAL FORCE PROCEDURE)
IMPORTANCE FACTOR (SEISMIC).................................. Ie= 1.0
SITE CLASS..................................................................... D
SPECTRAL RESPONSE ACCELERATIONS......................... Ss= 0.38
S1= 0.15
SPECTRAL RESPONSE COEFFICIENTS............................. Sds= 0.37
Sd1= 0.28
SEISMIC DESIGN CATEGORY....................................................... D
BOTH DIRECTIONS:
RESPONSE MODIFICATION COEFFICIENT.............................. R= 1.25
SEISMIC RESPONSE COEFFICIENT............................ Cs= 0.30
DESIGN BASE SHEAR (ULT)....................................... V= 1.44K ULT (rho=1.0)
CONCRETE AND REINFORCING STEEL:
1. CONCRETE CONSTRUCTION SHALL CONFORM TO ACI 318-19 AND THE 2024 INTERNATIONAL BUILDING CODE AS AMENDED BY THE STATE OF
OREGON (2025 OSSC).
2. THE MINIMUM 28 DAY CONCRETE STRENGTHS SHALL BE AS FOLLOWS:
F'c = 3000 PSI....................................FOR ALL USES UNLESS NOTED OTHERWISE.
(NOTE: FOOTINGS / STEM WALLS DESIGNED FOR F'c=2500 PSI, CONCRETE SPECIAL INSPECTION NOT REQUIRED FOR FOOTINGS / STEM
WALLS).
3. CONCRETE MIX DESIGNS, ALONG WITH TEST DATA AS REQUIRED, BY ACI 318-19, SECTION 26.4, SHALL BE SUBMITTED TO THE ARCHITECT/
ENGINEER FOR REVIEW A MINIMUM OF TWO WEEKS PRIOR TO CONCRETE POURS.
4. SPECIFIED CONCRETE STRENGTHS SHALL BE VERIFIED BY STANDARD 28-DAY CYLINDER TESTS PER ASTM C39, WHEN AND WHERE SPECIAL
INSPECTION IS REQUIRED.
5. A 20% MAXIMUM OF THE CEMENT CONTENT MAY BY SUBSTITUTED WITH FLYASH CONFORMING TO ASTM C618, TYPE F OR C. HIGHER
PERCENTAGES OF FLYASH MAY BE UTILIZED WITH ACCEPTANCE AND APPROVAL BY THE STRUCTURAL ENGINEER. ANY CONCRETE MIX
UTILIZING FLYASH SHALL BE VERIFIED WITH TEST DATA.
6. ADDITIONAL WATER SHALL NOT BE ADDED TO THE CONCRETE MIX AT THE JOBSITE. WATER REDUCING ADMIXTURES CONFORMING TO ASTM
C494 MAY BE UTILIZED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.
7. IF CONCRETE IS TO BE POURED AGAINST AN EXISTING CONCRETE SURFACE, THE EXISTING SURFACE SHALL BE CLEANED AND ROUGHENED TO
A MIN. 1/4" AMPLITUDE.
8. SLEEVES, OPENINGS, CONDUITS, AND OTHER EMBEDDED ITEMS NOT SHOWN ON THE STRUCTURAL DRAWINGS SHALL BE APPROVED BY THE
STRUCTURAL ENGINEER BEFORE POURING. CONDUITS EMBEDDED IN SLABS SHALL NOT BE LARGER IN OUTSIDE DIAMETER THAN ONE THIRD
THE THICKNESS OF THE SLAB AND SHALL NOT BE SPACED CLOSER THAN THREE DIAMETERS ON CENTER. PROVIDE 3/4" CHAMFERS ON ALL
EXPOSED CONCRETE EDGES UNLESS NOTED OTHERWISE ON ARCHITECTURAL OR LANDSCAPE DRAWINGS.
9. SHORING AND RESHORING:
SHORING AND RESHORING SHALL CONFORM TO ACI347.2 R-17. SHORING AND SUPPORTING FORMWORK SHALL NOT BE REMOVED FROM
HORIZONTAL MEMBERS BEFORE CONCRETE STRENGTH IS AT LEAST 70 PERCENT OF DESIGN STRENGTH, AS DETERMINED BY FIELD CURED
CYLINDERS. IN ADDITION, SHORING SHALL NOT BE REMOVED SOONER THAN RECOMMENDED BY ACI 347.2R-17. FORMWORK SHALL NOT BE
REMOVED IN LESS THAN (10) DAYS.
10. REINFORCING STEEL:
A. REINFORCING STEEL SHALL BE DETAILED, FABRICATED, AND INSTALLED ACCORDING TO THE "MANUAL OF STANDARD PRACTICE OF
REINFORCED CONCRETE CONSTRUCTION" BY THE CONCRETE REINFORCING STEEL INSTITUTE (CRSI).
B. REINFORCING STEEL SHALL CONFORM TO ASTM A615, GRADE 60.
C. SMOOTH BARS OR WELDED WIRE FABRIC SHALL CONFORM TO ASTM A1064.
D. REINFORCING STEEL REQUIRING WELDING OR PLACED WITHIN A SPECIFIED BOUNDARY ELEMENT OR MOMENT FRAME ELEMENT
SHALL CONFORM TO WELDABLE ASTM A706.
E. ALL LAP SPLICES OF REINFORCEMENT SHALL CONFORM TO CLASS B LAPS AS SHOWN ON THE LAP SPLICE SCHEDULE, UNLESS NOTED
OTHERWISE.
F. ANY MECHANICAL BAR SPLICES SHOWN SHALL BE MADE WITH DAYTON BAR-GRIP COUPLERS OR WITH AN APPROVED PRODUCT
SUBMITTED TO THE ENGINEER OF RECORD WITH AN ICBO REPORT.
G. UNLESS NOTED OTHERWISE, REINFORCING STEEL SHALL HAVE THE MINIMUM COVER OR PROTECTION FOR THE FOLLOWING USES
AS NOTED BELOW:
BEAMS, JOISTS, AND COLUMNS.............................. 1-1/2" (TO TIES OR STIRRUPS)
SLABS........................................................................1"
WALLS
INTERIOR FACES..........................................3/4"
EXPOSED TO EARTH OR WEATHER..............1-1/2" (#5 BARS AND SMALLER)
2" (#6 BARS AND LARGER)
FOOTINGS.................................................................3"
11. CONCRETE WALLS:
A. PROVIDE THE MINIMUM WALL REINFORCING AS SHOWN BELOW UNLESS NOTED OTHERWISE ON PLANS:
WALL THICKNESS REINFORCING
6" #4 VERT. @ 18" OC & #4 HORIZ. @ 16" OC @ ℄ OF WALL
8" #4 VERT. @ 18" OC & #4 HORIZ. @ 12" OC @ ℄ OF WALL
10" #5 VERT. @ 18" OC & #5 HORIZ. @ 15" OC @ ℄ OF WALL
12" #4 VERT. @ 18" OC & #4 HORIZ. @ 16" OC @ EACH FACE OF WALL (2" CLR.)
B. HOOKED DOWELS FROM FOUNDATIONS SHALL BE PROVIDED TO MATCH VERTICAL WALL REINFORCING.
C. PROVIDE HOOKED DOWELS MATCHING SLAB REINFORCING FROM WALLS TO SLABS OR HOOK SLAB REINFORCEMENT INTO WALLS.
D. UNLESS NOTED OTHERWISE, PLACE (2) #5 BARS IN WALLS W/ (2) LAYERS OF REINF. IN BOTH DIRECTIONS & (1) #5 BAR IN WALLS
HAVING SINGLE LAYER OF REINF. IN BOTH DIRECTIONS, ON ALL SIDES OF SLAB AND WALL OPENINGS EXTENDED 36" BEYOND
OPENING. PROVIDE (1) OR (2) 4'-8" LONG DIAGONAL #5 BARS AT EACH CORNER OF THE OPENING MATCHING THE LAYERS OF
REINFORCING.
STRUCTURAL STEEL:
1. STEEL DESIGN, FABRICATION, AND ERECTION SHALL CONFORM WITH "AISC SPECIFICATION FOR THE DESIGN, FABRICATION, AND ERECTION
OF STRUCTURAL STEEL FOR BUILDINGS" AND THE "CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES".
2. THE GRADE AND SPECIFICATION OF THE STEEL MEMBERS SHALL BE AS FOLLOWS:
WIDE FLANGE SHAPES, BRACED FRAME GUSSET PLATES ASTM A572 GRADE 50 OR ASTM A992 GRADE 50
WIDE FLANGE SHAPES SPECIFIED AS PART OF THE
LATERAL FORCE RESISTING SYSTEM ASTM A992 GRADE 50
CHANNELS, PLATES, BARS AND ANGLES (U.N.O.) ASTM A36
HOLLOW STRUCTURAL SECTIONS (TUBES) ASTM A500 GRADE B (FY=46 KSI)
HOLLOW STRUCTURAL SECTIONS (PIPES) ASTM A53 GRADE B (FY=35 KSI)
HIGH STRENGTH BOLTS ASTM A325/ F1852, TYPE 1, PLAIN
NUTS ASTM A563
WASHERS (REQ'D @ SLOTTED & OVERSIZE HOLES) ASTM F436
ANCHOR BOLTS ASTM F1554, GRADE 36
THREADED RODS ASTM A36
3. BOLTS SHALL CONFORM TO ASTM SPECIFICATIONS FOR HIGH STRENGTH A325 AND A490 BOLTS. ALL FAYING SURFACES SHALL BE PREPARED
AS REQUIRED FOR CLASS A OR BETTER SLIP-CRITICAL JOINTS. ALL BOLTS UTILIZED IN SEISMIC RESISTING ELEMENTS SHALL BE FULLY
TENSIONED.
4. WELDING SHALL CONFORM TO THE AWS CODES FOR BUILDING CONSTRUCTION. WELDING SHALL BE PERFORMED IN ACCORDANCE WITH A
WELDING PROCEDURE SPECIFICATION (WPS) AS REQUIRED IN AWS D1.1 AND APPROVED BY THE ENGINEER OF RECORD. THE WPS VARIABLES
SHALL BE WITHIN THE PARAMETERS ESTABLISHED BY THE FILLER-METAL MANUFACTURER.
5. ALL COMPLETE JOINT PENETRATION WELDS USED IN THE SEISMIC RESISTING SYSTEM SHALL BE MADE WITH A FILLER METAL THAT HAS A
MINIMUM CVN TOUGHNESS OF 20 FT-LBS AT MINUS 20° F, AS DETERMINED BY AWS CLASSIFICATION OR MANUFACTURER CERTIFICATION.
ALL COMPLETE JOINT PENETRATION WELDS FOR NON-SEISMIC RESISTING SYSTEMS SHALL BE MADE WITH A FILLER METAL THAT HAS A
MINIMUM CVN TOUGHNESS OF 20 FT-LBS AT 60° F.
6. FOR MEMBERS AND CONNECTIONS THAT ARE PART OF THE SEISMIC RESISTING SYSTEM, DISCONTINUITIES CREATED BY ERRORS OR BY
FABRICATION OR ERECTION OPERATIONS, SUCH AS TACK WELDS, ERECTION AIDS, AIR-ARC GOUGING, AND FLAME CUTTING, SHALL BE
REPAIRED AS REQUIRED BY THE ENGINEER OF RECORD.
7. WELDS SHALL UTILIZE E70XX ELECTRODES AND SHALL BE A MINIMUM OF 3/16" IN SIZE UNLESS NOTED OTHERWISE.
8. ALL STEEL EXPOSED TO SOIL, MOISTURE OR WEATHER SHALL BE HOT DIPPED GALVANIZED PER ASTM A123 OR HAVE ANOTHER APPROVED
PROTECTIVE COATING.
9. HEADED SHEAR STUDS, DEFORMED BAR ANCHORS AND THREADED STUDS SHALL BE NELSON PRODUCT OR APPROVED EQUAL. STUDS/
D.B.A.'S SHALL BE WELDED WITH AUTOMATICALLY TIMED STUD WELDING MACHINE PER AWS D1.1 SECTIONS 7 & 7.8.1.
STEEL DECK:
1. ALL METAL DECKING SHALL CONFORM TO THE SPECIFICATIONS OF THE STEEL DECK INSTITUTE.
2. STEEL FLOOR DECK SHALL BE COMPOSITE TYPE WITH FLUTES AT 12" OC AND CONFORM TO ASTM A653-SS DESIGNATION, GRADE 33
MINIMUM OR ASTM A611, GRADE C.
3. STEEL ROOF DECK SHALL BE 1-1/2" TYPE B AND CONFORM TO ASTM A653 - SS DESIGNATION WITH THE GALVANIZED COATING IN
ACCORDANCE WITH ASTM A653 G60 (G90 WHERE PERMANENTLY EXPOSED TO WEATHER).
4. THE MINIMUM DECK SIZES AND GAGES ARE AS NOTED ON THE PLANS AND ARE BASED ON A 3-SPAN, UNSHORED CONDITION. THE MINIMUM
DECK PROPERTIES ARE AS SHOWN BELOW:
1 1/2"-18 GAGE ROOF DECK MIN. I(IN⁴/FT) = 0.302, MIN. S(IN³/FT) = 0.314
5. STEEL ROOF DECK ATTACHMENT SHALL BE AS SPECIFIED BELOW.
-1/2" EFFECTIVE DIAMETER PUDDLE WELDS AT 12" OC AT TRANSVERSE AND PERIMETER SUPPORTS
-1/2" EFFECTIVE DIAMETER PUDDLE WELDS AT 12" OC AT LONGITUDINAL SUPPORTS
-BUTTON PUNCH AT 12" OC AT SIDE LAP CONNECTIONS
6. WELDERS SHALL BE AWS CERTIFIED FOR LIGHT GAUGE METAL WELDING.
COLD FORMED STEEL FRAMING:
1. COLD-FORMED STEEL FRAMING SHALL BE DESIGNED, FABRICATED AND ERECTED IN ACCORDANCE WITH AISI S-07 STANDARDS AND WITH
THE MANUFACTURER'S RECOMMENDATIONS.
2. PROVIDE METAL STUDS, JOISTS AND ACCESSORIES AS INDICATED ON THE DRAWINGS AND AS NEEDED FOR COMPLETE AND PROPER
INSTALLATION PER THE MANUFACTURER'S RECOMMENDATIONS.
3. PROVIDE ALL ACCESSORIES INCLUDING, BUT NOT LIMITED TO, TRACKS, CLIPS, WEB STIFFENERS, ANCHORS, FASTENING DEVICES, RESILIENT
CLIPS AND OTHER ACCESSORIES REQUIRED FOR A COMPLETE AND PROPER INSTALLATION.
4. ALL LIGHT-GAGE STEEL FRAMING SHALL BE AS SPECIFIED BELOW, UNLESS OTHERWISE NOTED ON THE PLANS:
ASTM A-446 GRADE D (Fy=50 KSI) FOR 16 GAGE AND HEAVIER
ASTM A-446 GRADE A (Fy=33 KSI) FOR 18 GAGE AND LIGHTER
5. FASTENING OF COMPONENTS SHALL BE WITH SELF-DRILLING SCREWS OR WELDING. SCREWS OR WELDS SHALL BE OF SUFFICIENT SIZE TO
ENSURE THE STRENGTH OF THE CONNECTION. ALL WELDING SHALL CONFORM TO AWS SPECIFICATIONS. ALL WELDERS SHALL BE CERTIFIED
FOR LIGHT GAGE STEEL UNDER AWS SPECIFICATIONS.
6. PRIOR TO FABRICATION OF FRAMING, THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS TO THE ARCHITECT AND ENGINEER FOR
APPROVAL.
7. ALL COMPONENTS SHALL BE CUT SQUARELY FOR ATTACHMENT TO PERPENDICULAR MEMBERS OR AS REQUIRED FOR AN ANGULAR FIT
AGAINST ABUTTING MEMBER.
8. WALL STUDS SHALL BE PLUMBED, ALIGNED AND SECURELY ATTACHED TO FLANGES OF BOTH UPPER AND LOWER RUNNERS. EXCEPT, NON-
LOAD BEARING WALL STUDS NEED NOT BE ATTACHED TO UPPER RUNNERS.
9. SPLICES IN AXIAL LOAD BEARING MEMBERS OTHER THEN RUNNER TRACK SHALL NOT BE PERMITTED.
10. RUNNER TRACKS SHALL BE SECURELY ANCHORED TO SUPPORTING STRUCTURE.
11. ANCHORAGE OF NON-LOAD BEARING WALLS SHALL ALLOW FOR VERTICAL MOVEMENT OF THE BUILDING STRUCTURE TO WHICH THEY ARE
ATTACHED.
12. STUDS AND JOISTS TO BE BRACED WITH BRIDGING/BRACING PER MANUFACTURER'S SPECIFICATIONS
13. ALL COLD FORMED STEEL CONNECTIONS SHALL BE MANUFACTURED BY THE STEEL NETWORK, INC. OR AN APPROVED EQUAL. THE
APPROVED EQUAL WITH ICBO REPORTS MUST BE SUBMITTED TO THE ENGINEER FOR APPROVAL. CONNECTIONS SHALL BE INSTALLED PER
THE MANUFACTURER'S INSTALLATION REQUIREMENTS.
ULT. DESIGN WIND PRESSURE (PSF) FOR 10 FT.2
ZONE 1 +12.5/ -21.7
ROOF (PSF)
WALL (PSF)
+12.5/ -36.5
+12.5/ -55.0
+21.7/ -23.6
+21.7/ -36.5
GENERAL STRUCTURAL NOTES:
ZONE 2
ZONE 3
ZONE 4
ZONE 5
CONCRETE AND REINFORCING STEEL CONT.:
12. ADDITIONAL CONCRETE ITEMS:
A. HEADED SHEAR STUDS AND DEFORMED BAR ANCHORS SHALL BE AN APPROVED NELSON PRODUCT OR APPROVED EQUAL.
B. WEDGE ANCHORS OR EXPANSION BOLTS SHALL BE HILTI KWIK BOLT-TZ OR AN APPROVED EQUAL SUBMITTED WITH ICBO REPORTS
TO THE ENGINEER FOR REVIEW.
C. EPOXY ANCHORS OR DOWELS SHALL BE INSTALLED WITH HILTI HIT-RE 500-V3 EPOXY ADHESIVE. AN APPROVED EQUAL IN CRACKED
OR UNCRACKED CONCRETE WITH ICBO REPORTS MAY BE SUBMITTED TO THE ENGINEER FOR APPROVAL.
D. UNLESS NOTED OTHERWISE, PERMANENTLY EXPOSED EMBEDDED PLATE AND ANGLE ASSEMBLIES SHALL BE HOT DIPPED
GALVANIZED AFTER FABRICATION. WELDS OR LOADS SHALL NOT BE PLACED ON THE EMBEDDED ASSEMBLIES FOR A MINIMUM OF
(7) DAYS AFTER CASTING IN CONCRETE.
13. REINFORCEMENT SHALL BE SECURED IN FORMS WITH SUITABLE TIES AND ANCHORAGE TO PREVENT DISPLACEMENT. BARS ADJACENT TO
EARTH SHALL BE SUPPORTED BY CEMENT MORTAR CUBES.
14. REINFORCING STEEL SHALL NOT BE DISPLACED FOR THE CONVENIENCE OF OTHER TRADES UNLESS APPROVED BY THE STRUCTURAL
ENGINEER OF RECORD.
15. "WET SETTING" OF REINFORCEMENT, ANCHOR BOLTS AND INSERTS IS NOT PERMITTED. STATEMENT OF SPECIAL INSPECTION NOTES:
1. SPECIAL INSPECTIONS SHALL CONFORM TO SECTION 1705 OF THE 2025 OSSC, CONTRACT DOCUMENTS AND APPROVED SUBMITTALS. REFER TO SPECIAL INSPECTION
AND TESTING TABLES FOR PROJECT REQUIREMENTS.
2. SPECIAL INSPECTIONS AND ASSOCIATED TESTING SHALL BE PERFORMED BY AN APPROVED ACCREDITED INDEPENDENT AGENCY MEETING THE REQUIREMENTS OF
ASTM E329 (MATERIALS). THE INSPECTION AND TESTING AGENCY SHALL FURNISH TO THE STRUCTURAL ENGINEER ARCHITECT A COPY OF THEIR SCOPE OF
ACCREDITATION. SPECIAL INSPECTORS SHALL BE APPROVED BY THE BUILDING OFFICIAL. WELDING INSPECTORS SHALL BE QUALIFIED PER SECTION 6.1.4.1(1) OF
AWS D1.1.
3. THE SPECIAL INSPECTOR SHALL OBSERVE THE INDICATED WORK FOR COMPLIANCE WITH THE APPROVED CONSTRUCTION DOCUMENTS. ALL DISCREPANCIES SHALL
BE BROUGHT TO THE ATTENTION OF THE CONTRACTOR FOR CORRECTION AND NOTED IN THE INSPECTION REPORTS.
4. THE SPECIAL INSPECTOR AND GEOTECHNICAL ENGINEER SHALL FURNISH INSPECTION REPORTS FOR EACH INSPECTION TO THE BUILDING OFFICIAL, STRUCTURAL
ENGINEER, ARCHITECT, CONTRACTOR, AND OWNER. THE SPECIAL INSPECTION AGENCY SHALL SUBMIT A FINAL REPORT STATING THAT THE WORK REQUIRING
SPECIAL INSPECTION WAS INSPECTED AND IS IN CONFORMANCE WITH THE APPROVED CONSTRUCTION DOCUMENTS AND THAT ALL DISCREPANCIES NOTED IN THE
INSPECTION REPORTS HAVE BEEN CORRECTED.
5. QUALITY ASSURANCE (QA) IS REQURIED FOR STRUCTURAL STEEL ITEMS PER AISC 360 AND 341 UNLESS SPECIFICALLY NOTED OTHERWISE. QUALITY CONTROL (QC)
TO BE PROVIDED BY THE FABRICATOR, ERECTOR OR OTHER RESPONSIBLE CONTRACTOR AS APPLICABLE. CONTRACTOR AND SPECIAL INSPECTOR TO DOCUMENT
QUALITY CONTROL AS REQUIRED IN AISC 360 SECTION N3 AND AISC 341 SECTION J2.
6. INSPECTION TYPES: CONTINUOUS: THE FULL-TIME OBSERVATION OF WORK REQUIRING SPECIAL INSPECTION BY AN APPROVED SPECIAL INSPECTOR WHO IS
PRESENT IN THE AREA WHERE THE WORK IS BEING PERFORMED. PERIODIC: THE PART-TIME OR INTERMITTENT OBSERVATION OF WORK REQUIRING SPECIAL
INSPECTION BY AN APPROVED SPECIAL INSPECTOR WHO IS PRESENT IN THE AREA WHERE THE WORK HAS BEEN OR IS BEING PERFORMED AND AT THE COMPLETION
OF THE WORK. OBSERVE: OBSERVE THESE FUNCTIONS ON A RANDOM, DAILY BASIS. OPERATIONS NEED NOT BE DELAYED PENDING OBSERVATIONS. PERFORM:
INSPECTIONS SHALL BE PERFORMED PRIOR TO THE FINAL ACCEPTANCE OF THE ITEM.
7. PERFORM INSPECTION PRIOR TO FINAL ACCEPTANCE OF THE ITEM FOR TEN WELDS TO BE MADE BY A GIVEN WELDER, WITH THE WELDER DEMONSTRATING
UNDERSTANDING OF REQUIREMENTS AND POSSESSION OF SKILLS AND TOOLS TO VERIFY THESE ITEMS, THE PERFORM DESIGNATION OF THIS TASK SHALL BE
REDUCED TO OBSERVE, AND THE WELDER SHALL PERFORM THIS TASK. SHOULD THE INSPECTOR DETERMINE THAT THE WELDER HAS DISCONTINUED PERFORMANCE
OF THIS TASK, THE TASK SHALL BE RETURNED TO PERFORM UNTIL SUCH TIME AS THE INSPECTOR HAS RE-ESTABLISHED ADEQUATE ASSURANCE THAT THE WELDER
WILL PERFORM THE INSPECTION TASKS LISTED.
8. SPECIAL INSPECTION OF MECHANICAL POST INSTALLED ANCHORS SHALL BE IN STRICT CONFORMANCE WITH THE ICC REPORT AND MANUFACTURER'S INSTALLATION
REQUIREMENTS. ANCHOR INSTALLERS SHALL BE QUALIFIED AS REQUIRED BY JURISDICTION REQUIREMENTS.●INSPECTION REPORTS SHALL IDENTIFY NAMES OF
INSTALLERS.●SPECIAL INSPECTOR SHALL PROVIDE DOCUMENTATION AT THE END OF ANCHOR INSTALLATIONS STATING THAT THE ANCHORS WERE INSPECTED PER
APPROVED ANCHOR EVALUATION REPORT.
9. TESTING ABBREVIATIONS:
NDT - NON-DESTRUCTIVE TESTING
C.J.P. - COMPLETE JOINT PENETRATION
MT - MAGNETIC PARTICLE TESTING
RBS - REDUCED BEAM SECTION
10. DOCUMENT (D): INDICATES CONTRACTOR AND SPECIAL INSPECTOR TO PROVIDE DOCUMENTATION IN ACCORDANCE WITH AISC 341.
11. THE CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION, SCHEDULING AND TIMELY NOTIFICATION OF THE DESIGNATED SPECIAL INSPECTOR PRIOR TO ALL
WORK REQUIRING SPECIAL INSPECTION.
CONTRACTOR RESPONSIBILITY: EACH CONTRACTOR RESPONSIBLE FOR THE CONSTRUCTION OF THE MAIN WIND-OR SEISMIC-FORCE-RESISTING SYSTEM, DESIGNATED
SEISMIC SYSTEM OR A WIND-OR SEISMIC-RESISTING COMPONENT LISTED THE TABLES SHALL SUBMIT A WRITTEN STATEMENT OF RESPONSIBILITY TO THE BUILDING
OFFICIAL AND THE OWNER PRIOR TO THE COMMENCEMENT OF WORK ON THE SYSTEM OR COMPONENT. THE CONTRACTOR'S STATEMENT OF RESPONSIBILITY SHALL
CONTAIN THE FOLLOWING:
ACKNOWLEDGEMENT OF AWARENESS OF THE SPECIAL REQUIREMENTS CONTAINED IN THE STATEMENT OF SPECIAL INSPECTIONS.
1. ACKNOWLEDGEMENT THAT CONTROL WILL BE EXERCISED TO OBTAIN CONFORMANCE WITH THE CONSTRUCTION DOCUMENTS APPROVED BY THE BUILDING
OFFICIAL.
2. PROCEDURES FOR EXERCISING CONTROL WITHIN THE CONTRACTOR'S ORGANIZATION, THE METHOD AND FREQUENCY OF REPORTING AND DISTRIBUTION OF THE
REPORTS.
3. IDENTIFICATION AND QUALIFICATIONS OF THE PERSON(S) EXERCISING SUCH CONTROL AND THEIR POSITION(S) IN THE ORGANIZATION.
SPECIAL INSPECTIONS:
1. THE ITEMS NOTED SHALL BE INSPECTED BY A CERTIFIED SPECIAL INSPECTION FROM AN ESTABLISHED TESTING AGENCY. FOR MATERIAL SAMPLING AND TESTING
REQUIREMENTS, REFER TO THE MATERIAL SAMPLING AND TESTING SECTION, THE PROJECT SPECIFICATIONS, AND THE SPECIFIC GENERAL NOTES SECTIONS. THE
TESTING AGENCY SHALL SEND COPIES OF ALL STRUCTURAL TESTING AND INSPECTION REPORTS DIRECTLY TO THE ARCHITECT, ENGINEER, CONTRACTOR, AND
BUILDING OFFICIAL. ANY MATERIALS WHICH FAIL TO MEET THE PROJECT SPECIFICATIONS SHALL IMMEDIATELY BE BROUGHT TO THE ATTENTION OF THE ENGINEER.
2. SPECIAL INSPECTION TESTING REQUIREMENTS APPLY EQUALLY TO ALL BIDDER DESIGNED COMPONENTS. SPECIAL INSPECTION IS NOT REQUIRED FOR WORK
PERFORMED BY AN APPROVED FABRICATOR PER 2025 OSSC SECTION 1704.2.5.1.
3. CONTINUOUS SPECIAL INSPECTION MEANS THAT THE SPECIAL INSPECTOR IS ON SITE AT ALL TIMES OBSERVING THE WORK REQUIRING SPECIAL INSPECTION PER
2025 OSSC 1702, PERIODIC SPECIAL INSPECTION MEANS THAT THE SPECIAL INSPECTOR IS ON SITE AT TIME INTERVALS NECESSARY TO CONFIRM THAT ALL WORK
REQUIRING SPECIAL INSPECTION IS IN COMPLIANCE.
4. THE CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION, SCHEDULING AND TIMELY NOTIFICATION OF THE DESIGNATED SPECIAL INSPECTOR PRIOR TO ALL
WORK REQUIRING SPECIAL INSPECTION.
STEEL - SPECIAL INSPECTIONS
SYSTEM OR MATERIAL
OSSC
CODE
REFERENCE
CODE OR
STANDARD
REFERENCE
INSPECTION (NOTES 5 AND 6)
REMARKS
"CONTINUOUS
/ PERFORM"
"PERIODIC
/ OBSERVE"
STRUCTURAL STEEL WELDING
VERIFYING USE OF PROPER WPS'S
"1705.2.1
AWS D1.1"
AISC 360 N3.2
RETAIN A RECORD OF WELDING PROCEDURE
SPECIFICATIONS
VERIFYING WELDER QUALIFICATIONS AWS D1.1 X RETAIN A RECORD OF QUALIFICATION CARDS
COMPLETE AND PARTIAL JOINT PENETRATION GROOVE WELDS
TABLE
1705.2-6
AWS D1.1
CLAUSE 6
X
MULTIPASS FILLET WELDS X
SINGLE PASS FILLET WELDS GREATER THAN 5/16" X ALL WELDS VISUALLY INSPECTED PER AWS D1.16.9
PLUG AND SLOT WELDS X
SINGLE PASS FILLET WELDS LESS THAN OR EQUAL TO 5/16" X
WELDING STAIR AND RAILING SYSTEMS 1705.2(2.5)
AWS D1.1
CLAUSE 6
X
"ALL WELDS VISUALLY INSPECTED PER AWS
D1.1
6.9"
VERIFICATION OF JOINT & CONNECTION DETAILS INCLUDING
MEMBER AND COMPONENT LOCATIONS, BRACING, AND
STIFFENERS
TABLE
1705.2-7
AWS D1.1 X
SNUG-TIGHT BOLT INSTALLATION
"1705.2.
TABLE
1705.2-
AISC
M2-5
AISC
N5-6"
"RCSC
SPECIFICATION
FOR
STRUCTURAL
JOINTS USING
ASTM A325
OR A490
BOLTS
SECTION 9
AISC 360
SECTION
M2.5"
X
ALL CONNECTIONS VISUALLY INSPECTED AND
VERIFIED SNUG
X
ALL CONNECTIONS VISUALLY INSPECTED.
CONNECTIONS USING DIRECT TENSION INDICATORS,
ALL BOLTS SHALL BE INSPECTED AFTER SNUGGING
AND AFTER PRETENSIONING
X ALL CONNECTIONS VISUALLY INSPECTED
s w S im p so n
A v e
S u it e
B e n d
O re g o n t
.3
.5 f
.3
.8
C O
P Y
R
IG
H T
B
B T
A R
C H
IT
E C
TS
Date
Project Number
40 NW Greenwood Ave, Suite 200
Bend, OR 97703
541.330.6869 www.walkerse.com
/2
/2
:0
:1
A
M
S0.1
GENERAL STRUCTURAL
NOTES, SPECIAL
INSPECTION TABLES &
DRAWING INDEX
HDESD MANZANITA
ENTRY CANOPY
1212 NE 5th Street, Redmond OR
10/22/2026
100%
CONSTRUCTION
DOCUMENTS
DRAWING INDEX
S0.1 GENERAL STRUCTURAL NOTES, SPECIAL INSPECTION TABLES & DRAWING INDEX
S2.1 STRUCTURAL FOUNDATION & FRAMING PLANS
S5.1 STRUCTURAL FOUNDATION & FRAMING DETAILS
FOUNDATION PLAN LEGEND
INDICATES STRUCTURAL FRAMING DETAIL. REFERENCE STRUCTURAL S2.1.
INDICATES STRUCTURAL COLUMN PER PLAN
A101
FOOTING SCHEDULE
MARK SIZE (WIDTH x LENGTH) "T"
18" MIN
REMARKS
(4) #5 EA WAY @ TOP & BTMA
B 12" MIN (4) #5 EA WAY @ TOP & BTM2'-6" x 2'-6"
2'-0" x 2'-0"
C 18" MIN (5) #5 EA WAY @ TOP & BTM2'-6" x 2'-6"
AA
BB
CC
A
A A A A
A
BB
C CHSS4x4x5/16
TYP. ALL COLUMNS
(14) PLACES
S5.1
SIM (4) PLACES
S5.1
S5.1
S5.1
S5.1
S5.1
S5.1
AA
BB
CC
HSS6x4x5/16
HSS6x4x5/16 HSS6x4x5/16
HSS6x4x5/16 HSS6x4x5/16
HSS6x4x5/16
H
SS
x4 x5 /1
(S
LO
P E
D
H
SS
x4 x5 /1
(S
LO
P E
D
H
SS
x4 x5 /1
(S
LO
P E
D
H
SS
x4 x5 /1
(S
LO
P E
D
H
SS
x4 x5 /1
H
SS
x4 x5 /1
H
SS
x4 x5 /1
R
ID
G E
B E
A M
D -1
D -1
D -1
HSS TRUSS
D-1 D-1
S5.1
S5.1
OPP
OPP
STEEL STUD OVERFRAME(2) PLACES
S5.1
S5.1
S5.1
S5.1
S5.1
S5.1
S5.1
S5.1
S5.1
SIM (2)
PLACES
S5.1
SIM
S5.1
S5.1
S5.1
SIM SIM
OPP
S5.1
S5.1
S5.1
ROOF FRAMING LEGEND
INDICATES STRUCTURAL FRAMING DETAILS. REFERENCE STRUCTURAL DETAIL SHEETS.
INDICATES SPAN DIRECTION OF 1-1/2" X 18 GA TYPE B METAL DECK W/ ATTACHMENT
PER GENERAL STRUCTURAL NOTES.
A101
D-1
1. DO NOT USE STRUCTURAL DRAWINGS ALONE FOR BUILDING LAYOUT. DO NOT SCALE
THESE DRAWINGS MANUALLY OR ELECTRONICALLY. COORDINATE LOCATIONS OF ALL
STRUCTURAL ELEMENTS, INCLUDING BUT NOT LIMITED TO, COLUMNS, WALLS, SLAB
EDGES, DEPRESSIONS AND OPENINGS WITH ARCHITECTURAL DRAWINGS AND RESOLVE
ANY CONFLICTS BETWEEN DRAWINGS OR ELEMENTS PRIOR TO CONSTRUCTION. A
REGISTERED SURVEYOR SHALL PERFORM BUILDING LAYOUT AND LOCATION OF ALL
STRUCTURAL ELEMENTS AT ALL LEVELS. REF. ARCH. DRAWINGS FOR ALL DIMENSIONS/
ELEVATIONS NOT SHOWN. CONTRACTOR IS RESPONSIBLE FOR CROSS REFERENCING ALL
DIMENSIONS/ ELEVATIONS SHOWN WITH ARCHITECTURAL DRAWINGS NOTIFY
ARCHITECT / ENGINEER OF RECORD IF THERE ARE ANY DISCREPANCIES.
FOUNDATION & ROOF FRAMING PLAN NOTES
s w S im p so n
A v e
S u it e
B e n d
O re g o n t
.3
.5 f
.3
.8
C O
P Y
R
IG
H T
B
B T
A R
C H
IT
E C
TS
Date
Project Number
40 NW Greenwood Ave, Suite 200
Bend, OR 97703
541.330.6869 www.walkerse.com
/2
/2
:0
:1
A
M
S2.1
STRUCTURAL
FOUNDATION &
FRAMING PLANS
HDESD MANZANITA
ENTRY CANOPY
1212 NE 5th Street, Redmond OR
10/22/2026
100%
CONSTRUCTION
DOCUMENTS
1/4" = 1'-0"
S2.1
STRUCTURAL FOUNDATION PLAN
1/4" = 1'-0"
S2.1
STRUCTURAL FRAMING PLAN
TYP HSS6X4X5/16 HORIZ W/ 5/16" CAP PL
FIELD WELD TO HSS COLUMN AS SHOWN
LINE OF SLOPED/HORIZONTAL HSS6X4X5/16
BEYOND W/ ATTACHMENT PER 5/S5.1
HSS4X4X5/16 COLUMN W/ 5/16" CAP PL
NOTE: DBL HSS COLUMN AT W/ SPLICE
BETWEEN COLUMNS @ SIM CONDITION
1-1/2" STEEL ROOF DECK,
ATTACH PER GENERAL NOTES
SLOPED HSS6X4X5/16
W/ 5/16" CAP PL EA END
1/4
1/4
HSS6X4X5/16 CONT.
OVER COLUMN
HSS4X4X5/16 CORNER
COLUMN W/ 5/16" CAP PL
1/4
1/4
TYP
1-1/2" STEEL ROOF DECK,
ATTACH PER GENERAL NOTES
HSS4X4X5/16 CORNER
COLUMN W/ 5/16" CAP PL
SLOPED HSS6X4X5/16
W/ 5/16" CAP PL EA END
1/4
1/4
HSS6X4X5/16 CONT.
OVER COLUMN
1/4
1/4
TYP
HSS6X4X5/16 CONT. RIDGE BEAM OVER
HSS4X4X5/16 VERT WELD PER 4/S5.1
1/4
1/4
TYP
1-1/2" STEEL ROOF DECK,
ATTACH PER GENERAL NOTES
HSS4X4X5/16 VERT W/ 5/16" CAP PL
HSS4X4X5/16 DIAGONAL WEB-WELD
TO HSS6X64X5/16 TOP CHORD
SLOPED HSS6X4X5/16
W/ 5/16" CAP PL EA END
HSS6X4X5/16 BTM CHORD
1/4
1/4
TYP
LINE OF
GRADE/PAVING
PER ARCH
FT
G
S C
H E
D U
LE
R E
F P
LA
N
C
LR
3" CLR
FTG SIZE & REINF
REF PLAN & SCHED FOR
M
IN
1/4
TYP
2 1/2" CLR1 1/2" TYP
C
LR
EMBED PL 5/8x10x1'-4"
W/ (6) #5 DBA's @ 7" OC
22"Ø SONOTUBE W/ (8) #6
EQUALLY SPACED & #3 SPIRAL TIE
W/ 4" PITCH (STD HOOK & BTM
HSS 4X4X5/15 COLUMN
V E
R
IF
Y
10"4"
CHAMFER CONC @ SONOTUBES
3" CLR
FTG SIZE & REINF
REF PLAN & SCHED FOR
EMBED PL 3/4x10x1'-4" W/
(6) 3/4" DIA X 10" HEADED
STUDS @ 7" OC
HSS 4X4X5/16 COLUMN
4"
PROVIDE 1/2" ISOLATION JOINT
MATERIAL AROUND HSS COLUMNS
C
LR
LINE OF GRADE/PAVING
PER ARCH
C
LR
3" CLR
FTG SIZE & REINF
REF PLAN & SCHED FOR
C
LR
EMBED PL 3/4x10x0'-10" W/
(4) 3/4" DIA X 10" HEADED
STUDS @ 7" OCPROVIDE 1/2" ISOLATION JOINT
MATERIAL AROUND HSS COLUMNS
HSS 4X4X5/16 COLUMN
LINE OF GRADE/PAVING
PER ARCH
(2) #10 SCREWS, TYP
1 1/2" x 20 GA TYPE "B" ROOF DECK
W/ ATTACHMENT PER GENERAL
STRUCTURAL NOTES
400S137-43 VERTS @ 24" OC
(ALONG EA BEAM/JOIST)
L2x2 x 16 GA x 0'-3" w/ (2) #10 SCREWS TO STUD/DECK
STEEL BEAM REF PLAN
METAL ROOF DECK
REF PLAN
400S137-43 RAFTERS
@ 24" OC
HSS6X4X5/16
CROSS BEAM W/
5/16" CAP PL
1-1/2" STEEL ROOF DECK,
ATTACH PER GENERAL NOTES
SLOPED HSS6X4X5/16
TRUSS MEMBER W/
5/16" CAP PL @ END
HORIZONTAL HSS6X4X5/16
TO EXTEND THROUGH HSS
COLUMNS
(1/4)
(1/4)
TYP
HSS4X4X5/16 COLUMN W/
SLOPED CAP PL AS SHOWN
(1/4)
(1/4)
HSS4X4X5/16 COLUMN
W/ CAP PL AS SHOWN
1/4
TOP & BTM RAKE WALL (NOT SHOWN W/
400S137-33 STUDS @ 24" OC
W/ #8 SMS EA SIDE TOP & BTM
FINISH PER ARCH
HSS6X4X5/16 CROSS BEAM
400T150-43 TOP & BTM TRACK
W/ 0.145" DIA PAF's @ 8" OC
TO HSS CROSS BEAM
HSS6X4X5/16 RIDGE BEAM
1/8 2-12
1/8 2-12
1-1/2" STEEL ROOF DECK
(DECK PARALLEL @ SIM)
FASCIA PER ARCH
L2X2X1/4 X CONT W/ 5/16" DIA HOLES
@ 16" OC FOR FASCIA ATTACHMENT
s w S im p so n
A v e
S u it e
B e n d
O re g o n t
.3
.5 f
.3
.8
C O
P Y
R
IG
H T
B
B T
A R
C H
IT
E C
TS
Date
Project Number
40 NW Greenwood Ave, Suite 200
Bend, OR 97703
541.330.6869 www.walkerse.com
/2
/2
:0
:1
A
M
S5.1
STRUCTURAL
FOUNDATION &
FRAMING DETAILS
HDESD MANZANITA
ENTRY CANOPY
1212 NE 5th Street, Redmond OR
10/22/2026
100%
CONSTRUCTION
DOCUMENTS
1" = 1'-0"
S5.1
HSS COLUMN CONNECTION
1" = 1'-0"
S5.1
HSS COLUMN CONNECTION
1" = 1'-0"
S5.1
HSS COLUMN CONNECTION
1" = 1'-0"
S5.1
HSS TRUSS DETAIL
1" = 1'-0"
S5.1
FOOTING/PEDESTAL DETAIL
1" = 1'-0"
S5.1
FOOTING/PEDESTAL DETAIL
1" = 1'-0"
S5.1
FOOTING/PEDESTAL DETAIL
1" = 1'-0"
S5.1
TYPICAL ROOF OVERFRAMING
1" = 1'-0"
S5.1
HSS TRUSS END CONNECTION
1" = 1'-0"
S5.1
RIDGE CONNECTION
1" = 1'-0"
S5.1
FASCIA DETAIL
A
ABBREVIATIONS
ABBRV.
WIRING DEVICE SYMBOLSLIGHTING SYMBOLSPOWER SYMBOLS
CONDUIT SYMBOLS TELECOM SYMBOLS DESIGNATION SYMBOLS
ELECTRICAL LEGEND
SYMBOLSYMBOLSYMBOL IDENTIFICATION
SYMBOL SYMBOL SYMBOL
LEGEND NOTES:
IDENTIFICATION IDENTIFICATION IDENTIFICATION
IDENTIFICATION IDENTIFICATION IDENTIFICATION
AC ALTERNATING CURRENT
AFF ABOVE FINISH FLOOR
AT TRIP RATING IN AMPERES
AF FRAME RATING IN AMPERES
AS SWITCH RATING IN AMPERES
ATS AUTOMATIC TRANSFER SWITCH
AV AUDIO VISUAL
C CONDUIT
CEC CALIFORNIA ELECTRIC CODE
CL CENTERLINE
DC DIRECT CURRENT
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE SINGLE THROW
(E) EXISTING TO REMAIN
ELEV ELEVATOR
EMT ELECTRO METALLIC TUBING
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
FVNR FULL-VOLTAGE, NON-REVERSING
FVR FULL-VOLTAGE, REVERSING
G GROUND
GFCI GROUND FAULT CIRCUIT INTERRUPTER
HID HIGH INTENSITY DISCHARGE
IG ISOLATED GROUND
LRC LIGHTING RELAY CABINET
NC NORMALLY CLOSED
NEMA NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION
NO NORMALLY OPEN
NTS NOT TO SCALE
PP POWER POLE
PTS PNEUMATIC TUBE STATION
PVC POLYVINYL CHLORIDE CONDUIT
RSC RIGID STEEL CONDUIT
SPDT SINGLE POLE, DOUBLE THROW
SPST SINGLE POLE, SINGLE THROW
TB TERMINAL BACKBOARD
TC TERMINAL CABINET
TEL TELEPHONE
UON UNLESS OTHERWISE NOTED
VFD VARIABLE FREQUENCY DRIVE
W WEATHERPROOF
WAP WIRELESS ACCESS POINT
W/ WITH
XFMR TRANSFORMER
XP EXPLOSION PROOF
NEC NATIONAL ELECTRIC CODE
(X) REMOVE EXISTING
(R) RELOCATE EXISTING
20A, 125V, DUPLEX RECEPTACLE OUTLET
20A, 125V, DOUBLE DUPLEX RECEPTACLE OUTLET
CONN CONNECTED
SPECIAL PURPOSE RECEPTACLE OUTLET; RATING AS SHOWN;
+18" AFF TP CENTERLINE
20A, 125V, SINGLE RECEPTACLE OUTLET
A = ABOVE COUNTER
C = CEILING MOUNTED
G = GFCI
S = SWITCHED RECEPTACLE
U = WITH (2) USB PORTS
W = WEATHERPROOF COVER AND GFCI
X
20A, 125V, DUPLEX RECEPTACLE OUTLET;
FLOOR RECESSED
20A, 125V, DOUBLE DUPLEX RECEPTACLE OUTLET;
FLOOR RECESSED
2-CHANNEL FLOOR BOX W/ (2) GANG POWER / (2) GANG DATA;
PROVIDE 1"C. FROM EACH DATA OUTLET TO ACCESSIBLE CEILING
SPACE. BASIS-OF-DESIGN: WIREMOLD 'RFB4'.
SINGLE POLE SWITCH
3 = THREE WAY SWITCH
4 = FOUR-WAY SWITCH
D = DIMMER SWITCH
K = KEY OPERATED SWITCH
M = MOTOR RATED SWITCH
T = INTERVAL TIMER
V = LOW VOLTAGE SWITCH
W = SINGLE POLE WEATHERPROOF SWITCH
X
PUSH BUTTON SWITCH
OCCUPANCY LIGHT CONTROL SWITCH; CEILING MOUNTED
OCCUPANCY LIGHT CONTROL SWITCH; WALL MOUNTED
PHOTOSENSOR; CEILING MOUNTED
C = DUAL TECH WITH CORRIDOR PATTERN
X
D = DIMMING
S = SWITCHEDX
A. ALL SYMBOLS MAY NOT BE USED IN THIS PROJECT.
B. SYMBOLS DO NOT ALWAYS REPRESENT REAL LIFE DIMENSIONS.
C. SEE BOOK SPECIFICATIONS FOR ADDITIONAL INFORMATION.
ELECTRIC VEHICLE CHARGING STATION
CONDUIT INSTALLED BELOW FINISHED FLOOR OR BELOW GRADE
CONDUIT INSTALLED ABOVE FINISHED FLOOR OR GRADE
INDICATES CONDUIT TURNING UP
CONDUIT HOMERUN; ROUTE TO PANELBOARD, CABINET, OR
TERMINAL BOARD INDICATED, AND TERMINATE CONDUCTORS
TO CIRCUIT OVER CURRENT PROTECTIVE DEVICE
TELEPHONE/DATA OUTLET; PROVIDE 1"C. W/ PULL-STRING TO
ACCESSIBLE CEILING SPACE
X
LUMINAIRE; CEILING OR SURFACE MOUNTED
LUMINAIRE; WALL MOUNTED
AREA POLE WITH MOUNTED LUMINAIRE
LUMINAIRE ON EMERGENCY POWER
EXIT SIGN; CEILING MOUNTED; ARROWS AND FACES AS
SHOWN ON PLANS
EXIT SIGN; WALL MOUNTED; ARROWS AND FACES AS
SHOWN ON PLANS
GRID LINE DESIGNATOR
FEEDER DESIGNATION TAG
SHEET KEYNOTE TAG
MECHANICAL EQUIPMENT TAG
CONTRACTOR EQUIPMENT TAG
LETTER INDICATES FIXTURES CONTROL (WHERE SHOWN)
NUMBER INDICATES CIRCUIT NUMBER (WHERE SHOWN)
SPD SURGE PROTECTION DEVICE
PH PHASE
REVISION DELTA WITH REVISION NUMBER
HORN/STROBE COMBINATION; CEILING MOUNTED
GND GROUND
C = CEILING MOUNTED; BACK BOX ONLY FOR FUTURE WAP
UNLESS OTHERWISE NOTED
This is the start of the file's text. The full file is on GovTribe.